DOCUMENT TITLE:
PRD CHKD APPD
NAME MWB MWB RSR SIZE
DATE 24-Feb-16 27-Feb-16 29-Feb-16 A4
DEC PROJECT NO NO. OF SHEETS (Incl. Title Sht.)
1 of 36
Relay setting calculations for the primary substation and Remote end grid stations
REVISION NO. 1 DOC NO:
INDEX
S.NO TITLE PAGE NO.
1.0 OBJECTIVE 3
2.0 CONSIDERATIONS AND ASSUMPTIONS 3 3.0 RELAY SETTING CALCULATION OF RUSAIL -09 PRIMARY SUBSTATION 5
3.1 415 V MCCB SETTING 5
3.2 PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 500KVA, 11/0.416 KV AUX. TRASFORMER FEEDER 6 3.3 PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 11KV SWITCHGEAR CAPACITOR
BANK FEEDERS 8
3.4 PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 11KV SWITCHGEAR OUTGOING POWER FEEDERS 10 3.5 PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 11KV BUS COUPLER 12 3.6 STAND-BY EARTH FAULT PROTECTION OF 33/11KV TRANSFORMER 14 3.7 DIRECTIONAL PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 11KV SWITCHGEAR INCOMER 15 3.8 RESTRICTED EARTH FAULT PROTECTION OF 33/11KV , 20 MVA TRANSFORMER 18 3.9 TRANSFORMER DIFFERENTIAL PROTECTION (87T) OF 33/11KV, 20MVA TRANSFORMER 22 3.10 PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 20MVA, 33/11KV TRANSFORMER FEEDER 27 3.11 PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 33KV BUS COUPLER 29 3.12 DIRECTIONAL PHASE OVER CURRENT & EARTH FAULT PROTECTION OF 33KV SWITCHGEAR INCOMER FEEDER 31 3.13 LINE DIFFERENTIAL PROTECTION OF RUSAIL -02 33KV INCOMER(S) FROM RUSAIL GSS 34 4.0 ANNEXURE -1 : OVER CURRENT PROTECTION COORDINATION 37 5.0 ANNEXURE -2 : OC TIME CURRENT CHARACTERISTIC CURVE 39 6.0 ANNEXURE -3 : EARTH FAULT PROTECTION COORDINATION 42 7.0 ANNEXURE -4 : EF TIME CURRENT CHARACTERISTIC CURVE 44 8.0 ANNEXURE -5 : SHORT CIRCUIT STUDY RESULTS 47 9.0 ANNEXURE -6 : DIGSI FILES FOR SIEMENS RELAYS
Tender No.: 08/2015 Calculation No.: 08/2015/E/1062/36/A4 Revision: 1 Title: Construction of 33/11kV, 3x20MVA RUSAIL-09 Primary Substation
Calculation Title: Relay Setting Calculations
Purpose:
These calculations are for the determination of protection Settings and relay coordination for The Electrical System of 33/11kV - 3X20 MVA RUSAIL-09 Pss for MEDC.
Considerations And Assumptions:
a) The resultant Fault Currents used for the protection settings calculation are based Upon The fault levels at the 33kV switchgear at RUSAIL 33kV GSS which received from MDEC and The same is attached in the annexures
b) Software tool ETAP 12.5 has been used for Fault level Calculation Study.
c) Protection Settings calculations are based on Vendor specified CT data and not on CT test reports.
d) Instantaneous elements of 33/11 KV outgoing feeders are blocked as per MDEC practice. e) The Over Current element of outgoing Feeders are based on 100% of rated current i.e. 400
A as per MDEC practice.
f) The protective rely settings are based on the short circuit currents. The relays are set to operate such as to isolate the faulted circuit from the electrical distribution system.
Max 3 Phase/ 1 Phase Fault current at RUSAIL 132kV BUS (2017) = 22.4 / 28.82 kA Max 3 Phase Fault current at RUSAIL 33kV BUS (2017) = 21.53 kA Voltage Level = 33.0kV - Due to Y-D Transformer winding connections and earthing arrangement via
IEC curves have been considered for relay setting and coordination. The time of operation of the relays using IEC curves can be calculated using the following formula:
At Time Multiplier Setting - TMS = 1
Extremely Inverse: t = 80 ÷ [(I/Is) 2 - 1] Very Inverse: t = 13.5 ÷ [(I/Is) - 1] Standard (normal) Inverse: t = 0.14 ÷ [(I/Is) 0.02 - 1] Where,
t = tripping time I = Fault Current
Is = Inverse time over current pickup TMS = Time Multiplier Setting I/Is = Plug setting Multiplier, PMS
The selection of the type of curve (EI, VI or SI) or DT is based on the best available option for proper coordination and fast fault clearing.
g) The fault current which is mentioned in this document are from ETAP short circuit Study. h) The required TMS of the relay has been choosen as per the required operating time i) Time grading margin of 250 mSec (approx) has been considered between the adjacent
Relay Type (Similar for all 415 V INCOMER MCCB) MCCB Make: SIEMENS
Protection feature: L:Long Time , S: Short Time , I: Instantaneous , G: Ground fault Location:
LVAC INCOMER Panels : =QA and =QB
Aux. Transformer data (Similar for all 33 kV Transformer Bays)
Rated Power: 0.5 MVA
Rated Voltage: 11 / 0.433 KV
Rated Current (Side-1) : 26.24 A
Rated Current (Side-2) : 666.69 A
Connection : Delta (HV), Star (LV)
Vector Group : Dyn11
Transformer Percentage Impedance, Z % : 4.75 %
415 V system data
0.433 KV
Rated short circuit current of 415 V BUS,Iscc (1 Sec) : 50 KA
50 Hz
415 V MCCB data Make:
Type:
Rated Current : A
415 V MCCB Settings (Similar for all 415 V INCOMER MCCB)
LONG TIME (L)
= 666.69 / 1250 = 0.53335 Selected Pick-up current setting, (I>) = 0.90 A
= 2.00 SEC
SHORT TIME (S)
Selected Pick-up current setting, (I>) = 2.00 A = 0.30 SEC
INSTANTANEOUS (I)
= Disabled
GROUND FAULT (G)
= 0.20 * 1250 = 250 Selected Pick-up current setting, (I>) = 0.20 A
= 0.30 SEC Time Setting Current Setting Current Setting Time Setting Time Setting Instantaneous Function Nominal frequency: 1250 SIEMENS 3WL1112-2FG48-5FM4 3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.1 415 V MCCB SETTING
Relay Type (Similar for all 11 kV Auxiliary Transformer Bays) 751A51 Make: SIEMENS
Protection feature: Non Directional Phase Over Current and Earth Fault Protection Location:
11 KV Auxiliary Transformer panels: =4H0 and =5H0
Aux. Transformer data (Similar for all 11 kV Aux. Transformer Bays)
Rated Power: 0.5 MVA
Rated Voltage: 11 / 0.433 KV
Rated Current (Side-1) : 26.24 A
Rated Current (Side-2) : 666.69 A
Connection : Delta (HV), Star (LV)
Vector Group : Dyn11
Transformer Percentage Impedance, Z % : 4.75 %
CT Ratios for 50, 51 & 51N Protection (Similar for all 11 kV Auxiliary Transformer Bays)
11 KV Aux. Transformer Feeders CT: 200 / 1 A Class: 5P20
The maximum transformer through-fault current calculation
short circuit MVA of the transformer = Transformer MVA ÷ %Z = 0.50 ÷ 4.75 short circuit MVA of the transformer = 10.5263 MVA
Fault current as referred to secondary = 10.5263 x 10^6 ÷ (SQRT(3)x 0.433 x 10^3) = 14035 A [ considered fault current for stability] Fault current as referred to 11 KV = 552 A
3PH fault Current at 11 KV side when 2 transformers in service = 14.6 KA 3PH fault Current at 11 KV side when one transformers in service = 8.3 KA
Relay Settings (Similar for all 11 kV Aux. Transformer Bays)
Instantaneous Phase Over Current Protection (50)
symmetrical through fault current = 1.30 x Symmetrical fault current
= 1.30 x 552.49 = 718.23 A Multiples of pickup current = 718.23 / 200 = 3.59117 In
Inrush current of the Transformer = 12 x Primary FLC [Assumed] = 12 x 26.24 = 314.92 A Multiples of pickup current = 314.92 / 200 = 1.57459 In
Since 1.3 x Tx through fault current is greater than transformer inruch current setting is selected to be greater than 1.3 x transformer through fault current.
Summary:
Selected Instantaneous Pick-up, (I>>) = 4.0 A
Time Delay, td = 0.0 Sec
Selected Tripping Characteristics = DMT
Non Directional Phase Over Current Protection (51)
Phase over current Pick-up = 120% of the Transformer full load current = ( 1.20 x 26.24 ) ÷ 200 = 0.16 A
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Selected Pick-up current setting, (I>) = 0.16 A ( Actual Pick-up current = 31.491833 A )
Multiples of pickup current = 552 / 31.49 = 17.54386
Selected Tripping Characteristics = SI (IEC Curve)
Operating Time desired = 415 LVAC Operating Time + Grading Margin Operating Time desired = 0.3 + 0.3
Operating time desired = 0.60 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.60 = 0.14 x TMS / [ ( 17.5 )^0.02 -1]
= 0.25
Summary:
Selected 51 Pick-up, (I>) = 0.16 A
Selected Tripping Characteristics = SI
Selected TMS = 0.25
Non Directional Earth Fault Protection (51N)
Ground fault currents are not transferred through delta-Wye transformer
1PH fault Current at 11 KV side when 2 transformers in service = 15.86 KA 1PH fault Current at 11 KV side when one transformers in service = 8.64 KA
Io Setting = 0.2 In TMS = 0.05
Selected Pick-up current setting, (Io>) = 0.20 A ( Actual Pick-up current = 40 A )
Multiples of pickup current = 8640 / 40.00 = 216 > 20 then , Multiples of pickup current = 20
Selected Tripping Characteristics = SI (IEC Curve)
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
= 0.14 x TMS / [ ( 20 )^0.02 -1]
= 0.11
Summary:
Selected 51N Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
Instantaneous Earth Fault Protection (50N)
Instantaneous Earth Fault pickup current = 5 Times of 51N current pickup current
= 5.00 x 0.20 = 1.00 In
Summary:
Selected Instantaneous Pick-up, (I>>) = 1.0 A
Time Delay, td = 0.0 Sec
Selected Tripping Characteristics = DMT
Relay operating time TMS
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 11 kV Capacitor Bank Bays) 751A51 Make: SIEMENS
Protection feature: Non Directional Phase Over Current and Earth Fault Protection Location:
11 KV Outgoing Feeder panels: =1K0 , =2K0 and =3K0
CT Ratios for 51 & 51N Protection (Similar for all 11 kV Capacitor Bank Bays)
11.5 KV Capacitor Bank CT: 400 / 1 A Class: 5P20
Relay Settings (Similar for all 11 kV Capacitor Bank Bays)
Non Directional Phase Over Current Protection (51)
3PH fault Current at 11 KV side when 2 transformers in service = 14.6 KA 3PH fault Current at 11 KV side when one transformers in service = 8.3 KA
As per Capacitor Bank Vendor Parameters , The rated Current for each Stage = 52.5 A The Capacitor bank full load Current = 5 Stages* 52.5 = 262.5 A
Phase over current Pick-up = 130% * the Capacitor bank full load Current = ( 1.30 x 262.50 ) ÷ 400
= 0.85 A
Selected Pick-up current setting, (I>) = 0.85 A ( Actual Pick-up current = 341.25 A )
Selected Tripping Characteristics = SI (IEC Curve)
= 0.05 (MDEC Practice)
Multiples of pickup current = 14.6 / 341.25 = 42.7839 > 20 Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
= 0.14 x 0.05/ [ ( 20 )^0.02 -1] = 0.11 Sec
Summary:
Selected 51 Pick-up, (I>) = 0.85 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
Instantaneous Setting = Blocked (MDEC Practice)
Non Directional Earth Fault Protection (51N)
1PH fault Current at 11 KV side when 2 transformers in service = 15.86 KA 1PH fault Current at 11 KV side when one transformers in service = 8.64 KA Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 400.00 ) ÷ 400
= 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 80 A )
Selected Tripping Characteristics = SI (IEC Curve)
= 0.05 (MDEC Practice)
Multiples of pickup current = 8.64 / 80 = 108 > 20 then , Multiples of pickup current = 20
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
= 0.14 x 0.05/ [ ( 20 )^0.02 -1] = 0.11 Sec
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.3 NON DIRECTIONAL PHASE & EARTH FAULT PROTECTION (51 & 51N) OF 11 KV CAPACITOR BANK
Selected TMS
Relay Operating Time Relay Operating Time
Selected TMS
Relay Operating Time Relay Operating Time
Summary:
Selected 51N Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
Instantaneous Setting = Blocked (MDEC Practice)
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 11 kV Outgoing Feeders Bays) 751A61 Make: SIEMENS
Protection feature: Non Directional Phase Over Current and Earth Fault Protection Location:
11 KV Outgoing Feeder panels: =11L5 To = 39L5
CT Ratios for 51 & 51N Protection (Similar for all 11 kV Outgoing Feeders Bays)
11.5 KV Outgoing Feeders CT: 400 / 1 A Class: 5P20
Relay Settings (Similar for all 11 kV Outgoing Feeders Bays)
Non Directional Phase Over Current Protection (51)
3PH fault Current at 11 KV side when 2 transformers in service = 14.6 KA 3PH fault Current at 11 KV side when one transformers in service = 8.3 KA Phase over current Pick-up = 100% of the CT ratio
= ( 1.00 x 400.00 ) ÷ 400
= 1.00 A
Selected Pick-up current setting, (I>) = 1.00 A ( Actual Pick-up current = 400 A )
Selected Tripping Characteristics = SI (IEC Curve)
= 0.05 (MDEC Practice)
Multiples of pickup current = 14.6 / 400 = 36.5 > 20 Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
= 0.14 x 0.05/ [ ( 20.0 )^0.02 -1] = 0.1134 Sec
Summary:
Selected 51 Pick-up, (I>) = 1.0 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
OC High set Setting = 8 In (MDEC Practice)
OC High set Clcs = Definite (MDEC Practice)
OC High set Time = 0 Sec (MDEC Practice)
Instantaneous Setting = Blocked (MDEC Practice)
Non Directional Earth Fault Protection (51N)
1PH fault Current at 11 KV side when 2 transformers in service = 15.86 KA 1PH fault Current at 11 KV side when one transformers in service = 8.64 KA Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 400.00 ) ÷ 400 = 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 80 A )
Selected Tripping Characteristics = SI (IEC Curve)
= 0.05 (MDEC Practice)
Multiples of pickup current = 8.64 / 80 = 108 > 20 Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
= 0.14 x 0.05/ [ ( 20 )^0.02 -1] = 0.1134 Sec
Relay Operating Time Relay Operating Time
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.4 NON DIRECTIONAL PHASE & EARTH FAULT PROTECTION (51 & 51N) OF 11 KV OUTGOING FEEDERS
Selected TMS
Relay Operating Time Relay Operating Time
Summary:
Selected 51N Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
EF High set Setting = 1.6 In (MDEC Practice)
EF High set Clcs = Definite (MDEC Practice)
EF High set Time = 0 Sec (MDEC Practice)
Instantaneous Setting = Blocked (MDEC Practice)
A/R setting :
No. of shots = 1
Dead Time for first shot = 180 Sec
Reset Time For reclose cycle = 60 Sec
Reset Time Form Lock Out = 60 Sec
Dead Time for 2 to 4th Shot = Infinite
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 11 kV Bus coupler Bays) 751A51 Make: SIEMENS
Protection feature: Non Directional Phase Over Current and Earth Fault Protection Location:
11 KV Bus Coupler panels: =3S0 and =4S0
CT Ratios for 51 & 51N Protection (Similar for all 11 kV Bus coupler Bays)
11.5 KV Bus Coupler CT: 1200 / 1 A Class: 5P20
Relay Settings (Similar for all 11 kV Bus coupler Bays)
Non Directional Phase Over Current Protection (51)
3PH fault Current at 11 KV side when one transformers in service = 8.3 KA
Phase over current Pick-up = 100% of Full Load current for one transformer = 1050
= ( 1.00 x 1050.00 ) ÷ 1200
= 0.88 A
Selected Pick-up current setting, (I>) = 0.88 A ( Actual Pick-up current = 1050 A )
Multiples of pickup current = 8.3 / 1200 = 6.91667 ˂ 20 Bus Section CB Operating Time required = Operating time of 11 KV Feeder CB + 0.25 Sec [Grading Margin]
= 0.36 Sec Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.36 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.36 = 0.14 x TMS / [ ( 6.9 )^0.02 -1]
= 0.10
Summary:
Selected 51 Pick-up, (I>) = 0.88 A
Selected Tripping Characteristics = SI
Selected TMS = 0.10
Instantaneous Setting = Blocked (MDEC Practice)
Non Directional Earth Fault Protection (51N)
1PH fault Current at 11 KV side when one transformers in service = 8.64 KA Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 1200.00 ) ÷ 1200 = 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 240 A )
Multiples of pickup current = 8.64 / 1200 = 7.2 ˂ 20 Bus Section CB Operating Time required = Operating time of 11 KV Feeder CB + 0.25 Sec [Grading Margin]
= 0.36 Sec Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.36 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.36 = 0.14 x TMS / [ ( 7 )^0.02 -1]
= 0.10
TMS
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.5 NON DIRECTIONAL PHASE & EARTH FAULT PROTECTION (51 & 51N) OF 11 KV BUS COUPLER
Summary:
Selected 51 Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.10
Instantaneous Setting = Blocked (MDEC Practice)
3.5 NON DIRECTIONAL PHASE & EARTH FAULT PROTECTION (51 & 51N) OF 11 KV BUS COUPLER 3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 11 kV Transformer Incomer Bays) 751A51 Make: SIEMENS
Protection feature: Stand-by Earth Fault Location:
11 KV Transformer Incomer panels: =1T0, =2T0 and =3T0
Transformer data (Similar for all 11 kV Transformer Incomer Bays)
Rated Power(ONAN/ONAF) : 20 MVA
Transformer Cooling ONAF/ONAN
Rated Voltage: 33 / 11.5 KV
Rated Current (HV) : 349.91 A
Rated Current (LV) : 1004.09 A
Connection : Delta (HV), Star (LV)
Vector Group : Dyn11
CT Ratios for 51G Protection (Similar for all 11 kV Transformer Incomer Bays)
LV 11.5 KV Transformer Feeder CT: 1200 / 1 A Class: 5P20
Relay Settings (Similar for all 11 kV Transformer Incomer Bays)
Stand-by Earth Fault Protection (51G)
1PH fault Current at 11 KV side when one transformers in service = 8.64 KA Earth Fault current Pick-up = 20% of the CT ratio
= ( 0.20 x 1200.00 ) ÷ 1200 = 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 240 A )
Multiples of pickup current = 8640 / 240 = 36 > 20 Required Relay operating time = 11 KV I/C 51N Relay Operating Time + Grading Margin [0.25]
= 0.61 + 0.25 = 0.91 Sec Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.91 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.91 = 0.14 x TMS / [ ( 20 )^0.02 -1] = 0.403
Summary:
Selected Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.40
Instantaneous Setting = Blocked (MDEC Practice)
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.6 STAND-BY EARTH FAULT PROTECTION (51G) OF 33/11 KV TRANSFORMER
Relay Type (Similar for all 11 kV Transformer Incomer Bays) 751201 Make: SIEMENS
Protection feature: Directional Phase Over Current and Earth Fault Protection Location:
11 KV Transformer Incomer panels: =1T0, =2T0 and =3T0
Transformer data (Similar for all 11 kV Transformer Incomer Bays)
Rated Power(ONAN/ONAF) : 20 MVA
Transformer Cooling ONAF/ONAN
Rated Voltage: 33 / 11.5 KV
Rated Current (HV) : 349.91 A
Rated Current (LV) : 1004.09 A
Connection : Delta (HV), Star (LV)
Vector Group : Dyn11
CT Ratios for 67 & 67N Protection (Similar for all 11 kV Transformer Incomer Bays)
LV 11.5 KV Transformer Feeder CT: 1200 / 1 A Class: 5P20
Relay Settings (Similar for all 11 kV Transformer Incomer Bays)
Directional Phase Over Current Protection (67)
Directional Phase over current Pick-up = 50% of the CT Ratio
= ( 0.50 x 1200.00 ) ÷ 1200
= 0.50 A
Selected Pick-up current setting, (I>) = 0.50 A ( Actual Pick-up current = 600 A )
Since the 67 Relay will operate only when both transformers will be in parallel and as per short circuit study the fault contribution (total) when both 20 MVA transformers are in parallel = 14.6 KA
Contribution of each transformer (fault seen by 67 relay CT) = 14.6 /2 = 7.3 KA
Selected Tripping Characteristics = SI (IEC Curve)
Multiples of pickup current = 7300 / 600 = 12.1667 ˂ 20 Operating time desired = 0.30 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.30 = 0.14 x TMS / [ ( 12 )^0.02 -1]
= 0.1
Summary:
Selected 67 Pick-up, (I>) = 0.5 A
Selected Tripping Characteristics = SI
Selected TMS = 0.1
Instantaneous Setting = Blocked (MDEC Practice)
Direction of operation = Forward ( TowardsTransformer)
RCA Recommended = 45.0 ◦ Directional Earth Fault Protection (67N)
Directional Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 1200.00 ) ÷ 1200 = 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 240 A ) 3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.7 DIRECTIONAL PHASE & EARTH FAULT PROTECTION (67 & 67N) OF 11KV SWITCHGEAR INCOMER
Since the 67 Relay will operate only when both transformers will be in parallel and as per short circuit study the fault contribution (total) when both 20 MVA transformers are in parallel = 15.86 KA
Contribution of each transformer (fault seen by 67 relay CT) = 15.86 /2 = 7.93 KA
Selected Tripping Characteristics = SI (IEC Curve)
Multiples of pickup current = 7930 / 240 = 33.0417 > 20
= 0.05 (MDEC Practice)
= TMS {0.14/((I/Is)^0.02-1)}
= 0.14 x 0.05/ [ ( 20 )^0.02 -1] = 0.1134 Sec
Summary:
Selected 67 Pick-up, (I>) = 0.20 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
Instantaneous Setting = Blocked (MDEC Practice)
Direction of operation = Forward ( TowardsTransformer)
RCA Recommended = -45 ◦ Non Directional Phase Over Current Protection (51)
3PH fault Current at 11 KV side when one transformers in service = 8.3 KA Non Directional Phase over current Pick-up= 100% of the CT Ratio
= ( 1.00 x 1200.00 ) ÷ 1200 = 1.00 A
Selected Pick-up current setting, (I>) = 1.00 A ( Actual Pick-up current = 1200 A )
Selected Tripping Characteristics = SI (IEC Curve)
Multiples of pickup current = 8300 / 1200 = 6.91667 ˂ 20 Operating time desired = Operating time of 11 KV bus coupler + 0.25 Sec [Grading Margin]
= 0.61 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.61 = 0.14 x TMS / [ ( 7 )^0.02 -1]
= 0.17
Summary:
Selected 51 Pick-up, (I>) = 1.0 A
Selected Tripping Characteristics = SI
Selected TMS = 0.17
Instantaneous Setting = Blocked (MDEC Practice)
Non Directional Earth Fault Protection (51N)
1PH fault Current at 11 KV side when one transformers in service = 8.64 KA Directional Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 1200.00 ) ÷ 1200
= 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 240 A ) 3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.7 DIRECTIONAL PHASE & EARTH FAULT PROTECTION (67 & 67N) OF 11KV SWITCHGEAR INCOMER
Selected TMS
Relay Operating Time Relay Operating Time Relay Operating Time
Selected Tripping Characteristics = SI (IEC Curve)
Multiples of pickup current = 8640 / 240 = 36 > 20 Operating time desired = Operating time of 11 Kvbus coupler + 0.25 Sec [Grading Margin]
= 0.61 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.61 = 0.14 x TMS / [ ( 20 )^0.02 -1]
= 0.27
Summary:
Selected 67 Pick-up, (I>) = 0.20 A
Selected Tripping Characteristics = SI
Selected TMS = 0.27
Instantaneous Setting = Blocked (MDEC Practice)
TMS
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 33 kV Transformer Bays) 751A51 Make: SIEMENS
Protection feature: High Impedance REF Protection Location:
11 KV Transformer Incomer panels: =1T0, =2T0 and =3T0 Transformer data (Similar for all 33 kV Transformer Bays)
Rated Power(ONAN/ONAF) : 20 MVA
Transformer Cooling ONAF/ONAN
Rated Voltage: 33 / 11.5 KV
Rated Current (HV) : 349.91 A
Rated Current (LV) : 1004.09 A
Connection : Delta (HV), Star (LV)
Vector Group : Dyn11
Transformer Percentage Impedance, Z % : 12.50 %
Impedance Tolerance Considered : ± 7.5 % [IEC tolerance]
Therefore Transformer Percentage Impedance, (Z%): 11.56 %
CT Ratios for High Impedance REF Protection (Similar for all 33 kV Transformer Bays)
11 KV Transformer Feeder CT: 11 KV Transformer Neutral CT:
CT Ratio: 1200 / 1 A CT Ratio: 1200 / 1 A
Class: X Class: X
Knee Point Voltage: 350 V Knee Point Voltage 350 V
CT mag. Current @ Vk/2 30 mA CT mag. Current @ Vk 30 mA
CT secondary resistance Rct: 6 Ohms CT secondary resistance Rct: 6 Ohms Relay Settings (Similar for all 33 kV Transformer Bays):
All CTs must have the same transformation ratio. To prevent maloperation of the relay during saturation of the CTs on an external fault, the actual stability voltage Vs must be at least the voltage Vs,min produced by the maximum secondary through fault current, flowing through the cable resistance and the CTs' internal resistance:
Vs > Vs,min
where
Vs,min = Ik,max,thr *(Isn/Ipn)*(Rlead + Ri)
In addition to this, the kneepoint voltage must be higher than twice the actual stability voltage: Vknee ≥ 2 * Vs (Requirement)
where :
Vs : actual stability voltage Vs,min : minimum stability voltage Vknee : kneepoint voltage of CT
Ik,max,thr : max. symmetrical short-circuit current for external faults Ipn : CT primary nominal current
Isn : CT secondary nominal current Ri : CT secondary winding Resistance Rlead :
3.0 RRELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.8 RESTRICTED EARTH FAULT PROTECTION (87NL) OF 33/11k,20MVA TRANSFORMER SECONDARY SIDE
Length 11 KV Side: lwire = 10 m Netural Side: lwire = 100 m Cross-section awire = 4 mm 2
As per vendor catalogue
Resistance (Cu)@20 ◦C Rcu20 = 0.00461 Ohms /m Temperature coefficient α per ◦C = 0.00393
Resistance (Cu)@75 ◦C Rcu75= pcu20 x (1+ α (75-20))
pcu75= 0.00561 Ohms /m Eff. Wire length p.u. k =
For 11 KV Side:
Rshortest loop = Ohm
For Neutral Side:
Rlongest loop = Ohm
in the below calculation, we will consider the resistance of the longest cable loop
Calculation of stability voltage:
The maximum transformer through-fault current calculation short circuit MVA of the transformer = Transformer MVA ÷ %Z =
= 20/ 11.56 = 172.972973 MVA
Maximum transformer through-fault current IF = short Circuit TX MVA / √3 x Rated secondary TX voltage = ( 172.973 /(√3*11))
= 8.684 KA
The minimum stability voltage of 7SJ8022 ANSI 64N(HI) to ensure stability on external faults: Vs,min = Ik,max,thr *(Isn/Ipn)*(Rlead + Ri)
Vs,min = 8684 /1200*( 1.1213 + 6 ) Vs,min = 51.5344 V
The actual stability voltageVs should be set to at least Vs,min. The actual stability voltage for the scheme can be then chosen:
Vs = 62 V (20 % Safety margin )
A higher value for the setting voltage Us is chosen in order to cater for all possible transient phenomena with a safety factor of about 1.2, a value of 65 V is selected.
The minimum knee point voltage of the CTs must be twice the relay setting voltage Vknee ≥ 2 * Vs
Vknee = 350 V
2 * Vs = 123.683 V Meets Requirement
CALCULATION OF CABLE BURDEN: Wire burden:
2 Rwire = k* lwire * Rcu75
0.1121 1.1213
CTs correctly dimensioned
3.0 RRELAY SETTING CALCULATION OF RUSAYL-9 PSS
The CT knee-point voltage of 350 V exceeds the selected stabilizing voltage of 62 V several times, so under in-zone fault condition the CTs will produce enough output to operate the relay.
Calculation of maximum sensitivity:
The higher is the sensitivity, the lower the value of the fault current that is detected by the relay. According to the actual stability voltage and considering that the relay has a variable a.c. current setting on the 1 A tap of 0.001 A to 1.6 A in 0.001 A steps, the maximum primary current sensitivity Ip can be obtained
IP = Ip/Is*[Is, min +n * Iknee*(Vs/Vknee)+Ivar]
where:
Ip : Maximum primary current sensitivity
Is,min : Minimum relay current setting ( 0.2 A ) Considered N : Number of CTs in parallel with relay ( 4 )
I knee : Mag. current Iknee at Uknee ( 0.03 A ) Vs : Actual stability voltage ( 61.84128033 V ) V knee : Knee point voltage of CT ( 350 V ) Ivar : Current in non-linear resistor at the relay circuit setting
voltage, calculated as follows:
Ivar = 0.52 * [ (√2 *Vs ) / C]^1/ᵦ
for the varistor consider C = 900 and β = 0.25 ( MEDC practice) Ivar = 0.05 mA
IP = 1200 * ( 0.200 + 0.04241 + 0.00005 )
IP = 290.942 A
The calculated current Ip corresponds to a sensitivity of 24.2451816 % of nominal primary current Ipn of CT. This corresponds to a sensitivity of 28.9758 % of nominal current of the object In_obj = 1.05 KA
Desired sensitivity calculation:
For a desired decreased sensitivity of 25 % of In_obj = 251.021856 A a corresponding relay current setting can be calculated:
Is = I p,des * (Isn/Ipn) - n * Iknee*(Vs/Vknee)-Ivar
where:
Is : secondary relay current setting to reach the desired sensitivity Ip,des : desired current sensitivity of object ( 251.021856 A )
Is = [ 0.20918 - 0.04241 - 0.000046] Is = 0.16673
Considering the setting range of the relay on the 1 A tap of 0.001 A to 1.6 A in 0.001 A steps the pickup current can be chosen: Is,set = 0.20 A
the relay setting Current Is= 0.20 A
Stabilizing Resistor Calculation (Rstab)
The stabilizing resistor Rstab to ensure protection stability is: Rstab = Vs / Is
Rstab = 62 / 0.20
Rstab = 309.206 Ω
309.2064016 Ω [ Available range is 0 - 1000 Ω]
Therefore Stabilising resistor Rstab shall be set as =
3.0 RRELAY SETTING CALCULATION OF RUSAYL-9 PSS
The stabilizing resistor Rstab can be chosen with a necessary minimum continuous power rating Pstab,cont of :
Pstab,cont ≥ ( Vs2 / Rstab )
Pstab,cont ≥ [ 3824.34 / 309.21 ]
Pstab,cont ≥ 12.3683 W
Moreover, Rstab must have a short time rating large enough to withstand the fault current levels before the fault is cleared. The time duration of 0.5 seconds can be typically considered (Pstab,0.5s) to take into account longer fault clearance times of back-up protection.
The rms voltage developed across the stabilizing resistor is decisive for the thermal stress of the stabilizing resistor. It is calculated according to formula:
V rms,f = 1.3 * 4√ ( V Knee 3 * Rstab * I k,Max ,int *(Isn/Ipn) )
where
I k,max,int: Max. symmetrical short-circuit current for internal faults = 8.683999 KA
V rms,f = V
The resulting short-time rating Pstab,0.5s equals to:
Pstab,0.5s ≥ ( Vrms2 /Rstab ) = 1692.90973 W
Check for the requirement of non-linear resistor (Metrosil)
If the peak voltage developed across the relay circuit under max. internal fault conditions exceeds 3000 V peak then a suitable non-linear resistor (Metrosil) should be connected across the relay and Stabilizing resistor, in order to protect the insulation of the CTs, relay and interconnecting leads.
The maximum fault voltage assuming no CT saturation shall be calculated using the below formula: RCT = CT Internal Resistance : 6 Ω
Rst ab = Stabilizing Resistor : 309.2064016 Ω
RL = One way CT lead resistance : 0.56064515 Ω
Ifmax = Maximum secondary external fault current : 8683.999349 A
Vk = Knee point voltage of the CT : 350 V
The max. fault voltage assuming no CT saturation, = Ifmax x (Isn/Ipn) x( RCT + 2 RL + Rstab) Vf = 7.23667 x ( 6 + 1.1213 + 309.206)
Vf = 2289.16 V
The peak Voltage, Vp = 2 x SQRT [ 2x Vk x ( Vf-Vk)]
Vp = 2 x SQRT [ 2 x 350 x ( 2289.16 - 350 )] Vp = 2330.16 V
As the Peak voltage is Less than 3000V hence Metrosil is not required For Safer Side Metrosil shall be considered
The type of metrosil required is chosen by its thermal rating as defined by the formula P = ( 4 / 3.14) x { If x Vk / CT ratio}
P = ( 4 / 3.14) x { 8684 x 350 / 1200 } P = 3224.9 J/S
P = 3.2249 KJ/S Select a metrosil with C=900 , β= 0.25
SUMMARY OF HIGH IMPEDANCE REF PROTECTION SETTINGS
Rstab = 309.206402 Ω
Is = 0.20 A
723.5043
3.0 RRELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 33 kV Transformer Bays) 7UT612 Make: SIEMENS
Location:
33 KV Transformer Relay Panels: =CB - 1H0, =CB - 2H0 and =CB - 3H0 Transformer data (Similar for all 33 kV Transformer Bays)
Rated Power(ONAN/ONAF) : 20 MVA
Transformer Cooling ONAF/ONAN
Rated Voltage: 33 / 11.5 KV
Rated Current (HV) : 349.91 A
Rated Current (LV) : 1004.09 A
Connection : Delta (HV), Star (LV)
Vector Group : Dyn11
Taps available @Transformer Primary: - 15% to 5% in steps of 1.67%
NO. of Taps w/o Center Tap 12.00
HV @ Highest tap position for +10% tap (Umax) : 34.65 KV
HV @ Lowest tap position for -10% tap (Umin): 28.05 KV
Transformer Percentage Impedance, Z % : 12.50 %
Impedance Tolerance Considered : ± 7.5 % [IEC tolerance]
Therefore Transformer Percentage Impedance, (Z%): 11.56 %
CT Ratios for Differential Protection (Similar for all 33 kV Transformer Bays)
HV 33 KV Transformer Feeder CT: 400 / 1 A Class: X
LV 11.5 KV Transformer Feeder CT: 1200 / 1 A Class: X
Relay Settings (Similar for all 33 kV Transformer Bays):
The individual reference currents for each winding of the transformer are calculated by 7UT612 on the basis of the set reference power and the set primary nominal voltages of the transformer.
= 20MVA/(√3x 33.00 KV) = 349.909 Amps 349.91 Amps = 20MVA/(√3x 11.5 KV) = 1004.09 Amps 1004.09 Amps Where: Reference Power
Reference Current of winding 1 and 2. Nominal voltage of winding 1 and 2 .
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.9 TRANSFORMER DIFFERENTIAL PROTECTION (87T) OF 33/11kV, 20MVA TRANSFORMER
INObj SIDE 1 = SN/(√3.VN SIDE 1)
INObj SIDE 1 =
INObj SIDE 2 = SN/(√3.VN SIDE 2)
INObj SIDE 2 = SN : INObj SIDE 1,2 : VN SIDE 1,2 : CT1 400/1 A CT2 1200/1 A SN = 20 MVA 33 KV 11 KV I1 I2
Differential Setting:
1. Idiff > 2. ldiff>>
3. SLOPE 1 and BASE POINT 1 4. SLOPE 2 and BASE POINT 2 5. Harmonic restraint
1. ldiff> : Differential current
Differential initial setting should be set above the steady-state magnetizing current of the transformer. Unbalance current checking in regarding with the tap changer position on highest and lowest tap positions.
CALCULATION OF AVRAGE VOLTAGE :
As per the relay manual ; If the transformer winding is regulated, not the actual rated voltage of the winding UNB is used, but rather the voltage which corresponds to the average current of the regulated range
Uaverage = 2/(1/Umin + 1/Umax) where,
Umax = maximum Voltage @ + 10 % Tap Umin = minimum Voltage @ -10 % Tap
Uavrg = 2/(1/Umin + 1/Umax)
Uavrg = 2 / ( 1 / 28.05 + 1 / 34.65 ) Uavrg = 31.00 KV
CALCULATION OF Idiff.> Tap Changer Regulation Effect:
Uavrg = 31.00 KV => IN,tap0= SN/Uavrg*SQRT(3) = 372.4524 A
Umax = 34.65 KV => IN,tap+= SN/Umax*SQRT(3) = 333.2469 A
Umax = 28.05 KV => IN,tap+= SN/Umax*SQRT(3) = 411.6579 A
Tap change regulation = (In,tap0 - In,tap+)/In,tap0
Tap change regulation = ( 372.4524 - 333.2469 ) / 372.4524
Tap change regulation = 10.53% (1)
Tap changer regulation Error:
INObj,tap0 = INObj1 = 372.45243 A ( IN,tap0 / CT1 ratio ) = ( 372.452 / 400 ) A INObj1 = 0.931131 A 1004.087 A ( remains Constant) ( INObj2 / CT2 ratio ) = ( 1004.09 / 1200 ) A INObj2 = 0.83674 A 0.83674 INObj
INObj2 @ the CT2 Secondary Side =
INObj2 @ the CT2 Secondary Side = 0.84
INObj2 =
INObj1 @ the CT1 Secondary Side = 0.931131068 3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.9 TRANSFORMER DIFFERENTIAL PROTECTION (87T) OF 33/11kV, 20MVA TRANSFORMER
Max. Full load Current of the Transformer @ Center Tap =
INObj1 @ the CT1 Secondary Side =
Max. Full load Current of the Transformer @ Max. Tap = 333.24691 A ( INObj,tap+ / CT1 ratio ) = ( 333.247 / 400 ) A INObj1 (+5%) = 0.833117 A 0.894737 INObj
Max. Full load Current of the Transformer @ Min. Tap = 411.65795 A
( INObj,tap- / CT1 ratio ) = ( 411.658 / 400 )
A
INObj1 (-15%) = 1.029145 A
1.105263 INObj
|INObj1(+5%) - INObj1|= 0.105263 INObj1
IDIFF = | 0.105263 INObj1 |
IDIFF = 0.10 INObj (2)
|INObj1(+5%) + INObj1|= 1.894737 INObj1
IRest = | 1.894737 INObj1 |
IRest = 1.76 INObj
|INObj1(-15%) - INObj1 |= 0.105263 INObj1
IDIFF = | 0.105263 INObj1 |
IDIFF = 0.098 INObj (3)
|INObj1(-15%) + INObj1|= 2.105263 INObj1
IRest = | 2.105263 INObj1 |
IRest = 1.96 INObj
From 1 ,2 and 3 ,the max. differential current due to Tap changer error = 0.10
Add to this other errors like CT error , CT Magnetizing and relay. Also, considering safety margin based on variations of above factors due to variation in system condition
Available setting: 0.05 to 2 x INObj (in steps of 0.01)
Hence the selected setting
Idiff > INObj = 0.2 IN/INObj
2. ldiff>> : High-current stage
This is a simple instantaneous unrestrained highest differential over current setting . It is not influenced by restraining current (triple slope characterstics), harmonic restraint, overfluxing restraint or saturation detector. Also,This setting is to be set just above the inrush current rms value so that blocking of the triple slope characteristic by second harmonic restraint or by saturation detector is removed.
Diff. Current @ Min. Tap IDIFF = Diff. Current @ Max. Tap IDIFF =
INObj1(+5%) @ the CT1 Secondary Side =
INObj1 (+5%)@ the CT1 Secondary Side = 0.833117272
INObj1 (+5%) =
INObj,tap- = INObj1 (- 15%) =
INObj1(-15%)@ the CT1 Secondary Side =
INObj1 (-15%)@ the CT1 Secondary Side = 1.029144865
INObj1 (-15%) =
Restraint Current @ Max. Tap IRest =
Restraint Current @ Min. Tap IRest =
INObj,tap+ = INObj1 (+ 5%) = 3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
CALCULATION OF HIGH SET TRIP :
short circuit MVA of the transformer = Transformer MVA ÷ %Z = 20.00 ÷ 12.50 short circuit MVA of the transformer = 160 MVA
Fault current as referred to secondary = 160 x 10^6 ÷ (SQRT(3)x 11.5 x 10^3) = 8033 A [ considered fault current for stability] Fault current as referred to 33 KV = 2799.274
High Set setting should be set higher than 1.3 x Tx through fault current 1.3 x Tx through fault current = 3639.06 Corresponding CT secondary Current = ( 3639 / 400 )
Corresponding CT secondary Current = 9.09764 INObj (4)
Normally the transformer inrush current may go from 8-12 times the rated current. Taking 12 times the rated current for calculation,
Maximum transformer inrush current = 12 x rated current
= 12 x 349.91 = 4199 Amps
Corresponding CT secondary Current = ( 4199 / 400 )
Corresponding CT secondary Current = 10.4973 INObj (5)
From 4 , 5 and as per manual the Available setting: 0.5 to 35 x INObj (in steps of 0.1) Hence the selected setting
Idiff >> INObj = 11 IN/INObj
3. SLOPE 1 and BASE POINT 1
This is the second section of the tripping characteristic covers the load current range, so that in this section we must reckon not only with the transformer magnetizing current, which appears as differential current, but also with diff. current that can be attributed to the position of the Tap changer of the voltage regulator.
Tap Range (Total) = 20% [ +5% and -15%] CT errors = 5% (Assumed)
Hence the Recommended Slope-1 setting = 25%
25% and BASE POINT 1 = 0 IN/INObj
4. SLOPE 2 and BASE POINT 2
This is the second knee point of the tripping characteristic,it is set to produce stabilization in the range of high currents which may lead to current transformer saturation.
A setting of 50% is selected for Slope-2 with relay default setting for BASE POINT 2.
Hence the selected setting
50% and BASE POINT 2 = 2.5 IN/INObj SLOPE 1 =
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.9 TRANSFORMER DIFFERENTIAL PROTECTION (87T) OF 33/11kV, 20MVA TRANSFORMER
5. Harmonic Restraint
Inrush Detector
This setting shall be "ENABLED"
When switching unloaded transformers, high magnetizing (inrush) currents may occur. These inrush currents produce differential quantities as they seem like single-end fed fault currents Hence this setting shall be enabled such that the relay is stable even during energizing the transformer
Cross Method of Measurement
Each phase is monitored and if the even harmonics present in any of the phase exceed the setting all the three phases are blocked. Hence Cross method of measurement is used for inrush detection.
2nd and 5th Harmonic Blocking Percentage (%)
The setting determines the level of harmonic (second and fourth) content in the relay operating current that will cause operation of the relay to be inhibited
As per the manufacture recommendation the setting of
15% is selected for 2nd harmonic blocking percentage setting 30% is selected for 5th harmonic blocking percentage setting
SUMMARY OF LOW IMPEDANCE TRANSFORMER DIFFERENTIAL PROTECTION SETTINGS
SN SIDE 1 , SN SIDE 2 = 20 MVA
UN-PRI SIDE 1 = 33 KV
UN-PRI SIDE 2 = 11.5 KV
CONNECTION S1, STARPNT SIDE 1 = D,Isolated CONNECTION S2, STARPNT SIDE 2 = Y, Earthed
VECTOR GRP S2 = 11
STRPNT->OBJ M1 , STRPNT->OBJ M2 = YES
IN-PRI CT M1 / IN-SEC CT M1 = 400 /1 A IN-PRI CT M2 / IN-SEC CT M2 = 1200/1 A
I-DIFF> = 0.2 I/InO
I-DIFF>> = 11 I/InO
SLOPE 1 = 25%
BASE POINT 1 = 0 I/InO
SLOPE 2 = 50%
BASE POINT 2 = 2.5 I/InO
2. HARMONIC = 15%
n. HARMONIC = 30%
3.9 TRANSFORMER DIFFERENTIAL PROTECTION (87T) OF 33/11kV, 20MVA TRANSFORMER 3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 33 kV Transformer Bays) 7SJ8021 Make: SIEMENS
Protection feature: Non Directional Phase Over Current and Earth Fault Protection Location:
33 KV Transformer Relay Panels: =CB -1H0, = CB - 2H0 and = CB - 3H0 Power Transformer data (Similar for all 33 kV Transformer Bays)
Rated Power: 20 MVA
Rated Voltage: 33 / 11.5 KV
Rated Current (HV) : 349.91 A
Connection : Delta (HV), Star (LV)
Vector Group : Dyn11
Transformer Percentage Impedance, Z % : 12.50 %
Impedance Tolerance Considered : ± 7.5 % [IEC tolerance]
Therefore Transformer Percentage Impedance, (Z%): 11.56 %
CT Ratios for 50, 51 & 51N Protection (Similar for all 33 kV Transformer Bays)
11 KV Aux. Transformer Feeders CT: 400 / 1 A Class: 5P20
The maximum transformer through-fault current calculation
short circuit MVA of the transformer = Transformer MVA ÷ %Z = 20.00 ÷ 11.56 short circuit MVA of the transformer = 172.973 MVA
Fault current as referred to secondary = 172.973 x 10^6 ÷ (SQRT(3)x 11.5 x 10^3) = 8684 A [ considered fault current for stability] Fault current as referred to 33 KV = 3026.242
Relay Settings (Similar for all 33 kV Transformer Bays)
Instantaneous Phase Over Current Protection (50)
symmetrical through fault current = 1.30 x Symmetrical fault current
= 1.30 x 3026.24 = 3934.11 A
Multiples of pickup = 3934.11 / 400 = 9.84 In Inrush current of the Transformer = 12x Primary FLC [Assumed]
= 12 x 349.91 = 4198.91 A
Multiples of pickup = 4198.91 / 400 = 10.50 In
Since transformer inrush current is greater than 1.3 x TX through fault current setting is selected to be greater than transformer inrush current.
Summary:
Selected Instantaneous Pick-up, (I>>) = 11.0 A
Time Delay, td = 0.0 Sec
Selected Tripping Characteristics = DMT
Non Directional Phase Over Current Protection (51)
Phase over current Pick-up = 110% of the Transformer full load current = ( 1.10 x 349.91 ) ÷ 400 = 0.96 A
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Selected Pick-up current setting, (I>) = 1.0 A ( Actual Pick-up current = 400 A )
Multiples of pickup current = 3026.24 / 400 = 7.56561 ˂ 20 Selected Tripping Characteristics = SI (IEC Curve)
33KV TX Incomer Operating Time required = Operating time of Incomer 11 KV + Zero Sec [Grading Margin] = 0.61 + 0.0
= 0.61 Sec Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.61 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.61 = 0.14 x TMS / [ ( 8 )^0.02 -1]
= 0.18
11 KV Side Standby Earth Fault Protection should be co-ordinate with the overcurrent protection (unbalance) on the transformer primary (33 KV) Delta side of the transformer , Because an earth fault on the secondary Side would appear on the Primary Side as 1/SQRT(3) P.u fault current in two phases
1PH fault Current at 11 KV side when one transformers in service = 8.64 KA 11 KV Standby Earth fault relay operating = 0.91 Sec
33 KV Current appearing on the winding = 8640 * 11/33/SQRT(3) = 1.66277 A
Multiples of pickup current = 1.66277 / 400 = 4.15692 ˂ 20 33 KV TX OC (51) Operating Time = 0.14 x 0.180.18 / [ ( 4.15692 )^0.02 -1]
= 0.88 Sec Hence required grading is achieved
Summary:
Selected Pick-up, (I>) = 1.0 A
Selected Tripping Characteristics = SI
Selected TMS = 0.18
Non Directional Earth Fault Protection (51N)
Ground fault currents are not transferred through delta-Wye transformer
1PH fault Current at 33 KV side when one Incomer in service = 1.48 KA Io Setting = 0.2 In
33KV TX Incomer Operating Time required = Operating time of Incomer 11 KV + Zero Sec [Grading Margin] Approx. Operating time = 0.61 Sec
Selected Pick-up current setting, (Io>) = 0.20 A ( Actual Pick-up current = 80 A )
Selected Tripping Characteristics = SI (IEC Curve)
Multiples of pickup current = 1480 / 80 = 18.5 ˂ 20 Operating time desired = 0.61 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.61 = 0.14 x TMS / [ ( 19 )^0.02 -1]
= 0.05
Summary:
Selected 51N Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
Instantaneous Setting = 6 A
TMS
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.10 NON DIRECTIONAL PHASE & EARTH FAULT PROTECTION(50,51 &51N)of 20MVA, 33/11 KV TRANSFORMER
Relay Type (Similar for all 33 kV Bus coupler Bays) 7SJ8021 Make: SIEMENS
Protection feature: Non Directional Phase Over Current and Earth Fault Protection Location: 33 KV Bus Coupler panels: =CB -1S0 and = CB - 2S0
CT Ratios for 51 & 51N Protection (Similar for all 33 kV Bus coupler Bays)
33 KV Bus Coupler CT: 1200 / 1 A Class: 5P20
Relay Settings (Similar for all 33 kV Bus coupler Bays)
Non Directional Phase Over Current Protection (51)
3PH fault Current at 33 KV side when 2 Incomers in service = 21.3 KA 3PH Fault Current that can be seen by 33 KV Bus Section CB = 10.13 KA 3PH fault Current at 33 KV side when one Incomer in service = 21.1 KA Fault Current that can be seen by 33 KV Bus Section CB = 21.1 A
Phase over current Pick-up = 100% of Full Load current for one transformer
= ( 1.00 x 350.00 ) ÷ 1200 = 0.29 A
Selected Pick-up current setting, (I>) = 0.29 A ( Actual Pick-up current = 350 A )
Multiples of pickup current = 10130 / 350 = 28.9429 > 20 Selected Tripping Characteristics = SI (IEC Curve)
33 KV B/C Relay operating time = 33 KV Incomer Relay Operating Time + Grading Margin [0.25] = 0.61 + 0.25 = 0.86 Sec
Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.86 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.86 = 0.14 x TMS / [ ( 20 )^0.02 -1]
= 0.43
Summary:
Selected Pick-up, (I>) = 0.29 A
Selected Tripping Characteristics = SI , Selected TMS = 0.43
Instantaneous Setting = Blocked (MDEC Practice)
Non Directional Earth Fault Protection (51N)
1PH fault Current at 33 KV side when 2 Incomers in service = 1.48 KA Fault Current that can be seen by 33 KV Bus Section CB = 0.696 KA
1PH fault Current at 33 KV side when one Incomer in service = 1.48 KA Fault Current that can be seen by 33 KV Bus Section CB = 1.48 KA
Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 1200.00 ) ÷ 1200 = 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 240 A )
Multiples of pickup current = 696 / 240 = 2.9 ˂ 20 33 KV B/C Relay operating time = 33 KV Incomer Relay Operating Time + Grading Margin [0.25]
= 0.61 + 0.25 = 0.86 Sec Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.86 Sec
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.11 NON DIRECTIONAL PHASE & EARTH FAULT PROTECTION (51 & 51N) OF 33 KV BUS COUPLER
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.86 = 0.14 x TMS / [ ( 3 )^0.02 -1]
= 0.13
Summary:
Selected Pick-up, (I>) = 0.20 A
Selected Tripping Characteristics = SI , Selected TMS = 0.13
Instantaneous Setting = Blocked (MDEC Practice)
TMS
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
Relay Type (Similar for all 33 kV RUSAYL Incomer Bays) 7SJ8041 Make: SIEMENS
Protection feature: Directional Phase Over Current and Earth Fault Protection Location: 33 KV UGC Incomer Relay Panels: =CB -1L5, = CB - 2L5 and = CB - 3L5 CT Ratios for 67 & 67N Protection (Similar for all 33 kV RUSAYL Incomer Bays)
33 Incomer Feeder CT: 400 / 1 A Class: 5P20
Relay Settings (Similar for all 33 kV RUSAYL Incomer Bays)
Directional Phase Over Current Protection (67)
3PH fault Current at 33 KV side when one Source in service = 21.1 KA Directional Phase over current Pick-up = 50% of the CT Ratio
= ( 0.50 x 400.00 ) ÷ 400 = 0.50 A
Selected Pick-up current setting, (I>) = 0.50 A ( Actual Pick-up current = 200 A )
Multiples of pickup current = 21100 / 200 = 105.5 > 20 Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.10 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.10 = 0.14 x TMS / [ ( 20 )^0.02 -1]
= 0.04
Summary:
Selected 67 Pick-up, (I>) = 0.5 A
Selected Tripping Characteristics = SI
Selected TMS = 0.050
Instantaneous Setting = Blocked (MDEC Practice)
Direction of operation = Forward ( Towards Feeder)
RCA Recommended = 45.0 ◦
Directional Earth Fault Protection (67N)
1PH fault Current at 33 KV side when one Source in service = 1.48 KA Directional Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 400.00 ) ÷ 400 = 0.20 A
Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 80 A )
Multiples of pickup current = 1480 / 80 = 18.5 ˂ 20 Selected Tripping Characteristics = SI (IEC Curve)
Operating time desired = 0.10 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
0.10 = 0.14 x TMS / [ ( 19 )^0.02 -1]
= 0.04
Summary:
Selected 67N Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.05
Direction of operation = Forward ( Towards Feeder)
RCA Recommended = - 45.0 ◦
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
3.12 DIR. AND NON DIR. PHASE & EARTH FAULT PROTECTION (67 /67N/51&51N) OF 33 KV RUSAYL FEEDER
TMS
Non Directional Phase Over Current Protection (51)
3PH fault Current at 33 KV side when one source in service = 21.1 KA Non Directional Phase over current Pick-up = 100% of the CT Ratio
= ( 1.00 x 400.00 ) ÷ 400 = 1.00 A
Selected Pick-up current setting, (I>) = 1.00 A ( Actual Pick-up current = 400 A )
Multiples of pickup current = 21100 / 400 = 52.75 > 20 Selected Tripping Characteristics = SI (IEC Curve)
33 KV Feeder EF Relay operating time = 33 KV BC Relay Operating Time + Grading Margin [0.25] Operating time desired = 1.11 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
1.11 = 0.14 x TMS / [ ( 20 )^0.02 -1]
= 0.49
Summary:
Selected 51 Pick-up, (I>) = 1.0 A
Selected Tripping Characteristics = SI
Selected TMS = 0.49
Instantaneous Setting = Blocked (MDEC Practice)
Non Directional Earth Fault Protection (51N)
1PH fault Current at 33 KV side when one source in service = 1.48 KA Non Directional Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 400.00 ) ÷ 400 = 0.20 A Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 80 A )
Multiples of pickup current = 1480 / 80 = 18.5 ˂ 20 Selected Tripping Characteristics = SI (IEC Curve)
33 KV Feeder EF Relay operating time = 33 KV BC Relay Operating Time + Grading Margin [0.25] Operating time desired = 1.11 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
1.11 = 0.14 x TMS / [ ( 19 )^0.02 -1]
= 0.48
Summary:
Selected 51N Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.48 Remote end setting
33 Incomer Feeder CT: 400 / 1 A Class: 5P20
Non Directional Phase Over Current Protection (51)
3PH fault Current at 33 KV side when one source in service = 21.1 KA Non Directional Phase over current Pick-up = 100% of the CT Ratio
= ( 1.00 x 400.00 ) ÷ 400 = 1.00 A Selected Pick-up current setting, (I>) = 1.00 A ( Actual Pick-up current = 400 A )
Multiples of pickup current = 21100 / 400 = 52.75 > 20 Selected Tripping Characteristics = SI (IEC Curve)
3.12 DIR. AND NON DIR. PHASE & EARTH FAULT PROTECTION (67 /67N/51&51N) OF 33 KV RUSAYL FEEDER
TMS
TMS
33 KV Remote Relay operating time = 33 KV Incomer Relay Operating Time + Grading Margin [0.25] = 1.11 + 0.25 = 1.36 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
1.36 = 0.14 x TMS / [ ( 20 )^0.02 -1]
= 0.60
Summary:
Selected 51 Pick-up, (I>) = 1.0 A
Selected Tripping Characteristics = SI
Selected TMS = 0.60
Instantaneous Setting = Blocked (MDEC Practice)
Non Directional Earth Fault Protection (51N)
1PH fault Current at 33 KV side when one Source in service = 1.48 KA Non Directional Earth Fault current Pick-up = 20% of the CT Ratio
= ( 0.20 x 400.00 ) ÷ 400 = 0.20 A Selected Pick-up current setting, (Ie>) = 0.20 A ( Actual Pick-up current = 80 A )
Multiples of pickup current = 1480 / 80 = 18.5 ˂ 20 Selected Tripping Characteristics = SI (IEC Curve)
33 KV Remote Relay operating time = 33 KV Incomer Relay Operating Time + Grading Margin [0.25] = 1.11 + 0.25 = 1.36 Sec
Relay operating time = TMS {0.14/((I/Is)^0.02-1)}
1.36 = 0.14 x TMS / [ ( 19 )^0.02 -1]
= 0.59
Summary:
Selected 51N Pick-up, (I>) = 0.2 A
Selected Tripping Characteristics = SI
Selected TMS = 0.59
TMS
TMS
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
SUMMARY OF LOW IMPEDANCE LINE DIFFERENTIAL PROTECTION SETTINGS
(For detailed relay settings, relay setting schedule shall be referred)
I-DIFF> = = 0.2 A
I-DIFF>>= = 1 A
Note:
Same CT Ratio and setting shall be adopted at 132/33 KV RUSAIL Grid S/S end.
3.0 RELAY SETTING CALCULATION OF RUSAYL-9 PSS
ANNEXURE – 6
Rusayl PSS / Incomer / 7SD522 V4.7
MLFB:
7SD52214CB999HJ0
Parameter set version:
V04.73.03
Device path: C:\Siemens\Digsi4\D4PROJ\Rusayl_P\P7DI\GV\SD\00000001
Author:
Creation date:
24.02.16 20:44:19
Last modified:
28.02.16 21:50:58
Operating mode:
Offline
Comment:
Setting values in:
Secondary value description
P R I N T - C O N T E N T S
...2
1 Device Configuration
...3
2 General Device Settings
...3
2.1 Group Device, General Settings
...4
3 Power System Data 1
...4
3.1 Group Power System Data 1; Group Transformers
...4
3.2 Group Power System Data 1; Group Power System
...4
3.3 Group Power System Data 1; Group Breaker
...5
3.4 Group Power System Data 1; Group CT Data
...6
4 Settings groups
...6
4.1 Group Power System Data 2; Group Local Line End
...6
4.2 Group Power System Data 2; Group Line Status
...6
4.3 Group 87 Differential Protection; Group General
...7
4.4 Group 87 Differential Protection; Group 87 Diff. Prot.
...7
4.5 Group 87 Differential Protection; Group Inrush
...7
4.6 Group Intertrip
...8
4.7 Group Measurement Supervision; Group Symmetry
...8
4.8 Group Measurement Supervision; Group Meas.Volt.Fail
...8
4.9 Group Measurement Supervision; Group I/U-Monitoring
...9
4.10 Group Measurement Supervision; Group VT mcb
...9
4.11 Group Measurement Supervision; Group Load Angle
...9
4.12 Group Protection Interface (Port D+E); Group General
...9
4.13 Group Protection Interface (Port D+E); Group Interface 1
...10
4.14 Group Differential Topology
1
Device Configuration
No. Function Scope
0103 Setting Group Change Option Disabled
0112 87 Differential protection Enabled
0115 21 Phase Distance Disabled
0116 21G Ground Distance Disabled
0119 Additional Threshold Iph>(Z1) Disabled
0120 68 Power Swing detection Disabled
0121 85-21 Pilot Protection for Distance prot Disabled
0122 DTT Direct Transfer Trip Disabled
0124 50HS Instantaneous SOTF Disabled
0125 Weak Infeed (Trip and/or Echo) Disabled
0126 50(N)/51(N) Backup OverCurrent Disabled
0131 50N/51N Ground OverCurrent Disabled
0132 85-67N Pilot Protection Gnd. OverCurrent Disabled
0138 Fault Locator Disabled
0139 50BF Breaker Failure Protection Disabled
0140 74TC Trip Circuit Supervision Disabled
0142 49 Thermal Overload Protection Disabled
0144 Voltage transformers connected
0145 Protection Interface 1 (Port D) Enabled
0146 Protection Interface 2 (Port E) Disabled
0160 Line sections for fault locator 1 Line Section
2
General Device Settings
2.1
Group Device, General Settings
Group Device, General Settings
No. Settings Value Group
0610 Fault Display on LED / LCD Display Targets on every Pickup All
0625A Minimum hold time of latched LEDs 0 min All
0640 Start image Default Display image 1 All
3
Power System Data 1
3.1
Group Power System Data 1; Group Transformers
Group Power System Data 1; Group Transformers
No. Settings Value Group
0201 CT Starpoint towards Line All
0203 Rated Primary Voltage 33.0 kV All
0204 Rated Secondary Voltage (Ph-Ph) 110 V All
0205 CT Rated Primary Current 400 A All
0206 CT Rated Secondary Current 1A All
0210 V4 voltage transformer is not connected All
0211 Matching ratio Phase-VT To Open-Delta-VT 1.73 All
0220 I4 current transformer is Neutral Current (of the protected line) All
0221 Matching ratio I4/Iph for CT's 1.000 All
3.2
Group Power System Data 1; Group Power System
Group Power System Data 1; Group Power System
No. Settings Value Group
0207 System Starpoint is Solid Grounded All
0208A 1-1/2 Circuit breaker arrangement NO All
0230 Rated Frequency 50 Hz All
3.3
Group Power System Data 1; Group Breaker
Group Power System Data 1; Group Breaker
No. Settings Value Group
0240A Minimum TRIP Command Duration 0.10 sec All
0241A Maximum Close Command Duration 1.00 sec All
0242 Dead Time for CB test-autoreclosure 0.10 sec All
3.4
Group Power System Data 1; Group CT Data
Group Power System Data 1; Group CT Data
No. Settings Value Group
0251 k_alf/k_alf nominal 1.00 All
0253 CT Error in % at k_alf/k_alf nominal 5.0 % All
0254 CT Error in % at k_alf nominal 15.0 % All
4
Settings groups
4.1
Group Power System Data 2; Group Local Line End
Group Power System Data 2; Group Local Line End
No. Settings Value Group
1103 Measurem:FullScaleVoltage(Equipm.rating) 33.0 kV A
1104 Measurem:FullScaleCurrent(Equipm.rating) 400 A A
1107 P,Q operational measured values sign not reversed A
4.2
Group Power System Data 2; Group Line Status
Group Power System Data 2; Group Line Status
No. Settings Value Group
1130A Pole Open Current Threshold 0.10 A A
1131A Pole Open Voltage Threshold 30 V A
1132A Seal-in Time after ALL closures 0.10 sec A
1133A minimal time for line open before SOTF 0.25 sec A
1134 Recognition of Line Closures with Current flow or Manual close BI A
1135 RESET of Trip Command with Pole Open Current Threshold only A
1136 open pole detector with measurement (V/I,trip, pickup, 52a A
1150A Seal-in Time after MANUAL closures 0.30 sec A
1151 Manual CLOSE COMMAND generation NO A
1152 MANUAL Closure Impulse after CONTROL <none> All
4.3
Group 87 Differential Protection; Group General
Group 87 Differential Protection; Group General
No. Settings Value Group
1201 State of differential protection ON A