• No results found

Input Command Description

In document Consilium Tablero c i (Page 85-99)

4.3 Inputs

4.3.2 Input Command Description

4.3.2.1 ALARM DELAY ON

Reads the status of the alarm delay function on the control panel. This description is only valid for a marine installation.

Syntax:

ALARM DELAY ON

Comments:

- Alarm delay is central dependent.

- Default: In marine applications, the alarm delay function is by default set to on. In industrial applications, the alarm delay function is by default set to off.

- The control panel: In marine applications, the ALARM DELAY indicator on the control panel is lit when the alarm delay is set to off. In industrial applications, the ALARM DELAY indicator on the control panel is lit when the alarm delay is set to on.

- To set alarm delay: The alarm delay is set on the control panel. For systems with only one control unit the unit number is omitted. For more information about the alarm delay function, see the User's Guide.

ALARM DELAY ON => OUT 1.1.2;

Output 2 on system module 1 is activated if the alarm delay function is true, i.e. the ALARM DELAY indicator is not lit. Output 2 is not active if the ALARM DELAY indicator is lit.

Related Commands:

Table 6.

AD [x S] [, Conditions] Specifies the alarm delay function for a marine installation.

MESSAGE ALARM DELAY {ON, OFF,

ON/OFF} Is used to change status of alarm delay function.

AH [x] S, [y] S, Input [, Condition] Specifies the alarm delay function for an industrial installation.

4.3.2.2 ALARM TRANSFER OFF

The command is true if outputs of type alarm transfer are disconnected.

Example:

ALARM TRANSFER OFF => OUT 1.1.2;

4.3.2.3 BATTERY FAULT

The BATTERY FAULT command is true if there is a battery fault in the system.

Syntax:

BATTERY FAULT

Example:

BATTERY FAULT => OUT 1.3.1;

Output 1 on system module 3 is active as long as there is a battery fault in the current central.

Related Commands:

Table 7.

NET FAULT Is true if there is a net fault in the system.

4.3.2.4 CONTROLS OFF

The CONTROLS OFF command is true if one or more outputs of the types General, Door, Fire, Fault, Ventilation or Indication hatch are switched off in the current central.

Syntax:

CONTROLS OFF

Example:

CONTROLS OFF => OUT 1.3.4;

Output 4 on system module 3 is active as long as there are outputs of the types General, Door, Fire, Fault, Ventilation or Indication hatch switched off.

Related Commands:

Table 8.

EXTALARM OFF Is true if one or more outputs of the type Alarm device (bell) are switched off.

4.3.2.5 CU z.x DOOR

Specifies if the door is open on panel x. The input CU z.x DOOR is true if the door of the specified panel is open.

Syntax:

CU z.x DOOR

Parameters:

Table 9.

z Specifies a central address.

x Specifies a panel address.

Examples:

CU 1.5 DOOR => OUT 1.3.2;

In this example, the command is true if the door is open on the panel in central 1 configured as 5.

4.3.2.6 DISC [ORDER]

The DISC command is true when there is a disablement (disconnection) in the system.

• DISC ADD is true for a short while when any disablement is added.

• DISC CHD is true for a short while when any disablement is added or removed.

• DISC REM is true for a short while when any disablement is removed.

Syntax:

DISC DISC ADD DISC CHD DISC REM

Example 1:

DISC CHD => SET FLAG 8;

FLAG 8 => OUT 1.4.1;

In this example, output 1 on system module 4 is activated for 5 seconds if a disablement is added or removed.

Example 2:

DISC => OUT 1.4.1

In this example, output 1 on system module 4 is activated as long as there is a disablement in the system.

4.3.2.7 DISC ZONE x ADDRESS y

Syntax:

DISC ZONE x ADDRESS y

Any disablement activated with the command on the same zone where “ADDRESS y” belongs to activates the output.

NOTE!

The instruction DISC ZONE x ADDRESS y should never be called with the same arguments more than once. If doing so the result may become very

nondeterministic. If the result is needed more than once, FLAG should be used.

However, you can of course use the same instruction with different input commands several times, such as:

DISC ZONE 12 ADDRESS 5 =>

DISC ZONE 12 ADDRESS 6 =>

CAUTION!

Due to the complexity of the instruction DISC ZONE x ADDRESS y the system will suffer a lot of processing power if too many are used. This slowdown will be noticed whenever a disablement is either added or removed. It is therefore recommended to not have more than 200 instances of this instruction in the configuration.

Example:

DISC ZONE 159 ADDRESS 30 => OUT 1.55.7;

In this example, command ADDRESS 30 is a smoke/heat detector; however a disablement of MCP(s) in the same zone (ZONE 159) will activate the output.

4.3.2.8 EXTALARM OFF

The EXTALARM OFF command is true if one or more outputs of the type Alarm device (bell) are switched off in the current central.

Syntax:

EXTALARM OFF

Examples:

EXTALARM OFF => OUT 1.3.2;

Output 2 on system module 3 is active as long as there are outputs of the type Alarm device (bell) switched off.

Related Commands:

Table 10.

CONTROLS OFF Is true if one or more outputs of the types General, Door, Fire, Fault, Ventilation or Indication hatch are switched off.

4.3.2.9 FAULT IN SYSTEM

Reads the fault status in the system. The FAULT IN SYSTEM command is true if one or more faults are present in the system. The command is true until all faults have been reset.

Syntax:

FAULT IN SYSTEM

Examples:

FAULT IN SYSTEM => OUT 1.1.2;

Output 2 on system module 1 is active if a fault is present in the system.

Related Commands:

Table 11.

UNMUTED FAULT Reads the unmuted fault status in the system.

4.3.2.10 FIRE IN SYSTEM

Reads the fire alarm status in the system. The FIRE IN SYSTEM command is true if there are one or more fire alarms in the system. The command remains true until all fire alarms have been reset.

Syntax:

FIRE IN SYSTEM

Example 1:

FIRE IN SYSTEM & NOT OPEN DOOR => OUT 1.3.7;

In this example, output 7 on system module 3 is activated if a fire alarm is detected and no panel door is open. This output may, for example, be connected to the fire brigade.

Example 2:

FIRE IN SYSTEM > 1 => OUT 1.3.8;

In this example output 8 on system module 3 is activated if there is at least two fire alarms in the system. Useful for example when making “2-detector dependency”

commands.

Related Commands:

Table 12.

ZONE x-y [Type] Reads the status of the fire alarms in zone/zones.

4.3.2.11 FLAG x / SYSTEM VIO x

The FLAG command is a macro command. You can use the FLAG command to replace long expressions of input commands. A total of 255 different FLAG configurations can be present at the same time.

SYSTEM VIO is used to configure menus connected to customer shortcuts on the panels. See user menu underCustom Keys Tab, page 36for more info.

CENTRAL VIO is used to define custom faults and alarms within a central. See VIO tab underDescription of the fields and buttons in the Central window, page 23for more info.

Syntax:

FLAG x

[SYSTEM] VIO x CENTRAL VIO x

Parameters:

Table 13.

x Select a number between 1 and 255.

Examples FLAG:

ZONE 1 DET 1-17 & ZONE 2 DET 5-19 & ZONE 3 DET 6-36 =>

FLAG 35;

In this example, FLAG 35 is used to define a fire zone, consisting of several zones.

ZONE 4 | FLAG 35 => OUT 1.3.3;

ZONE 5 | FLAG 35 => OUT 1.3.9;

The FLAG 35 is then used to activate output 3 on system module 3 in central 1 if a fire alarm is detected in zone four or in the defined fire zone. The FLAG is also used to activate output 9 on system module 3 in central 1 if a fire alarm is detected in zone 5 or in the configured fire zone.

Example SYSTEM VIO:

SYSTEM VIO 1 => OUT 1.5.2;

When custom shortcut 1 on Control Panel M 4.3 is pressed, user menu 1 is displayed. If row 1 in the user menu is pressed, output 2 on system module 5 will be activated (VIO 1 is set, as shown in the figure below).

Example CENTRAL VIO:

CENTRAL VIO 3 => OUT 1.1.2;

An expression with command CENTRAL VIO is used in the same way as SYSTEM VIO.

Related Commands:

Table 14.

RESET FLAG x It is possible to add functionality to the macro command FLAG with this command. Used only as an output command.

SET FLAG x It is possible to add functionality to the macro command FLAG with this command. Used only as an output command.

Comments:

- VIO can also be controlled in the Cause/Effect sheets, to give indications in the user menu. In this case, Indication only (refer to the figure above) must be selected.

4.3.2.12 IN z.x.y

CAUTION!

It is only allowed to use this command to control module outputs on the same central, and should never be used to control other central’s outputs.

True if input y on system module x on central z is activated.

Syntax:

IN z.x.y

Parameters:

Table 15.

z, x, y z specifies the central, x specifies system module address, y specifies input number.

Example:

IN 1.4.1 => OUT 1.5.2

Output 2 on system module 5 on central 1 is active if input 1 on system module 4 on central 1 is active.

Related Commands:

Table 16.

ZONE x IN y.z The command reads the input status of a control module.

4.3.2.13 MINI RESET alt MINIREPEATER RESET

This input follows the status of the output mini reset.

Example:

MINI RESET => OUT 1.1.6;

Output 6 on module 1 in central 1 is activated if output in mini reset is true.

4.3.2.14 MUTE MINI alt MUTE MINIREPEATER

True for 20 seconds when a mini repeater that has control privileges is muted.

Example:

FIRE IN SYSTEM & MUTE MINIREPEATER => SET FLAG 2

Sets flag 2 when fire in system and minirepeater with control privileges are muted.

4.3.2.15 NET FAULT

The command NET FAULT is true if there is a net fault in the current central.

Syntax:

NET FAULT

Examples:

NET FAULT => OUT 1.4.4;

Output 4 on system module 4 in central 1 is active as long as there is a net disturbance in the system.

Related Commands:

Table 17.

BATTERY FAULT Is true if there is a battery fault in the current central.

4.3.2.16 OUT z.x.y

Specifies the output y on system module x on central z.

Syntax:

OUT z.x.y

Parameters:

Table 18.

x, y, z x specifies system module address, y specifies output number, z specifies the central.

Example:

OUT 1.4.1 => CU 1.7 LED 4

LED 4 on panel 7 is lit if output 1 on module 4 in central 1 is activated.

Related Commands:

Table 19.

ZONE x OUT y.z [MSK n] The command reads the output status of a control module.

4.3.2.17 PRE-ALARM IN SYSTEM

The PRE-ALARM IN SYSTEM command is true if one or more pre-alarms are present in the system. The command is true until all pre-alarms are removed.

Syntax:

PRE-ALARM IN SYSTEM

Examples:

PRE-ALARM IN SYSTEM => OUT 1.1.2;

Output 2 on system module 1 in central 1 is active if a prealarm is present in the system.

4.3.2.18 TCMS_STATUS x.y

Input specific for train protocols.

Syntax:

TCMS_STATUS x.y

4.3.2.19 TCMS_STATUS_BYTE 0xYYYYYYYY

Input specific for train protocols.

Syntax:

TCMS_STATUS_BYTE 0xYYYYYYYY

4.3.2.20 SYSTEM VIO x

SeeFLAG x, page 101.

4.3.2.21 UNMUTED FAULT

Reads the fault status of the system. The UNMUTED FAULT command remains true until all faults in the system are muted.

Syntax:

UNMUTED FAULT

Examples:

UNMUTED FAULT : TIMER 60 S => OUT 1.4.1;

In this example output 1 on system module 4 is activated if the fault is not muted during the time delay.

Related Commands:

Table 20.

FAULT IN SYSTEM Reads the fault status in the system.

4.3.2.22 UNMUTED FIRE IN SYSTEM

LikeFIRE IN SYSTEMbut only true if one or more fire alarms in the system are unmuted.

Syntax:

UNMUTED FIRE IN SYSTEM

4.3.2.23 UNMUTED MINI alt UNMUTED MINIREPEATER

True for 20 seconds if a reset order fails on a mini repeater.

Example:

(NOT FIRE IN SYSTEM | UNMUTED MINIREPEATER) & FLAG 2 => RESET FLAG 2;

If flag 2 is set, it is reset if there is no fire in the system or a reset on a minirepeater fails.

4.3.2.24 UNMUTED ZONE [Type]

LikeZONE [Type]but only true when there is at least one unmuted fire alarm of the specified detector type.

Syntax:

UNMUTED ZONE [Type]

4.3.2.25 UNMUTED ZONE x [Type] [y[-z]]

LikeZONE x [Type] [y[-z]]but only true when there is at least one unmuted fire alarm of the specified Type within the address interval y-z in zone x.

Syntax:

UNMUTED ZONE x [Type][y[-z]]

4.3.2.26 UNMUTED ZONE x-y [Type]

LikeZONE x-y [Type]but only true when there is at least one unmuted fire alarm of the specified Type within the zone interval x-y.

Syntax:

UNMUTED ZONE x-y [Type]

4.3.2.27 WARNING IN SYSTEM

The WARNING IN SYSTEM command is true if one or more warnings are present in the system. The command is true until all warnings are removed.

Syntax:

WARNING IN SYSTEM

Examples:

WARNING IN SYSTEM => OUT 1.1.2;

Output 2 on system module 1 is active if a warning is present in the system.

4.3.2.28 ZONE [Type]

Specifies detector types that may indicate fire alarm. The ZONE command is true when there is a fire alarm of the specified type.

Syntax:

ZONE [Type]

Parameters:

Table 21.

Type Specifies the detector type. One of the following types can be used:

Type Explanation

All fire detectors, including manual call points.

All fire detectors, including manual call points.

All automatic fire detectors, excluding manual call points.

Flame detectors.

Heat detectors, both maximal and rate-of-rise.

Manual call points.

Smoke detectors.

Smoke/heat detectors.

Sprinklers.

Comments:

- Default values: The default value for Type is ALL.

- Type: The functions of the types ALL and ADDRESS are identical.

NOTE!

Items enclosed in square brackets are optional. Do not type the brackets when including an optional item.

Example:

ZONE => OUT 1.4.3;

All alarms from all zones in the central make output 3 on system module 4 in central 1 active.

4.3.2.29 ZONE x [Type] [y[-z]]

Specifies detectors in different zones that may indicate fire alarm. The ZONE command is true when there is a fire alarm of the specified Type within the address interval y-z in zone x.

Syntax:

ZONE x [Type][y[-z]]

Parameters:

Table 22.

x The zone number. All zones in one central unit are specified if you omit the zone number. The zone number is a number between 1- 65534.

Type Specifies the detector type. One of the following types can be used:

Type Explanation

All fire detectors, including manual call points.

All fire detectors, including manual call points.

All automatic fire detectors, excluding manual call points.

Flame detectors.

Heat detectors, both maximal and rate-of-rise.

Manual call points.

Smoke detectors.

Smoke/heat detectors.

Sprinklers.

y, z Specifies a single detector address or a detector address interval. y and z can be set to any number between 1-65534.

Comments:

- No parameters: The command reacts on all alarms on all zones in the central unit if you do not specify any parameter.

- Default values: The default value for x is all zones. The default value for Type is ALL.

- Type: The function of the types ALL and ADDRESS are identical.

NOTE!

Items enclosed in square brackets are optional. Do not type the brackets when including an optional item.

Examples:

ZONE 3 => OUT 1.4.8;

All alarms from zone 3 makes output 8 on system module 4 active.

ZONE 3 SD 2 => OUT 1.4.11;

A fire alarm on smoke detector 2 in zone 3 makes output 11 on system module 4 in central 1 active.

ZONE 3 DET 2-8 => OUT 1.4.7;

An alarm from any automatic detector in the interval 2-8 in zone 3 makes output 7 on system module 4 in central 1 active.

4.3.2.30 ZONE x-y [Type]

Specifies different zones where detectors may indicate fire alarm. The ZONE command is true when there is a fire alarm of the specified Type within the zone interval x-y.

The a single zone number or a zone number interval. All zones in one central unit are specified if you omit the zone number. The zone number is a number between 1- 65534.

Type Specifies the detector type. One of the following types can be used:

Type Explanation

All fire detectors, including manual call points.

All fire detectors, including manual call points.

All automatic fire detectors, excluding manual call points.

Flame detectors.

Heat detectors, both maximal and rate-of-rise.

Manual call points.

Smoke detectors.

Smoke/heat detectors.

Sprinklers.

Comments:

- No parameters: The command reacts to all alarms in all zones in the central unit if you do not specify any parameter.

- Default values: The default value for x is all zones. The default value for Type is ALL.

- Type: The functions of the types ALL and ADDRESS are identical.

NOTE!

Items enclosed in square brackets are optional. Do not type the brackets when including an optional item.

4.3.2.31 ZONE [Type] FAULT [FAULT TYPE]

Specifies faults. The command is true when a fault of the specified FAULT TYPE is present on a detector of the specified Type.

Syntax:

ZONE [Type] FAULT [FAULT TYPE]

Parameters:

See table for the ZONE [Type] parameters.

Comments:

See comments for the ZONE [Type].

Example:

ZONE FAULT => OUT 1.4.7

Output 7 on system module 4 is activated when any fault is reported from any zone.

4.3.2.32 ZONE x [Type] [y-[z]] FAULT [FAULT TYPE]

Specifies faults. The command is true when a fault of the specified FAULT TYPE is present on a detector of the specified Type in the address interval y-z in zone x.

Syntax:

ZONE x [Type] [y[-z]] FAULT [FAULT TYPE]

Parameters:

See table for the ZONE x [Type][y[-z]] parameters.

Comments:

See comments for the ZONE x [Type][y[-z]].

Examples:

ZONE 8 FAULT 128 => OUT 1.4.7

Output 7 on system module 4 is activated when fault no. 128 “no answer” is reported from any unit in zone 8.

ZONE 7 ALL 9-9 FAULT => OUT 1.5.2

Output 2 on system module 5 is activated when a fault is reported from loop unit 9 in zone 7.

4.3.2.33 ZONE x-y [Type] FAULT [FAULT TYPE]

Specifies faults. The command is true when a fault of the specified FAULT TYPE is present on a detector of the specified Type in the zone interval x-y.

Syntax:

ZONE x-y [Type] FAULT [FAULT TYPE]

Parameters:

See table for the ZONE x-y [Type] parameters.

Comments:

See comments for the ZONE x-y [Type].

4.3.2.34 ZONE x IN y.z

The command reads the input status of a control module.

Syntax:

ZONE x IN y.z

Parameters:

Table 24.

x

Specifies the zone number. All zones in one central unit are specified if you omit the zone number. The zone number is a number between 1-65534 depending on the configuration of the central unit.

y, z Specifies a single input address, y can be 1-65534 and z 1-8.

Examples:

ZONE 1 IN 1.5.1 => OUT 1.4.1;

Output 1 on system module 4 in central 1 is activated if input address 5.1 on zone 1 is set.

Related Commands:

Table 25.

IN z.x.y Specifies the input y on system module x in central z.

ZONE x OUT y.z [MSK n] Sets an output on a control module.

In document Consilium Tablero c i (Page 85-99)