able 8. Power supply
Description ype1 ype2
V nominal (V n) 100, 110, 120, 220, 240 V AC, 60 and 50 Hz
48, 60, 110, 125, 220, 250 V DC
24, 30, 48, 60 V DC
V nvariation 38...110% o V n(38...264 V AC) 80...120% o V n(38.4...300 V DC)
50...120% o V n (12...72 V DC)
Start-up threshold 19.2 V DC
(24 V DC * 80%) Burden o auxiliary voltage supply
under quiescent (Pq)/operating condition
DC < 12.0 W (nominal)/< 18.0 W (max), AC< 16.0 W (nominal)/<
21.0W (max)
DC < 12.0 W (nomi-nal)/< 18.0 W (max) Ripple in the DC auxiliary voltage Max 15% o the DC value (at requency o 100 Hz) Maximum interruption time in the
auxiliary DC voltage without resetting the relay
50 ms at nominal voltage 50 ms at nominal voltage
Fusetype 4A/250V
able 7. Dimensions
Description Value
Width rame 7.08” (179.8 mm)
case 6.46” (164 mm)
Height rame 6.97 (177 mm), 4U
case 6.30” (160 mm)
Depth case 7.64” (194 mm)
Weight relay 7.72 lbs. (3.5 kg)
draw-out unit 3.97 lbs. (1.8 kg)
able 9. Analog inputs
Description Value
Rated requency 60/50 Hz ± 5 Hz
Current inputs Rated current, In 5/1 A1) 0.2 A2)
Termal withstand capability:
• Continuously
• For 1 s
20 A 500 A
4 A 100 A Dynamic current withstand:
• Hal-wave value 1250 A 250 A
Input impedance <20 mΩ <100 mΩ
Voltage inputs Rated voltage V n 60...210 V AC (Parametrization) Voltage withstand:
• Continuous
• For 10 s
2 x V n(240 V AC) 3 x V n(360 V AC) Burden at rated voltage <0.05 VA
1)Phase and ground current inputs
2)Sensitive earth ault (SEF)/high impedance (HIZ) detection current input
able 10. Measuring range
Description Value
Measured currents on phases IA, IB and IC as multiples o
the rated currents o the analog inputs
0... 50 x In Ground current as a multiple o the rated current o the
analog input
0... 50 x In
able 11. Binary inputs
Description Value
Operating range ±20 % o the rated voltage
Rated voltage 24...250 V DC
Current drain 1.6...1.9 mA
Power consumption 31.0...570 mW
Treshold voltage 18...176 V DC
Reactiontime 3ms
able 12. Signal outputs (SO) on X120 and X130 [ypical operation time: 5...8 ms]
Description Value
Rated voltage 250 V AC/DC
Continuouscarry 5A
Make and carry or 3.0 s 10 A
able 13. Sel-diagnostics alarm signal output (SO) [ypical operation time: 5...8 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry or 3.0 s 10 A
Makeandcarry0.5s 15A
Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load 10 mA at 5 V AC/DC
able 14. Double-pole power output (PO) relays with CM [ypical operation time: 8...11 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8 A
Make and carry or 3.0 s 15 A
Makeandcarry0.5s 30A
Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC (two contacts connected in series)
5 A/3 A/1 A
Minimum contact load 100 mA at 24 V AC/DC
rip-circuit monitoring (CM):
• Control voltage range
• Current drain through the monitoring circuit
• Minimum voltage over the CM contact
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
able 15. Single-pole power output (PO) relays [ypical operation time: 8...11 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8 A
Make and carry or 3.0 s 15 A
Makeandcarry0.5s 30A
Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Minimum contact load 100 mA at 24 V AC/DC
able 17. High-speed output (HSO) devices [ypical operation time: 1 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 6 A
Make and carry or 3.0 s 15 A
Makeandcarry0.5s 30A
Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC
5 A / 3 A / 1 A
able 18. Ethernet interaces
Ethernet interace Protocol Cable Data transer rate
Front RJ-45 CP/IP Standard Ethernet Cat5 cable with RJ-45 connec-tor
10 MBits/s Rear RJ-45 or LC CP/IP Shielded twisted pair CA 5e cable with RJ-45
connector or ber-optic cable with LC connector
100 MBits/s
X5 Serial 10-pin counter connector Weidmuller BL
3.5/10/180F AU OR BEDR or 9-pin counter connector Weidmuller BL 3.5/9/180F AU OR BEDR1)1
115200 Bits/s
X16 Serial 9-pin D-sub connector DE-9 115200 Bits/s
X12 Serial Optical S-connector 115200 Bits/s
able 19. Network Ethernet ports specifcations
Connector Fibre type1) Wave length Max. distance Permitted path attenu-ation2)
LC SM 9/125 μm 1300 nm 2-20 km <8 dB
S MM 62.5/125 μm
glass bre core
820-900 nm 1 km <11 dB
able 16. Double-pole signal output (SO1) on X100 [ypical operation time: 8...11 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry or 3.0 s 15 A
Makeandcarry0.5s 30A
Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
1Depending on the optional communication module.
able 23. Environmental conditions
Description Value
Operating temperature range -25 C to +55° C
Short-term operating temperature range -40 C to +85° C (<16 h)1) 2)
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude Up to 6561 (2000 m)
ransport and storage temperature range -40...+85ºC
1)Degradation in MBF and L HMI perormance outside continuous operating temperature range
2)For relays with an LC communications interace, the maximum operating temperature is +70° C
Description Value
IRIG time code ormat B004, B0051)
Isolation 500V 1 min.
Modulation Unmodulated
Logic level L Level
Current consumption 2...4 mA
Power consumption 10...20 mW
able 21. Lens sensor and optical fbre or arc protection
Description Value
Fiber-optic cable including lens 1.5 m, 3.0 m or 5.0 m Normal service temperature range o the lens -40...+100°C
Maximum service temperature range o the lens, max 1 h
+140°C Minimum permissible bending radius o the
connection bre
100 mm
able 22. Degree o protection o ush-mounted relay
Description Value
Frontside IP54
Rear side, connection terminals IP 20
1)According to 200-04 IRIG -standard
able 24. Environmental tests
Description ype test value Reerence
Dry heat test (humidity
<50%)
• 96 h at +55ºC
• 16 h at +85ºC1)
• 12h at +85 ºC1) 2)
IEC 60068-2-2 IEEE C37.90-2005 Dry cold test • 96 h at -25ºC
• 16 h at -40ºC
• 12h at -40ºC1) 2)
IEC60068-2-1 IEEE C37.90-2005 Damp heat test, cyclic • 6 cycles (12 h + 12 h) at +25°C…+55°C, humidity >93%
• +25°C, Rh = 95%, 96h
IEC 60068-2-30 IEEE C37.90-2005 Storage test • 96 h at -40ºC
• 96 h at +85ºC
IEC 60068-2-48 IEEE C37.90-2005
1)For relays with an LC communication interace the maximum operating temperature is +70° C
Te EMC immunity test level meets the requirements listed below:
Description ype test value Reerence
1 MHz burst disturbance test, class III:
• Common mode
• Diferential mode
2.5 kV 2.5 kV
IEC 61000-4-18
IEC 60255-22-1, class III IEEE C37.90.1-2002
Electrostatic discharge test
• Contact discharge
• Air discharge
8 kV 15 kV
IEC 61000-4-2 IEC 60255-22-2 IEEE C37.90.3-2001
Radio requency intererence tests:
10 V (rms)
=150 kHz-80 MHz 10 V/m (rms)
=80-2700 MHz 10 V/m
=900 MHz 20 V/m (rms)
=80-1000 MHz
IEC 61000-4-6
IEC 60255-22-6, class III IEC 61000-4-3
IEC 60255-22-3, class III ENV 50204
IEC 60255-22-3, class III IEEE C37.90.2-2004 Fast transient disturbance tests:
•Allports 4kV
IEC 61000-4-4 IEC 60255-22-4 IEEE C37.90.1-2002 Surge immunity test:
• Communication
• Other ports
1 kV, line-to-earth 4 kV, line-to-earth 2 kV, line-to-line
IEC 61000-4-5 IEC 60255-22-5
Power requency (50 Hz) magnetic eld:
• Continuous
• 1-3 s
300 A/m 1000 A/m
IEC 61000-4-8
Voltage dips and short interruptions 30%/10 ms 60%/100 ms 60%/1000 ms
>95%/5000 ms
According to IEC 61000-4-11
able 26. Insulation tests
Description ype test value Reerence
Dielectric tests: According to IEC 60255-5
• est voltage 2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication Impulse voltage test:
• est voltage 5 kV, 1.2/50 μs, 0.5 J 1 kV, 1.2/50 μs, 0.5 J, communication
IEC 60255-5 and IEC 60255-27
Insulation resistance measurements
• Isolation resistance >100 MΩ, 500 V DC
IEC 60255-5 and IEC 60255-27 Protective bonding resistance
• Resistance <0.1 Ω (60 s)
IEC 60255-27
able 28. Product saety
Description Reerence
LVdirective 2006/95/EC
Standards EN 60255-27 (2005),
EN 60255-6 (1994)
able 27. Mechanical tests
Description Value
Vibration tests (sinusoidal) IEC 60068-2-6 (test Fc) IEC 60255-21-1
Class 2 Shock and bump test IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump) IEC 60255-21-2
Class 2
Seismic test IEC 60255-21-3 Class 2
Mechanical durability IEEE C37.90-2005 IEC 602556-6
•200 withdrawls and insertions o the plug-in unit
•200 adjustments o relay setting controls
Description ype test value Reerence
Emission tests:
• Conducted 0.15-0.50 MHz 0.5-30 MHz
• Radiated 30-230 MHz 230-1000 MHz
< 79 dB(μV) quasi peak
< 66 dB(μV) average
< 73 dB(μV) quasi peak
< 60 dB(μV) average
< 40 dB(μV/m) quasi peak, measured at 10 m distance
< 47 dB(μV/m) quasi peak, measured at 10 m distance
EN 55011, class A IEC 60255-25
able 29. EMC Compliance
Description Reerence
EMC directive 2004/108/EC
Standard EN 50263 (2000)
EN 60255-26 (2007)
able 30. RoHS compliance Description
Complies with the RoHS directive 2002/95/EC Protection unctions
able 31. Tree-phase non-directional overcurrent protection (50P, 51P)
Characteristic Value
Pickup accuracy 51P Depending on the requency o the current measured: n±2Hz
±1.5% o the set value or ±0.002 x In 50P-1, 50P-2
and 50P-3
±1.5% o set value or ±0.002 x In (at currents in the range o 0.1…10 x In)
±5.0% o the set value
(at currents in the range o 10…40 x In)
Pickup time1) 2) Minimum ypical Maximum
50P-3:
IFault= 2 x set Pickup value IFault= 10 x set Pickup value
15 ms 12 ms
16 ms 13 ms
17 ms 14 ms 50P-1, 50P-2 and 51P:
IFault= 2 x set Pickup value 23 ms 25 ms 28 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 30 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms3)
Suppression o harmonics RMS: No suppression
DF: -50dB at =
n x n, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression P-to-P+backup: No suppression
1)Set Operate delay time = 0,02 s, Operate curve t ype = ANSI denite time, Measurement mode = deault (depends on stage), current beore
ault = 0.0 x In, n = 50 Hz, ault current in one phase with nominal requency injected rom random phase angle, results based on statistical distribution o 1000 measurements
2)
able 32. Tree-phase non-directional overcurrent protection (50P, 51P) main settings
Parameter Function Value (Range) Step
Pickup value 51P 0.05...5.00 x In 0.01
50P-1, 50P-2 0.10...40.00 x In 0.01
50P-3 1.00...40.00 x In 0.01
ime multiplier 51P 0.05...15.0 0.05
50P-1, 50P-2 0.05...15.00 0.05
Denite time delay 51P 40...200000 ms 10
50P-1, 50P-2 40...200000 ms 10
50P-3 20...200000 ms 10
Operating curve type1) 51P Denite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
50P-1, 50P-2 Denite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
50P-3 Denite time
1)For urther reerence please reer to the Operating characteristics table at the end o the echnical data chapter
able 34. Tree-phase directional overcurrent protection (67/51P, 67/50P) main settings
Parameter Function Value (Range) Step
Pickup value 67/51P 0.05...5.00 x In 0.01
67/50P-1, 67/50P-2 0.10...40.00 x In 0.01
ime multiplier 67/51P, 67/50P-1, 67/50P-2 0.05...15.00 0.05
Denite time delay 67/51P, 67/50P-1, 67/50P-2 40...200000 ms 10 Directional mode 67/51P, 67/50P-1, 67/50P-2 1 = Non-directional
2 = Forward 3 = Reverse
Characteristic angle 67/51P, 67/50P-1, 67/50P-2 -179...180 degrees 1
Characteristic Value
Pickup accuracy Depending on the requency o the current/
voltage measured: n±2Hz
67/51P Current:
±1.5% o the set value or ±0.002 x In Voltage:
±1.5% o the set value or ±0.002 x V n Phase angle: ±2°
67/50P-1, 67/50P-2 Current:
±1.5% o set value or ±0.002 x In (at currents in the range o 0.1…10 x In)
±5.0% o set value
(at currents in the range o 10…40 x In) Voltage:
±1.5% o the set value or ±0.002 x V n Phase angle:
±2°
Pickup time1) 2) Minimum ypical Maximum
IFault= 2.0 x set Pickup value 38 ms 43 ms 46 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms3) Suppression o harmonics DF: -50dB at = n x n,
where n = 2, 3, 4, 5,…
1) Measurement mode and Pol quantity = deault, current beore ault = 0.0 x In, voltage beore ault 1.0 x Un, n= 50 Hz, ault current in one phase with nominal requency injected rom random phase angle, results based on statistical distribution o 1000 measurements
2) Includes the delay o the signal output contact
3) Maximum Pickup value = 2.5 x In, Pickup value multiples in range o 1.5 to 20
Characteristic Value Pickup
accuracy
Depending on the requency o the current measured: n±2Hz
51N, 51G, SEF ±1.5% o the set value or ±0.002 x In 50N-1, 50N-2, 50G-1, 50G-2
and
50N-3, 50G-3
±1.5% o set value or ±0.002 x In (at currents in the range o 0.1…10 x In)
±5.0% o the set value
(at currents in the range o 10…40 x In)
Pickup time1) 2) Minimum ypical Maximum
50N-3, 50G-3:
IFault= 2 x set Pickup value IFault= 10 x set Pickup value
15 ms 12 ms
16 ms 13 ms
17 ms 14 ms 50N-1, 50N-2, 50G-1, 50G-2 and
51N, 51G, SEF:
IFault= 2 x set Pickup value
23 ms 25 ms 28 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 30 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms3)
Suppression o harmonics RMS: No suppression
DF: -50dB at =
n x n, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1) Measurement mode = deault (depends on stage), current beore ault = 0.0 x In, n = 50 Hz, earth-ault current with nominal requency injected rom random phase angle, results based on statistical distribution o 1000 measurements
2) Includes the delay o the signal output contact
3) Maximum Pickup value = 2.5 x In, Pickup value multiples in range o 1.5 to 20
able 36. Non-directional ground ault protection (51N, 51G, 50N, 50G) main settings
Parameter Function Value (Range) Step
Pickup value 51N/51G 0.010...5.000 x In 0.005
50N-1, 50N-2, 50G-1, 50G-2 0.10...40.00 x In 0.01
50N-3, 50G-3 1.00...40.00 x In 0.01
ime multiplier 51N/51G 0.05...15.00 0.05
50N-1, 50N-2, 50G-1, 50G-2 0.05...15.00 0.05
Denite time delay 51N/51G 40...200000 ms 10
50N-1, 50N-2, 50G-1, 50G-2 40...200000 ms 10
50N-3, 50G-3 20...200000 ms 10
Operating curve type1) 51N/51G Denite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
50N-1, 50N-2, 50G-1, 50G-2 Denite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
50N-3, 50G-3 Denite time
1)For urther reerence please reer to the Operating characteristics table at the end o the echnical data chapter
Characteristic Value Pickup
accuracy
Depending on the requency o the current meas-ured: n±2Hz
67/51N Current:
±1.5% o the set value or ±0.002 x In Voltage:
±1.5% o the set value or ±0.002 x V n Phase angle:
±2°
67/50N-1, 67/50N-2 Current:
±2% o the set value or ±0.003 x In (at currents in the range o 0.1…10 x In)
±5.0% o the set value
(at currents in the range o 10…40 x In) Voltage:
±1.5% o the set value or ±0.01 x V n Phase angle: ±2°
Pickup time1) 2) Minimum ypical Maximum
67/50N-1, 67/50N-2:
IFault= 2 x set Pickup value 42 ms 45 ms 49 ms
67/51N-1:
IFault= 2 x set Pickup value 62 ms 65 ms 69 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 30 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms3)
Suppression o harmonics RMS: No suppression
DF: -50dB at =
n x n, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1)Set Denite time delay = 0,06 s, Inverse-time (IDM) and denite-time (D) cur ves = ANSI denite time, Measurement mode = deault (depends on stage), current beore ault = 0.0 x In, n = 50 Hz, earth-ault current with nominal requency injecte d rom random phase angle, results based on statistical distribution o 1000 measurements
2)Includes the delay o the signal output contact
3)Maximum Pickup value = 2.5 x In, Pickup value multiples in range o 1.5 to 20
Parameter Function Value (Range) Step
Pickup value 67/51N 0.010...5.000 x In 0.005
67/50N-1, 67/50N-2 0.10...40.00 x In 0.01 Directional mode 67/51N, 67N/ 50N-1 and
67/50N-2
1=Non-directional 2=Forward
3=Reverse
ime multiplier 67/51N 0.05...15.00 0.05
67/50N-1, 67/50N-2 0.05...15.00 0.05
Denite time delay 67/51N 60...200000 ms 10
67/50N-1, 67/50N-2 60...200000 ms 10
Operating curve type1) 67/51N Denite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
67/50N-1, 67/50N-2 Denite or inverse time Curve type: 1, 3, 5, 15, 17 Operation mode 67/51N, 67/50N-1
and 67/50N-2
1=Phase angle 2=I0Sin 3=I0Cos
4=Phase angle 80 5=Phase angle 88
able 39. Tree-phase non-directional long time overcurrent protection (51L)
Characteristic Value
Pickup accuracy
51L Depending on the requency o the current
measured: n±2Hz
±1.5% o the set value or ±0.002 x In Pickup time1) 2) 51L:
IFault= 2 x set Pickup value
Minimum ypical Maximum
23 ms 25 ms 28 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 30 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms4) Suppression o harmonics RMS: No suppression DF: -50dB at =
n x n, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression P-to-P+backup: No suppression
1)Set Operate delay time = 0.02 s, Operate curve type = ANSI denite time, Measurement mode = deault (depends on element), current beore ault
= 0.0 x In, n= 60 Hz, ault current in one phase with nominal requency injected rom random phase angle, results based on statistical distribution o
1000 measurements
2)Includes the delay o the signal output contact
3)Includes the delay o the heavy-duty output contact
4)Maximum Pickup value = 2.5 x In, Pickup value multiples in range o 1.5 to 20
able 41. Tree-phase overvoltage protection (59)
Characteristic Value
Pickup accuracy
Depending on the requency o the voltage measured: n±2Hz
±1.5% o the set value or ±0.002 x V n Pickup time1) 2) V Fault= 1.1 x set Pickup value Minimum ypical Maximum
23 ms 27 ms 30 ms
Resettime <40ms
Reset ratio Depends on the Relative hysteresis
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms3) Suppression o harmonics DF: -50dB at = n x n,
where n = 2, 3, 4, 5,…
1)Pickup value = 1.0 x Un, Voltage beore ault 0.9 x Un, n= 50 Hz, overvoltage in one phase-to-phase with nominal requence injected rom random phase angle, results based on statistical distribution o 1000 measurements
2)Includes the delay o the signal output contact
3)Maximum Pickup value = 1.20 x Un, Pickup value multiples in range o 1.10 to 2.00
1Embedded 10x actor in time multiplier to achieve ‘very long-time’ curve characteristic
able 42. Tree-phase overvoltage protection (59) main settings
Parameter Function Value (Range) Step
Pickup value 59 0.05...1.60 x V n 0.01
ime multiplier 59 0.05...15.00 0.05
Denite time delay 59 40...300000 ms 10
Operating curve type1) 59 Denite or inverse time
Curve type: 5, 15, 17, 18, 19, 20
1)For urther reerence please reer to the Operating characteristics table at the end o the echnical data chapter
able 40. Tree-phase non-directional long time overcurrent protection (51L) main settings
Parameter Function Value (Range) Step
Pickup value 51L 0.05 - 5.00 x In 0.01
ime multiplier 51L 0.10...15.001 0.01
Denite time delay 51L 0.020...200.001s 0.001
Operating curve type 51L Denite or inverse-time curve type: 6, 7, 14, 15, 17
Characteristic Value Pickup
accuracy
Depending on the requency o the voltage measured: n±2Hz
±1.5% o the set value or ±0.002 x V n Pickup time1) 2) V Fault= 0.9 x set Pickup value Minimum ypical Maximum
62 ms 66 ms 69 ms
Resettime <40ms
Reset ratio Depends on the set Relative hysteresis
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms3) Suppression o harmonics DF: -50dB at = n x n,
where n = 2, 3, 4, 5,…
able 44. Tree-phase undervoltage protection (27) main settings
Parameter Function Value (Range) Step
Pickup value 27 0.05...1.20 x V n 0.01
ime multiplier 27 0.05...15.00 0.05
Denite time delay 27 60...300000 ms 10
Operating curve type1) 27 Denite or inverse time
Curve type: 5, 15, 21, 22, 23
1)Pickup value = 1.0 x Un, Voltage beore ault 1.1 x Un, n= 50 Hz, undervoltage in one phase-to-phase with nominal requence injected rom random phase angle, results based on statistical distribution o 1000 measurements
2)Includes the delay o the signal output contact
3)Minimum Pickup value = 0.50, Pickup value multiples in range o 0.90 to 0.20
1)For urther reerence please reer to the Operating characteristics table at the end o the echnical data chapter
able 45. Positive sequence undervoltage protection (27PS)
Characteristic Value
Pickup accuracy
Depending on the requency o the voltage measured: n±2Hz
±1.5% o the set value or ±0.002 x V n Pickup time1) 2) V Fault= 0.99 x set Pickup value Minimum ypical Maximum
52 ms 55 ms 57 ms
V Fault= 0.9 x set Pickup value 44 ms 46 ms 49 ms
Resettime <40ms
Reset ratio Depends on the set Relative hysteresis
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms Suppression o harmonics DF: -50dB at = n x n,
where n = 2, 3, 4, 5,…
1)Pickup value = 1.0 x Un, Positive sequence voltage beore ault 1.1 x Un, n= 50 Hz, positive se quence undervoltage with nominal requence injected rom random phase angle, results based on statistical distribution o 1000 measurements
2)Includes the delay o the signal output contact
Parameter Function Value (Range) Step
Pickup value 27PS 0.010...1.200 x V n 0.001
Denite time delay 27PS 40...120000 ms 10
Voltage block value 27PS 0.01...1.0 x V n 0.01
able 47. Negative sequence overvoltage protection (47)
Characteristic Value
Pickup accuracy
Depending on the requency o the voltage measured: n±2Hz
±1.5% o the set value or ±0.002 x V n
Pickup time1) 2) Minimum ypical Maximum
V Fault= 1.1 x set Pickup value 33 ms 35 ms 38 ms
V Fault= 2.0 x set Pickup value 25 ms 27 ms 30 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms Suppression o harmonics DF: -50dB at = n x n,
where n = 2, 3, 4, 5,…
1)Negative sequence voltage beore ault 0.0 x Un, n= 50 Hz, negative sequence overvoltage with nominal requence injected rom random phase angle, results based on statistical distribution o 1000 measurements
2)Includes the delay o the signal output contact
able 48. Negative sequence overvoltage protection (47) main settings
Parameter Function Value (Range) Step
Pickup value 47 0.010...1.000 x V n 0.001
Denite time delay 47 40...120000 ms 1
able 49. Ground overvoltage protection (59G)
Characteristic Value
Pickup accuracy
Depending on the requency o the voltage measured: n±2Hz
±1.5% o the set value or ±0.002 x V n
Pickup time1) 2) Minimum ypical Maximum
V Fault= 1.1 x set Pickup value 55 ms 57 ms 60 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
Parameter Function Value (Range) Step
Pickup value 59G 0.010...1.000 x V n 0.001
Denite time delay 59G 40...300000 ms 1
able 51. Negative sequence overcurrent protection (46)
Characteristic Value
Pickup Accuracy Depending on the requency o the
current measured: n= ±2Hz
±1.5% o the set value or ±0.002 x In
Pickup time1) 2) Minimum ypical Maximum
IFault= 2 x set Pickup value IFault= 10 x set Pickup value
22 ms 14 ms
25 ms 17 ms
27 ms 19 ms
Resettime <40ms
Reset ratio ypical 0.96
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
rip time accuracy in inverse time mode ±5.0% o the theoretical value or ±20 ms3) Suppression o harmonics DF: -50dB at = n x n, where
n = 2, 3, 4, 5,…
1)Negative sequence current beore ault = 0.0, n= 50 Hz, results based on statistical distribution o 1000 measurements
2)Includes the delay o the signal output contact
3)Maximum Pickup value = 2.5 x In, Pickup value multiples in range o 1.5 to 20
able 53. Phase discontinuity protection (46PD)
Characteristic Value
Pickup Accuracy Depending on the requency o the current measured: n ±2Hz
±2% o the set value
Pickup time < 70 ms
Reset time < 40 ms
Reset ratio ypical 0.96
Retardation time < 35 ms
rip time accuracy in denite time mode ±1.0% o the set value or ±20 ms
Suppression o harmonics DF: -50dB at = n x n, where n = 2, 3, 4, 5,…
able 52. Negative sequence overcurrent protection (46) main settings
Parameter Function Value (Range) Step
Pickup value 46 0.01...5.00 x In 0.01
ime multiplier 46 0.05...15.00 0.05
Denite time delay 46 40...200000 ms 10
Operating curve type1) 46 Denite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
1)For urther reerence please reer to the Operating characteristics table at the end o the echnical data chapter
Parameter Function Value (Range) Step Pickup value
(Current ratio setting I2/I1)
46PD 10...100 % 1
Denite time delay 46PD 100...30000 ms 1
Min phase current 46PD 0.05...0.30 x In 0.01
able 57. Tree-phase thermal overload (49F)
Characteristic Value
Pickup Accuracy Depending on the requency o the current measured: n ±2Hz
Current measurement: ±0.5% or ±0.002 x In (at currents in the range o 0.01…4.00 x In)
rip time accuracy ±2.0% or ±0.50 s
able 56. Circuit breaker ailure protection (50BF, 50NBF, 50GBF) main settings
Parameter Function Value (Range) Step
Current value
(Operating phase current)
50BF, 50NBF, 50GBF 0.05...1.00 x In 0.05 Current value Res
(Operating residual current)
50BF, 50NBF, 50GBF 0.05...1.00 x In 0.05 CB ailure mode
(Operating mode o unction)
50BF, 50NBF, 50GBF 1=Current 2=Breaker status 3=Both
CB ail trip mode 50BF, 50NBF, 50GBF 1=Of
2=Without check 3=Current check
Retrip time 50BF, 50NBF, 50GBF 0...60000 ms 10
CB ailure delay 50BF, 50NBF, 50GBF 0...60000 ms 10
CB ault delay 50BF, 50NBF, 50GBF 0...60000 ms 10
able 55. Circuit breaker ailure protection (50BF, 50NBF, 50GBF)
able 55. Circuit breaker ailure protection (50BF, 50NBF, 50GBF)