Generator Insulation Testing
TC Conference Malaga October 2007
Agenda
• Purpose
• When to Test • Safety
• Prepare for the Test • The Tests
• Post Test • References • Other Tests
Insulation Quality
• Insulation Degrades Due To: – Electrical Stress – Mechanical Stress – Chemical Attack – Thermal Stress – Environmental Contamination – Time
• Can be Measured >> Maintenance Tool
Generator Insulation Testing purpose
• Manage the generator maintenance
• Determine the condition of the insulation • Identify insulation systems in need of drying
When is it Necessary to Test the Generator Insulation?
• After receipt of generator – Before storing
– Before initial startup – This Is “The Base-Line” • Prior to commissioning
– Don’t commission if results are questionable! • Prior to running after long period of no use
• After routine maintenance • Periodically
Periodic Testing
• Annually in clean, controlled environment • Quarterly in severe environments
– High humidity
– Water or snow ingestion – Smoke
– Chemicals in air
– Salty air (such as near the ocean) – Dusty environments (sand)
Monitoring Operations
• Trending
– Understand the Monitored Process – Normalized Readings
– Record on Chart
– Focus on Changes Occurring Over Time
• A plot of results over time
› Deterioration over time
› Abrupt changes from “normal”
» For example when moisture makes its way into the windings
Insulation Testing Safety Preparations
• People
– Have multiple people present for testing – Electrical safety training !
– Comply with all applicable safety standards
• For example IEEE510
– First aid training ! • Before testing
– Isolate the system to be tested
• Lock it out
– Barricade around the generator to keep people away – Use personal protection devices
Insulation Testing Safety
• During testing
– External arcing can occur
• For example if bare conductor is too close to ground
• Stay clear of the test equipment, conductors, and item being
tested • After testing
– Dissipate the energy after the test
• Short circuit the windings
› Use a grounding stick for high voltages
Pre-Test
• Understanding the test process • Tester selection
• Testing voltage
• Temperature compensation • Guard terminal
Test Process
• READ instruction manual of your instrument for detailed instructions – Test safety is paramount
• Test Process
– Apply a Test Voltage
• Less Than or Equal to Generator Operating Voltage
• Test Current Will Flow
Test Current Components
• Different processes cause insulation current to flow • Leakage Current
– High resistance in parallel with insulation capacitance – Reaches constant value quickly
• Polarization (absorption) Current
– Electric field causes charges to align themselves to the field – Moisture & contamination has large impact
– Duration in generators is usually minutes or more • Capacitive Charging Current
– Initially large, goes to zero
Insulation Tester Selection
• Tester models available from multiple vendors – EAMC (Chauvin Arnoux)
– Megger
– Numerous others
– Newer models are very portable • Key things to look for
– Adequate range
• At least to 100 GigaOhm (100,000 MegaOhm)
– Preprogrammed, automatic tests – Test voltages
• 500 Vdc, 1,000 Vdc, 5,000 Vdc
– Calibration program
Testing Voltage
• Test at a voltage near the rated voltage – Higher voltage
• Increases stress
• More likely to find weakness
• More expensive test as voltage goes up
• GM EMD study on their locomotive generators
Test Voltage Recommendations
• Main Stators
– Low voltage generators (100 v – 500 v)
• Test at 500 Vdc
– Low voltage generators (500 v – 1000 v)
• Test at 1,000 Vdc
– Medium voltage generators (2,400 v – 7,200 v)
• Test at 5,000 Vdc
– High voltage generators (10,000 v – 15,000 v)
• Test at 5,000 Vdc
• Can be tested at 10,000 Vdc
• Main rotors
– Test at 500 Vdc
• Exciters (stator and rotor)
Three phase machine testing
• Preferred to test each phase separately
– Significantly different results for each phase are a concern • Can test three phases at once
Interpreting the Results
• General result interpretation rules are included • Result interpretations are device dependent
– Test history
• Other vital information
– Previous history of the machine – Careful visual inspection
– Comparison with like devices in like circumstances – Log of previous testing
• Possible outcomes
– Machine is returned to service – Schedule repairs
– Clean, dry, retest
– Repair immediately, retest – Replace machine
Temperature Compensation
• Insulation resistance measurements are temperature dependent • Normalize to a standard temperature
– Typically either 25 °C or 40 °C
– Get exact temperature coefficient from manufacturer
• Rough estimate
› Resistance is cut by 50% for 10 °C increase in temperature
Guard Terminal - Leakage Current
• Leakage currents in parallel with the insulation – Voltage tracking
– Surface currents on exposed insulation – Can give false low resistance readings • Guard terminal connection
– Part of instrument
– Eliminates undesired currents
– Must be isolated from other connections
• Guard against flashover
– Usually connected to ground through a low impedance connection
• Older instruments may connect guard to high potential
Flashover
• Be prepared for arcing
– Not common but does happen
– Will distort results if not prevented – Careful • Internal arcing
– Test failure • External arcing
– Bare conductors too close together or too close to ground – Voltage tracking on insulation?
Insulation Quality Tests
• Visual Inspection • Insulation resistance • Polarization Index
• Dielectric Absorption Ratio • Dielectric Discharge
• Step Voltage • Hi-pot
• Other tests (appendix)
– Isothermal Relaxation Current (KDA test) – EDA Test
Visual Inspection
• Quick Look at Appearance
– Remove Terminal Box Panel
– Look at Winding End Turns Using Flashlight – Can look at internals with boroscope
• Indications
– Cleanliness
– Voltage Tracking – Visual Damage
• Black from arcing
• Discolored steel from overheating
Basic insulation resistance
• Insulation resistance reading – Resistance
– Temperature of insulation (windings)
• Or reference temperature if normalized
– Length of time voltage applied before reading • Document instrument used
– Calibration
• This basic test should be done regularly – Use trend charts
Insulation resistance – Test Considerations
• Insulation resistance measurements are temperature sensitive
– Resistance measurements without the winding temperature are meaningless!
• Use the resistance reading at same point in time – Suggest at 60 sec
Insulation resistance – 3-Phase Test Process
• 3-Phase testing
– Lock out device under test – Discharge leads
– Measure winding temperature
– Disconnect the 3 phases from the load, PTs, ground (neutral side) – Connect the 3 phases together
– Hook up tester – See tester instruction manual
• High side to the phase leads
• Low side to the core (laminations), steel frame, or rotor shaft
• Ground the frame
– Apply voltage
– Take reading - Typically after 60 sec – Discharge windings
• Tester may have provision for discharging
Insulation resistance – 1-Phase Test Process
• 1-Phase testing
– Lock out device under test – Discharge leads
– Measure winding temperature
– Disconnect the 3 phases from the load, PTs, ground (neutral side) – Connect the 2 phases not tested to the core, frame, or shaft
– Hook up tester – See tester instruction manual
• High side to the phase lead
• Low side to the core (laminations), steel frame, or rotor shaft
• Ground the frame
– Apply voltage
Insulation Resistance - Results Interpretation
• Interpretation of resistances corrected to 25 °C (or 40 °C) – Dry, new generator
• Very high resistance
• Typically higher than 1,000 MOhm (1 GOhm)
› Can be as high as 50,000 MOhm (50 GOhm) – Used generator
• Anywhere from a few MOhm to many GOhm
– Generator in questionable condition
• Significant decrease from readings when new
• Low MOhm readings
• Significant difference between phase readings
• Significant difference between component readings
› Main stator, main rotor, exciter stator, exciter rotor, PMG stator
Polarization Index (PI)
• Measurement
– The ratio of 10 min. reading to 1 min. reading
– Valuable test if no historical readings are available – Sensitive to moisture in or contamination of Insulation • Indicates
– Moisture Content of the Insulation – Good Indicator of the Drying Process
• Will not indicate the failure of an insulation layer in a multi-layer insulation
PI Results Interpretation
• PI > 6
– Very good
– Usually only seen when winding system is new • Newer designs – 1.5 < PI < 6 • Normal range – PI < 1.5 • Significant moisture in the windings
• Failure may occur at
any time
• Recommend to clean
and dry immediately
• Older designs – 2 < PI < 6 • Normal range – PI < 2 • Significant moisture in the windings
• Failure may occur at
any time
• Recommend to clean
Dielectric Absorption Ratio (DAR)
• Similar to Polarization Index
• Time at measurements different
– One typical combination is 60 sec divide by 30 sec reading
• > 1.4 is good
• Interpretation more difficult because currents may not have stabilized
Dielectric Discharge (DD)
• Measurement
– Insulation is Charged to Stable Condition – Insulation Discharge Current is Measured
• Voltage & Capacitance also measured
– Dielectric Discharge = I1 min / (V * C) • Indicates
– Moisture Content
DD Results Interpretation
• DD > 7
– Layer of multilayer insulation is damaged • 4 < DD < 7
– Questionable, damage may be possible • 2 < DD < 4
– Poor • DD < 2
Step Voltage
• Measurement
– Response to Increasing Voltage Steps
– Differences in Response Between Increasing Voltage Steps • Indicates
– Local Weak Spots
– Response Changes as Electrical Stress is Increased • Comments
– Use trend analysis.
Step Voltage Results Interpretation
• Traces for subsequent voltage steps overlay each other – Good, no layer damage
• Significant differences between traces – One or more damaged layers
Hi-Pot Test
• NOT RECOMMENDED
– Not recommended due to high stress placed on windings – Already Hi-Pot tested at the factory
– Wet insulation system increases likelihood of failure • Potentially destructive test!
– Pass / Fail
• Indicates condition under high stress conditions
• Test failure means repairs are mandatory! And may be expensive. • Test
– DC Voltage, between rated and twice rated, slowly ramped up – Applied for typically 1 min
Post-Test
• Discharging • Cleanup • Record keeping • Insulation drying • Insulation repairsDischarging
• Tester may have provision for discharging the windings – Use it • Recommend using a ground-stick for discharging
– Has built-in resistance to limit surges and voltage/current reflections
– Should be used if testing at higher voltages • Short circuit for 5x to 10x test time
Cleanup
• Clean up the test site
Record Keeping
• Keep a permanent record of all testing • Use charts to uncover trends
• Records can be used as reference for other tests • Will help in diagnosing failures
Insulation Drying
• Follow manufacturer drying instructions
• Apply heat to raise generator temperature above ambient • Heating insulation too fast will lead to steam formation
– Keep winding temperature below 100 °C
– Steam expands Causes cracks in insulation
• Retest to verify drying success • Drying may take days
Insulation Repairs
• Repair will be required if drying does not sufficiently raise the insulation resistance and polarization index
• Repairs must be undertaken by qualified generator / motor repair (or rewind) shop
• Repairs
– Deep clean & drying
• Repair shop can frequently do a more thorough cleaning at
their facility
– Local insulation replacement
• MAIA uses a rewind shop with true repair artists in Sardinia
– Rewind
• Be sure the rewind shop can handle the type of generator
Summary
• Insulation testing is a predictive maintenance tool
• Tracking results over time helps identify problems before they occur • Good tests are available even if no history exists
References - AEMC
• AEMC Instruments Inc.
» www.aemc.com
» Chauvin Arnoux Inc
– “Understanding Insulation Resistance Testing” 02/06 rev 02 – “Dielectric Discharge (DD) Testing” 08/02
– “Poor Man’s Step Voltage Testing” 09/03
– “Megohmmeter 5050/5060 User Manual” 03/07 – “Megohmmeter 5070 User Manual” 06/07
References – Megger®
• Megger Group Ltd
» www.megger.com
» www.biddlemegger.com (distributor site with information)
– “5kV Testing. How Much Is Enough?”
• Utility Products Showcase © 2002
– “Insulation Testing Large Rotating Machines”
– “Advanced Insulation Analysis Using Megger Insulation Testers” – “Salvaging Flood Damaged Electrical Equipment”
– “Choosing a Megger Insulation Tester”
– “The Lowdown On High-Voltage DC Testing” November 2002 Rev B – “A Guide To Diagnostic Insulation Testing Above 1kV” June 2002 – “’A Stitch in Time…’ The Complete Guide to Electrical Insulation
References - Standards
• IEEE 43 • IEEE 510
Other Tests
• Not commonly performed in the field • Power factor test
– Also Tan Delta Test
– Used on generators, generally not in the field • EDA
– Advanced instruments • Isothermal relaxation current
Power Factor Test
• Also Known as Tan Delta Test • Measurement
– Changes in Power Factor or Loss Angle – Bulky Test Equipment
• Difficult for Field Testing
• Indicates
EDA Test
• Measurement
– Combines Insulation Resistance, Polarization Index, and Dielectric Discharge Tests
• Indicates
– Same as Above Mentioned Tests
Isothermal Relaxation Current
• KDA test
• Applied to Cables
– Use with Generators is Unknown • Measurement
– Measures Discharge Current
– Using Modeling, Standard Discharge Shapes Are Curve Fit to Determine Time Constants
• Indicates