CCTV MONITORING SYSTEM

SECTION 17 VOICE / DATA SYSTEM

3.0 PRODUCT SPECIFICATIONS:

Horizontal Cable:

The horizontal cable shall constitute of four (4) individually screened Twisted Pair (SSTP), AWG23. The outer sheath shall be LSOH and the cable shall be specified up to 250MHz or better and should have the following values or better for Attenuation and NEXT:

Frequency (MHz) Attenuation (dB) NEXT (dB)

1 2.0 90

• The horizontal cabling shall be star-wired.

• The maximum horizontal distance shall be 90Mtr. between the outlet and the patch panel (excluding patch cords and line cords).

• The horizontal cabling shall be free of taps and bridges.

• One cable shall be strictly used for one application, cable sharing will not be acceptable.

Connecting Hardware for Horizontal Cable:

Connecting hardware shall be based on shielded RJ45 interface. The hardware shall feature excellent transmission performance and mechanical strength. Integral wire management and cable strain relief shall be integrated into the hardware. It should be possible to use the same RJ45 interface module at the outlet end as well as the patch panel (IDT) end. Termination of the cables on the hardware shall be accomplished without the use of any tools i.e. tools free installation. The termination at the patch panel end should cater to grounding of the panels using separate earthing facilities. The patch panels should consist of earthing kits to enable this grounding of shielded cabling.

Wherever single RJ45 outlet is used, it should be possible to easily upgrade to dual RJ45, without any major changes to the faceplate. The Screened RJ45 will have the following specification:-

- Comply with the latest standard proposals of ISO/IEC and EIA/TIA for Cat 6 requirements.

- Compatible with Category 6 Generic standard plugs.

- Tool-free connection technique (IDC) for data cables with AWG 23-26 wire diameter.

- Allows opto-mechanical control of the connection technique.

- Error-free connection according to EIA/TIA 568A/B/C without pair crossover.

- Patented shield contacting with integrated cable strain relief.

- Halogen-free material.

- SGS, UL, CSA certified.

Application:

- Draft IEC 60603-7-4: Unshielded 8-Way Connectors for Frequencies up to 250 MHz;

April 2000

- DRAFT ISO/IEC 11801 SECOND EDITIONS: ISO/IEC JTC 1/SC 25/WG3 N598S; 2000-05-08

- Draft EN 50173 second editions: CLC TC 215 WG1S 2/20; April 2000 Flame retardance :

In accordance with UL 94 V0 Rating

Mechanical, Electrical and Transmission Data (measured at 20°C):

Mechanical Data

Material Polycarbonate, (UL 94 V- ) Mating cycles > 750

Wire diameter 0,4 mm (AWG 26) – 0,57 mm (AWG 23) Insulation diameter 0,8 – 1,6 mm

Wire strain relief Through labyrinth in IDC block Cable strain relief Through cable ties

For shielded RJ45

Shield contacting Shield lance (on cable) Earthing terminals for flat plugs 4.8 x 0.5 mm Shield material CuSn, tin-plated, 2 – 4 µm Electric and Transmission Data

Contact resistance < 50 milli Ohm (conductor – conductor) Contact resistance 1< 20 milli Ohm (shield – shield)

Insulation resistance > 500 mega Ohm (500 VDC)

Dielectric strength 1000 Veff, 50 Hz/1 min (conductor – conductor) Dielectric strength 11500 Veff, 50 Hz/1 min (conductor – shield) Coupling resistance IEC 96-1

1 MHz < 15 milliohm

10 MHz < 100 milliohm

RJ45 Hardware Electrical Characterization, Transmission performances:

Worst Pair Combination with a Cat.6 Plug

Patch Cords & Line Cords:

The patch cords and line cords shall constitute of two modular RJ45 plugs assembled on shielded twisted pair stranded cable. The SSTP stranded cable shall be constructed using flexible cable . The sum length of all patch cords & line cords for one outlet shall not exceed 10Mtr. Under no circumstances shall locally assembled patch cords and line cords will be acceptable, all must be factory made.

Connecting Hardware for Voice Backbone Cable:

The voice backbone cables shall be terminated on high density 50 port RJ45 patch panels, which shall be housed in the 19" IDT cabinet. These panels shall accept UTP cables having AWG22-26 solid or stranded wire. Highly visible, colour coded strips shall be used to identify individual pair of the backbone cable. These panels shall have features like gas-tight connection, integral strain relief mechanism.

Data Backbone Cable:

Frequency Attenuation NEXT FEXT RL

[MHz] [dB] [dB] [dB] [dB] [dB] [dB] [dB] [dB]

The backbone cable for data applications shall comprise of fiber optic cables. The cables shall have minimum 8 or 12 cores of Multimode 50 /125 graded index fiber strands. The fiber optic cables shall have the following characteristics:

Wavelength (nm) Max. Attenuation (dB) Bandwidth (MHz x Km)

850 <2.5 >400

1300 <0.7 >1200

If the backbone distance exceeds 550Mtr, single mode fiber cables shall be installed.

These cables when installed, shall have the following characteristics:

Wavelength (nm) Max. Attenuation (dB) Bandwidth (GHz x Km)

The fiber optic (data backbone) cable shall be field terminated with ST connectors (with ceramic ferrule) on each fiber strand. These connectors shall be installed in fiber optic patch panel, mounted in 19" IDT cabinet. These shall feature sliding drawer type panels for better administration of the fiber cables. The panels shall have holes at the rear for inserting and strain-relieving cables with PG glands. Cable and fiber guides for buffer management within the panels shall be built-in the panel. The insertion loss on each SC connectors shall be < 0.2dB.

Fiber Optic Patch Cords:

Fiber optic patch cords need to be provided to enable rapid connection and disconnection repeatedly on a non-destructive basis. Fiber optic patch cords shall be supplied with each IDT. The sum total quantity of IDTs shall be supplied at the data MDT (SC-SC). The patch cords shall be Multimode Graded Index duplex 50 /125 with SC connectors on one end and the other end will have connectors to suit the network equipment (SC). Provide for Single mode patch cords, wherever necessary. The patch cords shall have a mating cycle of 1000 and maximum tensile load on the cable of 100N. Under no circumstances shall locally assembled patch cords and line cords will be acceptable, all must be factory made.

4.0 19" IDT/MDT/FO-CD CABINET

The cabinet shall provide a controlled environment to house telecommunications equipment, connecting hardware and to terminate the entire horizontal cabling, voice

backbone cabling and data backbone cabling. These cabinets shall be of high quality and include locking doors. The cabinet shall be either wall mounted (with access from back and front – Swing type frame) or freestanding (with wheels) depending on the size of the cabinet. The wall mount cabinet should have a minimum depth of 500mm and the freestanding cabinet shall have a minimum depth of 800mm. Provide sufficient space in the cabinet for telecommunications/network equipment and future expansion.

At IDTs where data backbone is not installed, allow sufficient space in the cabinet for installing data backbone in the future. Wherever data backbone is installed, the IDT cabinet shall be supplied with Fan Tray and UK type powerstrip. These cabinets shall be supplied with sufficient quantities of cable organisers for management/dressing of patch cords.

5.0 INSTALLATION

1. The contractor shall not engage any sub-contractor to carry out the structured cabling work.

2. The installation shall comply with the requirements of ISO-11801 Class E as appropriate.

3. The structured cabling system (cables, RJ45 outlets, panels etc) shall be labeled in accordance with EIA/TIA-606.

6.0 TESTING

1. The contractor shall test and demonstrate on site, to the satisfaction of the engineer, that the wiring is in full compliance with specific requirements of a Class E installation (250MHz). All the tests shall be carried out in accordance with TSB-67 standard.

2. The contractor shall provide test results (both hard copy and soft copy) for every data and every voice outlet.

7.0 DOCUMENTATION

1. The contractor shall submit a set of documentation comprising of layouts showing cable route & position of all outlets, labeling scheme, layout of cabinets and test results.

8.0 WARRANTY

1. The OEM through the specialist contractor shall provide 15 years component and system performance warranty.