Appendix A : Coating Systems

Appendix B : Coating Colour Schedule

Appendix C : Identification of Services – Colour Coding of Piping Appendix D : Coating Schedule (Other than Marine Environment) Appendix E : Coating Schedule – Marine environment

Appendix A Coating Systems

TYPE DESCRIPTION

01 Inorganic Zinc Silicate Primer

Dry film thickness 75 microns

Required surface profile: 50 microns Maximum temperature resistance: 400oC

Minimum Volume solids 58 ASTM D2697

02 High Temperature Silicone Acrylic

Dry film thickness : 50 microns

Required surface preparation: Clean,dry inorganic zinc primer (type 01)

Maximum temperature resistance 200oC

Minimum Volume solids 37 ASTM D2697

03 High Temperature Silicone Aluminium

Dry film thickness: 25 microns

Required surface preparation: Clean,dry inorganic zinc primer (type 01)

Maximum temperature resistance 600oC (1)

Minimum Volume solids 49 ASTM D2697

These materials must generally be exposed to 175 o C or higher to fully cure.

Coating must be capable of “curing” to handle at ambient temperature.

TYPE DESCRIPTION 04 Zinc Rich Epoxy Primer

Dry film thickness: 50 microns

Required surface preparation: 25-35 microns Maximum temperature resistance: 120oC

Minimum Volume Solids : 59 ASTM D2697

05 High Build MIO Epoxy Intermediate

Dry film thickness: 125 microns

Required surface preparation : Clean, dry epoxy primer (type 04)

Maximum temperature resistance : 120oC

Minimum Volume Solids : 55 ASTM D2697

The quantity of MIO in the main pigment shall be 80% by weight

06 Aliphatic Urethane Finish

Dry film thickness : 75 microns

Required surface preparation : Clean. Dry epoxy intermediate (type 05)

Maximum temperature resistance : 120oC

Minimum Volume Solids : 45 ASTM D2697

07 “Zinc Free” High Temperature Air Curing Finish Coat

Dry film thickness : 75 microns

Required surface preparation : Clean, dry and salt free Maximum temperature resistance : 600oC

08 High Build Epoxy for Stainless Steel

Dry Film thickness : 100 microns

Required surface profile : Sweep blast with aluminium oxide

TYPE DESCRIPTION

09 Coal Tar Epoxy

Dry film thickness: 175 microns Required surface profile: 75 microns

10 Amine Adduct Cured Epoxy

Dry film thickness: 80 microns Required surface profile: 50 microns

11 Inorganic sealer top coat

Wet film thickness : 50 microns

Dry film thickness: 10 microns (mini.)

Maximum temperature resistance: 600 oC

Minimum volume solids: 6% ASTM D2697

12 Polysiloxane high heat coating

Dry film thickness: 75 microns

Maximum temperature resistance: 600 oC

Minimum volume solids: 64% ASTM D2697

13 Inorganic Zinc Pre-construction Primer

Dry film thickness: 15-20 microns Maximum temperature resistance: 400 o C

TYPE DESCRIPTION

14 High Build Chlorinated Rubber Zinc Phosphate Primer

Single pack chlorinated rubber medium plasticised with unsaponifiable plasticiser pigmented with zinc phosphate

Dry film thickness: 75 microns

Required surface profile: 50 microns Maximum temperature resistance: 60 o C

Minimum volume solids: 45% ASTM D2697

Main pigment content shall be 40% by weight of total pigment (min.)

15 High Build Chlorinated Rubber MIO Paint

Dry film thickness: 75 microns

Maximum temperature resistance: 60 o C

Minimum volume solids: 50% ASTM D2697

The quantity of MIO in the main pigment shall be 60% by weight.

16 Chlorinated Rubber Finish

Single pack plasticised chlorinated rubber medium with chemical and weather resistant pigments.

Dry film thickness: 50 microns

Maximum temperature resistance: 60 o C

Minimum volume solids: 40% ASTM D2697

Main pigment content shall be 90% by weight of total pigment (Mini.).

17 Synthetic Enamel (Suitable for over-coating primer types 01 and finish coat type16)

Dry film thickness: 50 microns

Volume solids: 40% ASTM D2697

TYPE DESCRIPTION

18 Epoxy Finish Coat

Dry film thickness: 60 microns

Minimum volume solids: 45 ASTM D2697

19 High Build Epoxy Intermediate

Dry film thickness: 100 microns

Minimum Volume solids: 55 ASTM D2697

20 High Build Epoxy Intermediate

Dry film thickness: 65 microns

Minimum Volume solids: 55 ASTM D2697

The products identified in the following table match with the Coating System in Appendix ‘A’

TYPE COMPANY (Note 7)

CARBOLINE INTERNATIONAL AMERON BERGER ASIAN

01 Carbozinc 12 Interzinc 12 Dimetcote 9 FT Zinc Anode 11 Apcosil-605

02 Carboline 1248 Intertherm 875 Amercoat 891 -

-03 Carboline 4674 Intertherm 50 Amercoat 878 -

-04 Carboline 658 Interzinc 72 Amercoat 68HS Epilux 4HB Zinc Rich Primer

Asian EZRP PC 1299

05 Carboline

190HB MIO Interguard 400 Amercoat 383 MIO Epilux 155HB Ä (RPL MIO)

Apcodur MIO (RPL MIO) 06 Carboline

133HB Interthane 799 Amercoat 450 SA Berger Thane 41 S/G

Apcothane HBPU (PC 1303)

07 - Intertherm 50 or

Intern. XGP 639 Amercoat 741 - Apcotherm

HR finish

08 Carbomastic 15 Interplus 256 Amerlock 400 -

-09 Carbomastic 14 Á Intertuf 708 Amercoat SSPC.16 Epilux 555 Hb Apcodur CF655 10 Carboline 187

 À Interline 944 Amercoat 90 Epilux 78HBTL

Ã

Apcodur CF699 (Note 6)

11 - - Amercoat 710 -

-12 - Intertherm 601 Amercoat PSX 892

HS -

-13 Caroweld 11

HS Interplate 11 Dimetcote DSP - Apcocil-611

14 CDC

Multibond 2000 Interchlor HB Primer

-Linosol HB Red oxide ZP

Primer

Asiochlor EHB ZP (PC 1417)

15 CDC

Multibond 2001 Interchlor HB MIO - Linosol MIO Asiochlor HB MIO (PC 1416)

16 - Interchlor Finish - Linosol Hi Build

CR Paint

Coating (PC 1262)

19

-- - - Asian Epoxy HB

Coating (PC 1262)

20 - - -

-NOTE All vendor supplied items to conform to Appendix 'B'.

À For potable water service Interline 925@400 microns DFT shall be used in lieu of Interline 944

Á An alternative to Intertuf 708 is Intertuf JXA 727/720

 For potable water service, carboline 891 shall be used in lieu of carboline 187

à After complete cure the coating shall be thoroughly rinsed with potable water prior to being placed in service

Ä Epilux 155 HB MIO shall be "RIL" grade only. Standard material shall NOT be used

Å Apcodur-CF699 is approved for all services except POTABLE WATER

Æ Generally suitable for type of application , however Data Sheet should be checked to ensure compatibility for the operating temperature and other special features.

Appendix B : Coating Colour Schedule

CODE

LETTER DESCRIPTION COLOUR BRITISH

STD : 4800*

C Columns , Pressure Vessels, Exchangers Aluminium

-Tankages :

Heated (Except Acid, Caustic, Water) Black 00 - E - 53

Refrigerated, Tanks inside battery limits White

-F

All Tanks in Tank Farm Area Sand

-Rotating equipment :

Pumps, Compressors, Turbines, Fans, Motors Light Grey 10 - A - 03 G

Uncovered moving parts that could cause injury Orange 06 - E - 51

J Instrument Equipment Light Grey 10 - A – 03

Piping, Valves, Fittings etc :

AIR services, unless galvanised Light blue 20 - E - 51

Underground (Buried) Black 00 – E – 53

Above ground – Fire Water , Foam etc Fire Red 04 – E – 53

All other services except the above (Service identification

bands – Refer Appendix C ) Light Grey 10 – A – 03

L

Transition Flanges (between Above ground and Below

ground) Yellow 08 – E – 51

Structural Steel work (Unless Galvanised) and Concrete :

Framework, Columns, Beams and Pipe Supports Light Grey 10 - A - 03 Stairs, Platforms, Floor Plates, Kickplates Black 00 – E – 53 M

Ladders, Ladder Cages, Hand rails

Yellow 08 – E – 51 P Electrical Equipment Light Grey 10 – A – 03

Fire Protection Materials and Equipment : Foamatic Hydrants, Water Hydrants, Extinguishers, Sprinkler Systems, Alarm Boxes, Fire doors, Connections and Cabinets for Fire Blankets and Hoses

Fire Red 04 – E – 53 Safety Equipment :

Safety Showers, Eyewash fountains, First Aid Equipments, etc.

Green 14 – C – 39 Note : * Corresponding Equivalent / Nearest IS colour shade is enclosed in cl. 6.0 of Appendix – C

Table 1 : Identification of Services

WATER WB CRIMSON 04-D-45

-COOLING

WATER (FRESH) WC WHITE 00-E-55

-COOLING WATER (SEA WATER)

WC WHITE 00-E-55 YELLOW 10-C-33

DESALINATED

WATER WD SKY BLUE 18-E-49

-EFFLUENT

WATER WE BROWN 06-C-39 BLACK 00-E-53

WATER WITH

OIL WO BROWN 06-C-39

-POTABLE

WATER WP BLUE 18-E-53

-DEMINERALISED

WT BROWN 06-C-39 WHITE 00-E-55

UTILITY WATER WU PURPLE

BLUE 20-C-37

-SEA WATER WS YELLOW 10-C-33

-SOUR WATER WX VIOLET 22-D-45

-CONTAMINATED

WATER WK BROWN 06-C-39

-PROCESS WATER WR

(FRESH) WF RED 04-E-53 COMPLETE PIPE

FIRE WATER

(SEA WATER) WM RED 04-E-53 COMPLETE PIPE

DIESEL DL WHITE 00-E-55

-FUEL OIL FO CRIMSON 04-D-45

-LUBE OIL LO EMARALED

GREEN 14-E-53

-SEAL OR

GLAND OIL SO SALMN

PINK 04-C-33

-FLUSHING OIL FL PURPLE 24-C-33

-FIRE FOAM FF

BROWN

(For Oils) 06-C-39

RED 04-E-53

-BREATHING AIR AB PALE

GREEN 14-C-31 LIGHT BLUE FOR COMPLETE PIPE INSTRUMENT

AIR AI CREAM 08-C-31 LIGHT BLUE FOR

COMPLETE PIPE

BEIGE 10-B-17 LIGHT BLUE FOR COMPLETE PIPE

PIPE CONTENTS SYMBOLS

(SWEET) FG GREEN 14-C-39 PALE

GREEN 14-C-31

FUEL GAS (SOUR) FS GREEN 14-C-39 VIOLET 22-C-37

FLUE GAS LG VIOLET 22-C-37

-OVERHEAD GAS FROM AMINE PLANT

AG PURPLE 24-C-39

-REFRIGERANT RT SEA GREEN 16-C-37

-GENERAL

HYDROCARBONS PA BROWN 06-C-39

-HYDROCARBONS

WITH SULPHUR PB YELLOW 10-E-49

-HYDROCARBONS

WITH HYDROGEN PC PURPLE 24-C-33

-HYDROCARBONS WITH HYDROGEN

& H2S

PD PURPLE 24-C-33 YELLOW 10-E-49

HYDROCARBONS WITH

SOUR WATER

PE VIOLET 22-D-45 GREEN 12-D-45

PROCESS BLOWDOWN GENERAL

HYDROCARBONS BA BROWN 06-C-39

-HYDROCARBONS

WITH SULPHUR BB YELLOW 10-E-49

-HYDROCARBONS

WITH HYDROGEN BC PURPLE 24-C-33

-HYDROCARBONS WITH HYDROGEN

& H2S

BD PURPLE 24-C-33 YELLOW 10-E-49

HYDROCARBONS WITH SOUR WATER

BE VIOLET 22-D-45 GREEN 12-D-45

HYDROGEN HY CHARCOAL 00-A-13

-NITROGEN NI WHITE 00-E-55

-COKER MAZE

DRAIN MD BLACK 00-E-53 SKY

BLUE 18-E-49

CRACKED SLOPS SC BLACK 00-E-53 YELLOW 10-E-49

HEAVY SLOPS SH BLACK 00-E-53 GREEN

YELLOW 12-E-53

PIPE CONTENTS SYMBOLS

CATALYST CT PINK 04-C-33

-MOLTEN

SULPHUR SU YELLOW 10-E-49

-CHEMICALS CH LIGHT

SULPHURIC ACID VA YELLOW 10-D-45

-HYDROCHLORIC

ACID HA CREAM 10-B-15

-LOW STRENGTH

PRESSURE STEAM YS PALE

GREEN 14-C-31

-LOW PRESSURE

STEAM LS DARK

GREEN 14-C-39

-MEDIUM

PRESSURE STEAM MS GREEN 14-E-51

-HIGH PRESSURE

STEAM HS GREEN

YELLOW 12-D-43

-HIGH -HIGH

PRESSURE STEAM ZS GREEN

YELLOW 12-E-51

MC GREEN 14-E-51

-HIGH PRESSURE

-1.0 Flow Direction

Band markings and arrows shall be made at the unit battery limits and then on convenient location at the point of use. It is recommended to adopt one method for the entire plant.

1.1 Flow direction by bands

1.1.1 The coding shall be arranged as indicated in Figure – 1.

FIGURE 1

Basic Identification Colour Band Direction of Flow

Primary Colour Band

Dia PA

C A D A

Contents Code

B

1.1.2 For Dia > 4”, dimensions of ‘A’ and ‘D’ shall be 2 x Dia. (18” maximum) and dimensions of ‘B’ and ‘C’ shall be Dia / 2 (9” maximum).

1.1.3 For Dia < 4” , A = 100 mm, B = 50 mm, C = 25 mm and D = 100 mm.

1.1.4 Colour Band ‘C’ is located on down stream side of Basic Identification colour bands and indicates direction of flow. In case of double direction flow, the band ‘C’ will be located each side of band ‘A’.

1.2 Flow direction by Arrows

1.2.1 The arrows shall be situated in the proximity of the basic identification colour and painted White or Black in order to contrast clearly with the basic identification colour.

1.2.2 Arrow size :

- For pipes diameter 2” to 6”, arrow to fit in a 25 mm x 100 mm rectangular.

- For pipes diameter 8” and above, arrow to fit in a 50 mm x 150 mm rectangular.

1.2.3 Where flow of fluid is possible in either direction, the arrows will be indicated one above the other and the arrow heads in opposite directions. The colour of both the arrows will be same.

2.0 Identification with two colour bands (Primary and Secondary)

2.1. The procedure as indicated in Figure – 2 shall be used to identify services (such as for fuel gas, hydrocarbons etc) with two colour bands (Primary and Secondary) as described in Table – 1.

Figure- 2

Basic Identification Band Primary Band colour

D/3 D/3 D/3

Direction of Flow C B A A

D Secondary Band

2.2 The dimensions of ‘A’, ‘B’, ‘C’ and ‘D’ are same as per para 1.1.2 and 1.1.3.

3.0 Hazardous Mediums

Where the piping system carries a hazardous product, a panel of equal diagonal stripes (black and yellow colours) shall be superimposed on the pipe on both ends of the basic identification bands as detailed in Figure – 3.

Figure - 3

Direction of flow Basic Identification Bands

Equal Width Bands ** Primary Colour Band 45o

PA

A B C A D A B A Contents Code

Hazard Marking Hazard Marking

Note : 1) ** Stripes of Black 00-E-33 & Yellow 08-E-51 2) All other dimensions are as per para 1.1.2 & 1.1.3

B

4.0 Details of Contents Code Indication

4.1 The contents code indications shall be painted either in White or in Black in order to contrast clearly with the colour of paint on the pipe or equipment. For insulated lines the code indications shall be painted over the cladding of the insulation.

4.2 The name of fluid flowing inside a pipeline shall be indicated. The line number shall also be painted on the pipelines. The pressure or temperature of the fluid inside the pipeline shall not be indicated.

4.3 The contents code indication as described above shall be painted at following locations or such other places where quick identification is deemed necessary.

Pipe lines : At all junctions, both sides of valves, both sides of service appliances and at intervals of 30 Mtr on straight pipe lengths

For long straight lengths of pipelines, e.g., transfer lines, the interval of 30Mtr for code indication may be varied at the discretion of the Reliance.

4.4 The size of lettering for code indication on the insulated as well as uninsulated pipes is as follows. These sizes are only indicative and may be varied by the Reliance Engineer.

For Pipes : Diameter 2” NB - 25 mm letters For Pipes : Diameter 3” to 6” NB - 50 mm letters

For Pipes : Diameter 8”NB and above - 80 mm letters

5.0 Code Indication for Small Diameter Pipes

Code indication marking by paint may not be done for uninsulated pipelines of nominal diameter 1 ½” and below and for insulated lines less than 1” diameter.

For such pipes, the indication markings shall be punched on lead tags secured to the pipe. Such tags shall be provided at locations described in section 4.3 above. The size of the tag and the method of tying it with pipeline shall be as per advice of the Reliance Engineer.

6.0 Equivalent / Nearest IS Colour Shades SL

No. SHADE NAME SHADE NAME IS CODE /

BERGER

1 CHARCOAL / CHAR. GREY 00-A-13 IS 671

2 BLACK 00-E-53

-3 WHITE 00-E-55

-4 RED PURPLE 02-C-33 BERGER-589

5 SALMON PINK / PINK 04-C-33 BERGER-435

6 CRIMSON 04-D-45 IS 540

7 FIRE RED 04-E-53 IS 536

8 BROWN 06-C-39 IS 415

9 ORANGE 06-E-51 IS 557

10 CREAM 08-C-31 IS 442

11 YELLOW 08-C-35 IS 361

12 YELLOW 08-E-51 IS 356

13 LT GREY 10-A-03 IS 631

14 CREAM 10-B-15 BERGER-095

15 BEIGE 10-B-17 IS 364

16 YELLOW 10-C-33 IS 352

17 YELLOW 10-D-45 IS 222

18 YELLOW 10-E-49 IS 365

19 GREEN YELLOW / LT GREEN 12-C-33 IS 216

20 GREEN YELLOW 12-D-43 IS 278

21 GREEN 12-D-45 IS 219

22 GREEN YELLOW 12-E-51 IS 354

23 GOLD.YELLOW 12-E-53 IS 218

24 PALE GREEN 14-C-31 IS 275

25 GREEN / DARK GREEN 14-C-39 IS 226

26 GREEN 14-E-51 IS 280

27 EMERALD GREEN 14-E-53 IS 299

28 SEA GREEN 16-C-37 IS 102

29 SKY BLUE 18-E-49 IS 177

30 BLUE 18-E-53 IS 176

31 PURPLE BLUE 20-C-37 IS 166

32 LT. BLUE 20-E-51 BERGER-134

33 VIOLET 22-C-37 BERGER-712

Sl

No. SHADE NAME SHADE NAME IS CODE /

BERGER

34 VIOLET 22-D-45 IS 108

35 PURPLE 24-C-33 BERGER-728

36 PURPLE 24-C-39 IS 796

Appendix D : Coating Schedule (Other than Marine Environment)

“C’ Painting Schedule

Columns/Pressure Vessels/Exchangers/Heaters SURFACE PREPARATION , PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT

Ca To be insulated fireproofed upto 400o C

SA3 /

2 1/2 Shop 01 Shop - - 07 Shop 150

Cb

Uninsulated upto 120o C and nonfireproofed vessels skirts

SA2 1/2 Shop 04 Shop 05 Shop 06 Shop 245

Cc Uninsulated 121o C to 175o C

SA3 /

2 1/2 Shop 01 Shop - - 02 Shop 125

Primed surface to be free of zinc salts prior to finish coating

Cd Uninsulated 176o C to 400o C

SA3 /

2 1/2 Shop 01 Shop - - 03 Field 100

As “Cc” above notes.

Finish coat 03 may not fully cure until equipment is in service.

Ce

Ladders,platforms

including framing and steel supports other than vessel clips, handrails, stair treads, open grid flooring, toe boards, floor plates

SA2 1/2

Hot dip galvanise to BS 729. Min. Coating WT 610 grams/m2

Where not galvanised use systems “Cb” except as identified under code “Ch”

Cf

Austenitic stainless steel.

Operating between 50oC and 120o C

“See Remark”

SA 2 1/2

Shop - - - - 08 at

(100 DFT) Shop 100

Surface to be blast cleaned with “Vasilgrit” or other suitable Aluminium oxide abrasive.

Cg Austenitic stainless steel.

Operating between 120oC and 200o C

Shop 60 Surface to be blast cleaned with “Vasilgrit” or other suitable Aluminium oxide abrasive

Ch Stair treads, open grid

flooring, steel gratings SA 2

Shop - 3 Coats Bituminous paint to BS:3416 Type 1 applied by dipping, DFT 40 microns per coat

120

“C’ Painting Schedule

Columns/Pressure Vessels/Exchangers/Heaters SURFACE PREPARATION , PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT FINISH COAT

CODE DESCRIPTION

TYPE WHERE

DONE TYPE WHERE

APPLIED TYPE WHERE

APPLIED TYPE WHERE APPLIED

MIN.

TOTAL DFT MICRONS

REMARKS

Ci Direct buried vessels upto 400o C

SA 3 / 2

1/2 Shop 01 Shop 07

Note 3 Shop 11

Note 4

Shop or

Field 200

Note 3 Note 4 Note 5

For this service the coating shall be Amercoat 741 applied @ 125 microns D.F.T.

The coat (Amercoat 710 ) shall be applied after previous coat has fully cured only This system will only be used in tandem with cathodic protection.

Cj All vessels operating above

400o C SA2 1/2 Shop 12 Shop - - - - 75

“F’ Painting Schedule Tankage

SURFACE PREPARATION, PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT FINISH COAT

Insulated - No Painting

-Fb

External

Uninsulated upto 120oC

SA2 1/2 Field 01 Field 20 Field 18

(Note 1) Field 200

Where preparation is carried out in a shop or offsite it is mandatory that the first coat to be carried out at the same location

Fc

External

Uninsulated 121oC to 175oC

SA2 1/2 Field 01

Field - - 02 or

07 Field 125

Primed surface to be free of zinc salts prior to finish coating.

Shop built tanks will be shop painted

Fd Internal

Potable water SA2 1/2 Field 10 Field 10 Field 10 Field 240

Drinking water grade, approved National Water Council Certificate required.

Shop built tanks will be shop painted

Ff Internal SA2 1/2 Field 10 Field 10 Field 10 Field 240

This system for corrosive service only.

Shop built tanks will be shop painted

“F’ Painting Schedule Tankage (Continued)

SURFACE PREPARATION, PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT FINISH COAT CODE DESCRIPTION

TYPE WHERE

DONE TYPE WHERE

APPLIED TYPE WHERE

APPLIED TYPE WHERE APPLIED

MIN.

TOTAL DFT MICRONS

REMARKS

Fg External

Underside of all Tanks

SA2 ½

(Note 2) Field 09 Field - 175

A strip 75 mm wide at plate edge shall be left bare to avoid welding

contamination Fh

External

Austenitic stainless steel operating between 50o C and 120o C

- No Painting

Fi

External

Austenitic stainless steel operating between 121o C and 200o C

- No Painting

Note 1: Tankage within the Tank Farms that are designated Code Fb shall be camouflaged, as such they shall be finish painted with 60 microns of paint Type 18 to ensure a dull appearance.

Note 2: Where carboline Carbomastic 14 or Apcodur CF 655 (Asian) is used as the primer for the underside of tank plate , a commercial blast to SA 2 is acceptable.

( This does not apply to any immersion services)

“G’ Painting Schedule

Rotating Equipment (Including Pumps, Compressors, Fans, Motors, etc.)

SURFACE PREPARATION , PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT FINISH COAT

CODE DESCRIPTION

TYPE WHERE

DONE TYPE WHERE

APPLIED TYPE WHERE

APPLIED TYPE WHERE APPLIED

MIN.

TOTAL DFT MICRONS

REMARKS

Ga External

1. All except “Gb” as for codes Ca to Cg

2. Machinery and drivers, instruments and associated valves may be finish coated with manufacturer’s standard coating system.

Note: This standard will be subject to Reliance approval

Manufacturers should notify detauls of the proposed paints systems to facilitate repair and maintenance.

This system must be capable of the withstanding the enviornmental conditions for a period 5 years to Re 3 on European scale of degree of rusting.

Total system to be shop applied

Gb Moving Parts As for the system Cb with the exception that surface preparation will be to Standard ST3 Total system to be shop applied

Gc Austenitic stainless steel

Refer to Codes “Cf” and “Cg”.

“J’ Painting Schedule Instrumentation Equipment

SURFACE PREPARATION , PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT FINISH COAT CODE DESCRIPTION

TYPE WHERE

DONE TYPE WHERE

APPLIED TYPE WHERE

APPLIED TYPE WHERE APPLIED

MIN.

TOTAL DFT MICRONS

REMARKS

Ja Housing and Equipment

Supports Shop 04 Shop 05 Shop or

Field 06 Shop or

Field

245 Housing to be finished coated in seller works Jb Control panels This equipment shall have its surface prepared, primed and finished in accordance with manufacturers

standards.

Note: This standard will subject to Reliance approval. The system must be cable of withstanding the environmental conditions for a period of 5 years to ‘Re 3” on the European scale of degree of rusting.

All panels must display a smooth finish appearance.

Hammered or stippled etc. Are not

acceptable.

Jc Austenitic stainless steel Refer to Codes “Cf” and “Cg”.

“L” Painting Schedule Piping, Valves and Fittings SURFACE PREPARATION, PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT FINISH COAT

CS/AS Systems above 60oC but less than 120oC and not require steam out (Uninsulated)

SA2 1/2 Shop 01 Shop Note 4 - 06 Field 150

For PP insulated portion Type 01 to be applied.

La2

CS/AS Systems

(i) above 120oC but less than 200oC

(ii) Systems operating below 120oC but require steam out (Uninsulated)

SA2 1/2 Shop 01

Shop Note 4 - 02 Field 125

For PP insulated portion, generally no paint is required but Type 01 may be applied.

La3

Systems above 200oC but less than 400o C

(Uninsulated)

SA2 1/2 Shop 01 Shop Note 4 - 07

(Note 7) Field 150

For PP insulated portion, generally no paint is required but Type 01 may be applied.

Lb Systems upto 120oC that require

Colour coating SA2 1/2 Shop 01 Shop Note 4 - 06 Field 150 e.g. Fire water piping

1) Piping upto 60oC but not require steam out

Lc 2)Flare(OSBL)

SA2 1/2 Shop 14 Shop 15 Shop or

Field

16 Field 200 Type 15 to be applied in shop within 28 days of Primer application.

Lh1 Hot insulated piping 120o C SA2 1/2 Shop 01 Shop

This is also applicable for hot insulated piping upto 120o C which require steam out.

Lh2 Hot insulated piping > 120o C

-Note: The coating system for “Off the Shelf” valves could be manufactures standards subject to Reliance’s approval. The system must be capable of withstanding the environmental conditions for a period of 5 years to “Re 3” on the European scale of degree of rusting.

Contd. on next page

“L’ Painting Schedule

Piping, Valves and Fittings (Continued)

SURFACE PREPARATION, PRIMING & COATING SURFACE PREP FIRST COAT INTERMEDIATE

COAT FINISH COAT CODE DESCRIPTION

TYPE WHERE

DONE TYPE WHERE

APPLIED TYPE WHERE

APPLIED TYPE WHERE APPLIED

MIN.

TOTAL DFT MICRONS

REMARKS

Le Austenitic stainless steel

operating 50oC and 120oC - - -

-Lf Austenitic stainless steel

-Lf Austenitic stainless steel