• No results found

Negative Sequence Overcurrent Protection Settings

5 Management Function Table of Contents

7.3 Protection Settings

7.3.3 Negative Sequence Overcurrent Protection Settings

The negative sequence overcurrent protection settings (in the submenu “NegOC Settings”) are used to determine the characteristic of the negative sequence overcurrent protection.

No. Menu text Explanation Range Step

1 50/51Q1.I2_Set The current setting of the stage 1 negative

sequence overcurrent protection 0.05In~4In 0.001A 2 50/51Q1.t_Op The time setting of the stage 1 negative sequence

overcurrent protection 0~100s 0.001s

3 50/51Q1.En The logic setting of the stage 1 negative sequence

overcurrent protection 0~1 1

4 50/51Q1.OutMap The output matrix setting of the stage 1 negative sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1 5 50/51Q2.I2_Set The current setting of the stage 2 negative

sequence overcurrent protection 0.05In~4In 0.001A 6 50/51Q2.t_Op The time setting of the stage 2 negative sequence

overcurrent protection 0~100s 0.001s

7 50/51Q2.En The logic setting of the stage 2 negative sequence

overcurrent protection 0~1 1

8 50/51Q2.OutMap The output matrix setting of the stage 2 negative sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1 9 50/51Q2.Opt_Curve The setting is for selecting the inverse time

characteristic curve for the NOC2 protection 0~13 1 10 50/51Q2.TMS The time multiplier setting of the negative

sequence IDMT overcurrent protection 0.05~100.0 0.001 11 50/51Q2.tmin The minimum operation time setting of the

negative sequence IDMT overcurrent protection 0~100s 0.001s 12 50/51Q2.K Constant “k” for the negative sequence IDMT

overcurrent protection, see Section 3.7.2 0.001~120.0 0.0001 13 50/51Q2.C Constant “C” for the negative sequence IDMT

overcurrent protection, see Section 3.7.2 0.00~1.00 0.0001 14 50/51Q2.Alpha Constant “α” for the negative sequence IDMT

overcurrent protection, see Section 3.7.2 0.01~3.00 0.0001

7.3.4 Sensitive Earth Fault Protection Settings

The sensitive earth fault protection settings (in the submenu “SEF Settings”) are used to determine the characteristic of the sensitive earth fault protection.

All the settings of the sensitive earth fault protection are listed in the following table.

No. Menu text Explanation Range Step

1 50/51SEF.RCA The relay characteristic angle for the directional

sensitive earth fault protection -180°~179° 1° 2 50/51SEF.En_VTS_Blk

The logic setting of the function which blocks the SEF protection related voltage measurement when the voltage transformer is failed

0~1 1

3 50/51SEF1.3I0_Set The current setting of the stage 1 sensitive earth

4 50/51SEF1.t_Op The time setting of the stage 1 sensitive earth

fault protection 0~100s 0.001s

5 50/51SEF1.Opt_Dir The setting is used to select the directional mode

for the stage 1 SEF protection, see Section 3.6.3 0~2 1 6 50/51SEF1.En The logic setting of the stage 1 sensitive earth

fault protection 0~1 1

7 50/51SEF1.OutMap The output matrix setting of the stage 1 sensitive earth fault protection

0x00000000 ~ 0x7FFFFFFF 1 8 50/51SEF2.3I0_Set The current setting of the stage 2 sensitive earth

fault protection 0.005~0.4A 0.001A

9 50/51SEF2.t_Op The time setting of the stage 2 sensitive earth

fault protection 0~100s 0.001s

10 50/51SEF2.Opt_Dir The setting is used to select the directional mode

for the stage 2 SEF protection, see Section 3.6.3 0~2 1 11 50/51SEF2.En The logic setting of the stage 2 sensitive earth

fault protection 0~1 1

12 50/51SEF2.OutMap The output matrix setting of the stage 2 sensitive earth fault protection

0x00000000 ~ 0x7FFFFFFF 1 13 50/51SEF3.3I0_Set The current setting of the stage 3 sensitive earth

fault protection 0.005~0.4A 0.001A

14 50/51SEF3.t_Op The time setting of the stage 3 sensitive earth

fault protection 0~100s 0.001s

15 50/51SEF3.Opt_Dir The setting is used to select the directional mode

for the stage 3 SEF protection, see Section 3.6.3 0~2 1 16 50/51SEF3.En The logic setting of the stage 3 sensitive earth

fault protection 0~1 1

17 50/51SEF3.OutMap The output matrix setting of the stage 3 sensitive earth fault protection

0x00000000 ~ 0x7FFFFFFF 1 18 50/51SEF4.3I0_Set The current setting of the stage 4 sensitive earth

fault protection 0.005~0.4A 0.001A

19 50/51SEF4.t_Op The time setting of the stage 4 sensitive earth

fault protection 0~100s 0.001s

20 50/51SEF4.Opt_Dir The setting is used to select the directional mode

for the stage 4 SEF protection, see Section 3.6.3 0~2 1 21 50/51SEF4.En The logic setting of the stage 4 sensitive earth

fault protection 0~1 1

22 50/51SEF4.OutMap The output matrix setting of the stage 4 sensitive earth fault protection

0x00000000 ~ 0x7FFFFFFF 1 23 50/51SEF4.Opt_Curve The setting is for selecting the inverse time

characteristic curve for SEF4 protection 0~13 1

24 50/51SEF4.TMS The time multiplier setting of the IDMT sensitive

earth fault protection 0.05~100.0 0.001

25 50/51SEF4.tmin The minimum operation time setting of the IDMT

26 50/51SEF4.K Constant “k” for the IDMT sensitive earth fault

protection, see Section 3.6.2 0.001~120.0 0.0001 27 50/51SEF4.C Constant “C” for the IDMT sensitive earth fault

protection, see Section 3.6.2 0.00~1.00 0.0001

28 50/51SEF4.Alpha Constant “α” for the IDMT sensitive earth fault

protection, see Section 3.6.2 0.01~3.00 0.0001

NOTE!

1. The setting [50/51SEFx.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage x (x: 1~4) sensitive earth fault protection respectively. “0” is the non-directional mode; “1” is the forward directional mode; and “2” is the reverse directional mode.

7.3.5 Breaker Failure Protection Settings

The breaker failure protection settings (in the submenu “BFP Settings”) are used to determine the characteristic of the breaker failure protection.

All the settings of the breaker failure protection are listed in the following table.

No. Menu text Explanation Range Step

1 50BF.I_Set The current setting of the breaker failure

protection 0.05In~5.0In 0.001A

2 50BF.t_Op The time setting of the breaker failure protection 0~100s 0.001s 3 50BF.t_ReTrp The re-trip time setting of the breaker failure

protection 0~100s 0.001s

4 50BF.Opt_LogicMode The setting for selecting the criteria logic of the

breaker failure protection 1~4 1

5 50BF.En The logic setting of the breaker failure protection 0~1 1 6 50BF.En_ReTrp The logic setting of the re-trip function of the

breaker failure protection 0~1 1

7 50BF.OutMap The output matrix setting of the breaker failure protection

0x00000000 ~ 0x7FFFFFFF 1 8 50BF.OutMap_ReTrp The output matrix setting of the re-trip function of

the breaker failure protection

0x00000000 ~ 0x7FFFFFFF 1 NOTE!

1. The setting [50BF.Opt_LogicMode] is used to select the criteria logic of the breaker failure protection. Four criteria logics based on the phase currents and the circuit breaker state (based on the binary input [BI_52b]) are supported in this relay.

The two criteria conditions are list as below:

(A) The maximum phase current is greater than the setting [50BF.I_Set]. (B) The circuit breaker is still closed ([BI_52b] = 0).

Setting Value Criteria Condition Logic

1 Ipmax > [50BF.I_Set] Only A

2 NOT([BI_52b]) Only B

3 (Ipmax > [50BF.I_Set]) OR (NOT([BI_52b])) A OR B 4 (Ipmax > [50BF.I_Set]) AND (NOT([BI_52b])) A AND B

7.3.6 Broken Conductor Protection Settings

The broken conductor protection settings (in the submenu “BrknCond Settings”) are used to determine the characteristic of the broken conductor protection.

All the settings of the broken conductor protection are listed in the following table.

No. Menu text Explanation Range Step

1 50BC.I2/I1_Set The ratio setting for the broken conductor

protection 0.10~1.00 0.001

2 50BC.t_Op The time setting for the broken conductor

protection 0~200s 0.001s

3 50BC.En The logic setting for the broken conductor

protection 0~1 1

4 50BC.OutMap The output matrix setting of the broken conductor protection

0x00000000 ~ 0x7FFFFFFF 1

7.3.7 Cold Load Pickup Settings

The cold load pickup logic settings (in the submenu “CLP Settings”) are used to determine the characteristic of the cold load pickup logic.

All the settings of the cold load pickup logic are listed in the following table

No. Menu text Explanation Range Step

1 CLP.Opt_LogicMode The setting for selecting the cold load condition 1~2 1 2 CLP.t_Cold The time setting for ensuring the cold load

condition is met 0~4000s 0.001s

3 CLP.t_Rst The time setting for resetting the cold load pickup

logic 0~4000s 0.001s

4 CLP.t_ShortRst The time setting for fast resetting the cold load

pickup logic 0~600s 0.001s

5 CLP.En The logic setting of the cold load pickup logic

function 0~1 1

6 50/51P1.CLP.IMult The multiple setting of the stage 1 overcurrent

protection when CLP is active 1.00~10.00 0.001

7 50/51P1.CLP.t_Op The time setting of the stage 1 overcurrent

protection when CLP is active 0~100s 0.001s

8 50/51P2.CLP.IMult The multiple setting of the stage 2 overcurrent

9 50/51P2.CLP.t_Op The time setting of the stage 2 overcurrent

protection when CLP is active 0~100s 0.001s

10 50/51P3.CLP.IMult The multiple setting of the stage 3 overcurrent

protection when CLP is active 1.00~10.00 0.001

11 50/51P3.CLP.t_Op The time setting of the stage 3 overcurrent

protection when CLP is active 0~100s 0.001s

12 50/51P4.CLP.IMult The multiple setting of the stage 4 overcurrent

protection when CLP is active 1.00~10.00 0.001

13 50/51P4.CLP.t_Op The time setting of the stage 4 overcurrent

protection when CLP is active 0~100s 0.001s

14 50/51P4.CLP.TMS The time multiplier setting of the IDMT overcurrent

protection when CLP is active 0.05~100.0 0.001

15 50/51G1.CLP.IMult The multiple setting of the stage 1 zero sequence

overcurrent protection when CLP is active 1.00~10.00 0.001 16 50/51G1.CLP.t_Op The time setting of the stage 1 zero sequence

overcurrent protection when CLP is active 0~100s 0.001s 17 50/51G2.CLP.IMult The multiple setting of the stage 2 zero sequence

overcurrent protection when CLP is active 1.00~10.00 0.001 18 50/51G2.CLP.t_Op The time setting of the stage 2 zero sequence

overcurrent protection when CLP is active 0~100s 0.001s 19 50/51G3.CLP.IMult The multiple setting of the stage 3 zero sequence

overcurrent protection when CLP is active 1.00~10.00 0.001 20 50/51G3.CLP.t_Op The time setting of the stage 3 zero sequence

overcurrent protection when CLP is active 0~100s 0.001s 21 50/51G4.CLP.IMult The multiple setting of the stage 4 zero sequence

overcurrent protection when CLP is active 1.00~10.00 0.001 22 50/51G4.CLP.t_Op The time setting of the stage 4 zero sequence

overcurrent protection when CLP is active 0~100s 0.001s 23 50/51G1.CLP.TMS The time multiplier setting of the zero sequence

IDMT overcurrent protection when CLP is active 0.05~100.0 0.001

7.3.8 SOTF Protection Settings

The SOTF protection settings (in the submenu “SOTF Settings”) are used to determine the characteristic of the SOTF protection.

All the settings of the SOTF protection are listed in the following table.

No. Menu text Explanation Range Step

1 SOTF.t_En The enabling time setting of the SOTF protection 0~100s 0.001s 2 SOTF.Opt_Mode The setting for selecting the acceleration tripping

mode of the SOTF protection 0~1 1

3 50PSOTF.I_Set The current setting of the SOTF overcurrent

4 50PSOTF.t_Op The time setting of the SOTF overcurrent

protection 0~100s 0.001s

5 50PSOTF.En The logic setting of the SOTF overcurrent

protection 0~1 1

6 50PSOTF.OutMap The output matrix setting of the SOTF overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1 7 50GSOTF.3I0_Set The current setting of the zero sequence SOTF

overcurrent protection 0.05In~30In 0.001A

8 50GSOTF.t_Op The time setting of the zero sequence SOTF

overcurrent protection 0~100s 0.001s

9 50GSOTF.En The logic setting of the zero sequence SOTF

overcurrent protection 0~1 1

10 50GSOTF.OutMap The output matrix setting of the zero sequence SOTF overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1 NOTE!

1. The setting [SOTF.t_En] is used to enable the SOTF protection for the appointed time delay, when the enabling conditions are satisfied (See Section 3.10).

2. The setting [SOTF.Opt_Mode] is used for selecting the acceleration tripping mode of the SOTF protection. Setting as “1” means accelerated tripping before auto-reclosing; and setting as “0” means accelerated tripping after auto-reclosing.