• No results found

Generator Testing

N/A
N/A
Protected

Academic year: 2021

Share "Generator Testing"

Copied!
50
0
0

Loading.... (view fulltext now)

Full text

(1)

Generator Insulation Testing

TC Conference Malaga October 2007

(2)

Agenda

• Purpose

• When to Test • Safety

• Prepare for the Test • The Tests

• Post Test • References • Other Tests

(3)

Insulation Quality

• Insulation Degrades Due To: – Electrical Stress – Mechanical Stress – Chemical Attack – Thermal Stress – Environmental Contamination – Time

• Can be Measured >> Maintenance Tool

(4)

Generator Insulation Testing purpose

• Manage the generator maintenance

• Determine the condition of the insulation • Identify insulation systems in need of drying

(5)

When is it Necessary to Test the Generator Insulation?

• After receipt of generator – Before storing

– Before initial startup – This Is “The Base-Line” • Prior to commissioning

– Don’t commission if results are questionable! • Prior to running after long period of no use

• After routine maintenance • Periodically

(6)

Periodic Testing

• Annually in clean, controlled environment • Quarterly in severe environments

– High humidity

– Water or snow ingestion – Smoke

– Chemicals in air

– Salty air (such as near the ocean) – Dusty environments (sand)

(7)

Monitoring Operations

• Trending

– Understand the Monitored Process – Normalized Readings

– Record on Chart

– Focus on Changes Occurring Over Time

• A plot of results over time

› Deterioration over time

› Abrupt changes from “normal”

» For example when moisture makes its way into the windings

(8)
(9)

Insulation Testing Safety Preparations

• People

– Have multiple people present for testing – Electrical safety training !

– Comply with all applicable safety standards

• For example IEEE510

– First aid training ! • Before testing

– Isolate the system to be tested

• Lock it out

– Barricade around the generator to keep people away – Use personal protection devices

(10)

Insulation Testing Safety

• During testing

– External arcing can occur

• For example if bare conductor is too close to ground

• Stay clear of the test equipment, conductors, and item being

tested • After testing

– Dissipate the energy after the test

• Short circuit the windings

› Use a grounding stick for high voltages

(11)

Pre-Test

• Understanding the test process • Tester selection

• Testing voltage

• Temperature compensation • Guard terminal

(12)

Test Process

• READ instruction manual of your instrument for detailed instructions – Test safety is paramount

• Test Process

– Apply a Test Voltage

• Less Than or Equal to Generator Operating Voltage

• Test Current Will Flow

(13)

Test Current Components

• Different processes cause insulation current to flow • Leakage Current

– High resistance in parallel with insulation capacitance – Reaches constant value quickly

• Polarization (absorption) Current

– Electric field causes charges to align themselves to the field – Moisture & contamination has large impact

– Duration in generators is usually minutes or more • Capacitive Charging Current

– Initially large, goes to zero

(14)

Insulation Tester Selection

• Tester models available from multiple vendors – EAMC (Chauvin Arnoux)

– Megger

– Numerous others

– Newer models are very portable • Key things to look for

– Adequate range

• At least to 100 GigaOhm (100,000 MegaOhm)

– Preprogrammed, automatic tests – Test voltages

• 500 Vdc, 1,000 Vdc, 5,000 Vdc

– Calibration program

(15)

Testing Voltage

• Test at a voltage near the rated voltage – Higher voltage

• Increases stress

• More likely to find weakness

• More expensive test as voltage goes up

• GM EMD study on their locomotive generators

(16)

Test Voltage Recommendations

• Main Stators

– Low voltage generators (100 v – 500 v)

• Test at 500 Vdc

– Low voltage generators (500 v – 1000 v)

• Test at 1,000 Vdc

– Medium voltage generators (2,400 v – 7,200 v)

• Test at 5,000 Vdc

– High voltage generators (10,000 v – 15,000 v)

• Test at 5,000 Vdc

• Can be tested at 10,000 Vdc

• Main rotors

– Test at 500 Vdc

• Exciters (stator and rotor)

(17)

Three phase machine testing

• Preferred to test each phase separately

– Significantly different results for each phase are a concern • Can test three phases at once

(18)

Interpreting the Results

• General result interpretation rules are included • Result interpretations are device dependent

– Test history

• Other vital information

– Previous history of the machine – Careful visual inspection

– Comparison with like devices in like circumstances – Log of previous testing

• Possible outcomes

– Machine is returned to service – Schedule repairs

– Clean, dry, retest

– Repair immediately, retest – Replace machine

(19)

Temperature Compensation

• Insulation resistance measurements are temperature dependent • Normalize to a standard temperature

– Typically either 25 °C or 40 °C

– Get exact temperature coefficient from manufacturer

• Rough estimate

› Resistance is cut by 50% for 10 °C increase in temperature

(20)

Guard Terminal - Leakage Current

• Leakage currents in parallel with the insulation – Voltage tracking

– Surface currents on exposed insulation – Can give false low resistance readings • Guard terminal connection

– Part of instrument

– Eliminates undesired currents

– Must be isolated from other connections

• Guard against flashover

– Usually connected to ground through a low impedance connection

• Older instruments may connect guard to high potential

(21)

Flashover

• Be prepared for arcing

– Not common but does happen

– Will distort results if not prevented – Careful • Internal arcing

– Test failure • External arcing

– Bare conductors too close together or too close to ground – Voltage tracking on insulation?

(22)

Insulation Quality Tests

• Visual Inspection • Insulation resistance • Polarization Index

• Dielectric Absorption Ratio • Dielectric Discharge

• Step Voltage • Hi-pot

• Other tests (appendix)

– Isothermal Relaxation Current (KDA test) – EDA Test

(23)

Visual Inspection

• Quick Look at Appearance

– Remove Terminal Box Panel

– Look at Winding End Turns Using Flashlight – Can look at internals with boroscope

• Indications

– Cleanliness

– Voltage Tracking – Visual Damage

• Black from arcing

• Discolored steel from overheating

(24)

Basic insulation resistance

• Insulation resistance reading – Resistance

– Temperature of insulation (windings)

• Or reference temperature if normalized

– Length of time voltage applied before reading • Document instrument used

– Calibration

• This basic test should be done regularly – Use trend charts

(25)

Insulation resistance – Test Considerations

• Insulation resistance measurements are temperature sensitive

– Resistance measurements without the winding temperature are meaningless!

• Use the resistance reading at same point in time – Suggest at 60 sec

(26)

Insulation resistance – 3-Phase Test Process

• 3-Phase testing

– Lock out device under test – Discharge leads

– Measure winding temperature

– Disconnect the 3 phases from the load, PTs, ground (neutral side) – Connect the 3 phases together

– Hook up tester – See tester instruction manual

• High side to the phase leads

• Low side to the core (laminations), steel frame, or rotor shaft

• Ground the frame

– Apply voltage

– Take reading - Typically after 60 sec – Discharge windings

• Tester may have provision for discharging

(27)

Insulation resistance – 1-Phase Test Process

• 1-Phase testing

– Lock out device under test – Discharge leads

– Measure winding temperature

– Disconnect the 3 phases from the load, PTs, ground (neutral side) – Connect the 2 phases not tested to the core, frame, or shaft

– Hook up tester – See tester instruction manual

• High side to the phase lead

• Low side to the core (laminations), steel frame, or rotor shaft

• Ground the frame

– Apply voltage

(28)

Insulation Resistance - Results Interpretation

• Interpretation of resistances corrected to 25 °C (or 40 °C) – Dry, new generator

• Very high resistance

• Typically higher than 1,000 MOhm (1 GOhm)

› Can be as high as 50,000 MOhm (50 GOhm) – Used generator

• Anywhere from a few MOhm to many GOhm

– Generator in questionable condition

• Significant decrease from readings when new

• Low MOhm readings

• Significant difference between phase readings

• Significant difference between component readings

› Main stator, main rotor, exciter stator, exciter rotor, PMG stator

(29)

Polarization Index (PI)

• Measurement

– The ratio of 10 min. reading to 1 min. reading

– Valuable test if no historical readings are available – Sensitive to moisture in or contamination of Insulation • Indicates

– Moisture Content of the Insulation – Good Indicator of the Drying Process

• Will not indicate the failure of an insulation layer in a multi-layer insulation

(30)

PI Results Interpretation

• PI > 6

– Very good

– Usually only seen when winding system is new • Newer designs – 1.5 < PI < 6 • Normal range – PI < 1.5 • Significant moisture in the windings

• Failure may occur at

any time

• Recommend to clean

and dry immediately

• Older designs – 2 < PI < 6 • Normal range – PI < 2 • Significant moisture in the windings

• Failure may occur at

any time

• Recommend to clean

(31)

Dielectric Absorption Ratio (DAR)

• Similar to Polarization Index

• Time at measurements different

– One typical combination is 60 sec divide by 30 sec reading

• > 1.4 is good

• Interpretation more difficult because currents may not have stabilized

(32)

Dielectric Discharge (DD)

• Measurement

– Insulation is Charged to Stable Condition – Insulation Discharge Current is Measured

• Voltage & Capacitance also measured

– Dielectric Discharge = I1 min / (V * C) • Indicates

– Moisture Content

(33)

DD Results Interpretation

• DD > 7

– Layer of multilayer insulation is damaged • 4 < DD < 7

– Questionable, damage may be possible • 2 < DD < 4

– Poor • DD < 2

(34)

Step Voltage

• Measurement

– Response to Increasing Voltage Steps

– Differences in Response Between Increasing Voltage Steps • Indicates

– Local Weak Spots

– Response Changes as Electrical Stress is Increased • Comments

– Use trend analysis.

(35)

Step Voltage Results Interpretation

• Traces for subsequent voltage steps overlay each other – Good, no layer damage

• Significant differences between traces – One or more damaged layers

(36)

Hi-Pot Test

• NOT RECOMMENDED

– Not recommended due to high stress placed on windings – Already Hi-Pot tested at the factory

– Wet insulation system increases likelihood of failure • Potentially destructive test!

– Pass / Fail

• Indicates condition under high stress conditions

• Test failure means repairs are mandatory! And may be expensive. • Test

– DC Voltage, between rated and twice rated, slowly ramped up – Applied for typically 1 min

(37)

Post-Test

• Discharging • Cleanup • Record keeping • Insulation drying • Insulation repairs

(38)

Discharging

• Tester may have provision for discharging the windings – Use it • Recommend using a ground-stick for discharging

– Has built-in resistance to limit surges and voltage/current reflections

– Should be used if testing at higher voltages • Short circuit for 5x to 10x test time

(39)

Cleanup

• Clean up the test site

(40)

Record Keeping

• Keep a permanent record of all testing • Use charts to uncover trends

• Records can be used as reference for other tests • Will help in diagnosing failures

(41)

Insulation Drying

• Follow manufacturer drying instructions

• Apply heat to raise generator temperature above ambient • Heating insulation too fast will lead to steam formation

– Keep winding temperature below 100 °C

– Steam expands Causes cracks in insulation

• Retest to verify drying success • Drying may take days

(42)

Insulation Repairs

• Repair will be required if drying does not sufficiently raise the insulation resistance and polarization index

• Repairs must be undertaken by qualified generator / motor repair (or rewind) shop

• Repairs

– Deep clean & drying

• Repair shop can frequently do a more thorough cleaning at

their facility

– Local insulation replacement

• MAIA uses a rewind shop with true repair artists in Sardinia

– Rewind

• Be sure the rewind shop can handle the type of generator

(43)

Summary

• Insulation testing is a predictive maintenance tool

• Tracking results over time helps identify problems before they occur • Good tests are available even if no history exists

(44)

References - AEMC

• AEMC Instruments Inc.

» www.aemc.com

» Chauvin Arnoux Inc

– “Understanding Insulation Resistance Testing” 02/06 rev 02 – “Dielectric Discharge (DD) Testing” 08/02

– “Poor Man’s Step Voltage Testing” 09/03

– “Megohmmeter 5050/5060 User Manual” 03/07 – “Megohmmeter 5070 User Manual” 06/07

(45)

References – Megger®

• Megger Group Ltd

» www.megger.com

» www.biddlemegger.com (distributor site with information)

– “5kV Testing. How Much Is Enough?”

• Utility Products Showcase © 2002

– “Insulation Testing Large Rotating Machines”

– “Advanced Insulation Analysis Using Megger Insulation Testers” – “Salvaging Flood Damaged Electrical Equipment”

– “Choosing a Megger Insulation Tester”

– “The Lowdown On High-Voltage DC Testing” November 2002 Rev B – “A Guide To Diagnostic Insulation Testing Above 1kV” June 2002 – “’A Stitch in Time…’ The Complete Guide to Electrical Insulation

(46)

References - Standards

• IEEE 43 • IEEE 510

(47)

Other Tests

• Not commonly performed in the field • Power factor test

– Also Tan Delta Test

– Used on generators, generally not in the field • EDA

– Advanced instruments • Isothermal relaxation current

(48)

Power Factor Test

• Also Known as Tan Delta Test • Measurement

– Changes in Power Factor or Loss Angle – Bulky Test Equipment

• Difficult for Field Testing

• Indicates

(49)

EDA Test

• Measurement

– Combines Insulation Resistance, Polarization Index, and Dielectric Discharge Tests

• Indicates

– Same as Above Mentioned Tests

(50)

Isothermal Relaxation Current

• KDA test

• Applied to Cables

– Use with Generators is Unknown • Measurement

– Measures Discharge Current

– Using Modeling, Standard Discharge Shapes Are Curve Fit to Determine Time Constants

• Indicates

References

Related documents

The drying was run to investigate the drying time to complete the drying process of every mode using the fish moisture content of 20% to justify the resulted dry fish, and

From the drying curves, the drying properties like moisture content, moisture ratio, drying rate, shrinkage and rehydration ratio can be compared between direct and

When heated air is used in the drying process, the drying rate is faster, i.e., an increased air temperature leads to a decrease in the kernel’s moisture content, and

A sensitivity testing has been done on the machine to ascertain the effects ofthe moisture content,particle size, binder, operating speed and the drying process on

The drying process of the fermented locust beans for air temperature of 75°C was the shortest being the highest air temperature.The moisture content and the drying

Drying Time- Drying time depends upon the type of food and its moisture content and temperature... Difference between

Moisture content data were also used to assess a computer model that has been developed to predict the drying rates of roofing systems containing wet insulation.. Finally, the

The moisture content versus drying time for various layer thicknesses of bael fruit pulp and at the selected temperatures is shown in Figure 2.. Moisture loss of pulp as