SeCtIoN 2: Programming
4. PARTITIONS Programming
At ADDReSSeS 40хх are assigned the attributes of the А and В partitions in the system. Every partition can be armed
and disarmed independently.
ADDRESS 4010 - PROGRAMMING OF EXIT TIME FOR PARTITION А exit time
Partition А
Exit time is assigned to Entry/Exit type zones attached to Partition A. A double-digit number between 1 and 99 seconds is entered. For an interval of time, less than 10 seconds, the first digit must be 0. The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the digits can be browsed with the help of the arrows.
Default settings - 45 sec.
ADDRESS 4011 - PROGRAMMING OF ENTRY TIME FOR PARTITION А entry time
Partition А
Entry time is assigned to Entry/Exit type zones attached to Partition A. A double-digit figure between 1 and 99 seconds is entered. For a time interval of less than 10 seconds, the first digit must be 0. The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the digits can be browsed with the help of the arrows.
Default settings - 15 sec.
ADDRESS 4012 - PROGRAMMING OF BELL TIME FOR PARTITION А Bell time
Partition А
Duration is set for the bell time of the sirens attached to Partition A. A double-digit numberbetween 0 and 99 minutes is entered. For a time interval of less than 10 seconds, the first digit must be 0. The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the digits can be browsed with the help of the arrows.
Default settings - 03 min.
ADDRESS 4013 - PROGRAMMING OF BELL DELAY FOR PARTITION А Bell Delay
Partition А
Delay is set for initiating the bell time of the sirens attached to Partition A. A double-digit number be- tween 0 and 99 seconds is entered. For a time interval of less than 10 seconds, the first digit must be 0.
The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the digits can be browsed with the help of the arrows.
Default settings - 0 min.
ADDRESS 4014 - PROGRAMMING OF AUTO-ARM TIME FOR PARTITION А Auto-ARM
time Partition А
A time (HH:MM) for automatic arming at Partition A in the system is set.
Note: To take effect the programmed time on this address it is necessary the attribute "3. Auto Arm
Enbl." at ADDRESS 4016 to be assigned.
ADDRESS 4015 - FIRE SIGNAL DURATION FOR PARTITION А FIRe Signal
Duration Partition А
The duration of the alarm signal for a FIRE event at Partition A is assigned at this address. Programming this address affects the performance of the programmable SIREN output.
Every click of a digital button alternatively changes the type of duration of the sound signal. The display indication is shown in the tables.
Until a valid user code is entered
There is a FIRE alarm signal until a valid system user or master user code is introduced.
Indication LeD
1 2 3 4 5 6 LCDUntil the Bell time at Address 4012 ends.
The FIRE signal duration is set at address 4012 BELL TIME.
Indication LeD
(1) (2) (3) (4) (5) (6)LCD Default settings - Until a valid user code is enteredADDRESS 4016 - PROGRAMMING OF ATTRIBUTES FOR PARTITION А Attributes
Partition А
The attributes of Partition A are programmed at this address. Every attribute is activated with pressing of a digit button with a respective number (from 1 to 4). The choosen attribute is indicated with acti- vated number of the pressed digit.
Next pressing of the same button number will deactivate the attribute. At end of the procedure at the keyboard dispaly have to active only the numbers of the assigned attributes.
More than one attribute can be assigned at this address.
1. Sqwk
ARM The siren will activate singly for 1 second when arming the Partition A in the system. 2. Sqwk
DISARM The siren will activate twice when disarming the Partition A in the system.
3. Auto-Arm
enbl Enabling the automatic arming of Partition A in the system for the programmed ar ADDRESS 4014 Auto-ARM time.
Auto-Arm
enbl LeD LCDIndication
Disabled
3Enabled
(3)4. Auto Arm Full/Stay
Automatic arming the Partition A with specifing the arming mode: • Full
• Stay (the User can stay at some rooms).
Attribute LeD LCDIndication
Full
4Stay
(4)ADDRESS 4017 - NUMBER FOR COMMUNICATION WITH PARTITION А Number for
communica- tion
A number for communication between Partitin A and a central monitoring station is entered at this ad- dress.
4 digits have to be enetered. The valid digits are from 0 to 9 anf symbols from A to F.
Default settings - FFFF
ADDReSSeS 4020 ... 4024 - PRoGRAMMING oF tHe AttRIBUteS FoR PARtItIoN B
The programming is the same as for ADDRESS 4010 - 4014.
Default settings - Same as PARTITION A
ADDReSS 4025 - FIRe SIGNAL DURAtIoN FoR PARtItIoN B FIRe Signal
Duration Partition B
The duration of the alarm signal for a FIRE event at Partition A is assigned at this address. Programming this address affects the performance of the programmable SIREN output.
Every click of a digital button alternatively changes the type of duration of the sound signal. The display indication is shown in the tables.
Until a valid user code is entered
There is a FIRE alarm signal until a valid system user or master user code is introduced.
Indication LeD
1 2 3 4 5 6 LCDUntil the Bell time at Address 4012 ends.
The FIRE signal duration is set at address 4022 BELL TIME.
Indication LeD
(1) (2) (3) (4) (5) (6)LCD Default settings - Until a valid user code is enteredADDReSSeS 4026 and 4027 - PRoGRAMMING oF tHe AttRIBUteS FoR PARtItIoN B
The programming is the same as for ADDRESS 4016 and 4017.