CONFIGURATION AND PROGRAMMING
3-3.2 LIST MENU FUNCTIONS
The List functions are used to view the set of isolated initiating devices and control unit-based and SLC-based outputs. These functions are also used to display configuration settings for automatic initiating devices, to display the list of devices on the SLC, and to view lower-level events that are not displayed due to the occurrence of higher-level events.
Figure 3-13 through Figure 3-16 outline the List menu functions. Each function is explained in detail in the remainder of Section 3-3.2.
Figure 3-13. ARIES NETLink List Menu Functions (Fig. 1 of 4) 2. LIST
Cont’d
1. Isolated Devices
1. SLC Devices
2. Event Logs
Enter Begin and End Dates for Range Date Range *_-__-__ to __-__-__ (MMDDYY)
1. All System Events
2. Range of Events
3. SLC Test Results
4. Walk Test Results
SLC Module Selection
Enter SLC Module Number (1-8):_*
SLC Module Selection
Enter SLC Module Number (1-8):_*
3. Device Readings
SLC Module Selection
Enter SLC Module Number (1-8):_*
1
Enter Module Logical Address:_*
Isolate Control Modules
SLC Test Results Listing SLC Devices*__ to ___ (1-255)
Walk Test Results Listing SLC Devices*__ to ___ (1-255)
SLC Device Readings SLC Devices*__ to ___ (1-255)
FOOTNOTES (Figure 3-13):
1 Isolated Devices. Purpose: To view the list of isolated devices and output circuits.
2 All System Events. List the Entire Contents of the System Event Log. Purpose: To view the history of system events.
3 Range of Events. List the Contents of the System Event Log by Dates. Purpose: To view the history of system events by selected dates.
4 SLC Test Results. List the Most Recent Test Results for the Initiating Devices on the SLC.
Purpose: To view the most-recent test results for the initiating devices on the SLC. These tests confirm the abilities of the initiating devices to create and transmit alarm signals that can be properly interpreted and processed by the ARIES NETLink control unit.
5 Walk Test Results. List Most Recent WalkTest Results for the Initiating Devices on the SLC.
Purpose: To view the most-recent walk-test results for the initiating devices on the SLC.
6 Device Readings. List a Range of Automatic Detector Sensitivity Settings. Purpose: To view the pre-alarm and alarm thresholds for a range of automatic detectors and to view the fire signatures being currently measured by the detectors. This procedure fulfills the intent of NFPA 72 (2002) Paragraph 10.4.3.2.4, Part (4) as a test to ensure that each smoke detector is within its listed and marked sensitivity range.
Figure 3-14. ARIES NETLink List Menu Functions (Cont’d - Fig. 2 of 4)
FOOTNOTES (Figure 3-14):
7 Active Events. Purpose: To view the list of active events by event type. Use this option to view lower-level events such as trouble events whose display is suppressed by the concurrent occurrence of higher-level events.
2. LIST
Cont’d
1. Pre-Alarm Events
2. Alarm Events
3. Supervisories
4. Troubles
4. Active Events 5. Programming
5. Current Time/Date
1. EOC Program
2. SLC Assignments
3. On Board
4. Backplane
5. Control Modules
6. General Alarm
1. RDCM Config
2. LAM Config
3. Call for Service
Enter RDCM Address (1-15):_*
Enter LAM Address (1-16):_*
SLC Module Selection
Enter SLC Module Number (1-8):_*
1. NACs 2. RNACs 3. Relays
1. RNAC
2. Relay
3. City Tie
4. PMU
Enter Module Logical Address:_*
Enter Module Logical Address:_*
Enter Module Logical Address :_*
7
8
9
8 EOC Program. Purpose: To view the Event-Output-Control (EOC) part of the system configuration file.
9 SLC Assignments. Purpose: To view the registered devices on the SLC.
Figure 3-15. ARIES NETLink List Menu Functions (Cont’d - Fig. 3 of 4)
FOOTNOTES (Figure 3-15):
10 Line Voltage. List a Range of SLC Device Voltages. Purpose: To view the SLC line voltages for a range of initiating and/or control devices.
11 9 Volts. List a Range of SLC Devices’ 9-Volt Levels. Purpose: To view the internal power-supply voltages for a range of SLC initiating and/or control devices.
2. LIST
Cont’d
SLC Module Selection
Enter SLC Module Number (1-8):_*
6. Voltages
1. Line Voltage
2. 9 Volts
3. Battery Charge
SLC Module Selection
Enter SLC Module Number (1-8):_*
4. Gnd Fault Offset
Ground Fault Offset Voltage Enter Module Logical Address __
7. List Versions
1. Main CPU
3. SLC and Backplane
4. Control Modules
10
11
12
13
BATTERY VOLTAGE AND CURRENT Battery Data
OCBV:__.__ BCC:_.__ BCV:__.__
Main CPU App Version:_._._
Main CPU Boot Version:___.__
1. RNAC
Enter Logical Address Range: *__to__
2. Relay
Enter Logical Address Range: *__to__
3. City Tie
4. PMU
Enter Logical Address Range: *__to__
5. SLC
Enter Logical Address Range:*__to__
Enter Logical Address Range:*__to__
14 Main Display App Version:____
Main Display Boot Version:____
2. CPC
CPC App Version:_._._
CPC Boot Version:___.__
12 Battery Charge. View the Values of the Battery Voltage and Current. Purpose: To view the latest current and voltage values of the battery. Note: This command can only be used if battery supervision is enabled.
13 List Versions. View the Configurable Parameters for the Control Units On-Board Outputs.
Purpose: To determine how the control unit’s on-board outputs are programmed.
14 RDCM. List the Remote Display Control Modules Connected to the Control Unit. Purpose:
To view the list of remote-display modules connected to an ARIES NETLink control unit
Figure 3-16. ARIES NETLink List Menu Functions (Cont’d - Fig. 4 of 4)
FOOTNOTES (Figure 3-16):
15 RRM Memory Status. View the Memory Status of Remote Release Modules. Purpose: To get diagnostic information concerning the memory status of RRM modules. Contact Kidde Fire 2. LIST
9. RRM Data
1. RRM PSU Status
SLC Module Selection
Enter SLC Module Number (1-8):_*
2. RRM Memory Status 8. Serial Numbers
1. Main CPU
2. SLC and Backplane
3. Control Modules 1. RNAC
Enter Logical Address Range:*__to__
2. Relay
Enter Logical Address Range:*__to__
3. City Tie
4. PMU
Enter Logical Address Range:*__to__
5. SLC
Enter Logical Address Range:*__to__
1. Main Display
2. RDCM
3. LAM
Enter RDCM Address (1-15) __
Enter LAM Address (1-16) __
SLC Module Selection
Enter SLC Module Number (1-8):_*
15
City-Tie Serial Number:_______