Generator protection
Generator protection
Presented by
Presented by
Bipasha Jash (PEE)
Bipasha Jash (PEE)
NTPC
Classificat
Classificat
ion of
ion of
Generator Protection
Generator Protection
Stator Protection
Stator Protection
Generator
Generator
Abnormal
Abnormal
Operating
Operating
conditions
conditions
System back up
System back up
protections
protections
Rotor protection
Rotor protection
GT protections
GT protections
UT protections
UT protections
Classificat
Classificat
ion of
ion of
Generator Protection
Generator Protection
Stator Protection
Stator Protection
Generator
Generator
Abnormal
Abnormal
Operating
Operating
conditions
conditions
System back up
System back up
protections
protections
Rotor protection
Rotor protection
GT protections
GT protections
UT protections
UT protections
Over view of type of fault Vs protection
Over view of type of fault Vs protection
FAULT/ABNORMAL FAULT/ABNORMAL CONDITION CONDITION EFFECT PROTECTION EFFECT PROTECTION Thermal over Thermal over loading loading
Over heating of stator winding/ Over heating of stator winding/ insulation failure
insulation failure
Thermo couples/ Thermo couples/ Over current relays Over current relays
External fault
External fault Unbalanced Unbalanced loading loading stress stress Over Over load/negative load/negative phasephase sequence relay sequence relay Stator fault Stator fault Ph to Ph/Ph to E Ph to Ph/Ph to E Inter turn Inter turn
Winding burn out Winding burn out
Welding of core lamination Welding of core lamination
Differential prot Differential prot
100% E/F prot/95% E/F 100% E/F prot/95% E/F Inter turn prot
Inter turn prot Rotor fault
Rotor fault Damage Damage to to shaft/bearing shaft/bearing 2 2 stage stage rotor rotor E/F E/F protectionprotection Motoring
Motoring LFPR/Rev powerLFPR/Rev power O/V,O/F,U.F
O/V,O/F,U.F Insulation failure,Heating ofInsulation failure,Heating of core failure of blades
core failure of blades
O/V relay Volt/Hz relay O/V relay Volt/Hz relay U/F relay
U/F relay Loss of field
Loss of field Induction gen operationInduction gen operation Absorb MVAR from
Absorb MVAR from
system/damage to rotor wdg system/damage to rotor wdg
Loss of field Loss of field
Generator Connection Methods
The protection scheme depends on the type of
generator connection
A) Unit scheme:
In this scheme no switchgear is provided
between
the
generator
and
generator
transformer, which are treated as a unit; a unit
transformer is tapped off the interconnection
for supply of power to auxiliary plant.
B)
Generator circuit breaker scheme:
In this scheme a generator circuit breaker is
provided between the generator and generator
transformer
.TRIP LOGIC OF GENERATOR PROTECTION
TWO INDEPENDENT CHANNELS WITH INDEPENDENT CT/VT INPUTS/DC SUPPLY/TRIP RELAY
CLASS A TRIP
ALL ELECTRICAL TRIPS
TRIP TURBINE, GENERATOR, GT, UT CLASS-B TRIP
MECHANICAL TRIPS
AVOID OVER SPEEDING OF TURBINE DUE TO STEAM ENTRAPPED IN TURBINE. TURBINE TRIP SIGNAL IS GIVEN FIRST AND THE ACTIVE POWER, SENSED BY THE LOW FORWARD RELAY (32G) GIVES THE TRIP SIGNAL TO THE UNIT BREAKER & FIELD BREAKER AFTER A TIME DELAY
Class C
Typical Generator
protection
GENERATOR PROTECTIONS
NTPC PRACTICES
DIFFERENTIAL PROTECTION
UNIT TYPE PROTECTION
INSTANTANEOUS IN OPERATION.
COVERS THE STATOR WDG FOR PHASE TO PHASE FAULTS.
SINGLE PHASE TO EARTH FAULTS ARE NOT COVERED IN HIGH IMP EARTHING SYSTEMS (EARTH CURRENT IS LOW)
DUPLICATED DIFF USED FOR GCB SCHEME TYPICAL SETTING: HIGH IMP TYPE: 5%
STATOR EARTH FAULT PROTECTION
E/F CURRENT IS LIMITTED TO 10A THIS MINIMIZES THE DAMAGE FIRST FAULT LESS CRITICAL NEEDS CLEARANCE AS
IT MAY DEVELOP INTO A PH TO PH FAULT SECOND FAULT WILL RESULT IN VERY
HIGH CURRENT
FIRE MAY RESULT FROM EARTH FAULT. TWO TYPES:
100 % E/F 95 % E/F
95 % STATOR E/F
RESULTS IN VOLTAGE SHIFT OF GEN NEUTRAL W.R.T. GROUND
DETECTED BY OVER VOLTAGE RELAY CONNECTED ACROSS GROUNDING RESISTOR
PROTECTS APPROX 95% OF STATOR WDG TYP SETTING:
5V
TIME DELAY OF MORE THAN 1 SEC(GEN IDMT RELAY WITH PMS 5.4 AND TMS 1 IS USED)
100% Stator E/F Protection
THIRD HARMONIC PRINCIPLE
A RELAY WHICH RESPONDS TO THE REDUCTION OF THE 3RD HARMONIC COMPONENT
A STATOR PHASE-TO-GROUND FAULT OCCURS AT OR NEAR THE GENERATOR NEUTRAL, THERE WILL BE AN INCREASE IN THIRD HARMONIC VOLTAGE AT THE GENERATOR TERMINALS, WHICH WILL CAUSE RELAY OPERATION.
DISADVANTAGES
DUE TO DESIGN VARIATIONS, CERTAIN GENERATING UNITS MAY NOT PRODUCE SUFFICIENT THIRD HARMONIC VOLTAGES THIS METHOD DOES NOT PROTECT THE M/C DURING STAND STILL CONDITIONS.
100 % Stator E/F protection
LOW FREQUENCY INJECTION PRINCIPLE
THIS SCHEME DETECTS THE GROUND FAULTS BY
INJECTING A LOW FREQUENCY SIGNAL (SAY 20 HZ)AT THE NEUTRAL EARTHING TRFR OR LINE CONNECTED
EARTHING TRFR AND MONITOR EITHER THE EARTH
CURRENT IN THE WDG(INCREASES DURING A FAULT) OR THE STATOR EARTH RESISTANCE (REDUCES DURING FAULT)
PROVIDES PROTECTION EVEN DURING SHUT DOWN SETTINGS TYPICAL FOR 500 MW UNIT
14 mA /1 sec (current setting ) OR
Trip : 10 Ohm/1 sec
Alarm : 20 ohm/10 sec( for Imp measuring relay
SETTINGS ARE TO BE FINALISED DURING COMMISSIONING TEST IN LINE WITH INSTRUCTIONS OF RELAY CATALOGUE.
Rotor Earth Fault Protection
FIRST ROTOR E/F DOES NOT CAUSE IMMEDIATE DAMAGE SECOND E/F RESULTS IN A WDG SC OF ROTOR
CAUSE MAGNETIC UNBALANCE/MECH FORCES /DAMAGE METHODS OF DETECTION
POTENTIOMETER METHOD
A CENTRE TAPED RESISTOR IS CONNECTED ACROSS THE MAIN FIELD WINDING
THE CENTRE TAP IS CONNECTED TO EARTH THROUGH A VOLTAGE RELAY
AN EARTH FAULT ON THE FIELD WINDING WILL PRODUCE VOLTAGE IN THE RELAY, MAXIMUM VOLTAGE OCCURRING FOR END FAULTS
A BLIND SPOT EXISTS AT THE TAPPING POINT, TO AVOID THIS , THE TAPPING POINT IS VARIED WITH A PUSH BUTTON OR SWITCH , AND IS TESTED PERIODICALLY TO DETECT BLIND ZONE
LOW FREQUENCY INJECTION METHOD
MODERN ROTOR EARTH FAULT PROTECTION RELAY OPERATES ON THE PRINCIPLE OF LOW FREQUENCY
INJECTION INTO THE FIELD WINDING VIA CAPACITORS. IF AN EARTH FAULT OCCURS, THE CORRESPONDING
CURRENT OR RESISTANCE IS DETECTED TYP SETTING (500 MW)
ALARM 40 K OHM TIME = 10 SEC TRIP 5 K OHM TIME = 1 SEC
ACTUAL VALUES OF SETTING SHALL BE DECIDED AT SITE
DURING COMMISSIONING TO ACCERTAIN THE HEALTHY VALUE OF THE PARTICULAR M/C.
INTER TURN PROTECTION
CURRENT BASED SYSTEM
FOR GENERATORS WITH SPLIT NEUTRALS WITH ALL SIX TERMINALS BROUGHT OUT ON NEUTRAL SIDE
DELAYED LOW-SET O/C RELAY WHICH SENSES THE CURRENT IN THE CONNECTION BETWEEN THE
NEUTRALS OF THE STATOR WINDINGS VOLTAGE BASED SYSTEM
RELAY COMPARES THE NEUTRAL NGT SEC VOLTAGE AND GEN TERMINAL OPEN DELTA VOLTAGE
BALANCE DURING E/F OR NORMAL CONDITION
DURING INTER TURN FAULT OPEN DELTA VOLTAGE WILL BE DEVELOPED AND NGT SEC VOLTAGE WILL BE ZERO, RESULTING IN A DIFFERENTIAL VOLTAGE WHICH
MAKES THE RELAY OPERATE
O/V PROTECTION
TYP SETTINGS OF A 3 STAGE O/V RELAY IS AS FOLLOWS ALARM 110 % 2 SEC
TRIP 120 % 1 SEC
140 % INSTANTANEOUS
U/F O/F PROTECTION
TYPICAL SETTING:
ALARM - 47.8HZ 1 SEC TRIP - 47.4 HZ 2 SEC
SETTING NEED TO BE CO-ORDINATED WITH THE RESPECTIVE RLDC AND THE ISLANDING SCHEME SETTINGS
Negative Sequence protection
NEGATIVE SEQUENCE PROTECTION FOR GENERATOR
PROTECTS THE GENERATOR FROM EXCESSIVE HEATING IN THE ROTOR RESULTING FROM UNBALANCED STATOR
CURRENTS
CAUSED DUE TO
ONE POLE OPEN IN LINE
ONE POLE OPEN OF A CIRCUIT BREAKER
CLOSE IN UNCLEARED UNBALANCED FAULTS
THE NEGATIVE SEQUENCE PROTECTION RELAYS SHALL BE SET TO THE NPS CAPABILITY OF THE MACHINE WHICH IS K = I22* T
TYP FOR 500 MW
PERMISSIVE NEG SEQ CURRENT = 5 – 8 % OF STATOR CURRENT
PERMISSIVE I22* T = 5
– 10
SETTINGS ADOPTED FOR NTPC I2 = = 7.5 %
Loss of Field Protection
ACTS AS AN INDUCTION GENERATOR
INDUCED EDDY CURRENTS IN THE FIELD WINDING, ROTOR BODY, WEDGES AND RETAINING RINGS
MW FLOW IN TO THE SYSTEM/MVAR FLOWS IN TO THE MACHINE.
THE APPARENT IMP TRAVELS TO THE FORTH QUADRANT OF X-Y PLANE
METHODS OF DETECTION: UNDER VOLTAGE + O/C
MINIMUM IMPEDANCE WITH U/V
SOME RELAYS ARE SET IN THE ADMITTANCE PLANE MATCHING WITH THE CAPABILITY CURVE OF THE MACHINE
LOSS OF FIELD RELAY
BIG M/C WITH GOOD AVR
SMALL MACHINES
OUT OF STEP PROTECTION
MACHINE RUNS OUT OF SYNCHRONISM WITH THE NETWORK
CYCLIC VARIATION OF ROTOR ANGLE CURRENT INCREASES HEAVILY
FREQUENCY DEPEND ON THE RATE OF SLIP RESULT IN THE WINDING STRESS
IT MAY ALSO DAMAGE THE AUXILIARIES OF THE AFFECTED UNIT
DETECTED BY SENSING THE VARIATIONS IN IMP
DISTINGUISH BETWEEN THE RECOVERABLE SWING AND THE IRRECOVERABLE SWING
TWO BLINDERS(IMPEDANCE) + A SUPERVISORY MHO ELEMENT, TRIP WHEN IMP IS INSIDE THE MHO AND CROSED THE BLINDERS
MINIMUM IMPEDANCE (MULTIPLE ZONE) + COUNTING NO. OF SWINGS
POLE SLIPPING
CHARACTERISTIC
ACCIDENTAL BACK ENERGISATION
CAUSE OPERATION AS AN INDUCTION MOTOR DAMAGE MACHINE AND TURBINE
THE RAPID HEATING IRON PATHS NEAR THE ROTOR SURFACE DUE TO STATOR INDUCED CURRENT.
DETECTED BY
OVER CURRENT + CB AUXILIARY CONTACTS
CHECKS FOR THE CURRENT WHEN THE GEN BREAKER CONTACTS ARE OPEN
SET BELOW THE RATED CURRENT (50 –70%) O/C AND U/V MEASUREMENTS
Backup Impedance protection
FOR UNCLEARED SYSTEM FAULT
THE BACKUP PROTECTION IS TIME DELAYED TO COORDINATE WITH THE ZONE 3 SETTING OF LINES . DETECTED BY
OVER CURRENT DISTANCE
DISTANCE PREFFERED AS THE LINE IS PROVIDED WITH DISTANCE RELAYS
SETTING SHOULD BE MADE TO COVER THE GT IMP AND THE LONGEST LINE IMP
SETTING SHOULD TAKE CARE OF THE INFEED FROM OTHER GENERATORS CONNECTED TO THE SAME BUS ALSO
LOW FORWARD AND REVERSE POWER INTERLOCK
To protect the machine from motoring action
Trip under class B after a
short time
delay in
case the turbine is already tripped ( typ set at 2
sec)
Trip under class A, after a long time delay if
turbine is not tripped (typically set at 10 sec)
Power setting typ 0.5 % of rated power
GEN TRANSFORMER PROTECTION
DIFFERENTIAL
BIASED DIFFERENTIAL
10 % BIAS SETTING (TO COVER TAP RANGE AND CT MISMATCH, IF ANY)
TIME INSTANTANEOUS
BACK UP EARTH FAULT
DEF TIME OR IDMT RELAY
20 % WITH 2 SEC TIME DELAY
UT PROTECTION
DIFFERENTIAL
BIASED DIFF USED
BIASED SETTING 10%
BACK UP OVER CURRENT
2-3 TIMES THE FULL LOAD CURRENT DELAY 0.9 SEC
TAKE CARE OF ANY LARGE MOTOR STARTING CASE
RESTRICTED E/F
HIGH IMP DIFF
COMMONLY USED GEN/GEN TRFR RELAYS
PROTECTI ON
ALSTOM ABB SIEMENS REMARK HIGH IMP DIFF CAG 34 MICOM P343 RADHA REG 216 7UM 62 In case of duplicated diff, one low imp & one high imp preferred For trfr biased relay preferred BIASED DIFF MBCH MICOM P 633 RADSB RET 316 7 UT POWER RELAYS
RXPE PPX 7 UM SERIES Directional power relays LOSS OF
FIELD
RAGPC(DIR
O/C+U/V) YCGF
7UM SERIES Impedance /
admittance 100% E/F PVMM MICOM P343 PG871 GIX REG 216 7UE22 7UM SERIES Low frequency injection type preferred over 3 rd harmonic principle 95% E/F VDG 7UM SERIES Open delta of gen sec
VT BACK UP
IMP
PROTECT ION
ALSTOM ABB SIEMENS Remarks
OVER
FLUXING GTTM RATUBRALK 7RW IDMT
POLE
SLIPPING ZTO+YTGM15 RXZF+RXPE
7UM 516 IMPEDANCE
IMP+ DIR O/C
IMP+NO OF POWER SWINGS
ACC. BACK ENERG
CTIG RAGUA 7UM
SERIES O/C +CB AUX CONTACT CURRENT ELEMENT+U/V INTER TURN VDG 7UM SERIES
comp of open delta 0n gen term+ngt sec
voltage
NEG PH
SEQ CTN RARIB 7UMSERIES MEASUREMENT OF
I
2REF CAG/FAG RADHD 7UM
SERIES HIGH IMP PREFFERED ROTOR E/F VDG 7UR 22 7 UM SERIES
Type of fault Protection Channel Recommendation Short circuit 87 G1 87G2 87 GT 1 2 1&2 Stator Earth Fault 64G1
64G2
1 2
Inter turn 95G 1 &2
unbalance 46G 1&2
Over load 51G Alarm <
Loss of excitation 40G1 40G2
1
2 >100 MW
Out of step 98G 1&2
Motoring 32 G1/2 / 37 G1/G2 1 / 2 O/V,O/F U/F 59/99 81G1/81G1 1 /2 1/2 System back up 21G 1 & 2 Accidental energisation 50GDM 1 &2
Rotor E/F 64F 1 &2
Generator Transformer/Unit Transformer Protections
Fault Device no Channel Recommendation Short ckt (GT) 87T 87 HV 51 GT 1 2 2 Earth Fault(GT) 51 NGT 64GT(3 Ph GT) 64T 1 1 1/2 Short circuit(UT) 87 UT 51UT 1/2 1/2 Earth Fault UT 51 NUT
64 UT
1 2