Flexural creep of steel fiber reinforced concrete in the cracked
state
.
White Rose Research Online URL for this paper:
http://eprints.whiterose.ac.uk/91897/
Version: Accepted Version
Article:
Garcia-Taengua, E, Arango, S, Marti-Vargas, JR et al. (1 more author) (2014) Flexural
creep of steel fiber reinforced concrete in the cracked state. Construction and Building
Materials, 65. pp. 321-329. ISSN 0950-0618
https://doi.org/10.1016/j.conbuildmat.2014.04.139
© 2014, Elsevier. Licensed under the Creative Commons
Attribution-NonCommercial-NoDerivatives 4.0 International
http://creativecommons.org/licenses/by-nc-nd/4.0/
eprints@whiterose.ac.uk https://eprints.whiterose.ac.uk/
Reuse
Unless indicated otherwise, fulltext items are protected by copyright with all rights reserved. The copyright exception in section 29 of the Copyright, Designs and Patents Act 1988 allows the making of a single copy solely for the purpose of non-commercial research or private study within the limits of fair dealing. The publisher or other rights-holder may allow further reproduction and re-use of this version - refer to the White Rose Research Online record for this item. Where records identify the publisher as the copyright holder, users can verify any specific terms of use on the publisher’s website.
Takedown
If you consider content in White Rose Research Online to be in breach of UK law, please notify us by
LIST OF TABLES
Table 1. Variables considered.
Table 2. Combinations of variables corresponding to the variables tested.
Table 3. Experimental results from the creep tests performed.
Table 4. Results from the MLR analyses (additive models) on creep parameters.
Table 1. Variables considered.
Variables Levels Compressive strength
of concrete, fc
40 MPa 25 MPa Maximum aggregate size
(MAS)
10 mm 20 mm
Fiber slenderness, f
Fiber length, Lf
80/35 80/50 65/40 45/50 50/30
Fiber content, Cf
40 kg/m3
70 kg/m3
Nominal load ratio, IFn 60% 80%
Position of specimen
1 (top) 2
Table 2. Combinations of variables corresponding to the variables tested. Id. fc MPa Max.aggr. size, mm Cf
kg/m3 f
Lf
mm IFa
Table 3. Experimental results from the creep tests performed.
COR (x10–3) spCOR (x10–3)
(14) (30) (90) 0(14) 0(30) 0(90)
Id. r wci wcd(90) 0-14 14-30 30-90 0-14 14-30 30-90
Table 4. Results from the MLR analyses (additive models) on creep parameters.
fc MAS Cf fCf LfCf IFa Pos. R2
r (–) (–) (+) (+) -- -- 0.84
wci (+) (+) (–)3 0.80
wcd(90) (+) (–) (+) (–)3 0.77
COR(0-14) (+) (–)3 0.83
COR(14-30) (–) (+) 0.27
COR(30-90) (–) (–) (–) (+) (+) 0.63
spCOR(0-14) (+) (–) (+) (–)3 0.71
spCOR(14-30) (–) (+) 0.30
spCOR(30-90) (–) (–) (–) (+) 0.69
(14) (–) (–) (+) 0.40
(30) (–) (–) (–) (+) 0.47
(90) (–) (–) (–) (+) 0.55
o(14) (+) 0.56
o(30) (+) (–) (+) 0.58
o(90) (+) (–) (+) 0.55
(count) 6 6 5 11 4 12 4
+/− in each case indicates the sign of the coefficient multiplying the corresponding simple effect
Table 5. Results of the MLR analyses (constitutive models) on creep parameters.
IFa fc·IFa MAS·IFa Cf·IFa fCf·IFa LfCf·IFa Pos·IFa R2
r -- -- -- -- -- -- --
wci (+) (+) (–)3 0.84
wcd(90) (+) (–)3 0.72
COR(0-14) (+) (–)3 0.84
COR(14-30) (+) (+) (–) 0.24
COR(30-90) (+) (–) (–) 0.59
spCOR(0-14) (+) (–) (–) (–)3 0.76
spCOR(14-30) (+) (–) 0.31
spCOR(30-90) (+) (–) (+) (–) (–) 0.74
(14) (+) (–) 0.32
(30) (+) (–) 0.39
(90) (+) (–) 0.39
o(14) (+) 0.56
o(30) (+) 0.53
o(90) (+) (+) (–) 0.55
(count) 10 5 2 6 7 1 4
+/− in each case indicates the sign of the coefficient multiplying the corresponding simple effect or