• No results found

Configuration Configuration of of Inputs Inputs and and Outputs Outputs

In document Tm Mic Opmaint Eng (Page 69-72)

1.6. Switching Switching the the System System On On and and Off  Off

3.1.3. Engineering Engineering Offline Offline or or Online Online

3.1.3.5. Configuration Configuration of of Inputs Inputs and and Outputs Outputs

Optionally can be sent an SMS independently from the process communication upon stateOptionally can be sent an SMS independently from the process communication upon state change of up to 8 definable data points (phone number adjustable).

change of up to 8 definable data points (phone number adjustable).

For TM 1703 mic an automatic monitor can be set. At a fixed time the substation tries toFor TM 1703 mic an automatic monitor can be set. At a fixed time the substation tries to set up a connection to the master control. The time for the communication setup is free set up a connection to the master control. The time for the communication setup is free settable (hour, minute).

settable (hour, minute).

If in the network at a

If in the network at a defined moment a connection setup is carried out already (example:defined moment a connection setup is carried out already (example:

counter interrogation), delay times can be prevented as long as the monitoring function is counter interrogation), delay times can be prevented as long as the monitoring function is triggered temporal as far as

triggered temporal as far as possible from that moment.possible from that moment.

Selection "no Communication"

Selection "no Communication"

Optionally SMS can be sent. The p

Optionally SMS can be sent. The p reconditions for this are like for SMS upon dial-up traffic.reconditions for this are like for SMS upon dial-up traffic.

3.1.3.5.

3.1.3.5. Configuration Configuration of of Inputs Inputs and and Outputs Outputs

TM 1703 mic makes available integrated functions for the technological preparation of the TM 1703 mic makes available integrated functions for the technological preparation of the in-puts/outputs (preprocessing of signals, postprocessing of

puts/outputs (preprocessing of signals, postprocessing of signals).signals).

In a TM 1703

In a TM 1703 mic a maximum of 8 I/O modules can be operated. The following module typesmic a maximum of 8 I/O modules can be operated. The following module types are supported:

are supported:

Binary input moduleBinary input module

Binary output moduleBinary output module

Analog input moduleAnalog input module

Analog output moduleAnalog output module

Speed acquisition moduleSpeed acquisition module

In addition to this, the master control modules are also equipped with binary inputs/outputs.

In addition to this, the master control modules are also equipped with binary inputs/outputs.

Corresponding to the set configuration of the modules, their names can be found again in Corresponding to the set configuration of the modules, their names can be found again in thethe menu tree under the menu item P

menu tree under the menu item PERIPHERYERIPHERY. The same structure is also located under the. The same structure is also located under the menu item HW

menu item HW DDOCUMENTATIONOCUMENTATION..

In the mask P

In the mask P ARAMETER ARAMETER| P| PERIPHERYERIPHERY| <| <module namemodule name> | C> | CONFIGURATIONONFIGURATIONthe respective module-the respective module-specific inputs or outputs appear.

specific inputs or outputs appear.

Module specific a list of the pins and their settings appear. These settings specify type, name Module specific a list of the pins and their settings appear. These settings specify type, name and information object address (IOA) of each data point.

and information object address (IOA) of each data point.

Here, the inputs/outputs fixed assigned to the I/O module can be

Here, the inputs/outputs fixed assigned to the I/O module can be freely assigned from thefreely assigned from the hardware to data points in the software.

hardware to data points in the software.

Assignment of Inputs/Outputs to Information Objects Assignment of Inputs/Outputs to Information Objects Each I/O module is equipped with an individu

Each I/O module is equipped with an individu al number of physical input/outputs, that areal number of physical input/outputs, that are used for the acquisition or the output of electrical signals. In the configuration mask, for each used for the acquisition or the output of electrical signals. In the configuration mask, for each I/O module the module-specific inputs/outputs appear automatically together with the I/O module the module-specific inputs/outputs appear automatically together with the as-signed parameters.

signed parameters.

The assignment of the electrical signals to an I/O module is carried out according to the The assignment of the electrical signals to an I/O module is carried out according to the rela-tive terminal assignment. Based on the

tive terminal assignment. Based on the order of the configured modules, order of the configured modules, the system calcu-the system calcu-lates an absolute data point address (DP) for each input and output. Thi

lates an absolute data point address (DP) for each input and output. Thi s is unambiguouss is unambiguous  within a TM 1703 mic.

 within a TM 1703 mic.

Via parameter setting the electrical signals are

Via parameter setting the electrical signals are assigned to information objects. Each informa-assigned to information objects. Each informa-tion object is given an informainforma-tion object address (IOA1, IOA2, IOA3) for unambiguous tion object is given an information object address (IOA1, IOA2, IOA3) for unambiguous identi-fication. This address is used for

fication. This address is used for assigning the electrical signals for communication (telecon-assigning the electrical signals for communication (telecon-trol) and for control (automation).

trol) and for control (automation).

In the default is IOA1=DP, IOA2=0, IOA3=0. Alternatively for each information object an In the default is IOA1=DP, IOA2=0, IOA3=0. Alternatively for each information object an op-tional IOA (respectively between 0 and 255) can be

tional IOA (respectively between 0 and 255) can be parameterized.parameterized.

The exact details thereto can be found in

The exact details thereto can be found in thetheTM 1703 mic CP-60xx/CPC60 System Manual,TM 1703 mic CP-60xx/CPC60 System Manual, chapter "Architecture", section "Addressing of the Information Objects" 

chapter "Architecture", section "Addressing of the Information Objects" ..

 Altogether up to 256 data points can be configured. In addition, a long text of up to 10 chara  Altogether up to 256 data points can be configured. In addition, a long text of up to 10 charac-

c-ters can be freely assigned to each data point. This te

ters can be freely assigned to each data point. This te xt is used both in thext is used both in the DocumentationDocumentationasas  well as for a logging of the respective data point in the

 well as for a logging of the respective data point in theDisplay Event ListDisplay Event List..

 Assignment of information objects

 Assignment of information objects and inputs/outputs:and inputs/outputs:

Type

Type Meaning Meaning Connection Connection ScopeScope Single-point

Single-point informa-tion

tion

informatio

information n acquisition acquisition 1 1 binary binary inputinput

Double-point Double-point informa-tion

tion

information

information acquisitioacquisition n 2 2 successive successive binary binary inputsinputs

Integrated

Integrated total total count count pulse pulse acquisitioacquisition n 1 1 binary binary inputinput current

current acquisitioacquisition n 1 1 analog analog inputinput voltage

voltage acquisition acquisition 1 1 analog analog inputinput 2-wire

speed acquisition acquisition 1 1 impulse impulse inputinput Measured value

Measured value

frequency

frequency acquisition acquisition 1 1 impulse impulse inputinput

2 successive impulse inputs 2 successive impulse inputs 1-pole

1-pole 1 1 binary binary outputoutput 1½-pole

1½-pole*)*) 1 binary output + 1 binary 1 binary output + 1 binary outputoutput for group relay

for group relay Single

Single command command command command outputoutput

2-pole

2-pole*)*) 2 successive binary outputs2 successive binary outputs 1-pole

1-pole 2 2 successive successive binary binary outputsoutputs 1½-pole

1½-pole*)*) 2 successive binary outputs2 successive binary outputs + 1 binary output for group relay + 1 binary output for group relay Double

Double command command command command outputoutput

2-pole

2-pole*)*) 4 successive binary outputs4 successive binary outputs Single-Point

Single-Point Informa-tion

tion

binary

binary information information output output 1 1 binary binary outputoutput

Setpoint

Setpoint command command current current output output 1 1 analog analog outputoutput Setpoint

Setpoint command command voltage voltage output output 1 1 analog analog outputoutput

*)

*) does not apply for master controle module I/Os and DO-6200does not apply for master controle module I/Os and DO-6200

The precise description of the different information objects and the type identifiers (TI) can be The precise description of the different information objects and the type identifiers (TI) can be seen in the

seen in theTM 1703 TM 1703 mic CP-60xx/CPC60 System Manual, chapter "Telecontrol", sectionmic CP-60xx/CPC60 System Manual, chapter "Telecontrol", section

"Process Periphery" 

"Process Periphery" ..

In document Tm Mic Opmaint Eng (Page 69-72)