• No results found

Overvoltage Protection and Insulation Coordination

N/A
N/A
Protected

Academic year: 2021

Share "Overvoltage Protection and Insulation Coordination"

Copied!
29
0
0

Loading.... (view fulltext now)

Full text

(1)

Volt

Voltage St

age Stress

ress in Pow

in Power Sys

er Systems

tems -- Class

Classifica

ification

tion

IEC 60071-1 IEC 60071-1

(2)

Classification of real stress

Classification of real stress

Classification of real stress

Classification of real stress

Voltage Stress in Power

Voltage Stress in Power Systems

Systems

"

"CContinontinuous uous ((power-power-frequefrequency) ncy) voltvoltaage"ge"

Power-frequency voltage, considered having constant r.m.s. value, continuously applied to any pair of  Power-frequency voltage, considered having constant r.m.s. value, continuously applied to any pair of  terminals of an insulation configuration

terminals of an insulation configuration f f  = 50 Hz or 60 Hz= 50 Hz or 60 Hz

11 ≥≥ 3 600 s3 600 s

Æ

Æ Any power-frequency voltage lasting for 1 h or more is considered a continuous voltage! Any power-frequency voltage lasting for 1 h or more is considered a continuous voltage!

Standard voltage

Standard voltage

Standard voltage

Standard voltage

"Standard power-frequency voltage""Standard power-frequency voltage"

 A sinusoidal voltage with frequency of 50 Hz or 60 Hz  A sinusoidal voltage with frequency of 50 Hz or 60 Hz

11 to be specified by the apparatus committeesto be specified by the apparatus committees ÆÆ TT11 up tup to 2 yeao 2 years!rs! ÆÆ see next slidessee next slides

Conversion Conversion

into into

Volt

(3)

Example: Cable tests at power-frequency voltage

Example: Cable tests at power-frequency voltage

Voltage Stress in Power Systems

Voltage Stress in Power Systems - Classification

(4)

Example: Cable tests at power-frequency voltage

Example: Cable tests at power-frequency voltage

Voltage Stress in Power Systems

Voltage Stress in Power Systems - Classification

Source: Brugg Cables

(5)

Voltage Stress in Power Systems

"Temporary overvoltage"

Power-frequency overvoltage of relatively long duration. The overvoltage may be damped or  undamped. In some cases its frequency may be several times smaller or higher than power  frequency.

10 Hz < f < 500 Hz

3 600 s ≥ T 1 ≥ 0.02 s

Highest values by following main reasons:

• phase-to-earth Æ earth faults and load rejection

• phase-to-phase Æ load rejection

• longitudinal Æ phase opposition during synchronization of two grids

Standard voltage

Standard voltage

" Standard short-duration power-frequency voltage"

 A sinusoidal voltage with frequency between 48 Hz and 62 Hz

1 = 60 s

Conversion into

Classification of real stress

Classification of real stress

Example [THI-01]

(6)

Voltage Stress in Power Systems

" Transient overvoltage"

Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly damped. May be followed by temporary overvoltages. In this case, both events are considered as separate events.

Standard voltage

Standard voltage

"Standard switching impulse"

 An impulse voltage of 

p = 250 µs

2 = 2 500 µs

Conversion into

Classification of real stress

Classification of real stress

" Slow-front ov ervolt age" Transient overvoltage, usually unidirectional

5000 µs ≥ T p > 20 µs

2 ≤ 20 ms

Main reasons: line faults, switching

Example [THI-01]

(7)

Voltage Stress in Power Systems

" Transient overvoltage"

Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly damped. May be followed by temporary overvoltages. In this case, both events are considered as separate events.

Standard voltage

Standard voltage

"Standard lightning impulse"

 An impulse voltage of 

1 = 1.2 µs

2 = 50 µs

Conversion into

Classification of real stress

Classification of real stress

" Fast-front overvoltage" Transient overvoltage, usually unidirectional

20 µs ≥ T 1 > 0.1 µs

2 ≤ 300 µs

Main reasons: lightning strokes, switching

Example [THI-01]

(8)

Voltage Stress in Power Systems

" Transient overvoltage"

Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly damped. May be followed by temporary overvoltages. In this case, both events are considered as separate events.

Standard voltage

Standard voltage

not standardized

Conversion into

Classification of real stress

Classification of real stress

"Very-fast-front overvoltage" Transient overvoltage, usually unidirectional

< 100 ns

(T t ≤ 3 ms)

basic oscillation (1st harmonics) 30 kHz < f  < 300 kHz superimposed oscillations 300 kHz < f  < 100 MHz Main reasons: switching of disconnectors in GIS

Example [THI-01]

(9)

Voltage Stress in Power Systems

" Combined (temporary, slow -front, fast-front, very-fast-front) overvoltage"

Consisting of two voltage components simultaneously applied between each of the two phase

terminals of a phase-to-phase (or longitudinal) insulation and earth. It is classified by the component of the higher peak value.

Standard voltage

Standard voltage

" Standard combi ned switchi ng impulse"

Conversion into

Classification of real stress

Classification of real stress

Combined impulse voltage having two components of equal peak value and opposite polarity. The positive component is a standard switching impulse and the negative one is a switching impulse whose times to peak and half value should not be less than those of the positive impulse. Both

impulses should reach their peak values at the same instant. The peak value of the combined voltage is, therefore, the sum of the peak values of the components.

(10)

Temporary Overvoltages – Earth Faults

Reasons for temporary overvoltages:

• earth faults

• load rejection

• resonance phenomena

In case of earth faults the overvoltage amplitudes depend on

• neutral earthing

• fault location.

Important parameter: Earth fault factor 

k

Important parameter: Earth fault factor 

k

LE  b / 3 U  k  U  =

... in other "words":

LE... phase-to-earth voltage of sound phase during fault

b ... phase-to-phase voltage at same location before fault

(11)

Temporary Overvoltages – Earth Faults

The earth fault factor depends on the ratio of the complex impedances Z 

1

and

0

of the positive and zero sequence systems (German: "Mitsystem",

"Nullsystem"). In case of neglecting the resistances (possible in high-voltage

systems) it depends on the ratio of the reactances X 

0

and X 

1

:

(

)

2 0 1 0 1 0 1 1 / / 3 2 /  X X X X  k   X X  + + = ⋅ +

a ratio of  X 

0

/ X 

1

= -2 must be avoided!

  s

  o    l    i    d    l  y  e   a   r    t    h  e    d  n   e   u    t  r  a    l resonant earthed neutral, isolated neutral resonant earthed neutral, isolated neutral not for  practical use! according to [BAL-04]

(12)

Temporary Overvoltages – Earth Faults

Treatment of neutral in Germany (VDEW, 1998):

according to [BAL-04]

treatment of neutral

10 kV

20 kV

110 kV

380 kV

isolated

8.6%

< 0.1%

0.0%

0.0%

resonant earthed

77.8%

92.8%

80.9%

0.7%

solidly earthed

13.6%

2.2%

19.1%

99.3%

Earthing reactor (Petersen coil):

fixed or switchable type Earthing reactor (Petersen coil):variable core type

Pictures: VATech

Caused by several recent blackouts it has been considered internationally to increasingly operate sub-transmission

systems (U s ≤ 170 kV) in the resonant

earthed mode in order to increase reliability of power supply. [Information from a Cigré meeting in Frankfurt, October 2005]

Caused by several recent blackouts it has been considered internationally to increasingly operate sub-transmission

systems (U s ≤ 170 kV) in the resonant

earthed mode in order to increase reliability of power supply. [Information from a Cigré meeting in Frankfurt, October 2005]

(13)

Temporary Overvoltages – Earth Faults

 Active part of a high-voltage reactor with variable core

Fixed part of the core Drive

Lead screw (the core is actually in 100% position)

  c   o   r   e   m   o   v   e   m   e   n    t

(14)

Temporary Overvoltages – Earth Faults

Earth fault in case of isolated neutral system:

(15)

Temporary Overvoltages – Earth Faults

Earth fault in case of isolated neutral system:

fault

(16)

Temporary Overvoltages – Earth Faults

Earth fault in case of isolated neutral system:

fault clearing

k = 2 due to capacitances of zero sequence system, charged to a direct voltage

(17)

Temporary Overvoltages – Earth Faults

Intermitting earth fault in case of isolated neutral system:

new fault after initial fault clearing

voltage of faulty phase

(18)

Temporary Overvoltages – Earth Faults

Intermitting earth fault in case of isolated neutral system:

new fault after initial fault clearing

voltage of sound phase

(19)

Temporary Overvoltages – Earth Faults

Intermitting earth fault in case of isolated neutral system:

voltage of the zero sequence system

(20)

Temporary Overvoltages – Earth Faults

3 ... 2 k  1.4 k  1.4 < <≈k  1.8 3 ...1.85 k  IEC 60071-1

(21)

You're Reading a Preview

Unlock full access with a free trial.

(22)

Temporary Overvoltages – Load Rejection (Example 1)

Example according to [ETG-93]

Phase opposition between open circuit breaker terminals – stress of longitudinal insulation Phase opposition between open circuit breaker terminals – stress of longitudinal insulation

(23)

Temporary Overvoltages – Load Rejection (Example 2)

Example according to [DOR-81]

1: Excitation by rotating rectifiers

2: Constant excitation (manual regulation) Voltage increase by factor of 1.35; decrease to factor of 1.2 after 2 s. Voltage increase by factor of 1.35; decrease to factor of 1.2 after 2 s.

(24)

Temporary Overvoltages – Load Rejection (Example 3)

TOV at the end of a long transmission line TOV at the end of a long transmission line

• caused by capacitive currents

• can be controlled by parallel compensation

e 1

cos

a

 β 

=

e ... voltage at end of line

a ... voltage at line entrance

1 1 a v

ω 

 β 

=

 β1 ... phase angle of the positive system

1 1 1 1 v  L C  = ′ ′

1 ... phase velocity of the positive system

[DOR-81]

Not an issue for "normal"

length transmission lines

Not an issue for "normal"

length transmission lines

(25)

Temporary Overvoltages – Load Rejection (Summary)

Voltage increase factors due to load rejection:

• moderately extended systems: < 1.2 p.u. for up to several minutes

• widely extended systems:

1.5 p.u. for some seconds

• close to turbo generator:

1.3 p.u.

• close to salient pole (German: "Schenkelpol") generator:

1.5 p.u.

Voltage increase factors due to load rejection:

• moderately extended systems: < 1.2 p.u. for up to several minutes

• widely extended systems:

1.5 p.u. for some seconds

• close to turbo generator:

1.3 p.u.

• close to salient pole (German: "Schenkelpol") generator:

1.5 p.u.

Temporary overvoltages caused by load rejection depend on

• the rejected load

• the system layout after disconnection

• the characteristics of the sources (short-circuit power, generator type and regulation)

Extremes:

Low values of temporary overvoltages in systems with relatively short lines and high

values of the short-circuit power at the terminal stations.

High values of temporary overvoltages in systems with long lines and low values of

short-circuit power at the generating side (= typical situation of extra-high voltage systems in

their initial stage).

(26)

Temporary Overvoltages – Resonance Phenomena

Temporary overvoltages caused by resonance phenomena generally arise when circuits

with large capacitive elements, such as

• lines

• cables

• series compensated lines

and inductive elements having non-linear magnetizing characteristics, such as

• transformers

• shunt reactors

are energized, or as result of load rejections.

Can easily be avoided by de-tuning the system from the resonance frequency!

Can easily be avoided by de-tuning the system from the resonance frequency!

(27)

Temporary Overvoltages – Resonance Phenomena (Example 1)

Energizing a transformer in a grid tuned to resonance at 3rd harmonics (150 Hz)

Energizing a transformer in a grid tuned to resonance at 3rd harmonics (150 Hz)

Grid tuned to 150 Hz Æ TOV of 1.9 p.u. Grid tuned to (150 Hz – 7%) Æ TOV of 1.2 p.u.

(28)

Temporary Overvoltages – Resonance Phenomena (Example 2)

Load rejection with transformer in a grid tuned to resonance at 5th harmonics (250 Hz)

Load rejection with transformer in a grid tuned to resonance at 5th harmonics (250 Hz) [DOR-81]

length of line:a

Length of line: 174 km Æ f = 250 Hz

(29)

Temporary Overvoltages and Surge Arresters

Surge arresters cannot limit TOV!

Exception: resonance effects may be suppressed or even avoided by MO arresters.

Care has then to be taken not to thermally overload the arresters!

Surge arresters cannot limit TOV!

Exception: resonance effects may be suppressed or even avoided by MO arresters.

Care has then to be taken not to thermally overload the arresters!

0,8 0,85 0,9 0,95 1 1,05 1,1 1,15 1,2 1,25 1,3 0,1 1 10 100 1000 t  / s      k     t  o   v   =      U    /     U   r

Time duration of (over-)voltage

Possible voltages without arresters

Voltages limited by arresters

Withstand voltage of equipment

Lightning overvoltages (Microseconds) Switching overvoltages (Milliseconds) Temporary overvoltages (Seconds)

Highest voltage of equipment (Continuously)    M  a   g   n    i    t  u    d  e   o    f    (  o  v   e   r   -   )  v  o    l    t  a  g   e    /  p  .   u . 1 2 3 4 0 5

Time duration of (over-)voltage

Possible voltages without arresters

Voltages limited by arresters

Withstand voltage of equipment

Lightning overvoltages (Microseconds) Switching overvoltages (Milliseconds) Temporary overvoltages (Seconds)

Highest voltage of equipment (Continuously)    M  a   g   n    i    t  u    d  e   o    f    (  o  v   e   r   -   )  v  o    l    t  a  g   e    /  p  .   u . 1 2 3 4 0 5

region of impressed voltage

Æ current develops according to

U-I-characteristics

region of impressed voltage

Æ current develops according to

U-I-characteristics

region of impressed current

Æ voltage develops according to

U-I-characteristics

region of impressed current

Æ voltage develops according to

References

Related documents

To test the required insula- tion distances a high voltage test is undertaken on new equipment and systems; unlike the insulation measurement this test represents a

This hardware model of the proposed high voltage DC generator having cascaded voltage multiplier consist of power supply circuit, boost converter circuit and

This paper mainly studies the situation of single-phase and three-phase grounding short- circuit at rectifier side and inverter side respectively, and analyzes the voltage of each

This means that unlike typical grid connected AC systems, the available short circuit current is limited and the overcurrent protective devices will need to operate effectively on

overhead transmission lines creates difficulties, high and extra-high voltage underground electricity cable systems rated 220kV and above have become part of the backbone of

LIMITING SHORT-CIRCUIT CURRENTS In medium and high voltage installations, the short-circuit current is a function of the voltage and the inductive reactance of the

To test the required insula- tion distances a high voltage test is undertaken on new equipment and systems; unlike the insulation measurement this test represents a

From the DMPPT operating conditions established in Sections 2 and 3, two control systems are required for the DC-DC converter: an input voltage controller to regulate the PV