• No results found

Redundancy

In document imcam206 (Page 151-159)

7.3.1 Introduction

As control systems have become more complex the number of installed devices has multiplied, with each device potentially affecting the overall reliability of the system. System failures, whether due to hardware or software problems may cause downtime or compromise safety. To minimise downtime, vendors have developed products and solutions to provide fault tolerant systems by the use of redundant hardware or software.

Hardware solutions include the use of redundant power supplies, redundant processors, redundant I/O modules, multiple HMIs and redundant cabling. Software solutions might include using separate servers to install supposedly identical software or using different versions of software in master and slave controllers or PLCs. The figure below illustrates a typically distributed field station with redundancy built in, and the discussion below describes the different ways redundancy can be achieved. Figure 122 shows a typical arrangement.

Power supply redundancy: In Figure 122 each PSU is fed from a different UPS. These UPS would normally be configured in a redundant fashion with each one being supplied from different sides of the bus. Each PSU is feeding separate PLCs and I/O racks providing complete isolation of supply. One disadvantage of this setup is that the failure of a PSU will cause loss of a PLC and an I/O rack. An alternative power distribution configuration would be to feed the output of both power supplies to each module using decoupling diodes, as shown in Figure 123 to prevent a short circuit in one PSU affecting the other. The diodes should be tested periodically to ensure a hidden failure does not compromise redundancy.

PSU

CPU

PSU

CPUPSU ANALOGUE INPUT DIGITAL INPUT

DIGITAL OUTPUT

ANALOGUE OUTPUT PSU ANALOGUE INPUT DIGITAL INPUT

DIGITAL OUTPUT

Figure 122 – Typical redundant field station

PSU 2

Figure 123 – Redundant power supplies

PLC redundancy: This can be designed in several ways. The most common way is in a master/slave or „hot standby‟ arrangement where status is continuously monitored and data is synchronised between both controllers. On a failure of the master there will be a bumpless transfer to the slave. Only one controller actually outputs to the I/O modules.

An alternative way is to allow both processors to act as peers and, with both controllers outputting data to the I/O modules, voting is carried out using software algorithms and one or other of the signals is used.

I/O module redundancy: Identical racks can be configured to ensure each line of field I/O is duplicated; in this way the total failure of a single rack will not affect the operation.

Although this may give excellent fault tolerance it is expensive and somewhat complicated to implement. A more usual configuration is to split the I/O logically between the racks or I/O modules. Loss of a rack or power supply to a rack may have an effect on the redundancy of the system, and some field I/O will be lost, but the correct mapping of the I/O will ensure fault tolerance is maintained. For example, from Figure 122, if pumps are operating in a duty/standby configuration, control of one pump will be by I/O rack 1 and the other pump by I/O rack 2. Although loss of I/O rack 1 will cause loss of communication with the duty pump, the system can still start the standby pump as a precaution if required. Fail „as set‟ is the preferred failure mode for most propulsion related equipment such as pumps and cooling water valves. Some classification societies require a pulse-to-start, pulse-to-stop control strategy.

Sensor redundancy: Some critical systems may have twin sensors located close together, or even as part of the same unit. When the same action is carried out, if either or both sensors register a signal the sensors can be considered part of the redundancy system. Once again it enhances redundancy if the outputs from the sensors are mapped to different I/O modules.

Data communication redundancy: Data communication redundancy was discussed in the section on network topologies. The favoured solution at this time for the control network is Ethernet in a star/bus topology. It is normally installed as a dual independent system nominally net A and net B. All aspects of the network are duplicated including cabling, switches, Ethernet adapters, network interface cards (NIC). The drawing at Figure 124 illustrates this by showing separate net A and net B cabling to each of the PLCs. Within the communication module on the PLC there will be individual Ethernet interface adapters.

Figure 124 shows a typical DP/VMS control network. The network switches and any medium converters (STP to fibre) are housed in network distribution units (NDU). It can be seen that losing any single node on the network or any active component (like a switch) will not affect the operation of the overall system as communication is still operational on the

Thruster FS – Thruster Field Station Aux FS – Auxiliary Field Station

PMS FS – Power Management Field Station DPC – Dynamic Positioning Controller

Figure 124 – Typical control network

Normally there is no redundant cabling to the field I/O or even between field stations and main units like the generator control panels or MCCs. Communication is normally via a single Modbus or Profibus connection. However, on safety critical systems such as fire and gas, where a fieldbus connects the vendor specific equipment to the VMS system for activation of CO2, closing of dampers and ventilation etc., it is normal to have a dual Profibus link for redundancy purposes.

7.3.2 Alarm and Monitoring

Most DCS vendors provide an alarm and monitoring system as an integral part of their delivery, if not it will be available as an optional extra. The main purpose of the alarm and monitoring system is to give the operators the basic alarm and status information they require to maintain safe and efficient operation of the plant. Information relating to power management, propulsion, ballast control, HVAC, safety systems etc. should all be available.

To provide this data the distributed control system processes information from a multitude of different sources. It is not unusual for a system to interrogate over 2000 separate I/O devices and large vessels may have upwards of 5000 I/O.

Alarms: Built-in diagnostics should ensure that inconsistencies in expected results will be detected and reported. These inconsistencies may be due to faulty field equipment, faulty wiring, logic errors, incorrect configuration etc. The operator is made aware of these anomalies by the use of audio and visual alarms. The audio alarms are normally buzzers at

the VMS operator stations (OS). This is usually a generic alarm that the operator will silence locally at one of the HMI. The audio alarm is accompanied by a visual alarm on a reserved part of the screen at the operator station.

As all operator stations are peers, the visual alarm will show at each station. This is normally a banner alarm with a brief description of the fault and the tag number or I/O module generating the fault. Although different vendors have different systems, the alarm is normally colour coded with separate colours for severity of fault (yellow or red). Safety critical faults may have a different coloured banner.

Alarm printers are provided to give immediate hardcopy reports on alarms and incidents.

Historically these were parallel port dot matrix printers with a continuous form feed output.

In new or upgraded systems these are being superseded by network fed single sheet feed laser printers. This network is usually an Ethernet network connecting each HMI to the printer. This is a separate network from net A and net B, discussed earlier in the control network, and is normally referred to as net C or the „admin net‟. There is no requirement for redundancy in this network as there are no control functions involved.

Monitoring: Continuous monitoring of control functions is carried out by the alarm and monitoring system with all alarms and process events stored in a database within each operator station. Relevant parts of this history log can be called up within user-defined time slices and all alarms and events displayed. The operator can then use a search string to retrieve specific information.

To assist in fault analysis a history station can be provided, where in addition to alarms and process events, selectable vessel management parameters are recorded for a length of time decided by the operator. Information can then be offloaded to external media for in-depth analysis offsite, or fed into a simulator to recreate a specific situation. Software within the operator stations also allow real time trending to be carried out for most power management and propulsion parameters.

1.26kΩ

2.74kΩ

Switch Open: i=6mA Switch Closed: i=19mA

0V 24V

RCU 1

RCU 2 IO Module

Process Station Field IO

Figure 125 – Typical line monitoring circuit

Further monitoring is carried out including line monitoring of discrete inputs. The simplified drawing at Figure 125 shows a basic line monitoring circuit with a single field input to redundant RCUs. The line to the switch is active at 24V. With the switch open the current in the circuit will be 6mA, with the switch closed the current will be 19mA. Any other signal on the line will be incorrect and raise an alarm. It should be noted this circuit is for illustration of the principle only. In a real situation the resistor values would be different to take the resistance of the wire and impedance matching etc. into consideration.

Appendix 1

Abbreviations List

A

ABS American Bureau of Shipping

AC Alternating current

ACB Air circuit breaker

ACCU Automatic control centralised unmanned

AFE Active front end

AHU Air handling unit AHV Anchor handling vessel AMOT Name of valve manufacturer

ANSI American National Standards Institute

ASCII American Standard code for Information Interchange AVR Automatic voltage regulator

B

BA Bus arbiter

BTT Bow tunnel thruster C

CA Certifying authority CAN Controller area network CB Circuit breaker/control breaker

CW Clockwise

CCW Counter clockwise

CD Carrier detect/collision detect

CO2 Carbon dioxide

CoS Chamber of Shipping

CPP Controlled pitch propeller CPU Central processing unit

CR Close relay

CRC Cyclic redundancy check CSMA Carrier sense multiple access

CT Current transformer

D

DBR Dead bus relay

DBSR Dead bus slave relay

DC Direct current

DCS Distributed control system

DG Diesel generator

DGS Diesel generator set

DGPS Differential Global Positioning System

DI Digital input

DNV Det Norske Veritas

DO Diesel oil

DP Decentralised peripheral – when used as Profibus DP

DP Dynamic positioning

DPC Dynamic positioning console/cabinet DPO Dynamic positioning operator DPS Dynamic positioning system

DTE Data terminating equipment DTL Definite time lag

E

E0 E Zero – DNV notation for unmanned machinery space

ECR Engine control room

EG Emergency generator

EGB Electric governor – backup EPD Electrical power distribution

ER Engineroom

ESD Emergency shut down

F

F&G Fire and gas

FIP Factory interface protocol FMEA Failure mode and effect analysis

FMECA Failure modes and effects criticality analysis FMS Factory message specification

FO Fuel oil

FS Field station

FW Fresh water

FWC Fresh water cooling

Fwd Forward

G

GIF Graphics Interchange Format GPS Global Positioning System GSD Generic station description GTO Gate turn off (thyristor) H

HF High frequency

HFO Heavy fuel oil

HMI Human machine interface

HO Heavy oil

HP High pressure

HPP Hydraulic power pack

HPR Hydro-acoustic position reference HPU Hydraulic power unit

HT High temperature

HTFW High temperature fresh water

HV High voltage

HVAC Heating, ventilation and air conditioning

Hz Hertz

I

I> Low set current I>> High set current

I/O Input/Output

IAS Integrated Automation System

ICMS Integrated control and monitoring system ICS Integrated control system

IDMT Inverse definite minimum time

IEC International Electrotechnical Commission IGBT Insulated gate bipolar transistor

IMCA International Marine Contractors Association IMO International Maritime Organization

IP Internet Protocol

IP Industrial protocol

ISM International Safety Management ISO International Standards Organisation J

JB Junction box

JPG JPEG – Joint Photographic Experts Group

JW Jacket water

K

Kbps Kilo bits per second

kN Kilo newton

kV Kilo volt

kVA Kilo volt ampere

kVAr Kilo volt ampere reactive

kW Kilowatt

L

LAL Low level alarms

LCI Load commutated inverter

LCR Inductance (L), capacitance (C), resistance (R) LED Light emitting diode

LHS Left hand side

LO Lub oil

LOA Length over all

LR Lloyd‟s Register

LRC Longitudinal redundancy check

LS Load sharing

LT Low temperature

LTFW Low temperature fresh water

LV Low voltage

M

mA milliAmps

MAC Medium access control

MAP Main alarm panel

MARPOL Marine Pollution (International Convention for the Prevention of Pollution From Ships,)

MAU Medium access unit

MBC Micro biological contamination Mbps Mega bits per second

MCB Miniature circuit breaker MCC Motor control centre MCCB Moulded case circuit breaker MCOS Manual changeover system MCR Maximum continuous rating MDO Marine diesel oil

MFR Multi function relay MGE Main generator engine MGP Multi generator protection MMI Man machine interface MODU Mobile offshore drilling unit MRU Motion reference unit

MSB Main switchboard

MSC Maritime Safety Committee MTC Manual thruster controls

MUX Multiplexer

MVA Mega volt ampere

MVAr Mega volt ampere reactive MVR Manual voltage regulator

MW Megawatt

N

NC Normally closed

NDE Non drive end

NDU Network distribution unit

NIC Network interface connector/card

NO Normally open

NPS Negative phase sequence

NRZ Non return to zero

O

O2 Oxygen

O/C Open circuit

OIM Offshore installation manager OLE Object linking and embedding OLM Optical link module

OPC Object linking and embedding for process control OPLS Oil pressure low shutdown

OS Operator station/outstation OSI Open system interconnection OSV Offshore supply vessel

OT Operator terminal

P

PA Power available

PC Personal computer

PCU Process control unit

PDC Producer/ distributor/ consumer PID Proportional integral and differential PLC Programmable logic controller PMG Permanent magnet generator

PMS Power management system

PS Process station

psi Pounds per square inch

PSU Power supply unit

PWM Pulse width modulation Q

QC Quick closing

QCV Quick closing valve QoS Quality of service R

RAM Random access memory

RCS Remote control system RCU Remote control unit

RHS Right hand side

RMS Route mean squared ROV Remotely operated vehicle

RP Reverse power

RPM Revolutions per minute RTD Resistance temperature device S

s Second(s)

S/C Short circuit

SCADA Supervision control and data acquisition SCR Silicon control rectifier

SLD Single line diagram

SMS Safety management system

Stbd Starboard

STP Shielded twisted pair

SW Sea water

SWBD Switchboard

SWG Standard wire gauge T

TC Thruster controller

TCP/IP Transmission control protocol/internet protocol TDAVR Thyristor divert automatic voltage regulator THD Total harmonic distortion

TMCC Thruster motor control centre TMS Thruster management system

TW Taut wire

U

UHF Ultra high frequency

UMS Unattended machinery space UPS Uninterruptible power supply V

V Volts

VAr Volt ampere reactive VAS Vessel automation system VCB Vacuum circuit breakers VDU Visual display unit

VENT Ventilation

VHF Very high frequency VFD Variable frequency drive VMS Vessel management system VSD Variable speed drive

VT Voltage transformer

W

WCFDI Worst case failure design intent Z

Z Impedance

In document imcam206 (Page 151-159)