• No results found

TABLE B ABSORBER

In document DP03B (Page 38-46)

TABLE C

LOW SURFACE TENSION(SEE NOTE 1) Foaming

Factor

Molecular Weight

(Note 3) Foaming Factor MW Lean Oil Foaming Factor Multiplier

Surface Tension (dyn/cm (mN/m)

1 <150 1.05 <100 1.05 2-2.5

1.05 150-250 1.1 100-150 1.1 1.5-2

1.1 250-300 1.2 150-300 1.2 1-1.5

1.2 >300 1.3 >300 1.3 <1

Notes 1: Apply "low surface tension foaming factor multiplier" only if a foam factor not already available from Table 2.

2: The foam factors for ethylene recovery towers are being reevaluated. If applying these foam factors results in exceeding the allowable tray design criteria please consult with a FRACTIONATION SPECIALIST.

3: The information on the foam factor dependency on molecular weight is general guidance and may be conservative at times and it may be overridden if a particular engineer has experience that shows otherwise.

Table 3

Equations For Determining Liquid And Vapor Splits

The equations for liquid, vapor, and pressure drop distribution are presented here for three and four pass trays. The appropriate equations in each set are modified for the special case of vapor crossover. Each set of equations must be solved by trial-and-error. EMoTIP contains a convergence procedure that solves the flow rates and pressure drops for multipass trays. This program should be used for all multipass tray designs. Note that feed trays, drawoff trays, and reboiler return areas of three and four pass trays can get complicated, and may not be thoroughly discussed in Section III-H. Therefore, consultation with a FRACTIONATION SPECIALIST is recommended.

Three Pass Trays

To determine the vapor and liquid flow rates for each pass of a three pass tray, the following equations must be solved (refer to Figure 8). This is a trial and error procedure for rating purposes only.

NO VAPOR CROSSOVER WITH VAPOR CROSSOVER

Replace Eqs. (4) and (5) (1) QLa = QLC

(2) hdb = hdc

(3) QLa + QLb + QLc = QLtotal (4) If hta > htb, then hta = htb + hvt (4) wva = wvc If htb > hta, then htb = hta + hvt (5) hta + htc = 2 htb (5) htb = htc

(6) wva + wvb + wvc = wvtotal where:

hta = heda + hca htb = hedb + hcb htc = hedc + hcc

Note: Sub-subscripts a, b, and c refer to the pass of the tray.

Four Pass Trays

To determine the vapor and liquid flow rates for each pass of a four pass tray, the following equations must be solved (refer to Figure 9). This is a trial and error procedure.

NO VAPOR CROSSOVER WITH VAPOR CROSSOVER

REPLACE EQS. (5), (6), (7), AND (8) (1) QLa = QLc

(2) QLb = QLd (3) hdc = hdd

(4) QLa + QLb + QLc + QLd = QLtotal (5) If hta > htb, then hta = htb + hvt (5) wva = wvc If htb > hta, then htb = hta + hvt (6) wvb = wvd (6) htc = htd

(7) hta + htc = htb + htd (7) 2wva + 2wvb = wvtotal (8) wva + wvb + wvc +wvd = wvtotal (8) 2wvc + 2wvd = wvtotal where:

hta = heda + hca htb = hedb + hcb htc = hedc + hcc htd = hedd+ hcd

Note: Sub-subscripts a,b,c, and d refer to the pass of the tray

Table 4

Default Design Algorithm Values Table 4A (Customary Units)

Default Values (1)

Min Max Step Target

Fouling and service-specific geometries

Hole diameter (do), in. Determined from fouling factor

Tray thickness (t), in. Determined from service

Geometry limits

Downcomer clearance (C), in. (2) 3.5 0.125

Downcomer top width (r), in. 6 H (3) 0.25

Downcomer bottom width (rud), in. (4) 6 r 0.25

1-pass: rud fracmin = rud / Diameter (5) 0.1097

2-pass: rud fracmin = rud / Diameter (6) 0.0993

4-pass: rud fracmin = rud / Diameter (7) 0.0764

Tray spacing (H), in. (2) 36 3

Flow path length (lfp), in. 16 180

Number of passes (Np) 1 4 (Allows 1,2,4)

Tower diameter (Dt), ft.: 1-pass 2.5 50 0.5

2-pass 5 50 0.5

4-pass 10 50 0.5

Hole area to bubble area ratio (Ao/Ab): sieve 0.035 0.15 0.0025

valve 0.05 0.18 0.0025

Effective weir length [for cases w/ picket fence], in. 0.25

Glitsch valve pitch, in. 3.0

Operating limits

Liquid flowrate per outlet weir length, gpm/in. 1.5 17.5

Universal ultimate capacity, % 80

Tray ultimate capacity, % OFmax(8)

Downcomer flood, % OFmax(8)

Jet flood, % OFmax+6(8)

Dry tray pressure drop, in. of hot liquid 1.25 5.5 (9)

Overall flood, % 80

Downcomer choke due to vapor bubble velocity, % 95

Froth to spray transition (% of PEGASYS limit) 110

Entrainment [both Exxon and Mobil models], % 10

Geometric mean of % DC Froth Backup and % DC Choke 70

Downcomer seal, in. -0.5

Weeping, % 20

Velocity under the downcomer, (Vud) ft/s 1.3 1.1

Notes: Table 4A

(1) Allows user override of all geometry limits and operating limits (min, max, step, target).

(2) Determined from fouling factor and foaming factor.

(3) Large diameter towers are designed at the minimum rud / diameter given in table, and limited to a maximum of (r / H) = 1.20.

(4) Only straight downcomers are allowed when foaming factor ≥ 1.3.

(5) Based on 62.5% DC outlet length / diameter.

(6) Based on 60% side DC outlet length / nearest center DC chord length.

(7) Based on 60% side DC outlet length / nearest off-center DC chord length.

(8) OF designates overall flood.

(9) 2.25 if foaming factor ≥ 1.1.

Default Design Algorithm Values Table 4B (Metric Units)

Default Values (1)

Min Max Step Target

Fouling and service-specific geometries

Hole diameter (do), mm Determined from fouling factor

Tray thickness (t), mm Determined from service

Geometry limits

Downcomer clearance (c), mm (2) 90 3.125

Downcomer top width (r), mm 150 H (3) 6.25

Downcomer bottom width (rud), mm. (4) 150 r 6.25

1-pass: rud fracmin = rud / Diameter (5) 0.1097

2-pass: rud fracmin = rud / Diameter (6) 0.0993

4-pass: rud fracmin = rud / Diameter (7) 0.0764

Tray spacing (H), mm (2) 900 75

Flow path length (lfp), mm 400 4500

Number of passes, (NP) 1 4 (Allows 1,2,4)

Tower diameter (Dt), mm: 1-pass 750 15,000 150

2-pass 1500 15,000 150

4-pass 3000 15,000 150

Hole area to bubble area ratio (Ao/Ab): sieve 0.035 0.15 0.0025

valve 0.05 0.18 0.0025

Effective weir length [for cases w/ picket fence], mm 6.25

Glitsch valve pitch, mm 75

Operating limits

Liquid flowrate per outlet weir length, dm3/s/m 3.73 43.47

Universal ultimate capacity, % 80

Tray ultimate capacity, % OFmax(8)

Downcomer flood, % OFmax

Jet flood, % OFmax+6

Dry tray pressure drop, mm of hot liquid 31.75 139.7 (9)

Overall flood, % 80

Downcomer choke due to vapor bubble velocity, % 95

Froth to spray transition (% of PEGASYS limit) 110

Entrainment [both Exxon and Mobil models], % 10

Geometric mean of % DC Froth Backup and % DC Choke 70

Downcomer seal, mm -12.7

Weeping, % 20

Velocity under the downcomer, m/s 0.396 0.335

Notes: Table 4B

(1) Allows user override of all geometry limits and operating limits (min, max, step, target).

(2) Determined from fouling factor and foaming factor.

(3) Large diameter towers are designed at the minimum rud / diameter given in table, and limited to a maximum of (rud / H) = 1.20.

(4) Only straight downcomers are allowed when foaming factor ≥ 1.3.

(5) Based on 62.5% DC outlet length / diameter.

(6) Based on 60% side DC outlet length / nearest center DC chord length.

(7) Based on 60% side DC outlet length / nearest off-center DC chord length.

(8) OF designates overall flood.

(9) 57.15 if foaming factor ≥ 1.1.

Figure 1

Weeping And Dumping Regions

1.0

0.2

Weeping Region

Vapor Rate Dump

Point Dumping

Region 0

Fractional Weepage, fw

Unacceptable Efficiency

Fair To Poor

Efficiency Good

Efficiency

Good Efficiency

DP3BF10

Weep Point

Figure 2

EMoTIP Tray Performance Diagrams (Customary Units)

Figure 2A

EMoTip Performance Diagram For C6/C7, 24 PSIA Physical properties:

ρV = 0.321298 lb/ft3 ρL = 40.7 lb/ft3 µV = 0.0082 cP µL = 0.239 cP σ = 13.91 dyn/cm ff = 1.00

0 0.1 0.2 0.3 0.4 0.5 0.6

0 2 4 6 8 10 12 14 16

Liquid rate (gpm / inch of weir) Cb (ft/s)

Figure 2B

EMoTIP Performance Diagram For iC4/nC4, 165 Psia

Physical properties:

ρV = 1.78 lb/ft3 ρL = 30.7 lb/ft3 µV = 0.0096 cP µL = 0.089 cP σ = 5.15 dyn/cm ff = 1.00

0 0.1 0.2 0.3 0.4 0.5 0.6

0 2 4 6 8 10 12 14 16

In document DP03B (Page 38-46)

Related documents