Theses
Thesis/Dissertation Collections
1990
Heating, ventilation and air conditioning
engineering and design
Kurt Kuegler
Follow this and additional works at:
http://scholarworks.rit.edu/theses
This Thesis is brought to you for free and open access by the Thesis/Dissertation Collections at RIT Scholar Works. It has been accepted for inclusion
in Theses by an authorized administrator of RIT Scholar Works. For more information, please contact
.
Recommended Citation
Abstract
The
object ofthis
Design
Project
wasto
learn
anddemonstrate
the
engineering
anddesign
ofHeating,
Ventilation
andAir
Conditioning
systems.This
wasdone
in
two
parts.The
first
part
wasthe
design
project.The
design
project consisted ofdesigning
the
heating,
ventilation and
air-conditioning
systemsfor
athree
story
office
building.
The
second partdiscusses
the
theoretical
aspects of
heating,
ventilation andair-conditioning
systemsTable
ofContents
Part
1
1.
Design
Proposal
2
1.1
Proposal
2
1.2
The
Building
2
1.3
The
Choice
ofBuilding
Systems
2
1.4
Depth
ofAnalysis
andDesign
3
2.
Building
Loads
4
2.1
Method
Used
To
Determine
Loads
4
2.2
Building
Input
10
2.3
Determining
Building
Loads
13
2.4
Discussion
ofLoad
Calculations
14
3.
Building
Systems
16
3.1
General
16
3.2
Variable
Air
Volume
System
(VAV)
16
3.3
Water
Source
Heat
Pump
System
17
3.4
Ventilation
System
17
3.5
Exhaust
System
18
3.6
Water
Loop
System,
Boiler,
Fluid
Cooler,
Air
Separator,
Compression
Tank
andPumps
18
3.7
Controls
andControl
Sequence
19
4.
Psychrometrics
22
4.1
Variable
Air
Volume
System
22
4.2
Heat
Pump
System
34
5.
Components
50
5.1
Variable
Air
Volume
System
50
5.2
Heat
Pump
System
53
5.3
Ventilation
System
54
5.4
Exhaust
System
56
Part
2
6.
Thermodynamics
66
6.1
Basic
Concepts
andDefinitions
66
6.2
First
Law
of
Thermodynamics
69
6.3
Second
Law
ofThermodynamics
72
7.
Fluid
Flow
83
7.1
Eulerian
Integral
approach83
7.2
Basic
Equations
in
Integral
form
for
aControl
Volume
83
7.3
Bernoulli
Equation
(incompressible
invisid
flow)
-along
a streamline:
84
7.4
Static,
Stagnation,
andDynamic
Pressures
84
7.5
Unsteady
Bernoulli
Equation
86
7.6
Internal
Incompressible
Viscous
Flow
86
7.7
Calculation
ofHead
Loss
in
Piping
Systems
87
7.8
Static
Pressure
Loss
in
Air
Duct
Systems
94
8.
Heat
Transfer
101
8.1
Conduction
101
8.2
Convection
105
8.3
Radiation
106
9.
Mass
Transfer
111
9.1
Molecular
diffusion
111
9.2
Convection
ofMass
114
10.
Psychrometrics
118
10.1
Moist
Air
andthe
Standard
Atmosphere
118
10.2
Fundamental
Parameters
119
10.4
Classic
Moist
Air
Processes
125
10.5
The
Goff
andGrath
Tables
for
Moist
Air
133
11.
Comfort
andHealth
136
11.1
Thermal
Interchanges
Between
People
andTheir
Environments
136
11.2
Comfort
Conditions
141
11.3
Indoor
Climate
andHealth
142
11.4
Control
ofIndoor
Air
Quality
143
12.2
Convection
150
12.3
Thermal
Radiation
150
12.4
Overall
Heat
Transfer
Coefficient
(U)
155
13.
Solar
Radiation
165
13.1
The
motion ofthe
Earth
About
the
Sun
165
13.2
Time
167
13.3
Solar
Angles
168
13.4
Solar
Irradiation
172
14.
Space
Heat
Load
178
14.1
Outdoor
Design
Conditions
179
14.2
Indoor
Design
Conditions
179
14.3
Calculation
ofHeat
Losses
179
14.4
Heat
Losses
From Air
Ducts
192
14.5
Auxiliary
Heat
Sources
192
14.6
Intermittently
Heated
Structures
192
14.7
Estimating
Fuel
Requirements
192
15.
The
Cooling
Load
195
15.1
Heat
Gain,
Cooling
Load,
andHeat
Extraction
Rate
196
15.2
Outdoor
andIndoor
Design
Conditions
201
15.3
The
CLTD
Method
201
15.4
Cooling
Load-External
Sources
203
15.5
Cooling
Load
-Internal
Sources
222
15.6
Heat
Gain
From
Infiltration
andOutdoor
Ventilation
Air
228
15.7
Summation
ofHeat
Gains
andCooling
Loads
228
15.8
Cooling
Loads
by
the
Transfer
Function
Method
228
15.9
Heat
Extraction
Rate
andRoom
Temperature
238
16.
Water
Piping
Systems
242
16.1
The
Conventional
One-Pipe
System
243
16.2
The
Two-Pipe
Direct-Return
System
244
16.3
The
Two-Pipe
Reverse-Return
System
245
16.4
The
Three-Pipe
Arrangement
246
16.5
Four-Pipe
Arrangement
247
16.6
Pipe
Expansion
247
16.7
Pipe
Anchors
andSupports
249
16.8
Pumps
250
16.9
Special
Fittings
andDevices
Required
in
17.
Fans
andBuilding
Air
Distribution
256
17.1
Fans
256
17.2
Fan
Performance
258
17.3
Fan
Selection
265
17.4
Fan
Installation
267
17.5
Fans
andVariable
Air
Volume
Systems
268
17.6
Air
Flow
In
Ducts
andFittings
271
17.7
Duct
Design
-General
Considerations
271
17.8
Design
ofLow
Velocity
Duct
Systems
274
17.9
Turning
Vanes
andDampers
27 6
17.10
High
Velocity
Duct
Design
279
18.
Air-Conditioning
andHeating
Systems
282
18.1
All-Air
Systems
282
18.2
All-Water
Systems
302
18.3
Air-and-Water
Systems
305
18.4
Heat
Pumps
-Applied
308
19.
Special
Topics
322
19.1
Noise
andVibration
322
19.2
Codes
323
19.3
Controls
323
Refernces
324
Appendix
20.
Calculations
320
20.1
Load
Calculation
Sample
Output
321
20.2
Piping
System
322
21.
Drawings
323
21.1
Architectural
324
21.2
Mechanical
325
List
ofTables
Table
4-1,
Property
Chart
-VAV
Cooling
Table
4-2,
First
Law
Chart
-VAV
Cooling
Table
4-3,
Property
Chart
-Heat
Pump
Cooling
Table
4-4,
First
Law
Chart
-Heat
Pump Cooling
Table
4-5,
Property
Chart
-Heat
Pump Heating
Table
4-6,
First
Law
Chart
-Heat
Pump Heating
Table
5-1,
VAV
Boxes
Table
5-2,
Diffusers
Table
5-3,
Heat
Pumps
Table
5-4,
Ventilation
Fans
Table
5-5,
Exhaust
Fans
56
Table
7-1,
Minor
Loss
Coefficients
for
Pipe
Entrances
Table
7-2,
Loss
Coefficients
for
Gradual
Contractions
Round
andRectangular
Ducts
Table
7-3,
Representative
Dimensionaless
Equivalent
Lengths
(Le/D)
for
Valves
andFittings
Table
8-1,
Low-temperature
Emissivity
andHigh-temperature
Absorptivity
ofVarious
Surfaces
Table
8-2,
Spectral
Transmittance
ofGlass
Table
10-1,
Constants
A,
B
andC
(standard
atmospheric
pressure)
Table
12-1,
Table
12-2,
Table
12-3,
Table
12-4,
Table
12-5,
Table
12-6,
Table
12-7,
Table
12-8,
Thermal
Resistances
for
Some
Steady
state
Conduction
Problems
Thermal
Properties
ofBuilding
andInsulating
Materials
at aMean
Temperature
of75F
(English
Units)
Surface
Unit
Conductances
andUnit
Resistance
for
Air
Reflectance
andEmittance
ofVarious
Surfaces
andEffective
Emittance
ofAir
Spaces
Unit
Thermal
Resistance
of aPlane
3/4
inch
Air
Space
Unit
Thermal
Resistance
of aPlane
3.5
inch
Air
Space
Unit
Thermal
Resistance
ofPlane
Horizontal
Air
Spaces
With
Heat
Flow
Downward,
Temperature
Difference
10
Deg
F
Coefficients
ofTransmission
U
ofFrame
Walls,
BTU/(hr
ft2
F)
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12
Table
12-21
9,
Coefficients
ofTransmission
U
ofSolid
Masonry
Walls,
BTU/(hr
ft2
F)
10,
Coefficients
ofTransmission
U
ofMasonry Cavity Walls,
BTU/(hr
ft2
F)
Coefficients
ofTransmission
U
ofCeilings
andFloors,
BTU/(hr
ft2
F)
Coefficients
ofTransmission
U
ofFlat
Built
Up Roofs,
BTU/(hr
ft2
F)
Coefficients
ofTransmission
U
ofPitched
Roofs,
BTU/(hr
ft2
F)
Overall
Coefficients
ofHeat
Transmission
(U-Factor)
ofWindows
andSkylights,
BTU/(hr
ft2
F)
Adjustment
Factors
for
Coefficients
U
ofTable
12-14,
BTU/(hr
ft2
F)
Coefficients
ofTransmission
U
ofSlab
Doors,
BTU/(hr
ft2
F)
17,
Heat
Loss
Through
Basement
Floors
(for
Floors
More
Than
3
ft
Below
Grade)
18,
Heat
Loss
Rate
for
Below-Grade
Walls
With
Insulation
onInside
Surface
19,
Heat
Loss
ofConcrete
Floors
Ltss
Than
3
ft
Below
Grade
Floor
Heat
Loss
for
Concrete
Slabs
With
Embedded
Warm
Air
Perimeter
Heating
Ducts
(Per
Unit
Length
ofHeated
Edge)
Transmission
Coefficients
U
For
Horizontal
Bare
Steel
Pipes
andFlat
Surfaces,
BTU/(hr
ft2
F)
-11, -12, -13, -14, -15. -16, 20Table
13-1,
The
Equation
ofTime
Table
13-2,
Extraterrestrial
Solar
Radiation
andRelated
Data
for
Twenty-First
Day
ofEach
Month,
Base
Year
1964
Table
14-1,
Air
Changes
Taking
Place
Under
Average
Conditions
in
Residences.
Exclusive
ofAir
Provided
for
Ventilation
Pressure
Coefficients
for
aRectangular
Building
Table
14-3,
Window
Classification
Residential-Type
Door
Classification
Curtain
Wall
Classification
Table
14-2,
Table
14-4,
Table
14-5.
157
157
158
158
159
160
161
161
162
162
163
163
164
168
175
182
184
188
189
189
Table
15-1,
Cooling
Load
Temperature
Differences
for
Calculating
Cooling
Load
From
Flat
Roofs
205
Table
15-2,
Cooling
Load
Temperature
Differences
for
Table
15-7
Table
15-10
Table
15
Table
15
-11 -12Table
15-3,
CLTD
Correction
For
Latitude
andMonth
Applied
to Walls
and
Roofs,
North
Latitudes
207
Table
15-4,
Roof
Construction
Code
208
Table
15-5,
Wall
Construction
Group
Description
209
Table
15-6,
Thermal
Properties
andCode
Numbers
ofLayers
Used
in Calculations
ofCoefficients
for
Roof
andWall
210
Cooling
Load
Temperature
Difference
for
Conduction
Though
Glass
andConduction
Through
Doors
212
Table
15-8,
Shading
Coefficient
for
Single
Glass
and
Insulating
Glass
213
Table
15-9,
Shading
Coefficients
For
Single
Glass
With
Indoor
Shading
by
Venetian
Blinds
and
Roller
Shades
215
Shading
Coefficients
For
Insulating
Glass
With
Indoor
Shading
by
Venetian
Blinds
andRoller
Shades
216
Shading
Coefficients
For
Single
andInsulating
Glass
With
Draperies
218
Maximum
Solar
Heat
Gain
Factor
For
Externally
Shaded
Glass,
BTU/(HR-FT2)
(Based
onGround
Reflectance
of .2)219
Maximum
Solar
Heat
Gain
Factor,
BTU/(HR-FT2),
for
Sunlit
Glass,
North
Latitudes
220
Cooling
Load
Factors
for
Glass
Without
Interior
Shading,
North
Latitudes
221
Table
15-15,
Cooling
Load
Factors
for
Glass
With
Interior
Shading,
North
Latitudes
222
Table
15-16,
Rates
ofHeat
Gain
from
Occupants
ofConditioned
Spaces
223
Table
15-17,
Sensible
Heat
Cooling
Load
Factors
for
People
224
Table
15-18,
Cooling
Load
Factors
When
Lights
are on
for
10
Hours
225
Table
15-19,
"a"Classification
for
Lights
226
Table
15-20,
"b"Classification
for
Lights
227
Table
15-21,
Sensible
Heat
Cooling
Load
Factors
for
Appliances-Unhooded
227
Table
15-22,
Transfer
Function
Coefficients
for
Exterior
Walls
(Time
Interval
=1.0
hr)
231
Table
15-23,
Transfer
Function
Coefficients
for
Roofs
(Time
Interval
=1.0
hr)
232
Table
15-24,
Transfer
Function
Coefficients
for
Interior
Partitions,
Floors,
andCeilings
(Time
Interval
=1.0
hr)
233
Table
15-25,
Percentage
ofthe
Daily
Range
234
Table
15-13
Air
Circulation
Rates
andEnvelope
Construction
236
Table
15-28,
Normalized
Coefficients
ofthe
Room
Air
Transfer
Function
239
Table
16-1,
Linear
Expansion
ofPipe
in
Inches
per
100
Feet
248
Table
17-1,
Comparison
ofCentrifugal
Fan
Types
262
Table
17-2,
Pressure-Capacity
Table
for
aForward-curved
Blade
Fan
266
Table
17-3,
Recommended
Maximum
Duct
Velocities
for
High
Velocity
Systems
272
Table
17-4,
Recommended
andMaximum
Duct
Velocities
for
Low
Velocity
Systems
273
Table
18-1,
Common
Heat
Pump
Types
309
List
ofFigures
Figure
2-1,
Space
Input
Sheet
6
Figure
2-2,
Zone
Input
Sheet
9
Figure
4-1,
Floor
2,
VAV
System
Diagram,
Maximum
Cooling
23
Figure
4-2,
Floor
2,
VAV
Psychrometric
Chart,
Maximum
Cooling
26
Figure
4-3,
Floor
2,
VAV
System
Diagram,
Morning
Warm-up
31
Figure
4-4,
Floor
2,
VAV
Psychrometric
Chart,
Morning Warm-up
32
Figure
4-5,
Floor
2,
Heat
Pump
System
Diagram,
Maximum
Cooling
35
Figure
4-6,
Floor
2,
Heat
Pump
Psychrometric
Chart,
Maximum
Cooling
38
Figure
4-7,
Floor
2,
Heat
Pump
System
Diagram,
Morning
Warm-up
41
Figure
4-8,
Floor
2,
Heat
Pump
System
Diagram,
Maximum
Heating
44
Figure
4-9,
Floor
2,
Heat
Pump
Psychrometric
Chart,
Maximum
Heating
46
Figure
5-1,
Ventilation
Flow
Diagram
55
Figure
5-2,
Exhaust
Flow
Diagram
57
Figure
5-3,
Piping
Diagram
59
Figure
6-1,
Thermodynamic
System
70
Figure
6-2,
Carnot
Cycle
-Temperature
Versus
Entropy
Diagram
75
Figure
6-3,
Vapor
Compression
Refrigeration
System
76
Figure
6-4,
Vapor
Compression
Refrigeration
Cycle,
Pressure
Versus
Enthalpy
Diagram
77
Figure
6-5,
Vapor
Compression
Refrigeration
Cycle,
Temperature
Versus
Entropy
Diagram
77
Figure
6-7,
Vapor
Compression
Refrigeration
Cycle,
Pressure
Versus
Specific
Volume
78
Figure
6-8,
Compressor
78
Figure
6-9,
Condenser
79
Figure
6-10,
Throttle
80
Figure
6-11,
Evaporator
81
Figure
7-1,
Wall
Pressure
Tap
85
Figure
7-2,
Static
Pressure
Probe
85
Figure
7-3,
Stagnation
Pressure
Gauge
85
Figure
7-4,
Entrance
Length
andFully
Developed
Flow
87
Figure
7-5,
Friction
Factor
for
Fully
Developed
Flow
Figure
7-6,
Relative
Roughness
Values
for
Pipes
of
Common
Engineering
Materials
89
Figure
7-7,
Loss
Coefficients
for
Flow
through
Sudden
Area
Changes
91
Figure
7-8,
Pressure
Recovery
Data
for
Conical
Diffusers
withFully
Developed
Turbulent
Pipe
Flow
at
Inlet
92
Figure
7-9,
Representative
Resistance
values(Le/D)
for
(a)
90*Pipe
Bends
andFlanged
Elbows,
and
(b)
Miter
Bends
93
Figure
7-10,
Converging
andDiverging
Flows
99
Figure
8-1,
Conduction
Through
aSingle
Material
101
Figure
8-2,
One
Dimensional
System
in
Rectangular
Coordinates
102
Figure
8-3,
Volume
Element
in
Cylindrical
Coordinates
103
Figure
8-4,
One
Dimensional
System
103
Figure
8-5,
Materials
in
Series
104
Figure
8-6,
Composite
Wall
in
Series/Parallel
Arrangement
105
Figure
8-7,
Variation
ofNormal
Spectral
Emissivity
with
Wavelength
for
Several
Surfaces
108
Figure
8-8,
Variation
ofthe
Total
Normal
Emissivity
en
With
Temperature
109
Figure
8-9,
Variation
ofNormal
Spectral
Reflectivity
P0n andNormal
SpectralAbsorptivity
ot0nWith
Wavelength
for
Various
opaqueSurfaces
109
Figure
9-1,
Mass
Transfer
for
anExternal
Flow
115
Figure
9-2,
Mass
Transfer
for
anInternal
Flow
116
Figure
9-3,
Mass
Transfer
for
turbulent
Flow
Regions
117
Figure
10-1,
Adiabatic
Saturation
Device
123
Figure
10-2,
Psychrometric
Chart
124
Figure
10-3,
Heating
orCooling
Device
125
Figure
10-4,
Sensible
Heating
andCooling
126
Figure
10-5,
Cooling
andDehumidif ying
Process
127
Figure
10-6,
Heating
andhumidifying
Process
128
Figure
10-7,
Heating
andHumidifying
Device
129
Figure
10-8,
Humidif
ication
Process
Without
Heat
Transfer
130
Figure
10-9,
Adiabatic
Mixing
Device
131
Figure
10-10,
Adiabatic
Mixing
Process
131
Figure
10-11,
Error
ofPerfect
Gas
Relations
in
calculation of
humidity
ratio,
enthalpy,
and volume ofstandard
airFigure
13--1Figure
13--2Figure
13--3Figure
13--4Figure
13--5Figure
13--6Figure
13-7
Figure
11-1,
Acceptable
Ranges
of
Operative
Temperature
andHumidity
for
Persons
Clothed
in
Typical
Summer
andWinter
clothing,
atLight,
Mainly
Sedentary,
Activity
141
The
Effect
ofthe
Earth's
Tilt
andRotation
About
the
Sun
166
Latitude,
Hour
Angle,
andSun's
Declination
168
The
Solar
Altitude,
Zenith
Angle,
and
Azimuth
Angle
170
Wall
Solar
Azimuth,
Wall
Azimuth,
Angle
ofTilt
for
anArbitrary
Tilt
171
Shading
ofWindow
Set
Back
From
Plane
of aBuilding
172
Spectral
Distribution
ofDirect
Solar
Irradiation
atNormal
Incidence
During
Clear
Days
174
Conversion
ofHorizontal
Insolation
to
Insolation
on aTilted
Surface
177
Heat
Loss
Work
Sheet
180
Pressure
Difference
Due
to
Stack
Effect
186
Curtain
Wall
Infiltration
for
One
Room
orOne
Floor
187
Window
andResidential
Type
Door
Infiltration
Characteristics
187
Infiltration
Through
Closed
Swinging
Door
Cracks
188
Infiltration
for
Storm-Prime
Combination
Windows
190
Swinging
Door
Characteristics
With
Traffic
190
Flow
Coefficient
Dependence
onTraffic
Rate
191
Correction
Factor
CD
193
Schematic
Relation
ofHeat
Gain
to
Cooling
Load
197
Actual
Cooling
Load
andSolar
Heat
Gain
for
Light,
Medium,
andHeavy
Construction
197
Distribution
ofSolar
Radiation
Falling
onClear
Plate
Glass
211
Indoor
Shading
Properties
ofDrapery
Fabrics
217
Cooling
Load
Worksheet
229
Figure
15-7,
Room
Air
Temperature
andHeat
Extraction
Rates
for
Continuous
andIntermittent
Operation
241
Figure
16-1,
Series
Loop
Heating
System
242
Figure
16-2,
Conventional
One-Pipe
System
243
Figure
16-3,
Two-Pipe
Direct-Return
System
245
Figure
16-4,
Two-Pipe
Reverse-Return
System
245
Figure
16-5,
Three-Pipe
System
246
Figure
16-6,
Four-Pipe
System
247
Figure.
16-7,
Common
Expansion
Joints
andExpansion
Bends
249
Figure
17-1,
Exploded
View
of aCentrifugal
Fan
257
Figure
17-2,
Axial
Flow
Fans
257
Figure
17-3,
Forward-tip
Fan
Characteristic
260
Figure
17-4,
Backward-tip
Fan
Characteristic
260
Figure
17-5,
Radial-tip
Fan
Characteristic
260
Figure
17-6,
Conventional
Curves
for
Backward-curved
Blade
Fan
261
Figure
17-7,
Performance
Data
for
aTypical
Backward-curved
Blade
Fan
262
Figure
17-8,
Optimum Match
Between
System
andForward-curved
Blade
Fan
263
Figure
17-9,
Performance
Chart
Showing
Combination
ofFan
andSystem
264
Figure
17-10,
Comparison
ofGood
andPoor
Fan
Connections
267
Figure
17-11,
Performance
Curves
Showing
Modified
Fan
Curve
268
Figure
17-12,
Variable
Inlet
Vane
Fan
in
aVariable
Volume
System
270
Figure
17-13,
Variable
Inlet
Vane
Fan
in
aVariable
Volume
System
271
Figure
17-14,
Typical
Use
ofVanes
in
aRectangular
Duct
277
Figure
17-15,
Typical
Opposed
Blade
Damper
Assembly
278
Figure
17-16,
Combination
Turning
Vane
andDamper
Assembly
27 8
Figure
18-1,
Single-Zone
System
285
Figure
18-2,
Single-Zone
System
-Psychrometric
Chart
286
Figure
18-3,
Reheat
System
287
Figure
18-4,
Reheat
System
-Psychrometric
Chart
288
Figure
18-5,
Variable
Air
Volume
System
291
Figure
18-6,
Variable
Air
Volume
System
-Psychrometric
Chart
292
Figure
18-7,
Series
Arrangement
-Plan
View
298
Figure
18-8,
Parallel
Arrangement
-Plan
View
298
Figure
18-10,
Dual
Path
System
-Psychrometric
Chart
301
Figure
18-11,
Typical
Fan
Coil
Unit
303
Figure
18-12,
Typical
Fan-Coil
Unit
Arrangements
303
Figure
18-13,
Air-Water
Induction
Unit
307
Figure
18-14,
Water-to-Water
Heat
Pump
System
311
Figure
18-15,
Air-to-Water
Single
Stage
Heat
Pump
313
Figure
18-16,
Air-to-Air
Heat
Pump
315
Figure
18-17,
Heat
Transfer
Heat
Pump
withDouble-Bundle
Condenser
316
Figure
18-18,
Heat
Transfer
System
withStorage
Tank
317
Figure
18-19,
Multistage
(Cascade)
Heat
Transfer
System
318
Figure
18-20,
Closed
Loop
Solar
Heat
Pump
System
319
Figure
18-21,
Heat
Transfer
System
Using
Introduction
"By
the
end
ofthe
19thcentury
the
concept
ofcentral
heating
wasfairly
well
developed,
andearly
in
the
twentieth
century
cooling
for
comfort
got
its
starf'l.
Since
this
time
there
have
been
many
developments
to
bring
the
industry
to
the
level
of
design
it
has
now.The
greatest
developments
have
been
made
in
the
detailed
analytical
methods
needed
for
the
design
oflarge
systems.
The
most
recentmajor
development
has
been
in
designing
heating,
ventilation
and airconditioning
systems
through
the
use ofcomputers.
The
Heating
Ventilation
andAir
Conditioning
field
is
very
large
in
engineering
andit
has
grown
through
the
input
ofthousand
ofengineers,
their
names
aretoo
numerous
to
list.
This
Design
Project
is
broken
down
into
two
parts.
The
first
part
is
the
design
of aheating
ventilation
andair-conditioning
systemfor
athree
story
office
building.
The
second
part
discusses
the
theoretical
aspect
ofheating
ventilation
and airconditioning
engineering
anddesign.
1
Faye
C.
Mc
.Quiston
andJerald
D.
Parker.
Heating
Ventilation
andAir
Conditioning
Analysis
and
Design.
The
purpose ofthe
design
project wasto
demonstrate
the
concepts
andtheory
ofheating,
ventilation and
air-conditioning
design.
This
wasdone
by
designing
the
heating,
ventilation andair-conditioning
systemsfor
athree
story
officebuilding.
The
design
usedmany
different
types
ofsystems and combinations of systems.
1.2
The
Building
The
building
usedin
this
design
was athree
story
office
building
approximately
160'by
100' or48,000
square
feet.
The
building
wasdesigned
for
tenant
fit
up.
Tenant
fit
up
meansthat
the
office spacefloor
area
is
open andthe
tenant
willinstall
his
own wallsto
createthe
tenant's
desired
office area.The
building's
main entranceis
two
storieshigh
and
leads
into
the
main corridor.This
corridoris
the
samefor
the
othertwo
floors.
The
building's
exterior wall area
is
approximately
40%
glass and60%
brick.
The
building
has
nobasement,
it
is
slab ongrade.
The
roof ofthe
building
is
metaldeck
with afoam/roof
membrane covering.Further
details
ofthe
building
(wall
and roofsections)
canbe
seen onthe
plans .
versus
function.
The
systems
were chosento
demonstrate
the
knowledge
andunderstanding
for
the
HVAC
field.
The
systemin
the
building
uses a waterloop
heat
transfer
system,
using
Water-to-Air
Unitary
heat
pumpsfor
the
building
perimeter and aVariable
Air
Volume
system with central electric
heat
for
the
interior.
The
system uses a gasboiler
and afluid
coolerto
maintain
the
watertemperature
in
the
waterloop.
A
more
detailed
discussion
ofthese
systemsis
givenin
the
chapter"Discussion
ofBuilding
Systems".
1.4
Depth
ofAnalysis
andDesign
The
heating
andcooling
load
analysis wasperformed
in
detail.
The
psychrometric analysis anddesign
portion ofthe
project was performedin
partialdetail.
What
is
meantby
this
is
that
the
psychrometric
analysis,
duct
static pressurecalculations and water
loop
system static pressurecalculations were
only
performedin
detail
for
the
second
floor
ofthis
building.
This
wasdone
because
these
calculations wouldbe
redundant workif
preformed
for
the
othertwo
floors.
The
basis
ofthis
design
projectis
to
showthe
basic
understanding
ofA
computerprogram
was usedto
determine
the
heating
andcooling
loads
for
the
building.
The
computer program used was
the
Hourly
Analysis
Program
by
Carrier.
This
program
used separate methodsfor
determining
the
heating
andcooling
loads.
2.1.1
Heating
Design
Load
Analysis
-The
"Design
Point"analysis
technique
was usedto
determine
the
heating
loads.
A
design
point was usedbecause
usually
the
coldest part ofthe
yearis
at nightat a specific
temperature.
At
this
pointthe
program analyzes
transmission,
ventilation andinfiltration
loads.
This
point selectedis
notassociated with
any
particular month orhour.
2.1.2
Cooling
Design
Load
Analysis
-Cooling
loads
have
to
take
into
consideration ofthe
loads
causedby
thermal
storage and solarheat
gain.Therefor,
anhour
by
hour
analysis was preformedto
computethe
cooling
loads.
From
this
analysis
the
maximumcooling
load
wasdetermined.
Often
this
maximumcooling
load
does
not correspondto
the
maximum outdoortemperature.
2.1.3
Weather
Data
-Weather
data
for
the
cooling
analysis was given
by
a pair ofhourly
wetbulb
empirical method and represents
1%
cooling
design
conditions.
For
design
heating
load
calculations,
the
99%
Winter
design
point wasused.
The
program contains pre-stored weatherdata
ofthis
type
for
over500
cities worldwide.2.1.4
Schedule
Data
-Schedules
were usedto
givehourly
characteristics of
internal
heat
gains.Such
characteristics were
lighting,
occupancy,
miscellaneous
internal
loads
and equipmentoperations .
2.1.5
Define
Spaces
-Spaces
in
abuilding
are areaswhich
have
load
related elementslike
walls,
glass and ceilings.
Usually
spaces areindividual
rooms orfor
vary
large
roomsthere
could
be
many
spaces.For
each spacethere
is
aspace
input
sheetthat
mustbe
filled
out soits
data
canbe
enteredinto
the
computer.An
example of
this
sheetis
onthe
following
two
COMPLEX SPACE INPUT
SHEET
SPACE NAME
PAGE 1 OF 2
WALL INFORMATION
(NUMBER
OF
WALL
TYPES
=)
Weight
(H, M,
L
orIb/sqft)
Ext Color
(D, M, L)
U-Value
(BTU/hr/sqft/F)
Wall Type
1Wall
Type
2Wall Type 3
NET WALL AREAS
(SOFT)
Exposure
Wall
Type
1
Wall Type 2
Wall Type 3
Northeast
East
Southeast
South
Southwest
West
Northwest
North
ROOF INFORMATION
(NUMBER
OF
ROOFTYPES
=)
Weight
(H, M,
L
orIb/sqft)
Ext Color
(D,
M, L)
U-Value
(BTU/hr/sqft/F)
Area
(sqft)
Roof Type 1
Roof Type 2
Roof Type 3
GLASS
INFORMATION
(NUMBER OFGLASS TYPES
=)
U-Value
(BTU/hr/sqft/F)
Glass
FactorInternal
Shades?
Glass Type
1Glass Type
2Glass Type
3
EXTERNAL
SHADING
INFORMATIONWindow
Height
()
Window Width()
Reveal Depth(In)
Overhang
Height
(In)
Overhang
Extension
(In)
Fin
Separation
(In)
Fin
Extension
(In)
Shade
1
Shade
2
Shade
3
Glass Type 1
Glass Type 2
Glass
Type 3
INTERNAL LOADS
SPACE
DATA
:Floor
Area
PEOPLE
: sqft/personSchedule
No.
Sensible Gain
LIGHTING
:W/sqfl
Schedule
No.
Fixture Type
OTHER ELECTRIC
:W/sqft
Schedule
No.
MISC
SENSIBLE
:Load
MISC LATENT
:Load
sqft
Building
Wt.
Total People
Activity
Level
Latent
Gain
Total Watts
Wattage Mult
Total Watts
BTU/hr
Schedule No.
BTU/hr
Schedule No.
PARTITIONS, INFILTRATION,
GROUND
PARTITIONS
(Next to Unconditioned
Spaces)
Area
U-Value
(sqft)
(BTU/hr/sqft/F)
Unconditioned
Space
Temp.
Cooling
Heating
(deg
F
or%)
(deg
F
or%)
Walls
Ceilings
Floors
INFILTRATION
GROUND
ELEMENTCooling
CFM/sqft
=CFM
Area
sqftHeating
CFM/sqft
:CFM
Perimeter
Typical
CFM/sqft
=CFM
Depth
KEYS:
People
Activity
Levels:
1.
Seated
atRest
2.
Office Work
3.
Sedentary
Work
4.
Medium Work
5.
Heavy
Work
(230S/120L)
(245S/205L)
(280S/270L)
(295S/455L)
(525S/925L)
Lighting
Fixture Type:
1.
Recessed,
not vented2.
Vented
characteristics.
Usually
a zoneis
selectedfor
group
of spacesthat
willbe
underthe
sameHVAC
system.
An
example
of a zoneinput
sheetis
onthe
following
page.2.1.7
Running
the
Program
-The
program canbe
runfor
asingle
hour
calculation or multiplehour
calculations.
Usually
multiplehour
calculations are used
to
determine
the
peakcooling
load
ofthe
system.A
single pointcalculation
is
usedto
determine
the
peakZONE INPUT
SHEET
1.
ZONE NAME AND
TYPE
7one Name
2.
THERMOSTAT
AND EQUIPMENT SCHEDULE
COOLING
EQUIPMENT
Joh NameZone
Type
= 1Normal
Zone
2
Single-Space Zones
Unoccupied
coStarling
hour,
cNo.
hours
in
ocHEATING
EQUIP
Heating
thermc
oling
setpoint -F
r.r.{ipiprlppr
cnpied period
MENT
stat setpoint -
F
3.
COOLING
SYTEM
PARAMETERS
SUPPLY
AIRType
ofInput
= 1CFM/sqft
2
CFM
3Temperature
Supply
Air
4.
HEATING
SYSTEM PARAMETERS
HEATING SOURCE
Type
ofheating
sytem = 1Warm Air
2
Hydronic
(If Warm
Air:)
Supply
Temperature
-F
(If
Hydronic:)
Water Temperatiire
Drnp
_F
VENTILATION
AIR
Type
ofInput
= 1CFM/sqft
2
CFM
3
%
suddIvairVENTILATION
AIR
Type
ofInput
=1
CFM/sqft
2
CFM
3 %
supply
air4
CFM/person
Ventilation Air
SAFETY
FACTOR
Clq
Safety
Factor
= %Ventilation Air
SAFETY FACTOR
Heating Safety
4
CFM/person
Factor = V.
5.
OTHER
SYSTEM PARAMETERS
SUPPLY
FANTotal
static pressureTotal
efficiency
_
in wg
%
2(Blow-Thru)
%
of vent airFan
configurationEXHAUST AIR
Direct
exhaustairflow
rate= 1
(Draw-Thru)
RETURN AIR
Is
a return air plenum used(If
Yes:)
%
oflighting
load
toplenum%
of roofload
toplenum%
ofwallload
toplenumCOIL
DATA
Cooling
coilbypass
factor
?
Y
N
%
%
%
6.
SPACE SELECTION
Space Name
Qty
Space Name
Qty
Space Name
Qty
1
18
35
2 19
36
3
20
37
4 21
38
5
22
39
6
23
40
7
2441
8
25
42
9
26
43
10
2744
11
28
45
12
29
46
13
3047
14
3148
15
32
49
16
33
50
2.2
Building
Input
2.2.1
Weather
Input
-Weather
data
wastaken
from
the
area of
Hartford
Connecticut.
2.2.2
Schedule
Data
-There
weretwo
type
ofschedules,
people and
lighting
&
electric.
The
peopleschedule was as
follows:
Week
Day
100%
occup.
8:00
amto
5:00
pm20%
occup.5:00
pmto
8:00
pm0%
occup.8:00
pmto
8:00
amSaturday
20%
occup.8:00
amto
1:00
pm0%
occup.1:00
pmto
8:00
amSunday
0%
occup.All
Day
The
lighting
and electric schedule was asfollows.
Week
Day
100%
8:00
amto
8:00
pm0%
8:00
pmto
8:00
amSaturday
100%
8:00
amto
1:00
pm0%
1:00
pmto
8:00
amSunday
0%
All
Day
2.2.3
Defining
Spaces
-Since
the
floor
areas wereopen,
the
spaces weredivided
into
interior
spaces andperimeter spaces.
Perimeter
spaces extendedfrom
the
outside wallto
approximately
12
feet
to
the
inside
portion ofthe
building.
This
wasdone
because
it
was assumedthat
these
perimeterspaces were
going
to
be
madeinto
private6
approximately
equal
areas.The
names andlocations
ofthese
spaces
canbe
found
in
the
plan
section
ofthis
paper.In
reviewing
the
complex spaceinput
sheet,
the
first
information
that
has
to
be
givenis
the
wall,
roof and glassinformation
data.
The
wall,
roof and glass areas canbe
found
in
the
appendix.
The
weight,
exteriorcolor,
U-value
for
the
walls were calculatedto
be
46
lb.
/sq.ft.,
dark
and .0441BTU/h/sq.
f
t
./
'F
respectively.
The
weight,
exterior color andthe
U-value
for
the
roof were calculatedto
be
3.165
lb.
/sq.ft.,
dark
and .075BTU/h/sq.
ft
./F
respectively.
The
glasshad
aU-value
of .53BTU/h/sq.
ft
./F and a glassfactor
of .6.There
were no
internal
shades or external shadesOn
the
second page ofthe
spaceinput
sheetthe
first
sectiondeals
withinternal
loads.
The
spacedata
varies with each space.The
people
data
was givenin
the
following
form:
The
number of people were given
in
squarefeet
perperson and
ASHRAE
estimatesthat
their
areapproximately
110
sq
.ft
./person
for
an officebuilding.
The
schedule number was given ofthe
occupancy
schedule.The
activity
level
wasThe
lighting
and
other electric were combinedas
6.0
wattsper
square
foot,
which was anaverage
given
by
ASHRAE.
The
schedule wasassociated
withthe
lighting
and electricschedule.
There
were nomiscellaneous
sensibleor
latent
loads.
Partition
data
was enteredaccording
to
the
needs of each space.
Infiltration
data
wasentered as
cfm/sq.ft..
The
valuesinputted
were.05 cfm/sq.ft.
for
perimeter
spaces and0.0
cfm/sq.ft.
for
interior
spaces.Initially
the
air change method was used on
this
building
but
the
values obtainedfrom
this
method weretoo
high
for
aninternally
dominated building.
The
ground element varied
according
to
each space.2.2.4
Defining
Zones
-The
spaces werebroken
up
into
6
different
zones.Each
floor
had
2
zones,
onezone was
for
the
interior
spacesthe
other wasfor
the
perimeter spaces.Inputting
the
zones'data
andreferring
back
to
the
zoneinput
sheet,
the
cooling
systemparameters,
heating
system parameters and othersystem
data
remainedthe
samefor
allthe
zones.The
cooling
system parameters were given as a75F
indoor
dry
bulb
with a50%
relativehumidity,
asupply
airtemperature
input
type
of(a
requirement
given
by
Building
Officials
andCode
Administrators,
BOCA,
codefor
an officebuilding)
and afactor
ofsafety
of10%.
The
heating
systemparameters
were given as anindoor
dry-bulb
temperature
of68
F,
aheating
source as warm air and a
supply
temperature
102F,
ventilation
air was given as20
cfm/person
and asafety
offactor
10%.
The
other systemdata
inputted
was asfollows:
a return air plenum wasused,
100%
ventilation air was
exhausted,
the
lighting
load
to
the
plenum was10%,
andthe
roofload
to
the
plenum was
30%.
The
supply
fan
data
was asfollows:
an exhaust static pressure of ofwater,
adraw
through
configuration,
a coilby
pass
factor
of .05, and a24
hours
of systemoperation.
The
spacesfor
each zonedepended
onthe
specific zone.
Space
multipliers were1.
The
input
for
each zone canbe
found
in
the
appendix.
2.3
Determining
Building
Loads
Four
sets ofheating
andcooling
loads
were run.The
first
setdetermined
the
maximumcooling
andheating
loads
for
the
entire year.The
second,
third
and
fourth
setsdetermined
the
cooling
andheating
This
wasdone
to
determine
if
aheat
pump
system was aviable system
for
this
building.
2.4
Discussion
ofLoad
Calculate
nns2.4.1
Discussion
ofOutput
An
example
ofthe
output canbe
found
in
the
appendix.
2.4.1.1
Maximum
Heating
andCooling
Loads
-These
loads
werecalculated
in
orderthat
the
HVAC
system could
be
sized properly.This
meansthe
HVAC
systemhas
to
meetthe
maximumload
on
the
building.
These
loads
arethe
extremecases
that
the
building's
HVAC
system wouldhave
to
operate under.The
results obtainedthrough
this
analysis were checked againstthe
average values obtainedfrom
ASHRAE
andthese
results correspondedin
an acceptablerange.
The
results areto
lengthy
to
be
presented
in
this
chapter.2.4.1.2
Heating
andCooling
Loads
for
January,
March
and
October
-Heating
andcooling
loads
werecalculated
for
these
monthsto
showthat
aheat
pump
system canbe
usedefficiently
in
this
building
application.To
determine
if
aheat
pump
systemis
viablethere
mustbe
aneed
for
cooling
in
the
building
in
the
Fall,
Winter
andSpring
months sothat
the
heat
transferred
to
other areas ofthe
building.
From
studying
the
cooling
loads
for
these
months
(found
in
the
appendix)
there
is
enough
heat
generated
from
the
needfor
cooling
to
make aheat
pump
system viable.The
largest
generator
ofheat
wasfound
to
be
the
interior
portion
ofthe
building
whichis
obvious
from
examining
the
building
design.
Examining
the
design
load
cooling
summary
sheets
the
largest
contributor ofthe
internal
heat
generated wasdue
to
the
lighting
and electricloads.
The
secondlargest
contributorto
the
internal
heat
generated was
the
people.Certain
areas ofthe
perimeter portionof
the
building
also neededcooling
in
the
winter months.
These
areas are onthe
southern exposer of
the
building.
The
largest
heat
gainin
these
areas wasdue
to
3.
Building
Systems
3.1
General
The
system usedheat
pumps
to
heat
and coolthe
perimeter
spaces ofthe
building
and used a selfcontained
variable
airvolume
system with centralelectric
heat
to
cool andheat
the
interior
spaces ofthe
building.
Return
airfor
both
systemsflowed
through
areturn
air plenumlocated
in
the
ceiling
space.
The
system wasdesign,
through
a waterloop
system,
to
transfer
heat
generatedfrom
the
interior
portion of
the
building
to
the
perimeter portionfor
the
Fall,
Winter
andSpring
months.3.2
Variable
Air
Volume
System
(VAV)
Each
floor
has
a self containedVAV
systemthat
heats
and coolsthe
interior
spaces ofthe
building.
The
system used alooped
ductwork
networkto
supply
airto
the
VAV
boxes.
The
VAV
boxes
controlthe
volume of airthat
is
distributed
to
the
dif f
users.Each
VAV
box
is
controlledby
athermostat
that
is
located
in
the
areathat
the
VAV
box
serves.The
diffusers
are connectedto
the
VAV
box
by
flexible
duct.
This
wasdone
sothat
the
dif
f
user canbe
relocated
easily
for
tenant
fitup.
Air
is
returned
to
the
systemthrough
return airlouvers
into
the
returnThe
selfcontained
VAV
unitdischarges
its
heat
generated
during
its
cooling
cycleinto
the
waterloop
network.
3.3
Water
Source
Heat
Pump
System
Heat
pumps are usedto
heat
and coolthe
perimeterspaces of
the
building.
The
heat
pumps are connectedto
the
waterloop
system wereit
absorbs or rejectsits
heat.
The
heat
pumps are connectedto
the
diffusers
by
flexible
duct.
This
wasdone
in
casethe
diffusers
have
to
be
relocatedfor
tenant
fitup.
Air
is
returnedthrough
to
the
heat
pumpsthrough
returnlouvers
into
the
return air plenumlocated
abovethe
ceiling.
Individual
heat
pumps are controlledby
thermostats
located
in
the
respected areathat
the
heat
pump
serves.3.4
Ventilation
System
There
aretwo
different
types
of ventilationsystems,
the
first
supplies ventilation airto
the
VAV
systems and
the
second supplies airto
the
heat
pump
systems .
The
first
system supplies ventilation airto
the
return side of
the
self containedVAV
units.Ventilation
airis
suppliedto
the
VAV
systemsby
asingle
duct
that
is
connectto
a ventilationfan
mounted on
the
roof.The
second system supplies ventilation airto
the
the
area wherethe
heat
pump
returnis
located.
There
are
two
separate
ventilation
fan
systems.
One
system
supplies
onehalf
ofthe
building
andthe
other systemsupplies
the
otherhalf.
The
ventilation
fans
aremounted on
the
roof
and a set ofducts
channelthe
airto
the
heat
pumps.
3.5
Exhaust
System
There
aretwo
systemsthat
exhaust airfrom
the
building.
The
first
system
andthe
largest
systemexhausts
airfrom
the
return
airplenum
on eachfloor
from
a point nearthe
returnfor
the
selfcontained
VAV
units.
The
airis
exhaustedthrough
an exhaustduct
by
an exhaustfan
mounted onthe
roof.The
second exhaust system exhausts air
from
the
bathrooms.
Air
is
exhaustfrom
the
bathrooms
because
the
BOCA
code requires
that
the
bathrooms
be
exhausted.The
air
is
exhaustedthrough
an exhaustduct
by
an exhaustfan
located
onthe
roof.3.6
Water
Loop
System,
Boiler.
Fluid
Cooler.
Air
Separator.
Compression
Tank
andPumps
The
waterloop
systemis
usedto
supply
heat
orremove
heat
that
is
neededfor
the
operation ofthe
heat
pumps andto
removeheat
that
is
generatedby
the
self contained
VAV
units.Connected
to
the
systemis
a
boiler
and afluid
cooler.These
componentsmaintain
the
fluid
temperature
in
the
waterloop
soproperly-
An
airSeparator
is
usedin
the
systemto
remove air and other
gases
from
the
waterloop.
A
compression
tank
is
usedto
absorbthe
expansion ofwater
in
the
system.The
pumpsin
the
systemdrive
the
fluid
through
the
piping
system.Each
floors'loop
is
of a reverse returndesign.
The
loop
is
connectedto
a riserthat
leads
to
the
penthouse,
onthe
roof ofthe
building.
This
is
wherethe
pumps,
boiler
andfluid
cooler arelocated.
The
location
ofthe
penthouseis
overthe
corridorarea,
in
orderthat
the
noise generatedby
the
equipmentwill not reach
the
office areas.3.7
Controls
andControl
Seguence
The
controlsin
this
building
willbe
ofthe
electronic
type
and willbe
usedto
regulatethe
equipment
in
the
building.
Controls
will notbe
selected
because
it
is
out ofthe
scope ofthis
project
but
the
control sequences willbe
specified.3.7.1
Cooling
Season
-During
the
cooling
seasonboth
the
heat
pumps andthe
self co