Bank 31: Binary output data of the AS-i slaves 1B – 31B
6.2 Error Displays of the CP 243-2 / Remedying Errors
<F 1>The following table lists the possible causes of errors that can occur when operating the CP 243-2 and how to remedy the problem.
Table 6-1 Error Displays of the CP 243-2 / Remedying Errors
Error Possible Cause Remedy
APF LED lit The AS-Interface power supply unit is not connected or is defec-tive.
Check the connection of the AS-Interface power supply unit; if ne-cessary replace the power supply unit.
Power requirements of the AS-In-terface slaves are too high. Re-sult: The voltage on the AS-Inter-face cable is too low.
Check the power requirements of the AS-Interface slaves. If neces-sary, supply the slaves with power externally.
Short-circuit on the AS-Interface cable.
Check the AS-Interface cable and the attached slaves.
SF lights up without pressing the SET button.
The CP 243-2 is defective. Inter-nal EEPROM error.
Replace the CP 243-2.
SF is lit when the SET button is pressed.
An AS-Interface slave with ad-dress 0 exists when there is a change to the protected mode.
Remove the slave with address 0 from the AS-Interface cable.
CER is lit permanently. The CP 243-2 has not yet been configured.
Configure the CP 243-2 using the mode button on the front panel.
A configured AS-Interface slave has failed (evaluate the slave dis-play).
Replace the defective AS-Inter-face slave or configure the CP 243-2 again if the slave is not required.
An unconfigured AS-Interface slave was connected to the AS-In-terface cable.
Remove the AS-Interface slave or reconfigure the CP 243-2 . An AS-Interface slave was
con-nected whose configuration data (I/O configuration, ID codes) do not match the values of the confi-gured AS-Interface slave.
Check whether the wrong AS-In-terface slave has been connec-ted. If necessary, reconfigure the CP 243-2.
CER display flickers, in other words a configured AS-Interface slave is lost sporadically.
Bad electrical connection. Check the electrical connections of the AS-Interface slaves.
Noise affecting the AS-Interface cable.
Check the correct grounding of the S7-200 and check the AS-In-terface cable. Check that the shield of the AS-Interface power supply unit is connected correctly.
Table 6-1 Error Displays of the CP 243-2 / Remedying Errors
Error Possible Cause Remedy
The CP 243-2 does not switch from the configuration mode to the protected mode.
The S7-200 CPU is in the “RUN”
mode.
Switch the S7-200 CPU to
“STOP”. This sets the PLC_RUN bit to 0.
The SET button was not pressed long enough.
Press the button for at least 0.5 seconds.
A slave with address “0” is con-nected to the AS-Interface cable.
The CP 243-2 cannot change to the protected mode as long as this slave exists.
Remove the slave with address 0.
The CP 243-2 does not switch from the protected mode to the configuration mode.
The S7-200 CPU is in the “RUN”
mode.
Switch the S7-200 CPU to
“STOP”.
This sets the PLC_RUN bit to ‘0’.
Button not pressed long enough Press the button for at least 0.5 seconds.
After failure of an AS-Interface slave, the “AUP” display remains off.
The CP 243-2 is in the configura-tion mode.
“Automatic programming” is not possible in the configuration mode.
Program the address of the new AS-Interface slave with the ad-dressing unit.
More than one AS-Interface slave has failed.
Check the AS-Interface cable.
If “APF” is displayed at the same time, check the power supply on the AS-Interface cable.
If more than one AS-Interface slave is defective, program the ad-dress on the replaced AS-Inter-face slaves using the addressing unit.
The CP 243-2 has not detected configured AS-Interface slaves.
Remove the unconfigured AS-In-terface slaves from the AS-Inter-face cable.
The AUTO_ADDR_ENABLE flag is not set.
Set the bit with the appropriate commands or by pressing the SET button during AS-i Power Fail.
Table 6-1 Error Displays of the CP 243-2 / Remedying Errors
Error Possible Cause Remedy
Automatic address programming is unsuccessful although the
“AUP” display is lit.
The configuration data (I/O confi-guration, ID codes) of the repla-ced AS-Interface slave do not match the values of the original AS-Interface slave.
Check whether the correct “repla-cement slave” was used.
Compare the information from the manufacturer about configuration data.
If you want to replace the original AS-Interface slave with a different type, assign the address with the addressing unit and reconfigure the CP 243-2 (for example by pressing the SET button).
The replaced AS-Interface slave does not have the address “0”.0
Set the address of the replaced AS-Interface slave with the ad-dressing unit.
Replaced AS-Interface slave is not correctly connected or is de-fective.
Check the connections of the AS-Interface slave and if necessary replace the AS-Interface slave.
The “CER” LED and the LEDs of active AS-Interface slaves flicker irregularly.
An extender is installed in the AS-Interface with “Line1” and “Line2”
connections reversed.
Correct the connections to the ex-tender.