Conventional
Introduction 3-7
Premier SX Conventional
Fire Alarm Panel 8
Premier Elite Conventional
Fire Alarm Panel 9
Premier Conventional Repeater Panel 10 Premier M Plus 8-24 Zone
Conventional Fire Alarm Panel 11
Premier M Plus Repeater Panel 12
Premier 48 M Plus 24-48 Zone
Conventional Fire Alarm Panel 13
Premier 48 M Plus Repeater Panel 14
Premier MX Conventional
Fire Alarm Panel 15
Fyreye Extra Conventional
Optical Smoke Detector 16
Fyreye Extra Conventional Rate of
Rise and Fixed Heat Detectors 17
Fyreye Extra Conventional
Opto-Heat Detector 18
Fyreye Conventional
Ultra-Violet Flame Detector 19
Fyreye Conventional Detector Bases 20
Zeta Remote LED Indicator 21
Fyreye 50 & 100m Reflective Beam
Smoke Detector 22-23
Fyreye 50 & 100m Auto-aligning Beam
Smoke Detector Systems 50 & 100m 24-25
Zeta UV/IR Optical Flame Detectors 26-27
Zeta Conventional Manual Call Points 28
Zeta Conventional
Weatherproof Call Point 29
Zeta Conventional Explosion Proof
Manual Call Point 30
Miditone Conventional
Electronic Sounder 31
Miditone Conventional Combined
Electronic Sounder & Flasher 32
Securetone Conventional
Electronic Sounder 33
Secure Light Xenon Flasher 34
Maxitone Conventional Sounder and
Combined Sounder & Flasher 35
Zeta Conventional Fire Alarm Bells 36
Zeta Flame Proof Siren 37
Zeta Flame Proof Gong Bell 38
Zeta Magnetic Door Holders 39
Zeta Duct Unit 40
Premier Power Pack EN 54-4 Power
Supply with LCD Screen 41
Zeta Alarm Systems, a trading name of GLT Exports Ltd, was founded
in 1985 and is a privately held UK manufacturer of Fire Alarm, Gas
Detection and Emergency Systems.
Our brand name is well known throughout the industry and is acclaimed in over forty countries worldwide. We are currently represented in the UK, Europe, Africa, the Middle East, Southern Asia & South America and this list continues to grow.
Complete System Supplier
To meet the requirements of our ever-changing market, we pride ourselves on being a complete system
supplier. This means our customers can rely on us for their entire system requirements.
One of the main advantages of using a complete system supplier, compared with a component supplier, is that system wide compatibility is assured and there is one point of contact.
Marketing our products as systems has played a vital role in our worldwide success.
The Future
Our continued inward investment and constant
endeavour to offer the very best products is recognised by our increased turnover and profit margin year-on-year. Our mission is to support our existing & future customers by providing them with the highest quality products, at the most competitive prices.
Customer Support & Product Warranty
We value our customers greatly and to ensure they have the best experience we have a dedicated support team who are able to assist with sales, technical or logistical queries.
Our products carry a full 24 month manufacturers’ guarantee from the date of purchase. Our network of authorised agents is fully trained on the use of our products and will provide a helpful & friendly service.
Research & Development
As with all electronic equipment there is an ever present drive to manufacture products that are increasingly effective whilst becoming more cost sensitive. To meet this objective we spend a significant percentage of our profits on the continued development of products, whether it be introducing new items, or improving existing ones. We have a team of engineers & designers all of whom have vast industry knowledge & experience.
As a manufacturer we always follow the market needs closely to evaluate how we should adapt our product range. This, combined with welcomed customer feedback, has proved to be a successful formula for meeting the current and future industry needs.
Statement Of Quality Policy
We maintain a Quality System, which conforms to BS EN ISO9001:2008. We are committed, where applicable, to manufacture in compliance with all appropriate legislation & regulatory requirements.
Alarm Systems BS5839
Risk Assessment
The ‘Fire precautions (Workplace) Regulations’ require any business employing five or more persons to hold a written ‘Fire Risk Assessment’ and ‘Emergency Plan’. This must be periodically reviewed.
The local fire brigade can enforce compliance, and close any building that does not meet this act. In the event of a fire in a building without a written ‘Fire Risk Assessment’, those responsible may face fines and imprisonment, and/or private litigation.
What the law requires you to do:
Complete a fire risk assessment for your work place (considering all employees, the public, disabled people and people with special needs).
Identify and record any significant findings or persons at risk.
Provide and maintain fire precautions. Provide information, instruction and training. Nominate persons responsible to implement your emergency plan.
Consult employees about the above nominations and your proposals to improve fire precautions.
Inform other employees who may have work places in the building about any significant risks which may affect their safety and co-operate with them to reduce/control these risks.
If you are not an employer, but control premises which contain more than one workplace, you are responsible for complying with fire regulations.
You must establish a suitable means of contacting the emergency services.
Your employees must co-operate to ensure the workplace is safe from fire and its effects.
Alarm Systems
Fire alarm systems are used to detect a
fire, and to signal a warning alarm to the
appropriate source.
In general, there are 3 types of system;
1. Manual Fire Alarm Systems – which rely on manual call points to signal an alarm
2. Life Protection Fire Alarm Systems – these are designed to protect the occupants of a building 3. Property Protection Fire Alarm Systems – these
are designed to protect buildings
The warning may be simply ringing fire alarm sirens, however if a building is likely to be unoccupied, it may be more appropriate to signal to a monitoring station, or at least send a message to the building owner via telephone.
If the total floor area is greater than
300m
2:
The maximum area for a zone is 2000m2
If a stairwell (or similar) extends beyond one floor it should be a separate zone.
If a zone covers more than one fire compartment then the zone boundaries should follow the compartment boundaries.
The search distance within the zone in order to ascertain the position of the fire should not exceed 60m. Remember that the use of Remote Indicator lamps may help to reduce the distance travelled.
If a building is divided between occupiers, zones must not be shared between them.
Information
60m Max.
Manual Call Points
A ‘Manual Call Point’ is a device which enables personnel to raise an alarm in the event of a fire incident by pressing a frangible element to activate the alarm system.
Manual Call Points should be installed at a height of 1.2m above floor level at easily accessible, conspicuous positions, on exit routes, at the entry floor landings of staircases and at all exits to the open air.
Manual Call Points should be spaced so that one may always be found within a maximum distance of 45m apart or 25m for disabled person.
1.2m - 1.4m
45m Max. or
25m Max. for disabled person
The following guide lines should be observed: If the total floor area of the building is less than 300m2 then the building needs only one zone,
regardless of the number of storeys.
In order to aid identification of the source of a possible fire, the protected building should be divided into ‘zones’. When deciding on a suitable zoning scheme for a building, consideration should be given to the size, any existing fire routines, escape routes, zone accessibility, and structural fire compartmentation.
Automatic Detectors
When deciding on the type of detector to be used in any area it is important to remember that the detector has to discriminate between a genuine fire and the normal conditions existing therein.
Smoke Detectors
In open spaces under flat horizontal ceilings, every point should lie within 7.5m of a smoke detector.
Smoke detection should be generally avoided in the following areas to avoid unwanted alarms. They should be protected by means of other detectors such as heat detectors.
Contamination in dusty areas may cause unwanted alarms and reduce the life of the detector.
Damp or humid conditions such as showers, bathrooms and external areas should be avoided as the water vapour may cause unwanted alarms and reduce the life of the detector.
Detectors should not be mounted where gases, vapours or fumes are present.
Detectors should never be used at low temperature where ice or condensation can affect detector sensitivity.
Kitchens, garages, welding shops and boiler houses should generally be avoided.
5.3m 10.6m 112m² (10.6m x 10.6m) 7.5m Room boundary
Heat Detectors General
In open spaces under flat horizontal ceilings, every point should lie within 5.3m of a heat detector.
Heat detectors are designed to either detect a rapid rise in temperature or to operate at a fixed temperature. Although they provide a slower response time than smoke detectors they do provide a method of protection for areas where smoke detectors cannot be used.
Heat detectors should not be used for the protection of life or where extensive property loss may be expected.
‘Rate of Rise’ Heat Detectors
‘Rate of Rise’ heat detectors respond to both rapid increases of temperature and to fixed top temperature.
‘Fixed Temperature’ Heat Detectors
Fixed temperature heat detectors are available with different temperature settings, and are normally installed in kitchens, boiler rooms, etc.
3.8m 7.5m 56.3m² (7.5m x 7.5m) 5.3m Room boundary
building with an even distribution, to generally provide a minimum sound level of 65dB(A) or 5dB(A) above any background noise which is likely to persist for more than 30 seconds.
Where the alarm may have to arouse sleeping persons e.g. Hotel bedrooms, nursing homes, etc, a minimum sound level of 75dB(A) is required, at the bed head with all the doors shut.
All fire alarm sounders in a building should produce the same sound, distinct from any other audible warning devices in the building.
Where fire alarm sounders are required in extremely noisy areas e.g. Machine shops, it may be necessary to install additional ‘Visual Indication Beacons’.
65dB(A)
@ 500Hz - 1000Hz @ 500Hz - 1000Hz+5dB(A) Background noise
75dB(A)
to rise towards the highest point (apex) of the roof, therefore detection should be placed in the apex. As the slope tends to reduce the delay before smoke or heat reaches the detectors, it is permissible to use a greater spacing between the detectors mounted there.
Limits of Ceiling Height
Small Apex = Standard Spacing Apex <150mm Heat Detector Apex <600mm Smoke Detector Apex >150mm Heat Detector Apex >600mm Smoke Detector Large Apex = Extended Spacing
Cabling
The operation of a Fire Alarm and Detection System’ depends on the cabling and connections between the components. It is essential that connection between Manual Call Points and Detectors function correctly when they are operated.
Cables within the system are required to function correctly for significant periods after being attacked by fire. These include the power supply cables to the control panel, the detection circuits and the fire alarm sounder circuits. Thus the cables chosen must be correctly rated to withstand these conditions.
Premier SX Conventional Fire Alarm Panel
(NPSX1, NPSX2, NPSX4, NPSX6, NPSX8)
The Premier SX control panel range is available
in 1, 2, 4, 6 and 8 zones, housed in a light grey
flame retardant ULV0 enclosure, designed to
meet modern architectural surroundings, with
a removable hinged door.
The Premier SX has been designed with ease of
installation in mind, in addition to the robust electronic design expected from Zeta Alarm Systems.
Model NPSX1 NPSX2 NPSX4 NPSX6 NPSX8
Part No. 37-050 37-051 37-052 37-053 37-054
Mains Voltage 230V AC +10% / -15% @ 50/60Hz
System Voltage 24V DC (nominal)
Zone Voltage 21V DC (nominal)
Sounder Alarm Output 2 x 400mA @ 24V DC (nominal)
Fault Relay Output 1 x relay SELV @ 1A maximum
Fire Relay Output 1 x relay SELV @ 1A maximum
Zone Capacity 32 devices per zone
Remote Sounder Activation Via N/O contact (class change)
Sounder Activation Delay 0-9 minutes in 1 minute increments
Zone End Of Line IN4002 Diode (cathode stripe to +)
Sounder End Of Line 10K resistor
Charger Voltage 28.4V @ 20°C (with battery disconnected)
Zone Short Circuit Protection 100mA
Charger Short Circuit Protection Battery voltage less than 20V
Enclosure Size 355 (l) x 275 (h) x 100 (d) mm
Weight 3.25kg (excluding batteries)
Features
LPCB Approved to EN54 parts 2 & 4 One man test facility
Disablement facility for zones & sounders Space for up to 7Ahr batteries
Sounder delay option (0 – 9 min) Panel can be flush mounted
73mm 100mm
Wall Mount Flush Mount
Premier Elite Conventional Fire Alarm Panel
(PE1, PE2, PE4, PE6, PE8)
The Premier Elite 1-8 zone fire alarm
panels are ideal for small to medium sized
installations. They meet all the requirements
of EN54 parts 2 & 4, and come in an
attractively styled enclosure.
The zonal output card gives a drive voltage to operate zonal alarm relays, or a hardwired repeater panel.
Model PE1 PE2 PE4 PE6 PE8
Part No. 37-040 37-041 37-042 37-043 37-044
Detection Zones 1 2 4 6 8
Mains Voltage 230V AC +10%/-15% @ 50/60Hz
System Voltage 24V DC (nominal) 29V DC (nominal)
Zone Voltage 22V DC (nominal)
Sounder Alarm Output 2 x 400mA @ 24V DC (nominal)
Fault Relay Output N/A 1 x relay SELV @ 1A maximum
Fire Relay Output 1 x relay SELV @ 1A maximum
Zone Capacity 20 Devices 32 Devices
Remote Sounder Activation N/A Via N/O Contacts
Sounder Activation Delay N/A 0-9 minutes in 1 minute increments
Zone End Of Line 10K resistor IN4002 Diode (cathode stripe to +)
Sounder End Of Line 10K resistor 10K resistor
Charger Voltage 27.6V DC (No Batt Connected) 28.4V @ 25°C (No Battery Connected)
Zone Short Circuit Protection N/A 100mA
Charger Short Circuit Protection N/A Batteries less than 21V
Operating Temperature 0°C to 50°C
Enclosure Size 355 x 275 x 100mm
Weight 2.5kg (excluding batteries) 3.25kg (excluding batteries)
Features
Fault relay (4, 6 & 8 zone only) Alarm relay
Current limited charger to prevent flat batteries drawing too much current (4, 6 & 8 zone only) Built in diode base compatibility (4, 6 & 8 zone
only)
Sounder delay facility (4, 6 & 8 zone only) Connection to optional add on zonal output card
(4, 6 & 8 zone only)
Zone disablement facility (4, 6 & 8 zone only) One man test facility (4, 6 & 8 zone only)
73mm 100mm
Wall Mount Flush Mount
Premier Conventional Repeater Panel
(PRE-REP)
Model PRE-REP
Part No. 37-045
Supply Voltage 20–35V DC
Supply Voltage 29V DC (nominal)
Connections A+ 0V GA CF- TN-Z1- to Z8-Supply +VE Supply –VE General Alarm Common Fault Tone (Buzzer Active) Zonal Alarm
Operating Temperature -0°C to 50°C
Enclosure Size 355 x 275 x 100mm
Weight 1kg
The Premier Repeater panel is a hard-wired
repeater panel for use with the Premier SX (all
sizes), and the Premier Elite (4-8 zone) panels.
It is display only (no controls) and indicates power, general fault, general fire & the zone in alarm. It also has an internal buzzer to indicate that it requires attention.
It comes supplied with an interface card to connect to the Premier SX and Premier Elite (4-8 zone) panels.
Features
Zonal indication for fire Common fault indication Surface or semi flush fixing
73mm 100mm
Wall Mount Flush Mount
Premier M Plus 8-24 Zone Conventional Fire
Alarm Panel
(PMP8, PMP16, PMP24)
The Premier M Plus control panels are designed
to fulfil the requirements of EN54 parts 2 & 4
as well as being easy to install, operate and
maintain.
Being of modular construction, the basic M Plus panel has 8 zone capacity, expandable to 16, 20 and 24 zones. The Premier M Plus is suitable for surface mounting or semi-flush fitting (with just the door protruding).
Model PMP8 PMP16 PMP24
Part No. 37-020 37-022 37-024
Detection Zones 8 16 24
Mains Voltage 230V AC +10% / -15% @ 50/60 Hz
System Voltage 24V DC (nominal)
Zone Voltage 21V DC
Sounder Alarm Output 4 x 150mA @ 24V DC
Fault Relay Output 1 x relay SELV @ 1A maximum
Fire Relay Output 1 x relay SELV @ 1A maximum
Zone Capacity 32 Devices
Remote Sounder Activation N/A
Sounder Activation Delay 0 – 9 minutes in 1 minute increments
Zone End Of Line IN4002 Diode
Sounder End Of Line 10KΩ Resistor
Charger Voltage 28.4V DC (batteries disconnected)
Zone Short Circuit Protection 100mA
Charger Short Circuit Protection Batteries less than 20V
Charger Size 3.0 Amp
Operating Temperature 0°C - 50°C
Enclosure Size 485 x 477.5 x 125mm
Features
4 Common sounder circuits (150mA each) Optional add-on zonal sounder circuits (50mA
Max.)
Serial repeater output
Auxiliary supply (29 Volts, 250mA) Zone & sounder disablement facility Sounder delay facility
Zonal to common timer (when fitted with zonal sounder boards)
Premier M Plus Repeater Panel
(PMP-REP, PMP-REP/M)
Model PMP-REP PMP-REP/M
Part No. 37-026 37-027
Functions Display & control Control only
Supply Voltage 20-30V DC
Max. Quantity Per System 1 5
Connections Serial Repeater A Serial Repeater B +24V DC 0V Operating Temperature 0°C to 50°C Enclosure Size 375 x 335 x 125mm Weight TBC
The Premier M Plus repeater is available in 2
versions – standard & multiple.
The standard repeater offers display & control functions, however it is limited to one per system. The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system).
A single repeater can be powered from the panels’ auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required.
Premier 48 M Plus 24-48 Zone Conventional
Fire Alarm Panel
(PMP48/24, PMP48/32, PMP48/40, PMP48/48)
The Premier 48 M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate & maintain.
Being of modular design, the basic panel has 24 zones built in and it can be expanded to 32, 40 & 48 zones. The construction of the panel is epoxy painted steel enclosure, with top & rear cable entries.
Model PMP48/24 PMP48/32 PMP48/40 PMP48/48
Part No. 37-030 37-032 37-034 37-036
Detection Zones 24 32 40 48
Supply Voltage 230V AC +10%/-15% @ 50/60 Hz
System Voltage 29V DC (nominal)
Zone Voltage 21V DC
Sounder Alarm Output 4 X 400mA @ 24V DC
Fault Relay Output 1 relay SELV @ 1A (normally energised)
Fire Relay Output 1 relay SELV @ 1A maximum
Other Connections Class Change Input (N/O Contact) / F.A.R.E. Output / Serial Repeater Output (4 Wire)
Zone Capacity Up to 32 devices
Remote Sounder Activation N/A
Sounder Activation Delay 0 to 9 minutes
Zone End Of Line 100μF capacitor
Sounder End Of Line 10K resistor
Charger Voltage 28.4V DC (Batteries disconnected)
Zone Short Circuit Protection 100mA
Charger Short Circuit Protection Batteries less than 20V
Charger Size 3 Amp
IP Rating IP43
Operating Temperature 0°C to 50°C
Enclosure Size 675 x 480 x 135mm
Weight 13kg
Features
4 common sounder circuits (400mA each) Optional add-on zonal sounder circuits (50mA
Max)
Serial repeater output
Auxiliary supply (29 Volts, 250mA) Zone & sounder disablement facility Sounder delay facility
Zonal to common timer (when fitted with zonal sounder boards)
Premier 48 M Plus Repeater Panel
(PMP48-REP, PMP48-REP/M)
Model PMP48-REP PMP48-REP/M
Part No. 37-037 37-038
Functions Display & control Control only
Supply Voltage 20–30V DC
Maximum Quantity Per System 1 5
Connections Serial Repeater A Serial Repeater A +24V DC 0V Operating Temperature 0°C to 50°C Enclosure Size 480 x 330 x 60mm Weight 4.8kg
The Premier 48 M Plus repeater is available in
2 versions – standard & multiple.
The standard repeater offers display & control functions, however is limited to one per system. The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system).
A single repeater can be powered from the panels’ auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required.
Premier MX Conventional Fire Alarm Panel
(MX-16 & MX-32)
The Premier MX ranges of panels are available
in either 16 or 32 zone versions and have been
approved by LPCB to EN54 parts 2 & 4.
The panels offer an extensive range of configuration options whilst remaining easy to install and configure.
Features
LPCB Approved to EN54 parts 2 & 4 Zonal one-man test facility
Latching or non-latching zones
Delayed or non delayed zone operation Standard or intrinsically safe zone mode
Short circuit to fire mode for compatibility with old detectors
Zonal or common alarm operation (requires output expansion PCBs)
Latching or non-latching fault modes Fault routing, fire routing & fire protection
relays can be programmed as 24V output (monitored) or volt free
Fault routing, fire routing & fire protection relays can have delayed operation in any configuration
The panel is available as flush mount on request Repeater panel option (up to 5 maximum per
panel)
Model MX-16 MX-32
Part No. 37-140 37-142
Detection Zones 16 32
Supply Voltage 230V AC +/- 10%
System Voltage 24V DC (Nominal)
Zone Voltage 24V DC (Nominal) Relay, SELV @ 1A
Zone End of Line 22uF, 35V Axial Capacitor
Sounder Output 4 X 1.0A @ 24V DC
Sounder EOL 3K9 Resistor
Aux DC Output 24V DC (Nominal) 1A
Repeater option Yes
Panel Inputs Remote Evacuation Remote Silence Alarms Remote Reset Class Change Panel Outputs Fault Routing Relay, SELV @ 1A Fire Routing Relay, SELV @ 1A
Fire Protection Relay, SELV @ 1A Disablement Active (Open Collector Output) Evacuation Active (Open Collector Output)
Buzzer Active (Open Collector Output) RS 485 Repeater Connection Operating Temperature -5°C to 40°C Size 325 x 370 x 126mm 400 x 441 x 131mm Weight 7.05kg 9.35kg
Fyreye Extra Conventional
Optical Smoke Detector
(FEOE2000)
The Fyreye Extra optical smoke detector uses
a pulsing IR LED & photodiode to detect IR
scatter caused by smoke entering the chamber.
The detector is particularly suitable for detecting optically dense smoke, involving materials such as soft furnishings, PVC, plastic, foam and all similar materials which produce small visible particles (0.5 to 10μm). The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.
Features
Designed to meet EN54 requirements Attractive design
Dual LEDs for 360° visibility
Lockable base to stop unauthorised removal Compatible with all Fyreye bases
Model FEOE2000
Part No. 80-022
Detector Class Optical Smoke
Design Standard EN54 part 7
Approval DIFT
Operating Voltage 9-33V DC
Quiescent Current 65μA
Alarm Current @ 24V DC 53mA MAX
Operating Temperature -10°C to +50°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH non-condensing
Alarm Condition 2.4% obscuration per metre
Coverage 100m2
IP Rating IP43
Start-up Time 10 Seconds
Size (with Base) 100 x 37mm (101 x 53mm)
Weight (with Base) 95g (153g)
37mm 100mm
Fyreye Extra Conventional Rate of Rise and
Fixed Heat Detectors
(FEHE2000 & FEFHE2000)
The Fyreye Rate of Rise heat detector
(FEHE2000) uses a thermistor arrangement
to sense a quick rise in temperature and also
a final threshold temperature of 57°C. The
Fyreye fixed heat detector (FEFHE2000) has a
single thermistor arrangement that gives an
alarm at a temperature of 90°C.
The detectors will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.
Model FEHE2000 FEFHE2000
Part No. 80-038 80-039
Detector Class Rate of Rise & Fixed Heat Detector Fixed Heat Only
Design Standard EN54 part 5
Approval DIFT
Operating Voltage 9-33V DC
Quiescent Current 40μA
Alarm Current @ 24V DC 34mA
Operating Temperature -10°C to +50°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH non-condensing
Alarm Condition Rate of rise or fixed heat trigger @ 57°C Fixed heat trigger @90°C
Coverage 50m²
IP Rating IP43
Start-up Time 10 Seconds
Size (with Base) 100 x 48 mm (101 x 64 mm)
Weight (with Base) 75g (133g)
Features
Designed to meet EN54 requirement
Lockable to base to stop unauthorised removal Remote LED output
Dual LEDs for 360° visibility Compatible with all Fyreye bases
48mm 100mm
Fyreye Extra Conventional
Opto-Heat Detector
(FEOH2000)
The Fyreye Extra opto-heat detector
incorporates both an optical chamber and
heat sensing element with advanced detection
technology & discrimination algorithms. This
multisensor is the perfect replacement for
ionisation detectors.
The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.
Features
Advanced electronic technology used to minimise false alarms
Designed to meet EN54 requirement Built-in 10 seconds alarm verification
Lockable to base to stop unauthorised removal Remote LED output
Dual LEDs for 360° visibility Compatible with all Fyreye bases
Model FEOH2000
Part No. 80-025
Detector Class Optical / Heat
Design Standard EN54
Approval DIFT
Operating Voltage 17-20V DC
Quiescent Current 100μA
Alarm Current @ 24V DC 70mA MAX
Operating Temperature -20°C to +60°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH non-condensing
Alarm Condition 3% obscuration per metre
Coverage 100m²
IP Rating IP43
Start-up Time 10 Seconds
Size (with Base) 100 x 50mm (100 x 66mm)
Weight (with Base) 95g (153g)
50mm 100mm
Fyreye Conventional
Ultra-Violet Flame Detector
(FEUV2000)
Model FEUV2000
Part No. 80-045
Detector Class Ultra Violet Flame Detector
Operating Voltage 12-28V DC
Quiescent Current 320μA
Alarm Current @ 24V DC 45-50mA
Operating Temperature 0°C to 45°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH non-condensing
Alarm Condition 10 seconds for 30mm flame @ 4 metres
Detection Angle 120°
UV Sensitivity 185-260nm
Size (with Base) 98 x 36mm (98 x 52mm)
Weight (with Base) 85g (143g)
The Fyreye ultra-violet flam detector is
particularly suited to applications where
flames can be expected to develop initially
rather than smoke. This is typically due to the
nature of the materials being protected for
instance camera film, computer, audio & video
tapes or disks.
The detector is for indoor use only and should not be exposed to spurious sources of UV, such as sparks, uncovered halogen lights, lightening, etc. as these may trigger a false alarm.
Due to the operational nature of flame detectors it is generally recommended to fit just one detector per zone.
Features
Low profile shape
The detector is solar blind and incorporates an electronic filter to eliminate unwanted alarms from naturally occurring phenomena
Fast response time
High immunity to electrical noise & RF interference UV EMISSION POINT VERTICAL VIEWING (top fig.) HORIZONTAL VIEWING (bottom fig.) 90° 90° 60° 60° 30° 30° 0° ANODE CATHODE 90° 90° 60° 60° 30° 30° 0° ANODE CATHODE
Fyreye Conventional Detector Bases
(FE-CB, FE-DB, FE-RB)
Model FE-CB FE-CB/S FE-CB/D FE-DB FE-DB/S FE-DB/D FE-RB
Part No. 80-050 80-050S 80-050D 80-052 80-052S 80-052D 80-054
Type Common base Diode base Relay base
Supply Voltage 9-33V DC 24V DC
Quiescent Current @ 24V 0μA
Alarm Current @ 24V 0mA 15mA
Relay Max Switching Power N/A 30W, 50VA
Relay Max Switching Power N/A 30W, 50VA
Relay Max Switching Current N/A 1A resistive
Relay Max Switching Voltage N/A 50V AC
Relay Minimum Capability N/A 10μA, 10mV
Relay Dropout Voltage N/A <6V
Operating Temperature -20°C to 90°C (non-condensing or icing)
Max. Wind Speed Not affected
Connections L1in, L1out, L2, -R & Earth
Size 100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm
Weight 48g 42g 61g 48.2g 42.2g 61.2g 171.4g
FE-RB FE-DB
FE-CB/D
FE-CB FE-CB/S
There are 3 types of base available for the Fyreye conventional range of detectors namely common base, diode base and relay base.
The Fyreye common base and diode base are available in standard, shallow or deep versions.
The common base is used on systems that do not need to keep line
integrity on head removal and also on addressable systems.
The diode base is used on systems that do need line integrity on head removal. This would include all conventional systems that mix detectors & call points on the same line (please note that the Premier M Plus panels will need an active end of line to work with diode bases). The relay base is mainly used on 12V security systems to signal detector operation to the panel. They can
also be used on 24V fire systems where the activation of a particular detector requires a signal to nearby equipment (for instance door holders).
Please note that a remote led indicator cannot be used with a relay base as the detector cannot sink enough current to operate both.
Zeta Remote LED Indicator
(ZT-RL)
Model ZT-RL
Part No. 48-023
Input Voltage 5 – 30vdc
Quiescent Current 0mA
Alarm Current 12mA
Operating Temperature 0°C - 50°C
Max Humidity 95% Relative Humidity Non-condensing
IP Rating IP41
Size 85 x 85 x 70mm
Weight 113g
Remote LEDs indicators are used in
installations where a detector going to alarm is
likely to occur out of sight (for instance behind
a locked door or in a ceiling void). In these
instances the indicator will then show the
location of the alarm.
Features
Twin LED’s
Fyreye 50 & 100m Reflective Beam
Smoke Detector
(ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV)
The Fyreye reflective beam detectors comprise
of a single unit incorporating an infrared
transmitter & receiver. The signal is reflected
by a prism and analysed for smoke presence.
Should a predetermined level be reached then
the detector will signal an alarm.
The system is designed to be mounted so that the beam will project between 0.3 and 0.6 metres below the ceiling and parallel to it. Lateral detection may be up to 7.5 metres either side of the beam.
Features
50 or 100 metre reflective beam smoke detector VdS approved
Complies fully to; BS 5839 part 5 EN54 part 12 Single compact housing
Horizontal or vertical mounting 12-24V DC operation
Low current consumption Latching or non latching alarm
Reflector targeting mode to ease set-up Microprocessor controlled
Automatic contamination compensation Selectable sensitivity Robust construction 126mm 120mm 140mm 210mm 70mm 100mm 100mm 9.5mm
Model ZT-50RZ ZT-100RZ ZT-50RV ZT-100RV
Part No. 47-050 47-051 47-050A 47-051A
Range 5-50m 50-100m 5-50m 50-100m
Number of Wires 2 4
Supply Voltage 10.2V to 30V DC
Quiescent Current <4mA
Operating Temperature -30°C to 55°C
Max Humidity 95% RH non-condensing
Max Wind Speed Not affected
Alarm Current 35mA (typical) <15mA
Fire Output 470 OHM resistor placed across zone internally Fire relay closing (relay contact is normally open)
Fault Output Schottky diode introduced between –VE in & -VE out Fault relay opening (relay contact is normally closed)
Power Down Reset <2 seconds >5 seconds
Beam Misalignment Tolerance
at 35% Detector ± 0.8° Prism ± 5.0°
Alarm Thresholds 2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
Optical Wavelength 880nm
Construction Flame Retardant ABS (Grey /Black)
IP Rating IP50
Size 130 x 210 x 120mm
Weight 0.75kg 0.7kg
Typical Applications
Beam detectors are generally used for two purposes; either to cover a wide-open space and/or in places where several regular smoke detectors would be aesthetically unacceptable.
Such places include; Shopping centres Heritage sites Churches or mosques Museums
Leisure centres
Open Plan offices Warehouses Factories Power stations and more The 2 wire models (ZT-50RZ & ZT-100RZ) are zone powered (please note these will only work on Premier SX & M Plus panels).
The 4 wire models (ZT-50RV & ZT-100RV) require an external 24V power supply and have a fire & fault relay output for wide compatibility.
Fyreye 50 & 100m Auto-aligning Beam Smoke
Detector Systems 50 & 100m
(ZT-5000R & ZT-5000R/100)
Features
Worldwide approvals including EN54:12 and UL268
Up to 4 detectors per system controller Each detector configurable from 8m to 100m Integral LASER
Auto-align fast automatic beam alignment Auto-optimise building movement and
contamination compensation Low level system controller
20mm cable gland knockouts on system controller
2-wire interface from system controller to detector
Additional System Components
ZT-5000R/DH - 47-072 - Fyreye Auto-aligning Single Beam Detector Head 50m
ZT-5000R/100/DH - 47-073 - Fyreye Auto-aligning Single Beam Detector Head 100m
ZT-5000R/LRK - 47-074 - Fyreye Auto-aligning Beam Detector Long Range Kit
The system consists of 2 parts; the beam detector itself and a low level control unit.
The system can be fully customised, according to local conditions and installation guidelines; alarm thresholds (sensitivity) and time to alarm/fault can be set from the low level system controller.
Each detector head is independently configurable from 8m through to 100m and has its own individual fire threshold. The system controller retains one set of fire and fault relays that is common to all detectors that are installed.
The system is supplied as either a 50 or 100 metre version with a single detector head. Additional heads and a long range kit (additional prisms to allow the detector head to reach 100m) are available separately.
Based on the proven technology of the
standard Fyreye reflective beam detectors, the
Fyreye auto-aligning beam detector has been
designed to help improve ease of installation.
The system is ideally suited for the protection of large areas where the use of traditional detection technologies would prove to be too difficult and/or costly to install.
The system combines an infrared transmitter and receiver in the same discrete unit and operates by projecting a well-defined beam to a reflective prism, which returns the beam to the receiver for analysis. Smoke in the beam path causes a drop in power, which, if below a pre-determined level, results in an alarm signal.
Model ZT-5000R ZT-5000R/100
Part No. 47-070 47-071
Range 50m 100m
Number of Wires 4
Supply Voltage 14-28V DC
Operating Current 8-12mA (low current mode with 1 detector) 48-52mA (high current mode with 1-4 detectors)
Operating Temperature -20°C to 55°C
Storage Temperature -40°C to 85°C
Max Humidity 85% RH non-condensing
Max Wind Speed Not affected
Alarm Current 35mA (typical)
Fire Output Volt free relay contact
Fault Output Volt free relay contact
Beam Misalignment Tolerance @ 35% Detector ± 0.8°, Prism ± 5.0°
Alarm Thresholds 2.50dB (25%), 3.74dB (35%) & 6.02dB (50%)
Optical Wavelengths 850nm
Construction Flame Retardant ABS (Grey / Black)
IP Rating IP54 Detector Size 135 x 135 x 135mm Detector Weight 0.5kg Controller Size 202 x 230 x 81mm Controller Weight 0.9kg 230mm 135mm
Zeta UV/IR Optical Flame Detectors
(VS-200P & VS-200EX)
Features
UV/IR spectrum for medium distance detection and high false alarm immunity
Compact & lighter design
User selectable sensitivity & functions
Multiple output options (relays for alarm & fault, 0-20mA (stepped) and RS-485/RS-232 spectrum monitoring)
ATEX approved by DNV for explosion-proof (VS-200EX UV/IR only)
CE certified
Typical
Applications
Non-hazardous (VS-200P) Parking buildings WarehouseWaste disposal facilities Culture centres
Hazardous (VS-200EX)
Offshore oil & gas installations Onshore oil & gas
installations and pipelines Petrochemical plants Chemical plants Shipbuilding facility Automotive industry Storage tank farms Power generation
facility
Petrochemical plants Painting industry Warehouse
Waste disposal facility Explosive & munitions
The VS-200P & VS-200EX UV/IR flame detectors
detect fuel & gas fires at long distances with
the highest immunity to false alarms. The
detectors can detect a 0.1m² gasoline pan fire
at 30m in less than 5 seconds.
Spectrum Response
(at highest sensitivity setting for 0.1m² pan fire)
Fuel n-Heptane Gasoline Diesel LPG* Distance 30m 30m 20m 20m Fuel Ethanol IPA Methanol Distance 20m 25m 20m *0.5m high / 0.2m width plume fire
Response Time Typically 5 seconds
Adjustable Time Delay Up to 20 seconds
Sensitivity Range 4 sensitivity ranges for 0.1m² n-Heptane pan fire from 15m to 65m
Field of View Horizontal 90°, Vertical 90°
Built-in-Test Manual (optionally Automatic)
Temperature Range Operating/Storage: -40°C to 75°C
Humidity Up to 95% non-condensing
Operating Voltage 24VDC norminal (17-31VDC)
Power Consumption Standby: max. 35mA, Alarm: max. 75mA
Cable Entry 1 x M20 (ISO)
Wiring AWG 16-26 (Str 1.5mm² to 0.13mm²)
Electromagnetic Compatibility EMI/RFI protected to EN61000 series
Electrical Interface The detector includes twelve(12) terminals with four(4) wiring options
Relays Alarm, Fault. SPST volt-free contacts rated 5A at 30VDC or 250VAC
0-20mA (stepped)
Non-isolated “Source” configuration Fault: Normal: Alarm: 0 +1mA 4mA±10% 20mA±10% Bit Fault: Warning: Resistance Loop: 2mA±10% 16mA±10% Max. 800Ω
Materials Polycarbonate Enclosure
Heavy duty copper free aluminium (less than 1%) with bright grey anodizing finish
Enclosure options - Stainless Steel 316L with electro polish finish
Mounting (Tilt Mount) Stainless Steel
Heavy duty copper free aluminium (less than 1%) with grey epoxy enamel finish
Options - Stainless Steel 316L with electro polish finish
Dimensions Detector: 80 x 82 X 86 mm Detector: 83(d) x 126(l) mm
Weight
Detector : 0.3kg (1.0kg with cable gland / 1m-length cable / Tilt Mount)
Detector (aluminium): 1.1 kg (1.4 kg with Ex cable gland / 1m-length
Detector (St. SUS316L): 2.0 kg
Tilt mount (aluminium/ St.): 0.3kg / 0.7kg
Water and Dust IP66 per EN60529 IP66 and IP67 per EN60529
EMI/RFI CE Marking ATEX Ex II 2 G
Exd IIC T6, -40°C to +75°C (DNV 09 ATEX 0000)
Performance EN54-10 (designed to meet) KFI (Korea)
Zeta Conventional Manual Call Points
(ZT-CP2, ZT-CP2/W, ZT-CP1 & ZT-CP1/W)
The Zeta conventional manual call point has
a modern design and has been approved by
BSI to EN54 part 11. It is a resettable call
point that signals an alarm with a yellow flag
entering the window area and a red alarm LED.
There are two versions available; the ZT-CP2 call points comes complete with a protective Perspex cover as well as a “snaplatch” catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a Type B call point). Alternatively the ZT-CP1 is supplied without the Perspex cover & “snaplatch” and is single action or Type A call point.
The recommended colour for these call points is red however white is also available to meet architectural requirements.
Model ZT-CP2 ZT-CP2/W ZT-CP1 ZT-CP1/W
Part No. 43-300 43-314 43-301 43-317
Type Type B Type A
Element Type Resettable
Alarm Activation Break “snaplatch”, lift Perspex cover, press element Press element
Colour Red White Red White
Input Voltage 9-33V DC
Quiescent Current 0mA
Alarm Current Typical 35mA (maximum 51mA)
Alarm Load 470 Ω resistor
Operating Temperature -20°C to 50°C
Max Humidity 95% RH non-condensing
IP Rating IP43
Size 111 x 100 x 67mm 105 x 100 x 58mm
Weight 198g 175g
Features
BSI approved to EN54 part 11 Attractive design
Zeta Conventional Weatherproof Call Point
(ZT-CP2/WP)
Model ZT-CP2/WP
Part No. 43-350
Type Type B
Element Type Resettable
Alarm Activation Break “snaplatch”, lift Perspex cover, press element
Colour Red
Input Voltage 9-33V DC
Quiescent Current 0mA
Alarm Current Typical 35mA (maximum 51mA)
Alarm Load 470 Ω resistor
Operating Temperature -20°C to 50°C
Max Humidity 95% RH non-condensing
IP Rating IP65
Size 87 x 87 x 70mm
Weight 198g
The Zeta conventional weatherproof manual
call point is an IP65 rated call point which
complies with EN54 part 11. It is resettable
and signals an alarm with a yellow flag
entering the window area and a red alarm LED.
The call point comes complete with a protective Perspex cover as well as a “snaplatch” catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a Type B call point).
Features
Complies with EN54 part 11 Attractive design
Resettable element Protective cover
Zeta Conventional Explosion Proof
Manual Call Point
(ZT-BGU/WP/R & ZT-BGU/WP)
The Zeta conventional explosion proof manual
call point is manufactured from aluminium
with a built-in push button activator. The call
point is finished with red anti-corrosive epoxy
powder coating with 2 x 20mm cable entries.
This unit is equipped with a stainless steel
hammer and chain.
Two models are available; the ZT-BGU/WP/R with 470Ω built-in resistor for connection to a standard fire alarm system or the ZTBGU/WP for mains connection.
Model ZT-BGU/WP/R ZT-BGU/WP
Part No. 43-300/WP 43-305/WP
Contact Rating 10 Amp
Voltage Rating 500V AV
Build-in Resistor 470Ω N/A
IP Rating IP65
Earthling 2No M6 eternal & 1No M5 internal
Size TBC Weight 1.5kg 2 Nos.0.75″ET B R E AK G L ASS IN CASE OF F I R E 185mm 105mm 4 Holes - ø7 Hammer Chain
Miditone Conventional Electronic Sounder
(ZMDD/8R & ZMDD/8W)
The Miditone sounder is a small, high output
conventional sounder which designed to meet
the requirements of EN54 part 3 and is CE
marked.
The sounder is a compact unit that fits a standard European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 95dB @ 1m with volume control.
It is available in red or white to meet architectural requirements.
Features
Complies to EN54 part 3 95dB @ 1m sound output 8 Tone patterns
Flush or surface fixing
Model ZMDD/8R ZMDD/8W
Part No. 42-040 42-040A
Sound Output See current consumption table
Colour Red White
Operating Voltage 9-30V DC
Quiescent Current 0mA
Alarm Current @ 24V See current consumption table
Operating Temperature -10°C to 50°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH Non Condensing
IP Rating IP43
Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm)
Weight (with Back Box) 100g (150g)
DIL Switch Settings (SW4 N/A)
1 2 3 Tone Description dB Level Current (mA)
Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 97 (+/- 2dB) 21
On Off Off Alternating 554 and 440Hz 0.5s Each 95 (+/- 2dB) 17
Off On Off Continuous 660Hz 96 (+/- 2dB) 22
On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 94 (+/- 2dB) 17
Off Off On Intermittent 970Hz @ 0.5s On/Off 93 (+/- 2dB) 8-24
On Off On Continuous 970Hz 95 (+/- 2dB) 25.5
Off On On Sweep Positive 800-970Hz 99 (+/- 2dB) 25
Miditone Conventional Combined Electronic
Sounder & Flasher
(ZMDF/8R, ZMDF/8A, ZMDF/8B, ZMDF/8C & ZMDF/8G)
The Miditone combined sounder & flasher is a small, high output conventional sounder & flasher which is designed to meet the requirements of EN54 part 3 and is CE marked.
The device is a compact unit that fits a standard European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 95dB @ 1m with volume control. This is an ideal solution to upgrade an existing sounder to a combined sounder & flasher.
It is available with either a red, amber, blue, clear or green lens to meet architectural requirements.
Model ZMDF/8R ZMDF/8A ZMDF/8B ZMDF/8C ZMDF/8G
Part No. 42-024 42-024A 42-024B 42-02C 42-024G
Sound Output See current consumption table
Lens Colour Red Amber Blue Clear Green
Operating Voltage 17-30V DC
Quiescent Current 0mA
Alarm Current @ 24V See current consumption table
Operating Temperature -10°C to 50°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH non condensing
IP Rating IP43
Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm)
Weight (with Back Box) 112g (162g)
Features
Complies to EN54 part 3 95dB @ 1m sound output 8 tone patterns
Flush or surface fixing
DIL Switch Settings (SW4 N/A)
1 2 3 Tone Description dB LEVEL CURRENT (mA)
Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 102 (+/- 2dB) 35
On Off Off Alternating 554 and 440Hz 0.5s Each 100 (+/- 2dB) 27
Off On Off Continuous 660Hz 100 (+/- 2dB) 33
On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 98 (+/- 2dB) 26
Off Off On Intermittent 970Hz @ 0.5s On/Off 93 (+/- 2dB) 13 - 35
On Off On Continuous 970Hz 103 (+/- 2dB) 37
Securetone Conventional Electronic Sounder
(ZST/8R & ZST/8W)
The Securetone sounder is designed to be
aesthetically pleasing and unobtrusive. It has
an elegant round design and fits to its supplied
mounting plate with a bayonet action to avoid
unsightly screws.
It has 8 selectable tones with a volume adjust screw to set the required sound level.
This product is designed to meet the requirements of EN54 part 3 and is CE marked.
Features
8 selectable tones Volume control
Model ZST/8R ZST/8W
Part No. 42-004 42-004A
Sound Output 100dBA @ 1 metre
Colour Red White
Operating Voltage 10-30V DC
Quiescent Current 0mA
Alarm Current @ 24V 35mA MAX
Operating Temperature -0°C to 50°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH Non Condensing
IP Rating IP43
Size (including Plate) 100 x 100 x 75mm (100 x 100 x 85mm)
Weight (including Plate) 230g (260g)
85mm
Secure Light Xenon Flasher
(ZTSL6/R & ZTSL6/A)
The Secure Light Xenon Flasher range is
designed to provide a visual warning at alarm
condition.
Both red and amber versions are available with the lenses constructed of high-Impact and heat resistant ACRYREX. The case is made of high-impact resistant ABS plastic.
Features
Available in Red & Amber Fits onto a standard outlet box
Model ZST/8R ZST/8W
Part No. 42-035 42-038
Colour Red Amber
Flash Energy 3 Watt
Flash Frequency 60 times per minute
Operating Voltage 20-30V DC
Quiescent Current 0mA
Alarm Current @ 24V 100mA MAX
Operating Temperature -30°C to 60°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH Non Condensing
IP Rating IP54
Size 97 x 100mm
Weight (including Plate) 231g
97mm
Maxitone Conventional Sounder and
Combined Sounder & Flasher
(ZMT/8R, ZMT/8W & ZMTF/8R)
The Maxitone sounder is an ideal alternative
to fire bells and for external use. It is housed
in an attractive horn comprises of flame
retardant ABS. Eight selectable tones and
volume control are featured to meet most
requirements.
The Maxitone is also available with transparent polycarbonate front which will provide both visual and audible alarm.
Model ZMT/8R ZMT/8W ZMTF/8R
Part No. 42-001 42-001A 42-032
Sound Output See current consumption table
Colour Red White Red
Operating Voltage 17-30V DC
Quiescent Current 0mA
Alarm Current @
24V See current consumption table
Operating
Temperature -20°C to 60°C
Minimum Continuous
Temperature 0°C
Maximum Humidity 95% RH non condensing
IP Rating IP65 Size 124 x 130 x 100mm Weight 357g 120mm 126mm 107mm
DIL SWITCH SETTINGS (SW4 N/A)
1 2 3 Tone Description dB Level Current (mA)
Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 101 (+/- 2dB) 27 On Off Off Alternating 554 and 440Hz 0.5s Each 98 (+/- 2dB) 20
Off On Off Continuous 660Hz 101 (+/- 2dB) 27
On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 98 (+/- 2dB) 19 Off Off On Intermittent 970Hz @ 0.5s On/Off 98 (+/- 2dB) 20
On Off On Continuous 970Hz 103 (+/- 2dB) 29.3
Off On On Sweep Positive 800-970Hz 103 (+/- 2dB) 38 On On On Alternating 800 and 970Hz @ 0.25s Each 102 (+/- 2dB) 35
Features
High output 8 selectable tones Volume control
Zeta Conventional Fire Alarm Bells
(ZTB6B, ZTB8B/230, ZTB8B & ZTB8B/WP)
The Zeta motorised fire alarm bells combine
styling and functional efficiency. They
incorporate a low power rotary centrifugal
mechanism, which gives a high sound output
with low current consumption at 24V dc.
The bells are available in 2 sizes; 6″ (152mm) and 8″ (203mm). These sizes suit a wide variety of installations. There is a 230V ac version of the 6″ bell, and a 24V dc Weatherproof version of the 8″ bell.
Features
Low current
Universally accepted fire evacuation signal
Model ZTB6B ZTB8B/230 ZTB8B ZTB8B/WP
Part No. 41-003 41-004 41-005 41-006
Supply Voltage 18-30V dc 200-250V AC 18-30V dc
Diameter 6″ (152mm) 8″ (203mm)
Quiescent Current 25mA 28mA
Nominal Output @ 1M 95dB(A) 97dB(A)
Dimensions 152 x 152 x 55mm 203 x 203 x 55mm Weight 860g 960g 1700g 1800g ZTB6B ZTB8B 152mm 55mm 55mm 152mm 203mm 203mm
Zeta Flame Proof Siren
(ZTSR/EXD24 & ZTSR/EXD230)
The Zeta flame proof siren is an explosion
proof siren available in either 24V or 230V
versions.
An intrinsically safe circuit is housed in the main chamber and it is duly wired up to terminal chamber through sealed bushes. The horn unit is placed on the main chamber cover and the output signals are taken through sealed coils. Neoprene ‘0’ rings are provided for the weather proof protection.
Model ZTSR/EXD24 ZTSR EXD230
Part No. 42-100/24 42-105/230
Type Of Protection Flame proof – Exd T6 IP 65 Area Classification Zone 1 & 2
Gas Groups Group I, II A, II B, II C
Apparatus
Standard IS - 2148
CMRI Certificate CMRI / TC / S / H388
Approvals CCE, DGFAS
Materials Cast Aluminium LM 6
Weight 5 Kg (approx.)
Size 170 (w) x 390 (h) x 240 (d) mm
IP Protection IP 65 to IS 13947 / 93
Finish Anti corrosive Epoxy – Powder Coated
Cable Entry 2 x ¾″ ET
Gasket Neoprene
Hardware Stainless Steel
Terminals 4 x 2.5 sq. mm (standard) 6 x 2.5 sq.
mm (for looping)
Voltage 24 V DC 230 V AC – 50 Hz
Output Current 600mA Peak. Galvanically Isolated
Power Rating 18 Watts
Sound Output 106 db 900 Hz On & Off alternatively at 1C/s
Earthing External: 2 Nos. - M6 Internal: 1 No. - M5
170mm 240mm
Zeta Flame Proof Gong Bell
(ZTB8B/EXD/24)
The Zeta flame proof gong bell is an explosion
proof gong bell with a terminal chamber.
A highly reliable electric circuit is housed inside to control the frequency of the gong operating spindle. The operating spindle and dish are made out of stainless steel thereby ensuring a long life.
The electric circuits are connected to terminals in the terminal chamber through nipple. The covers are provided with neoprene gaskets for weatherproof protection.
Model ZTB8B/EXD
Part No. 41-075
Type Of Protection Flame proof – Exd T6 IP 65
Area Classification Zone 1 & 2
Apparatus Standard IS - 2148
Material Cast Aluminium LM 6
Weight 3 Kg (approx.)
Size 225(w) x 285(h) x 160(d) mm
IP Protection IP 65 to IS 13947 / 93
Finish Anti Corrosive Epoxy – Powder coated
Cable Entry 1 X 3/4″ ET
Gasket Neoprene
Hardware Stainless steel
Voltage 24V DC or 110V / 230V AC – 50 Hz
Power Rating 12 Watt
Sound Output 112db
Terminals 4 x 4 mm²
Earthing External: 2 Nos – M6 Internal: 1 No. - M5
225mm 160mm
Zeta Magnetic Door Holders
(ZT-DR24 & ZT-DR240)
Model ZT-DR24 ZT-DR240
Part No. 50-001 50-002
Rated Voltage 24V DC 230V AC
Rated Current 65mA 6mA
Switch Through Aux Yes No
Needs Back EMF Diode Yes No
Holding Force 400 N
Size (Main Unit) 110 x 85 x 38mm
Dimensions (Keeper Plate) 55 x 55 x 50mm
Weight (Main Unit) 404g
Weight (Keeper Plate) 153g
The Zeta magnetic door holders are designed
to retain a fire door open against the force of
its own closing device. In the event of a fire,
the door holder magnet can be turned off by
the fire alarm, allowing the door to shut.
The manual release button is changeable from the base side to left or right. Cable entry is possible from rear side by means of enclosed exits from the base side, left or right.
An optional bracket is also available for floor or wall mounting (ZT-BR).
Features
Tested according to EN1155
Zeta Duct Unit
(ZT-DU, ZT-DU/12 & ZT-DU/230)
The Zeta duct unit allows air in a ventilation
duct to be monitored for smoke via a smoke
detector mounted externally in a sealed
chamber. The unit comes supplied with 2
sampling probes (one in & one out) which are
mounted through the duct in the centre of the
air flow.
There are 3 versions of the unit
available which are as follows;
ZT-DU – enclosure supplied with a Fyreye common base (FE-CB) allowing either a conventional or addressable Fyreye detector to be connected and wired as part a system.
ZT-DU/12 – enclosure c/w Fyeye base and relay board with form C relay outputs for alarm and for fault which requires 12V power supply.
ZT-DU/230 - enclosure c/w Fyeye base and relay board with form C relay outputs for alarm and for fault which requires 230V power supply.
Please note for reliable smoke detection the air speed in the duct must be at least 2.5m/s.
Features
Fire and Fault relays
Option for latching or non-latching Manual reset (latching option)
Model ZT-DU ZT-DU/12 ZT-DU/230
Part No. 48-011A 48-011B 48-011C
Supply Voltage N/A 12V 230V
Stand by current N/A 46mA (From 12v supply)
Alarm current N/A 86mA (From 12v supply)
Fault current N/A 26mA (From 12v supply)
Indications N/A Power, fault & alarm
Outputs N/A 1 x fault relay & 1 x alarm relay
Size 190 x 227 x 70mm
Weight 728g 989g
Direction of Airflow Duct Wall
Premier Power Pack EN 54-4 Power Supply
with LCD Screen
(PP-2/12, PP-5/17)
The Premier Power Pack Power supply uses an
innovative design that allows the engineer to
view system status through the on board LCD
screen. The screen can display several power
supply parameters, including output voltage,
and output current.
The power supply itself uses a 3 state charger which uses BOOST, FLOAT, and PULSE modes, depending on the state of the battery.
The PSU will disconnect the batteries under mains fail condition, when the batteries are fully discharged to prevent damage to the batteries.
The PSU will also monitor the battery for high internal resistance, and signal a fault if that condition is detected.
Screen Information
System Normal Screen
Z E T A A L A R M S Y S T E M S P R E M I E R P O W E R - P A C K R A T I N G 3 0 V D C 2 . 0 A S Y S T E M N O R M A L
Screen 1 - Main Information
M A I N S : O K B A T T S : O K V ( A ) = 2 9 . 5 V ( B ) = 2 9 . 5 C U R R E N T 0 . 1 2 A M P S
Screen 2 - Battery Info
B A T T E R Y I M P : 0 . 0 0 3 7 C H A R G E R V O L T : 2 5 . 4 5 V C H A R G E T Y P E : B O O S T B A T T E R Y S T A T E : G O O D Screen 3 - Misc. E A R T H : 2 . 4 4 7 V G O O D C H A R G E R C I R C U I T : O K B A D B A T T E R Y L V L X . X R
Screen 4 - Software Information
S o f t w a r e P S U : 2 V 0 0 S o f t w a r e L C D : 2 V 0 0 Model PP-2/12 PP-5/17 Part No. 46-300 46-305 Input Voltage 170-264V AC 47-63 Hz
Output Voltage 28V DC Nominal 28V DC Nominal
Power Rating 75W 150W
Efficiency 79% 86%
Total Power
Output 2.0 Amp 5.0 Amp
Power Supply
Outputs 2 Fused Outputs 2 Fused Outputs
Maximum Current
Per Output 0.625mA 2.0 Amps
Battery Charging
Current 750mA 920mA
Fault Relay Rating SELV 1A SELV 1A
IP Rating IP30 IP30
Batteries
(Z20201, Z20301, Z20651, Z21251 & Z21751)
As fire alarm systems are life safety systems,
they must have a battery backup to ensure full
functionality is maintained in the event of a
mains failure. All parts of the system (including
auxiliary power supplies) must have a battery
backup.
All the batteries stocked are 12V meaning that 2 batteries are required for a 24V systems. The standard capacities available are 2.2Ah, 3.2Ah, 7Ah, 12Ah and 17Ah.
It is important to choose the correct battery size for the system load to give the required standby time (usually 24 or 48 hours).
Model Z20201 Z20301 Z20651 Z21251 Z21751
Part No. 46-002 46-100 46-003 46-105 46-004
Type Sealed lead acid
Voltage 12V DC
Capacity 2.2 Ah 3.2 Ah 7.2 Ah 12 Ah 17 Ah
Size 178 x 34 x 65mm 132 x 59 x 65mm 151 x 65 x 98mm 150 x 98 x 103mm 178 x 75 x 168mm
Weight 1.0kg 1.25kg 2.5kg 3.5kg 5.8kg
Battery Calculation
To calculate the required battery backup, we use the
equation:-Battery Size (Standby time in Amp Hours) = 1.25 x [(TALM x IALM) + (TSBY x ISBY)] Where:
TALM = Maximum time in hours required for the alarm [½ hour is most common time]
IALM = Total Alarm Current in amps for all alarm devices connected to the alarm circuits
TSBY = Standby time in hours for the system after mains failure [normally 24, 48 or 72 hr]
ISBY = Quiescent current in amps of control panel in fault condition [because of mains failure] PLUS all loop devices
Tel: +44 (0) 1792 455 175 Fax: +44 (0) 1792 455 176 E-mail: info@zetaalarmsystems.com Detection House 72-78 Morfa Road Swansea SA1 2EN