Magnum DS Breaker Catalog Identification
Table 1. Catalog Numbering System
1
6000 A Breaker available only in ABCABC configuration. Must order Forced Cooled Module from Asheville.
Note:
Narrow Frame available as Drawout up to 1600AF, 65 kA.
Note:
Narrow Frame available as Fixed Mounted up to 2000 A, 65 kA.
3. Circuit Breaker Frame
N = Narrow Frame
S = Standard
M D
A
-
X
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
13 and 14. Trip Unit
NN = Unprotected
22 =
220 LI
52 =
520 LSI
5G =
520 LSIG
M2 = 520M LSI
MT = 520M LSI 24/48 Vdc
MU = 520M LSI 120 Vac
MV = 520M LSI 240 Vac
MG = 520M LSIG
MH = 520M LSIG 24/48 Vdc
MM = 520M LSIG 120 Vac
MN = 520M LSIG 240 Vac
ME = 520M LSIA 24/48 Vdc
MC = 520M LSIA 120 Vac
MF = 520M LSIA 240 Vac
CT =
520MC LSI 24/48 Vdc
CU = 520MC LSI 120 Vac
CV =
520MC LSI 240 Vac
CH =
520MC LSIG 24/48 Vdc
CM = 520MC LSIG 120 Vac
CN = 520MC LSIG 240 Vac
CE =
520MC LSIA 24/48 Vdc
CC =
520MC LSIA 120 Vac
CF =
520MC LSIA 240 Vac
1A =
1150 LSI 24/48 Vdc
1C =
1150 LSI 120 Vac
1E =
1150 LSI 240 Vac
1F =
1150 LSIG 24/48 Vdc
1G =
1150 LSIG 120 Vac
1H =
1150 LSIG 240 Vac
1J =
1150 LSIA 24/48 Vdc
1K =
1150 LSIA 120 Vac
1M = 1150 LSIA 240 Vac
18. UVR/Second ST
N = None
A = 110 - 127 Vac (Instant.)
R = 208 - 240 Vac (Instant.)
C = 24 Vdc (Instant.)
G = 32 Vdc (Instant.)
H = 48 Vdc (Instant.)
E = 110 - 125 Vdc (Instant.)
F = 220 - 250 Vdc (Instant.)
X = 380 - 415 Vac (Instant.)
J = 480 Vac (Instant.)
K = 600 Vac (Instant.)
1 = 110 - 127 Vac/Vdc (2nd ST)
2 = 208 - 250 Vac/Vdc (2nd ST)
3 = 24 Vdc (2nd ST)
4 = 48 Vdc (2nd ST)
23. Latch Check Switch/Load Side Voltmeter
LCS
Metering TU Volt. Configuration
Connection
(1150 Only)
N = None
Standard
M = None
Load (1150 Only)
L = SR Standard
Y = SR
Load (1150 Only)
C = Cust Standard
D = Cust
Load (1150 Only)
19. Auxillary Switch
N = None
2 = 2A/2B
4 = 4A/4B
6 = 6A/6B
21. Padlocks
N = None
M = Metal
P = Plastic
C = Block Close PB Metal
H = Block Close PB Plastic
22. Operations Counter / Keylock
X
Counter
Keylock
N
None
None
K None Kirk
C None Castell
R None Ronis
A
Counter None
Y
Counter
Kirk
L
Counter
Castell
H
Counter
Ronis
15. Shunt Trip
N = None
A = 110 - 127 Vac/Vdc
R = 208 - 250 Vac/Vdc
C = 24 Vdc
H = 48 Vdc
16. Motor Operator
M = Manual Operated
N = 110 - 125 Vac
P = 220 - 250 Vac
L = 24 Vdc
K = 48 Vdc
W = 110 - 125 Vdc
T = 220 - 250 Vdc
17. Spring Release
N = None
A = 110 - 127 Vac/dc
R = 208 - 250 Vac/dc
C = 24 Vdc
H = 48 Vdc
4. Interrupt/Withstand
5 and 6. Continuous Amperes
7. Poles
8. Mounting Configuration
9. Nameplate Language
11 and 12. Sensor/Plugs
4 = 42/42
5 = 50/50
6 = 65/65
8 = 85/85
C = 100/85 - 100/100
3 = Three
4 = Four
08 = 800
16 = 1600
20 = 2000
30 = 3000
32 = 3200
40 = 4000 ABCABC
50 = 5000 ABCABC
60 = 6000 ABCABC
4N = 4000 AABBCC
5N = 5000 AABBCC
F = Fixed Front
H = Fixed Horizontal
V = Fixed Vertical
W = Drawout Vertical
L =
Drawout (Narrow Frame)
E = English
A = Spanish
NN = None
01 = 100
02 = 200
05 = 250
03 = 300
04 = 400
06 = 600
07 = 630
08 = 800
10 = 1000
12 = 1200
16 = 1600
20 = 2000
25 = 2500
30 = 3000
32 = 3200
40 = 4000
50 = 5000
60 = 6000
24. Shipping Instuctions
A =
Fixed or Drawout ACB Alone
C =
Drawout ACB in Narrow Cassette
Drawout ACB in Universal Cassette
P =
Drawout ACB in Pre-Wired
Narrow
Cassette
Drawout ACB in Pre-Wired
Universal Cassette
S =
Drawout ACB in Narrow Cassette
with Shutters
Drawout ACB in Universal Cassette
with Shutters
W =
Drawout ACB in Pre-Wired
Narrow
Cassette with Shutters
Drawout ACB in Pre-Wired
Universal Cassette with Shutters
24. Future Use
X = All Breakers
20. OTS/Bell Alarm
N = None
with Trip Indicator
E = None
without Trip Indicator
Y = 2 Form C
1
Figure 1. Magnum DS Circuit Breakers with Digitrip RMS 520/520M/520MC/520i/520Mi/520MCi Trip Unit
Typical Long Delay and Short Delay Time/Phase Current Characteristic Curve (LS)
.01 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 MINUTE 2 HO U RS TIME IN S E C O N D S 1 HO U R 10000 .01 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 HO U R TIME IN S E C O N D S 2 HO U RS
Current in Multiples of Long Delay Setting ( I
r)
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 2 3 4 5 6 7 8 9 10 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 2 3 4 5 6 7 8 9 10 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100 .1 .2 .3 .4 .5 4 7 24 15 .1* .3* .5*
.
.
.
.
.
Available Long Delay
Setting
0.4 to 1x I
n= I
rin 0.1 increments
Maximum Total
Clearing Time
Available Short
Delay Settings
2 to 10x I
r±
5%
See note 9
Minimum
Total
Clearing
Time
Available Flat Short
Delay Time 0.1 to 0.5
seconds
Available I
2t Short
Delay Time Response
.1*, .3*, .5* seconds
6 8 10 3 4 2 2.5 3 2Available Long
Delay Time
Shown @ 6x I
r2,4,7,10,12,15,20,24
seconds+0/-30%
Long Delay Time curves
can extend down to M1
(Max Short Delay Setting)
See note 9
2 2.5Application
Determines
end of curve
Circuit Breaker Time/Current Curves (Phase Current)
Magnum Power Circuit Breakers
Response: Long Delay & Short Delay Trip (FLAT & I2T)
This curve is for 50Hz or 60Hz applications.
Notes:
1. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory.
2. The end of the curve is determined by the interrupting rating of the circuit breaker. 3. For the ground fault time/current curve see curve 70C1008. For the Instantaneous see
curve 70C1007.
4. The Long Delay Pickup Point (indicated by rapid flashing of Unit Status LED on the product) occurs at 110%, with a ± 5% tolerance. The Instantaneous settings have conventional 100% ±10% at the pick up points.
5. With zone interlocking on Short Delay utilized and no restraining signal, the minimum time band applies regardless of the setting.
6. This curve is shown as a multiple of the Long Delay Setting.
7. Breakpoint back to FLAT response indicated by dots occurs @8x Ir for upper line of I2T curve.
8. Total clearing times show include the response times of the trip unit, the breaker opening and the interruption of the current.
9. Additional available max M1 settings Narrow Frame
200A through 1250A M1 = 14x In 1600A, 2000A M1 = 12x In Standard Frame:
200A through 1250A M1 = 14x In 1600A, 2000A, 2500A M1 = 12x In
3000A, 3200A, M1 = 10x In Double Wide Frame:
2000A, 2500A M1 = 14x In 3200A, 4000A, 5000A M1 = 12x In 6300A (IEC only) M1 = 10x In
10. Curve applies from -20∞C to +55∞C ambient. Temperatures above +85∞C cause automatic trip. Breaker must be applied according to “Continuous Rating at Different Ambient” table.
2500A 3000A 3200A 4000A 5000A 6300A Available Sensors and Matching Rating Plug in Amperes
800A 1000A 1200A 1250A 1600A 2000A 200A 250A 300A 400A 630A 600A
70C1006
Figure 2. Magnum DS Circuit Breakers with Digitrip RMS 520/520M/520MC/520i/520Mi/520MCi Trip Unit
Typical Instantaneous Time/Phase Current Characteristic Curve (I)
Current in Multiples of Rating ( I
n)
.01 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 MI NUTE
2
HO
U
R
S
T
IM
E
I
N
S
E
C
O
N
D
S
1 HO U R 3 6 8 4Available Instantaneous
Setting 2 to 10x I
n±
10%
See notes 7, 8
2 10 1 2 3 4 .5 .6 .7 .8 .9 10 20 30 40 50 0 6 70 80 90 100 00 2 3 00 4 00 5 00 6 00 7 00 8 00 9 00 1000 000 2 3000 4000 5000 6000 7000 8000 9000 10000 5 6 7 8 9 .01 1 2 3 4 .5 .6 .7 .8 .9 10 20 0 3 40 0 5 60 70 80 90 100 200 300 400 500 00 6 700 00 8 900 1000 2000 3 000 4 000 5 000 8 000 7 000 6 000 9 000 5 6 7 8 9 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 HO U R T IM E I N S E C O N D S 2 HO U R S 50 60 70 80 90Circuit Breaker Time/Current Curves (Phase Current)
Magnum and Magnum DS Circuit Breakers Response: Instantaneous Trip This curve is for 50Hz and 60Hz applications.
Notes:
1. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory.
2. The end of the curve is determined by the interrupting rating of the circuit breaker.
3. For the ground fault time/current curve see curve 70C1008. 4. This curve is shown as a multiple of the Rating Plug ( In ). 5. The Instantaneous settings have conventional 100% ± 10% as the pickup points.
6. Total clearing times shown include the response times of the trip unit, the breaker opening and the interruption of the current.
7. Additional settings of OFF and M1 are also available with: Narrow Frame:
200A through 1250A M1 = 14x In 1600A M1 = 12x In
2000A (IEC only) M1 = 12x In
Standard Frame:
200A through 1250A M1 = 14x In 1600A, 2000A, 2500A M1 = 12x In 3000A, 3200A M1 = 10x In
4000A (IEC only) M1 = 10x In
Double Wide Frame:
2000A, 2500A M1 = 14x In 3200A, 4000A, 5000A M1 = 12x In 6300A (IEC only) M1 = 10x In
8. For Standard Frame having a 100kA rms interruption rating, an additional High Instantaneous Trip Module is provided in the breaker set to pickup at 170kA±10% Instantaneous peak current level. This protection is functional even when the Instantaneous is set to the OFF position.
Application and
Breaker Ratings
determine end
of curve
Instantaneous
Trip
2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 100 KA70C1007
Figure 3. Magnum DS Circuit Breakers with Digitrip RMS 520/520M/520MC/520i/520Mi/520MCi Trip Unit
Typical Ground Fault Time/Phase Current Characteristic Curve (G)
.01 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .91 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 MINUTE 2 HO U RS TIME IN S E C O N D S 1 HO U R 10000 .01 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 HO U R TIME IN S E C O N D S 2 HO U RS .0 7 .0 9 .0 8 .0 5 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .0 8 .0 5 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .0 6 .0 6 .0 6 .0 6 .0 7 .0 6 .0 9 .25 .35 .5 .4 .3 .2 .1
.1*
.3*
.5*
.25Current in Multiples of Rating ( I
n)
Available Ground Setting
.25 to 1.0x I
n±
10%
See note 6
Available Flat Response
Ground Time
0.1 to 0.5 seconds
I
2t Slope for
Ground Time
Available
I
2t Response
Ground Time
.1*, .3*, .5*
seconds
Flat shape for
Ground Time
.75 1.0 .3 .4 .6 .5 .5Circuit Breaker Time/Current Curves (Ground Current)
Magnum and Magnum DS Circuit Breakers Response: Ground Trip (FLAT & I 2T)
This curve is for 50Hz or 60Hz applications.
Notes:
1. The end of the curve is determined by the interrupting rating of the circuit breaker.
2. For phase current time/current curves, see 70C1006 and 70C1007. 3. The curve is shown as a multiple of the Rating Plug ( In ). 4. The ground fault settings have conventional 100% ± 10% as the pickup points.
5. Except as noted tolerances on current level are ±10% of values shown in chart.
6. The ground fault pick up is limited to 1200A setting for non international styles.
7. The rating plug is for 50Hz and 60Hz applications.
8. With zone interlocking on ground fault utilized and no restraining signal, the minimum time band applies regardless of setting. 9. For additional curve tolerances contact Cutler-Hammer.
10. Total clearing times shown include the response time for the trip unit, the breaker opening and the current interruption.
11. Transition point from I2T back to FLAT response indicated by dot occurs @ 0.625x In for upper boundary of I 2T curve.
Figure 4. Magnum DS Circuit Breakers with Digitrip RMS 1150/1150i — I
2
T Trip Unit
Typical Long Delay and Short Delay Time/Phase Current Characteristic Curve (LS)
.01 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 MINUTE 2 HO U RS TIME IN S E C O N D S 1 HO U R
Current in Multiples of LONG PU ( I
r)
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 2 3 4 5 6 7 8 9 10 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 2 3 4 5 6 7 8 9 10 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100 24 10 4 2 0.50s 0.50s
Adjustable LONG PU
0.4 to 1.0x In = Ir
with 0.05 increments
See note 2
Minimum
clearing time
Adjustable
LONG TIME
2-24 seconds
(+0 -30%) @ 6x I
rWith 0.5s
increments
See note 7
Max Total
clearing time
Minimum
clearing time
Adjustable I
2T
response
SHORT TIME
0.10 to 0.50
Adjustable
SHORT TIME
0.10s to 0.50s
With 0.05 steps
See note 6
Available Sensors and Matching Rating Plug in Amperes 800A 1000A 1200A 1250A 1600A 2000A 2500A 3000A 3200A 4000A 5000A 6300A 200A 250A 300A 400A 630A 600A
Circuit Breaker Time/Current Curves (Phase Current)
Magnum and Magnum DS Circuit Breakers
Response: Long Delay (I2T) & Short Delay Trip (FLAT & I2T)
This curve is for 50Hz or 60Hz applications.
Notes:
1. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the LONG PU value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in a shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory.
2. This curve shown as a multiple of the LONG PU Setting (Ir). The actual Pickup point (indicated by rapid flashing of Unit Status LED on the product) occurs at 110% of the Ir, current, with a ±5% tolerance.
LongTIME Curve Equation: Trip = LongTIME *36/ I2, where I is a multiple of I r.
The SHORT TIME function and the LongTIME function act independently and the entire set of LongTIME curves continue to be active even after the curves intersect. 3. With zone interlocking on Short Delay utilized and no restraining signal, the minimum SHORT
TIME band (0.10s) applies regardless of the SHORT TIME setting. 4. SHORT PU (Max M1 setting) is a additional setting, based on In (Plug), that can extend out where the SHORT PU will function.
Standard Breaker: Double Wide Breaker: 200A through 1250A M1=14x In 2000A, 2500A M1=14x In 1600A, 2000A, 2500A M1=12x In 3200A, 4000A, 5000A M1=12x In 3000A, 3200A . M1=10x In 6300A M1=10x In 5. The SHORT PU points have 100% ± 5% tolerance.
6. SHORT SLOPE: FLAT
Tolerance is +0/ -80 ms for all settings except 0.10s setting is 0.06 to 0.13 0.20s setting is 0.15 to 0.22 7. SHORT SLOPE: I2T
I2T slope flattens out at 8 x I
r for top of band with FLAT time minimum value
prevailing for bottom of band.
Curve Trip Equation: Trip = SHORT TIME * 64/ I2, where I is a multiple of I r (top)
Curve Trip Equation: Trip = SHORT TIME * 64/ I2 * 0.70 (bottom)
The above equations indicate tolerance is +0/ -30% for all settings except 0.10s is +30%-25%
0.20s is +10%-25%
For all curves the lower flat response time value projected to I2T line will
determine the other Break Point and shape of the curve.
8. The end of the curve is determined by the interrupting rating of the circuit breaker. 9. Curve applies from -20∞C to +55∞C ambient. Temperatures above +85∞C cause automatic trip. Breaker must be applied according to “Continuous Rating at Different Ambient” table.
0.10s
Max clearing time
Break point
@ 8x I
rto FLAT
Adjustable
SHORT PU
1.5x to 10x or
12x or 14x I
rWith 0.5
increments
See note 4
See note 4
70C1034
Figure 5. Magnum DS Circuit Breakers with Digitrip RMS 1150/1150i — I
4
T Trip Unit
Typical Long Delay and Short Delay Time/Phase Current Characteristic Curve (LS)
.01 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 MINUTE 2 HO U RS TIME IN S E C O N D S 1 HO U R
Current in Multiples of LONG PU ( I
r)
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 2 3 4 5 6 7 8 9 10 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 03 40 05 60 70 80 90100 2 3 4 5 6 7 8 9 10 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100 5 1
Available LONG PU
Settings (I
r)
0.4 to 1 x I
n= I
rin 0.05 increments
Adjustable LongTIME
1-5 seconds
(+10 -40%) @ 6x I
rWith 0.5s increments
See note 7
0.10s 0.50sSee note 3
Minimum
clearing time
See notes 6, 7
Available Sensors and Matching Rating Plug in Amperes 800A 1000A 1200A 1250A 1600A 2000A 2500A 3000A 3200A 4000A 5000A 6300A 200A 250A 300A 400A 630A 600A
Circuit Breaker Time/Current Curves (Phase Current)
Magnum and Magnum DS Circuit Breakers Response: Long Delay (I4T) & Short Delay Trip
This curve is for 50Hz or 60Hz applications.
Notes:
1. There is a Long MEMORY (if enabled) effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the LONG PU value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory.
2. This curve is shown as a multiple of LONG PU Setting (Ir).
The actual Pickup point occurs at 110% of the Ir, current, with a ±5% tolerance.
LongTIME Curve Equation: Trip = LongTIME *1296/I4,where I is a multiple of I r.
3. In this time region £ 0.5 seconds the I4 T Long TIME function will flatten out
and be no faster than the Short TIME setting. This is to avoid a notch in graph. 4. SHORT PU (Max M1 setting) is an additional setting.
Standard Breaker:
200A through 1250A M1=14x In 1600A, 2000A, 2500A M1=12x In
3000A, 3200A M1=10x In Double Wide Breaker: 2000A, 2500A M1=14x In 3200A, 4000A, 5000A M1=12x In
6300A M1=10x In
5. The SHORT PU points have conventional 100% ± 5% tolerance. 6. SHORT TIME: FLAT only - setting 0.1s through 0.5s in .05s increments. Tolerance is +0/ -80 ms of setting except
0.10s setting is 0.06 to 0.13 0.20s setting is 0.15 to 0.22
7. With zone interlocking on Short Delay utilized and no restraining signal, the minimum SHORT TIME band (0.10s) applies regardless of the SHORT TIME setting.
8. The end of the curve is determined by the interrupting rating of the circuit breaker.
9. Curve applies from -20∞C to +55∞C ambient. Temperatures above +85∞C cause automatic trip. Breaker must be applied according to “Continuous Rating at Different Ambient” table.
Adjustable
SHORT PU
1.5x to 10x or
12x or 14x I
rWith 0.5
increments
See note 4
70C1035
Figure 6. Magnum DS Circuit Breakers with Digitrip RMS 1150/1150i Trip Unit
Typical Instantaneous Time/Phase Current Characteristic Curve (I)
.01 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 MINUTE 2 HO U RS TIME IN S E C O N D S 1 HO U R
Current in Multiples of Rating ( I
n)
2 0 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 05 60 70 80 90 100 2 3 4 5 6 7 8 9 10 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100
Circuit Breaker Time/Current Curves (Phase Current)
Magnum and Magnum DS Circuit Breakers Response: Instantaneous Trip This curve is for 50Hz or 60Hz applications.
Notes:
1. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the Long Delay Pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 2. The end of the curve is determined by the interrupting rating of the circuit breaker.
3. This curve is shown as a multiple of the Rating Plug (In). 4. The Instantaneous settings have conventional 100% ± 10% as their pick up points.
5. Total clearing times shown include the response times of the trip unit, the breaker opening and the interruption of the current. 6. Additional settings of OFF and M1 are also available with Standard Frame: Double Wide Frame: 200A through 1250A M1=14x In 2000A, 2500A M1=14x In
1600A, 2000A, 2500A M1=12x In 3200A, 4000A, 5000A M1=12x In 3000A, 3200A M1=10x In 6300A M1=10x In
7. For breakers rated 3200A and less having a 100kA rms interruption rating, an additional High Instantaneous Trip Module is provided in the breaker set to trip at a 170kA ± 10% instantaneous peak current level. This protection is functional even when the Instantaneous is set to the OFF position. .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 03 40 50 60 70 80 90 100 2 0 3 0 4 0 5 0 8 0 7 0 6 0 9 0 100
Available INST PU
Setting 2 to 10x I
n±
10%
with 0.5 increments
See notes 6, 7
3 0 4 0 5 0 6 0 7 0 8 0 9 0 100kA
Application and
Breaker Ratings
determine end
of curve
Instantaneous Trip
at high fault currents
Figure 7. Magnum DS Circuit Breakers with Digitrip RMS 1150/1150i Trip Unit
Typical Ground Time/Phase Current Characteristic Curve (G)
.01 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 MINUTE 2 HO U RS TIME IN S E C O N D S 1 HO U R 10000 .01 .02 .03 .04 .05 .06 .07 .08 .09 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 1000 900 800 700 600 500 400 300 200 2000 3000 4000 5000 6000 7000 8000 9000 10000 1 HO U R TIME IN S E C O N D S 2 HO U RS .0 7 .0 9 .0 8 .0 5 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 8 7 6 9 10 .0 8 .0 5 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 .0 6 .0 6 .0 6 .0 6 .0 7 .0 6 .0 9
Current in Multiples of Rating ( I
n)
Available GND
PU Setting 0.25 to
1.0x I
n±
10% with
steps of 0.01.
See note 6
FLAT response for
GROUND TIME
See notes 7, 9
See notes
9, 10
Min Clearing Time
for 0.1 s setting
Max Clearing
Time
Circuit Breaker Time/Current Curves (Ground Current)
Magnum and Magnum DS Circuit BreakersResponse: Ground (Earth) Trip (FLAT & I2T)
This curve is for 50Hz or 60Hz applications.
Notes:
1. The end of the curve is determined by the interrupting rating of the circuit breaker.
2. For phase current time/current curves, see curves 70C1031 through 70C1040.
3. The curve is shown as a multiple of the Rating Plug (In).
4. The Ground Fault settings have conventional 100% ± 10% as their pick-up points.
5. Except as noted, tolerances on current levels are ±10% of values shown in chart.
6. The Ground Fault Pickup is limited to 1200A setting for the Digitrip 1150 unit. The Digitrip 1150i unit only has a minimum Earth Pickup setting starting at 0.1 x In.
7. With zone interlocking on ground fault utilized and no restraining signal, the minimum time band (FLAT) applies regardless of setting. 8. Total clearing times shown include the response time of the trip unit, the breaker opening, and the interruption of the current. 9. Ground Slope: FLAT
Tolerance is +0 / -80 ms except 0.10s setting band is 0.06 to 0.13 0.20s setting band is 0.15 to 0.22 10. Ground Slope: I2T
I2T slope flattens out at 0.625x I
n for top of band with FLAT time
minimum value prevailing for bottom of band. Curve Trip Equation: Trip = (GROUND TIME) x 0.39 / In
2 (top)
Curve Trip Equation: Trip = ((GROUND TIME) x 0.39 / In
2) * 0.70(bottom)
The above equations indicate tolerance is +0 / -30% for all settings except 0.10s is +30% -25% 0.20s is +10% -25% 0.50s 0.50s 0.10s