• No results found

Conventional Fire Alarm Systems

N/A
N/A
Protected

Academic year: 2021

Share "Conventional Fire Alarm Systems"

Copied!
44
0
0

Loading.... (view fulltext now)

Full text

(1)

Conventional

(2)

Introduction 3-7

Premier SX Conventional

Fire Alarm Panel 8

Premier Elite Conventional

Fire Alarm Panel 9

Premier Conventional Repeater Panel 10 Premier M Plus 8-24 Zone

Conventional Fire Alarm Panel 11

Premier M Plus Repeater Panel 12

Premier 48 M Plus 24-48 Zone

Conventional Fire Alarm Panel 13

Premier 48 M Plus Repeater Panel 14

Premier MX Conventional

Fire Alarm Panel 15

Fyreye Extra Conventional

Optical Smoke Detector 16

Fyreye Extra Conventional Rate of

Rise and Fixed Heat Detectors 17

Fyreye Extra Conventional

Opto-Heat Detector 18

Fyreye Conventional

Ultra-Violet Flame Detector 19

Fyreye Conventional Detector Bases 20

Zeta Remote LED Indicator 21

Fyreye 50 & 100m Reflective Beam

Smoke Detector 22-23

Fyreye 50 & 100m Auto-aligning Beam

Smoke Detector Systems 50 & 100m 24-25

Zeta UV/IR Optical Flame Detectors 26-27

Zeta Conventional Manual Call Points 28

Zeta Conventional

Weatherproof Call Point 29

Zeta Conventional Explosion Proof

Manual Call Point 30

Miditone Conventional

Electronic Sounder 31

Miditone Conventional Combined

Electronic Sounder & Flasher 32

Securetone Conventional

Electronic Sounder 33

Secure Light Xenon Flasher 34

Maxitone Conventional Sounder and

Combined Sounder & Flasher 35

Zeta Conventional Fire Alarm Bells 36

Zeta Flame Proof Siren 37

Zeta Flame Proof Gong Bell 38

Zeta Magnetic Door Holders 39

Zeta Duct Unit 40

Premier Power Pack EN 54-4 Power

Supply with LCD Screen 41

(3)

Zeta Alarm Systems, a trading name of GLT Exports Ltd, was founded

in 1985 and is a privately held UK manufacturer of Fire Alarm, Gas

Detection and Emergency Systems.

Our brand name is well known throughout the industry and is acclaimed in over forty countries worldwide. We are currently represented in the UK, Europe, Africa, the Middle East, Southern Asia & South America and this list continues to grow.

Complete System Supplier

To meet the requirements of our ever-changing market, we pride ourselves on being a complete system

supplier. This means our customers can rely on us for their entire system requirements.

One of the main advantages of using a complete system supplier, compared with a component supplier, is that system wide compatibility is assured and there is one point of contact.

Marketing our products as systems has played a vital role in our worldwide success.

The Future

Our continued inward investment and constant

endeavour to offer the very best products is recognised by our increased turnover and profit margin year-on-year. Our mission is to support our existing & future customers by providing them with the highest quality products, at the most competitive prices.

Customer Support & Product Warranty

We value our customers greatly and to ensure they have the best experience we have a dedicated support team who are able to assist with sales, technical or logistical queries.

Our products carry a full 24 month manufacturers’ guarantee from the date of purchase. Our network of authorised agents is fully trained on the use of our products and will provide a helpful & friendly service.

Research & Development

As with all electronic equipment there is an ever present drive to manufacture products that are increasingly effective whilst becoming more cost sensitive. To meet this objective we spend a significant percentage of our profits on the continued development of products, whether it be introducing new items, or improving existing ones. We have a team of engineers & designers all of whom have vast industry knowledge & experience.

As a manufacturer we always follow the market needs closely to evaluate how we should adapt our product range. This, combined with welcomed customer feedback, has proved to be a successful formula for meeting the current and future industry needs.

Statement Of Quality Policy

We maintain a Quality System, which conforms to BS EN ISO9001:2008. We are committed, where applicable, to manufacture in compliance with all appropriate legislation & regulatory requirements.

(4)

Alarm Systems BS5839

Risk Assessment

The ‘Fire precautions (Workplace) Regulations’ require any business employing five or more persons to hold a written ‘Fire Risk Assessment’ and ‘Emergency Plan’. This must be periodically reviewed.

The local fire brigade can enforce compliance, and close any building that does not meet this act. In the event of a fire in a building without a written ‘Fire Risk Assessment’, those responsible may face fines and imprisonment, and/or private litigation.

What the law requires you to do:

Complete a fire risk assessment for your work place (considering all employees, the public, disabled people and people with special needs).

Identify and record any significant findings or persons at risk.

Provide and maintain fire precautions. Provide information, instruction and training. Nominate persons responsible to implement your emergency plan.

Consult employees about the above nominations and your proposals to improve fire precautions.

Inform other employees who may have work places in the building about any significant risks which may affect their safety and co-operate with them to reduce/control these risks.

If you are not an employer, but control premises which contain more than one workplace, you are responsible for complying with fire regulations.

You must establish a suitable means of contacting the emergency services.

Your employees must co-operate to ensure the workplace is safe from fire and its effects.

Alarm Systems

Fire alarm systems are used to detect a

fire, and to signal a warning alarm to the

appropriate source.

In general, there are 3 types of system;

1. Manual Fire Alarm Systems – which rely on manual call points to signal an alarm

2. Life Protection Fire Alarm Systems – these are designed to protect the occupants of a building 3. Property Protection Fire Alarm Systems – these

are designed to protect buildings

The warning may be simply ringing fire alarm sirens, however if a building is likely to be unoccupied, it may be more appropriate to signal to a monitoring station, or at least send a message to the building owner via telephone.

(5)

If the total floor area is greater than

300m

2

:

The maximum area for a zone is 2000m2

If a stairwell (or similar) extends beyond one floor it should be a separate zone.

If a zone covers more than one fire compartment then the zone boundaries should follow the compartment boundaries.

The search distance within the zone in order to ascertain the position of the fire should not exceed 60m. Remember that the use of Remote Indicator lamps may help to reduce the distance travelled.

If a building is divided between occupiers, zones must not be shared between them.

Information

60m Max.

Manual Call Points

A ‘Manual Call Point’ is a device which enables personnel to raise an alarm in the event of a fire incident by pressing a frangible element to activate the alarm system.

Manual Call Points should be installed at a height of 1.2m above floor level at easily accessible, conspicuous positions, on exit routes, at the entry floor landings of staircases and at all exits to the open air.

Manual Call Points should be spaced so that one may always be found within a maximum distance of 45m apart or 25m for disabled person.

1.2m - 1.4m

45m Max. or

25m Max. for disabled person

The following guide lines should be observed: If the total floor area of the building is less than 300m2 then the building needs only one zone,

regardless of the number of storeys.

In order to aid identification of the source of a possible fire, the protected building should be divided into ‘zones’. When deciding on a suitable zoning scheme for a building, consideration should be given to the size, any existing fire routines, escape routes, zone accessibility, and structural fire compartmentation.

(6)

Automatic Detectors

When deciding on the type of detector to be used in any area it is important to remember that the detector has to discriminate between a genuine fire and the normal conditions existing therein.

Smoke Detectors

In open spaces under flat horizontal ceilings, every point should lie within 7.5m of a smoke detector.

Smoke detection should be generally avoided in the following areas to avoid unwanted alarms. They should be protected by means of other detectors such as heat detectors.

Contamination in dusty areas may cause unwanted alarms and reduce the life of the detector.

Damp or humid conditions such as showers, bathrooms and external areas should be avoided as the water vapour may cause unwanted alarms and reduce the life of the detector.

Detectors should not be mounted where gases, vapours or fumes are present.

Detectors should never be used at low temperature where ice or condensation can affect detector sensitivity.

Kitchens, garages, welding shops and boiler houses should generally be avoided.

5.3m 10.6m 112m² (10.6m x 10.6m) 7.5m Room boundary

Heat Detectors General

In open spaces under flat horizontal ceilings, every point should lie within 5.3m of a heat detector.

Heat detectors are designed to either detect a rapid rise in temperature or to operate at a fixed temperature. Although they provide a slower response time than smoke detectors they do provide a method of protection for areas where smoke detectors cannot be used.

Heat detectors should not be used for the protection of life or where extensive property loss may be expected.

‘Rate of Rise’ Heat Detectors

‘Rate of Rise’ heat detectors respond to both rapid increases of temperature and to fixed top temperature.

‘Fixed Temperature’ Heat Detectors

Fixed temperature heat detectors are available with different temperature settings, and are normally installed in kitchens, boiler rooms, etc.

3.8m 7.5m 56.3m² (7.5m x 7.5m) 5.3m Room boundary

(7)

building with an even distribution, to generally provide a minimum sound level of 65dB(A) or 5dB(A) above any background noise which is likely to persist for more than 30 seconds.

Where the alarm may have to arouse sleeping persons e.g. Hotel bedrooms, nursing homes, etc, a minimum sound level of 75dB(A) is required, at the bed head with all the doors shut.

All fire alarm sounders in a building should produce the same sound, distinct from any other audible warning devices in the building.

Where fire alarm sounders are required in extremely noisy areas e.g. Machine shops, it may be necessary to install additional ‘Visual Indication Beacons’.

65dB(A)

@ 500Hz - 1000Hz @ 500Hz - 1000Hz+5dB(A) Background noise

75dB(A)

to rise towards the highest point (apex) of the roof, therefore detection should be placed in the apex. As the slope tends to reduce the delay before smoke or heat reaches the detectors, it is permissible to use a greater spacing between the detectors mounted there.

Limits of Ceiling Height

Small Apex = Standard Spacing Apex <150mm Heat Detector Apex <600mm Smoke Detector Apex >150mm Heat Detector Apex >600mm Smoke Detector Large Apex = Extended Spacing

Cabling

The operation of a Fire Alarm and Detection System’ depends on the cabling and connections between the components. It is essential that connection between Manual Call Points and Detectors function correctly when they are operated.

Cables within the system are required to function correctly for significant periods after being attacked by fire. These include the power supply cables to the control panel, the detection circuits and the fire alarm sounder circuits. Thus the cables chosen must be correctly rated to withstand these conditions.

(8)

Premier SX Conventional Fire Alarm Panel

(NPSX1, NPSX2, NPSX4, NPSX6, NPSX8)

The Premier SX control panel range is available

in 1, 2, 4, 6 and 8 zones, housed in a light grey

flame retardant ULV0 enclosure, designed to

meet modern architectural surroundings, with

a removable hinged door.

The Premier SX has been designed with ease of

installation in mind, in addition to the robust electronic design expected from Zeta Alarm Systems.

Model NPSX1 NPSX2 NPSX4 NPSX6 NPSX8

Part No. 37-050 37-051 37-052 37-053 37-054

Mains Voltage 230V AC +10% / -15% @ 50/60Hz

System Voltage 24V DC (nominal)

Zone Voltage 21V DC (nominal)

Sounder Alarm Output 2 x 400mA @ 24V DC (nominal)

Fault Relay Output 1 x relay SELV @ 1A maximum

Fire Relay Output 1 x relay SELV @ 1A maximum

Zone Capacity 32 devices per zone

Remote Sounder Activation Via N/O contact (class change)

Sounder Activation Delay 0-9 minutes in 1 minute increments

Zone End Of Line IN4002 Diode (cathode stripe to +)

Sounder End Of Line 10K resistor

Charger Voltage 28.4V @ 20°C (with battery disconnected)

Zone Short Circuit Protection 100mA

Charger Short Circuit Protection Battery voltage less than 20V

Enclosure Size 355 (l) x 275 (h) x 100 (d) mm

Weight 3.25kg (excluding batteries)

Features

LPCB Approved to EN54 parts 2 & 4 One man test facility

Disablement facility for zones & sounders Space for up to 7Ahr batteries

Sounder delay option (0 – 9 min) Panel can be flush mounted

73mm 100mm

Wall Mount Flush Mount

(9)

Premier Elite Conventional Fire Alarm Panel

(PE1, PE2, PE4, PE6, PE8)

The Premier Elite 1-8 zone fire alarm

panels are ideal for small to medium sized

installations. They meet all the requirements

of EN54 parts 2 & 4, and come in an

attractively styled enclosure.

The zonal output card gives a drive voltage to operate zonal alarm relays, or a hardwired repeater panel.

Model PE1 PE2 PE4 PE6 PE8

Part No. 37-040 37-041 37-042 37-043 37-044

Detection Zones 1 2 4 6 8

Mains Voltage 230V AC +10%/-15% @ 50/60Hz

System Voltage 24V DC (nominal) 29V DC (nominal)

Zone Voltage 22V DC (nominal)

Sounder Alarm Output 2 x 400mA @ 24V DC (nominal)

Fault Relay Output N/A 1 x relay SELV @ 1A maximum

Fire Relay Output 1 x relay SELV @ 1A maximum

Zone Capacity 20 Devices 32 Devices

Remote Sounder Activation N/A Via N/O Contacts

Sounder Activation Delay N/A 0-9 minutes in 1 minute increments

Zone End Of Line 10K resistor IN4002 Diode (cathode stripe to +)

Sounder End Of Line 10K resistor 10K resistor

Charger Voltage 27.6V DC (No Batt Connected) 28.4V @ 25°C (No Battery Connected)

Zone Short Circuit Protection N/A 100mA

Charger Short Circuit Protection N/A Batteries less than 21V

Operating Temperature 0°C to 50°C

Enclosure Size 355 x 275 x 100mm

Weight 2.5kg (excluding batteries) 3.25kg (excluding batteries)

Features

Fault relay (4, 6 & 8 zone only) Alarm relay

Current limited charger to prevent flat batteries drawing too much current (4, 6 & 8 zone only) Built in diode base compatibility (4, 6 & 8 zone

only)

Sounder delay facility (4, 6 & 8 zone only) Connection to optional add on zonal output card

(4, 6 & 8 zone only)

Zone disablement facility (4, 6 & 8 zone only) One man test facility (4, 6 & 8 zone only)

73mm 100mm

Wall Mount Flush Mount

(10)

Premier Conventional Repeater Panel

(PRE-REP)

Model PRE-REP

Part No. 37-045

Supply Voltage 20–35V DC

Supply Voltage 29V DC (nominal)

Connections A+ 0V GA CF- TN-Z1- to Z8-Supply +VE Supply –VE General Alarm Common Fault Tone (Buzzer Active) Zonal Alarm

Operating Temperature -0°C to 50°C

Enclosure Size 355 x 275 x 100mm

Weight 1kg

The Premier Repeater panel is a hard-wired

repeater panel for use with the Premier SX (all

sizes), and the Premier Elite (4-8 zone) panels.

It is display only (no controls) and indicates power, general fault, general fire & the zone in alarm. It also has an internal buzzer to indicate that it requires attention.

It comes supplied with an interface card to connect to the Premier SX and Premier Elite (4-8 zone) panels.

Features

Zonal indication for fire Common fault indication Surface or semi flush fixing

73mm 100mm

Wall Mount Flush Mount

(11)

Premier M Plus 8-24 Zone Conventional Fire

Alarm Panel

(PMP8, PMP16, PMP24)

The Premier M Plus control panels are designed

to fulfil the requirements of EN54 parts 2 & 4

as well as being easy to install, operate and

maintain.

Being of modular construction, the basic M Plus panel has 8 zone capacity, expandable to 16, 20 and 24 zones. The Premier M Plus is suitable for surface mounting or semi-flush fitting (with just the door protruding).

Model PMP8 PMP16 PMP24

Part No. 37-020 37-022 37-024

Detection Zones 8 16 24

Mains Voltage 230V AC +10% / -15% @ 50/60 Hz

System Voltage 24V DC (nominal)

Zone Voltage 21V DC

Sounder Alarm Output 4 x 150mA @ 24V DC

Fault Relay Output 1 x relay SELV @ 1A maximum

Fire Relay Output 1 x relay SELV @ 1A maximum

Zone Capacity 32 Devices

Remote Sounder Activation N/A

Sounder Activation Delay 0 – 9 minutes in 1 minute increments

Zone End Of Line IN4002 Diode

Sounder End Of Line 10KΩ Resistor

Charger Voltage 28.4V DC (batteries disconnected)

Zone Short Circuit Protection 100mA

Charger Short Circuit Protection Batteries less than 20V

Charger Size 3.0 Amp

Operating Temperature 0°C - 50°C

Enclosure Size 485 x 477.5 x 125mm

Features

4 Common sounder circuits (150mA each) Optional add-on zonal sounder circuits (50mA

Max.)

Serial repeater output

Auxiliary supply (29 Volts, 250mA) Zone & sounder disablement facility Sounder delay facility

Zonal to common timer (when fitted with zonal sounder boards)

(12)

Premier M Plus Repeater Panel

(PMP-REP, PMP-REP/M)

Model PMP-REP PMP-REP/M

Part No. 37-026 37-027

Functions Display & control Control only

Supply Voltage 20-30V DC

Max. Quantity Per System 1 5

Connections Serial Repeater A Serial Repeater B +24V DC 0V Operating Temperature 0°C to 50°C Enclosure Size 375 x 335 x 125mm Weight TBC

The Premier M Plus repeater is available in 2

versions – standard & multiple.

The standard repeater offers display & control functions, however it is limited to one per system. The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system).

A single repeater can be powered from the panels’ auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required.

(13)

Premier 48 M Plus 24-48 Zone Conventional

Fire Alarm Panel

(PMP48/24, PMP48/32, PMP48/40, PMP48/48)

The Premier 48 M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate & maintain.

Being of modular design, the basic panel has 24 zones built in and it can be expanded to 32, 40 & 48 zones. The construction of the panel is epoxy painted steel enclosure, with top & rear cable entries.

Model PMP48/24 PMP48/32 PMP48/40 PMP48/48

Part No. 37-030 37-032 37-034 37-036

Detection Zones 24 32 40 48

Supply Voltage 230V AC +10%/-15% @ 50/60 Hz

System Voltage 29V DC (nominal)

Zone Voltage 21V DC

Sounder Alarm Output 4 X 400mA @ 24V DC

Fault Relay Output 1 relay SELV @ 1A (normally energised)

Fire Relay Output 1 relay SELV @ 1A maximum

Other Connections Class Change Input (N/O Contact) / F.A.R.E. Output / Serial Repeater Output (4 Wire)

Zone Capacity Up to 32 devices

Remote Sounder Activation N/A

Sounder Activation Delay 0 to 9 minutes

Zone End Of Line 100μF capacitor

Sounder End Of Line 10K resistor

Charger Voltage 28.4V DC (Batteries disconnected)

Zone Short Circuit Protection 100mA

Charger Short Circuit Protection Batteries less than 20V

Charger Size 3 Amp

IP Rating IP43

Operating Temperature 0°C to 50°C

Enclosure Size 675 x 480 x 135mm

Weight 13kg

Features

4 common sounder circuits (400mA each) Optional add-on zonal sounder circuits (50mA

Max)

Serial repeater output

Auxiliary supply (29 Volts, 250mA) Zone & sounder disablement facility Sounder delay facility

Zonal to common timer (when fitted with zonal sounder boards)

(14)

Premier 48 M Plus Repeater Panel

(PMP48-REP, PMP48-REP/M)

Model PMP48-REP PMP48-REP/M

Part No. 37-037 37-038

Functions Display & control Control only

Supply Voltage 20–30V DC

Maximum Quantity Per System 1 5

Connections Serial Repeater A Serial Repeater A +24V DC 0V Operating Temperature 0°C to 50°C Enclosure Size 480 x 330 x 60mm Weight 4.8kg

The Premier 48 M Plus repeater is available in

2 versions – standard & multiple.

The standard repeater offers display & control functions, however is limited to one per system. The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system).

A single repeater can be powered from the panels’ auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required.

(15)

Premier MX Conventional Fire Alarm Panel

(MX-16 & MX-32)

The Premier MX ranges of panels are available

in either 16 or 32 zone versions and have been

approved by LPCB to EN54 parts 2 & 4.

The panels offer an extensive range of configuration options whilst remaining easy to install and configure.

Features

LPCB Approved to EN54 parts 2 & 4 Zonal one-man test facility

Latching or non-latching zones

Delayed or non delayed zone operation Standard or intrinsically safe zone mode

Short circuit to fire mode for compatibility with old detectors

Zonal or common alarm operation (requires output expansion PCBs)

Latching or non-latching fault modes Fault routing, fire routing & fire protection

relays can be programmed as 24V output (monitored) or volt free

Fault routing, fire routing & fire protection relays can have delayed operation in any configuration

The panel is available as flush mount on request Repeater panel option (up to 5 maximum per

panel)

Model MX-16 MX-32

Part No. 37-140 37-142

Detection Zones 16 32

Supply Voltage 230V AC +/- 10%

System Voltage 24V DC (Nominal)

Zone Voltage 24V DC (Nominal) Relay, SELV @ 1A

Zone End of Line 22uF, 35V Axial Capacitor

Sounder Output 4 X 1.0A @ 24V DC

Sounder EOL 3K9 Resistor

Aux DC Output 24V DC (Nominal) 1A

Repeater option Yes

Panel Inputs Remote Evacuation Remote Silence Alarms Remote Reset Class Change Panel Outputs Fault Routing Relay, SELV @ 1A Fire Routing Relay, SELV @ 1A

Fire Protection Relay, SELV @ 1A Disablement Active (Open Collector Output) Evacuation Active (Open Collector Output)

Buzzer Active (Open Collector Output) RS 485 Repeater Connection Operating Temperature -5°C to 40°C Size 325 x 370 x 126mm 400 x 441 x 131mm Weight 7.05kg 9.35kg

(16)

Fyreye Extra Conventional

Optical Smoke Detector

(FEOE2000)

The Fyreye Extra optical smoke detector uses

a pulsing IR LED & photodiode to detect IR

scatter caused by smoke entering the chamber.

The detector is particularly suitable for detecting optically dense smoke, involving materials such as soft furnishings, PVC, plastic, foam and all similar materials which produce small visible particles (0.5 to 10μm). The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.

The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.

Features

Designed to meet EN54 requirements Attractive design

Dual LEDs for 360° visibility

Lockable base to stop unauthorised removal Compatible with all Fyreye bases

Model FEOE2000

Part No. 80-022

Detector Class Optical Smoke

Design Standard EN54 part 7

Approval DIFT

Operating Voltage 9-33V DC

Quiescent Current 65μA

Alarm Current @ 24V DC 53mA MAX

Operating Temperature -10°C to +50°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH non-condensing

Alarm Condition 2.4% obscuration per metre

Coverage 100m2

IP Rating IP43

Start-up Time 10 Seconds

Size (with Base) 100 x 37mm (101 x 53mm)

Weight (with Base) 95g (153g)

37mm 100mm

(17)

Fyreye Extra Conventional Rate of Rise and

Fixed Heat Detectors

(FEHE2000 & FEFHE2000)

The Fyreye Rate of Rise heat detector

(FEHE2000) uses a thermistor arrangement

to sense a quick rise in temperature and also

a final threshold temperature of 57°C. The

Fyreye fixed heat detector (FEFHE2000) has a

single thermistor arrangement that gives an

alarm at a temperature of 90°C.

The detectors will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.

The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.

Model FEHE2000 FEFHE2000

Part No. 80-038 80-039

Detector Class Rate of Rise & Fixed Heat Detector Fixed Heat Only

Design Standard EN54 part 5

Approval DIFT

Operating Voltage 9-33V DC

Quiescent Current 40μA

Alarm Current @ 24V DC 34mA

Operating Temperature -10°C to +50°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH non-condensing

Alarm Condition Rate of rise or fixed heat trigger @ 57°C Fixed heat trigger @90°C

Coverage 50m²

IP Rating IP43

Start-up Time 10 Seconds

Size (with Base) 100 x 48 mm (101 x 64 mm)

Weight (with Base) 75g (133g)

Features

Designed to meet EN54 requirement

Lockable to base to stop unauthorised removal Remote LED output

Dual LEDs for 360° visibility Compatible with all Fyreye bases

48mm 100mm

(18)

Fyreye Extra Conventional

Opto-Heat Detector

(FEOH2000)

The Fyreye Extra opto-heat detector

incorporates both an optical chamber and

heat sensing element with advanced detection

technology & discrimination algorithms. This

multisensor is the perfect replacement for

ionisation detectors.

The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal.

The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition.

Features

Advanced electronic technology used to minimise false alarms

Designed to meet EN54 requirement Built-in 10 seconds alarm verification

Lockable to base to stop unauthorised removal Remote LED output

Dual LEDs for 360° visibility Compatible with all Fyreye bases

Model FEOH2000

Part No. 80-025

Detector Class Optical / Heat

Design Standard EN54

Approval DIFT

Operating Voltage 17-20V DC

Quiescent Current 100μA

Alarm Current @ 24V DC 70mA MAX

Operating Temperature -20°C to +60°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH non-condensing

Alarm Condition 3% obscuration per metre

Coverage 100m²

IP Rating IP43

Start-up Time 10 Seconds

Size (with Base) 100 x 50mm (100 x 66mm)

Weight (with Base) 95g (153g)

50mm 100mm

(19)

Fyreye Conventional

Ultra-Violet Flame Detector

(FEUV2000)

Model FEUV2000

Part No. 80-045

Detector Class Ultra Violet Flame Detector

Operating Voltage 12-28V DC

Quiescent Current 320μA

Alarm Current @ 24V DC 45-50mA

Operating Temperature 0°C to 45°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH non-condensing

Alarm Condition 10 seconds for 30mm flame @ 4 metres

Detection Angle 120°

UV Sensitivity 185-260nm

Size (with Base) 98 x 36mm (98 x 52mm)

Weight (with Base) 85g (143g)

The Fyreye ultra-violet flam detector is

particularly suited to applications where

flames can be expected to develop initially

rather than smoke. This is typically due to the

nature of the materials being protected for

instance camera film, computer, audio & video

tapes or disks.

The detector is for indoor use only and should not be exposed to spurious sources of UV, such as sparks, uncovered halogen lights, lightening, etc. as these may trigger a false alarm.

Due to the operational nature of flame detectors it is generally recommended to fit just one detector per zone.

Features

Low profile shape

The detector is solar blind and incorporates an electronic filter to eliminate unwanted alarms from naturally occurring phenomena

Fast response time

High immunity to electrical noise & RF interference UV EMISSION POINT VERTICAL VIEWING (top fig.) HORIZONTAL VIEWING (bottom fig.) 90° 90° 60° 60° 30° 30° 0° ANODE CATHODE 90° 90° 60° 60° 30° 30° 0° ANODE CATHODE

(20)

Fyreye Conventional Detector Bases

(FE-CB, FE-DB, FE-RB)

Model FE-CB FE-CB/S FE-CB/D FE-DB FE-DB/S FE-DB/D FE-RB

Part No. 80-050 80-050S 80-050D 80-052 80-052S 80-052D 80-054

Type Common base Diode base Relay base

Supply Voltage 9-33V DC 24V DC

Quiescent Current @ 24V 0μA

Alarm Current @ 24V 0mA 15mA

Relay Max Switching Power N/A 30W, 50VA

Relay Max Switching Power N/A 30W, 50VA

Relay Max Switching Current N/A 1A resistive

Relay Max Switching Voltage N/A 50V AC

Relay Minimum Capability N/A 10μA, 10mV

Relay Dropout Voltage N/A <6V

Operating Temperature -20°C to 90°C (non-condensing or icing)

Max. Wind Speed Not affected

Connections L1in, L1out, L2, -R & Earth

Size 100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm

Weight 48g 42g 61g 48.2g 42.2g 61.2g 171.4g

FE-RB FE-DB

FE-CB/D

FE-CB FE-CB/S

There are 3 types of base available for the Fyreye conventional range of detectors namely common base, diode base and relay base.

The Fyreye common base and diode base are available in standard, shallow or deep versions.

The common base is used on systems that do not need to keep line

integrity on head removal and also on addressable systems.

The diode base is used on systems that do need line integrity on head removal. This would include all conventional systems that mix detectors & call points on the same line (please note that the Premier M Plus panels will need an active end of line to work with diode bases). The relay base is mainly used on 12V security systems to signal detector operation to the panel. They can

also be used on 24V fire systems where the activation of a particular detector requires a signal to nearby equipment (for instance door holders).

Please note that a remote led indicator cannot be used with a relay base as the detector cannot sink enough current to operate both.

(21)

Zeta Remote LED Indicator

(ZT-RL)

Model ZT-RL

Part No. 48-023

Input Voltage 5 – 30vdc

Quiescent Current 0mA

Alarm Current 12mA

Operating Temperature 0°C - 50°C

Max Humidity 95% Relative Humidity Non-condensing

IP Rating IP41

Size 85 x 85 x 70mm

Weight 113g

Remote LEDs indicators are used in

installations where a detector going to alarm is

likely to occur out of sight (for instance behind

a locked door or in a ceiling void). In these

instances the indicator will then show the

location of the alarm.

Features

Twin LED’s

(22)

Fyreye 50 & 100m Reflective Beam

Smoke Detector

(ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV)

The Fyreye reflective beam detectors comprise

of a single unit incorporating an infrared

transmitter & receiver. The signal is reflected

by a prism and analysed for smoke presence.

Should a predetermined level be reached then

the detector will signal an alarm.

The system is designed to be mounted so that the beam will project between 0.3 and 0.6 metres below the ceiling and parallel to it. Lateral detection may be up to 7.5 metres either side of the beam.

Features

50 or 100 metre reflective beam smoke detector VdS approved

Complies fully to; BS 5839 part 5 EN54 part 12 Single compact housing

Horizontal or vertical mounting 12-24V DC operation

Low current consumption Latching or non latching alarm

Reflector targeting mode to ease set-up Microprocessor controlled

Automatic contamination compensation Selectable sensitivity Robust construction 126mm 120mm 140mm 210mm 70mm 100mm 100mm 9.5mm

(23)

Model ZT-50RZ ZT-100RZ ZT-50RV ZT-100RV

Part No. 47-050 47-051 47-050A 47-051A

Range 5-50m 50-100m 5-50m 50-100m

Number of Wires 2 4

Supply Voltage 10.2V to 30V DC

Quiescent Current <4mA

Operating Temperature -30°C to 55°C

Max Humidity 95% RH non-condensing

Max Wind Speed Not affected

Alarm Current 35mA (typical) <15mA

Fire Output 470 OHM resistor placed across zone internally Fire relay closing (relay contact is normally open)

Fault Output Schottky diode introduced between –VE in & -VE out Fault relay opening (relay contact is normally closed)

Power Down Reset <2 seconds >5 seconds

Beam Misalignment Tolerance

at 35% Detector ± 0.8° Prism ± 5.0°

Alarm Thresholds 2.50dB (25%), 3.74dB (35%), 6.02dB (50%)

Optical Wavelength 880nm

Construction Flame Retardant ABS (Grey /Black)

IP Rating IP50

Size 130 x 210 x 120mm

Weight 0.75kg 0.7kg

Typical Applications

Beam detectors are generally used for two purposes; either to cover a wide-open space and/or in places where several regular smoke detectors would be aesthetically unacceptable.

Such places include; Shopping centres Heritage sites Churches or mosques Museums

Leisure centres

Open Plan offices Warehouses Factories Power stations and more The 2 wire models (ZT-50RZ & ZT-100RZ) are zone powered (please note these will only work on Premier SX & M Plus panels).

The 4 wire models (ZT-50RV & ZT-100RV) require an external 24V power supply and have a fire & fault relay output for wide compatibility.

(24)

Fyreye 50 & 100m Auto-aligning Beam Smoke

Detector Systems 50 & 100m

(ZT-5000R & ZT-5000R/100)

Features

Worldwide approvals including EN54:12 and UL268

Up to 4 detectors per system controller Each detector configurable from 8m to 100m Integral LASER

Auto-align fast automatic beam alignment Auto-optimise building movement and

contamination compensation Low level system controller

20mm cable gland knockouts on system controller

2-wire interface from system controller to detector

Additional System Components

ZT-5000R/DH - 47-072 - Fyreye Auto-aligning Single Beam Detector Head 50m

ZT-5000R/100/DH - 47-073 - Fyreye Auto-aligning Single Beam Detector Head 100m

ZT-5000R/LRK - 47-074 - Fyreye Auto-aligning Beam Detector Long Range Kit

The system consists of 2 parts; the beam detector itself and a low level control unit.

The system can be fully customised, according to local conditions and installation guidelines; alarm thresholds (sensitivity) and time to alarm/fault can be set from the low level system controller.

Each detector head is independently configurable from 8m through to 100m and has its own individual fire threshold. The system controller retains one set of fire and fault relays that is common to all detectors that are installed.

The system is supplied as either a 50 or 100 metre version with a single detector head. Additional heads and a long range kit (additional prisms to allow the detector head to reach 100m) are available separately.

Based on the proven technology of the

standard Fyreye reflective beam detectors, the

Fyreye auto-aligning beam detector has been

designed to help improve ease of installation.

The system is ideally suited for the protection of large areas where the use of traditional detection technologies would prove to be too difficult and/or costly to install.

The system combines an infrared transmitter and receiver in the same discrete unit and operates by projecting a well-defined beam to a reflective prism, which returns the beam to the receiver for analysis. Smoke in the beam path causes a drop in power, which, if below a pre-determined level, results in an alarm signal.

(25)

Model ZT-5000R ZT-5000R/100

Part No. 47-070 47-071

Range 50m 100m

Number of Wires 4

Supply Voltage 14-28V DC

Operating Current 8-12mA (low current mode with 1 detector) 48-52mA (high current mode with 1-4 detectors)

Operating Temperature -20°C to 55°C

Storage Temperature -40°C to 85°C

Max Humidity 85% RH non-condensing

Max Wind Speed Not affected

Alarm Current 35mA (typical)

Fire Output Volt free relay contact

Fault Output Volt free relay contact

Beam Misalignment Tolerance @ 35% Detector ± 0.8°, Prism ± 5.0°

Alarm Thresholds 2.50dB (25%), 3.74dB (35%) & 6.02dB (50%)

Optical Wavelengths 850nm

Construction Flame Retardant ABS (Grey / Black)

IP Rating IP54 Detector Size 135 x 135 x 135mm Detector Weight 0.5kg Controller Size 202 x 230 x 81mm Controller Weight 0.9kg 230mm 135mm

(26)

Zeta UV/IR Optical Flame Detectors

(VS-200P & VS-200EX)

Features

UV/IR spectrum for medium distance detection and high false alarm immunity

Compact & lighter design

User selectable sensitivity & functions

Multiple output options (relays for alarm & fault, 0-20mA (stepped) and RS-485/RS-232 spectrum monitoring)

ATEX approved by DNV for explosion-proof (VS-200EX UV/IR only)

CE certified

Typical

Applications

Non-hazardous (VS-200P) Parking buildings Warehouse

Waste disposal facilities Culture centres

Hazardous (VS-200EX)

Offshore oil & gas installations Onshore oil & gas

installations and pipelines Petrochemical plants Chemical plants Shipbuilding facility Automotive industry Storage tank farms Power generation

facility

Petrochemical plants Painting industry Warehouse

Waste disposal facility Explosive & munitions

The VS-200P & VS-200EX UV/IR flame detectors

detect fuel & gas fires at long distances with

the highest immunity to false alarms. The

detectors can detect a 0.1m² gasoline pan fire

at 30m in less than 5 seconds.

(27)

Spectrum Response

(at highest sensitivity setting for 0.1m² pan fire)

Fuel n-Heptane Gasoline Diesel LPG* Distance 30m 30m 20m 20m Fuel Ethanol IPA Methanol Distance 20m 25m 20m *0.5m high / 0.2m width plume fire

Response Time Typically 5 seconds

Adjustable Time Delay Up to 20 seconds

Sensitivity Range 4 sensitivity ranges for 0.1m² n-Heptane pan fire from 15m to 65m

Field of View Horizontal 90°, Vertical 90°

Built-in-Test Manual (optionally Automatic)

Temperature Range Operating/Storage: -40°C to 75°C

Humidity Up to 95% non-condensing

Operating Voltage 24VDC norminal (17-31VDC)

Power Consumption Standby: max. 35mA, Alarm: max. 75mA

Cable Entry 1 x M20 (ISO)

Wiring AWG 16-26 (Str 1.5mm² to 0.13mm²)

Electromagnetic Compatibility EMI/RFI protected to EN61000 series

Electrical Interface The detector includes twelve(12) terminals with four(4) wiring options

Relays Alarm, Fault. SPST volt-free contacts rated 5A at 30VDC or 250VAC

0-20mA (stepped)

Non-isolated “Source” configuration Fault: Normal: Alarm: 0 +1mA 4mA±10% 20mA±10% Bit Fault: Warning: Resistance Loop: 2mA±10% 16mA±10% Max. 800Ω

Materials Polycarbonate Enclosure

Heavy duty copper free aluminium (less than 1%) with bright grey anodizing finish

Enclosure options - Stainless Steel 316L with electro polish finish

Mounting (Tilt Mount) Stainless Steel

Heavy duty copper free aluminium (less than 1%) with grey epoxy enamel finish

Options - Stainless Steel 316L with electro polish finish

Dimensions Detector: 80 x 82 X 86 mm Detector: 83(d) x 126(l) mm

Weight

Detector : 0.3kg (1.0kg with cable gland / 1m-length cable / Tilt Mount)

Detector (aluminium): 1.1 kg (1.4 kg with Ex cable gland / 1m-length

Detector (St. SUS316L): 2.0 kg

Tilt mount (aluminium/ St.): 0.3kg / 0.7kg

Water and Dust IP66 per EN60529 IP66 and IP67 per EN60529

EMI/RFI CE Marking ATEX Ex II 2 G

Exd IIC T6, -40°C to +75°C (DNV 09 ATEX 0000)

Performance EN54-10 (designed to meet) KFI (Korea)

(28)

Zeta Conventional Manual Call Points

(ZT-CP2, ZT-CP2/W, ZT-CP1 & ZT-CP1/W)

The Zeta conventional manual call point has

a modern design and has been approved by

BSI to EN54 part 11. It is a resettable call

point that signals an alarm with a yellow flag

entering the window area and a red alarm LED.

There are two versions available; the ZT-CP2 call points comes complete with a protective Perspex cover as well as a “snaplatch” catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a Type B call point). Alternatively the ZT-CP1 is supplied without the Perspex cover & “snaplatch” and is single action or Type A call point.

The recommended colour for these call points is red however white is also available to meet architectural requirements.

Model ZT-CP2 ZT-CP2/W ZT-CP1 ZT-CP1/W

Part No. 43-300 43-314 43-301 43-317

Type Type B Type A

Element Type Resettable

Alarm Activation Break “snaplatch”, lift Perspex cover, press element Press element

Colour Red White Red White

Input Voltage 9-33V DC

Quiescent Current 0mA

Alarm Current Typical 35mA (maximum 51mA)

Alarm Load 470 Ω resistor

Operating Temperature -20°C to 50°C

Max Humidity 95% RH non-condensing

IP Rating IP43

Size 111 x 100 x 67mm 105 x 100 x 58mm

Weight 198g 175g

Features

BSI approved to EN54 part 11 Attractive design

(29)

Zeta Conventional Weatherproof Call Point

(ZT-CP2/WP)

Model ZT-CP2/WP

Part No. 43-350

Type Type B

Element Type Resettable

Alarm Activation Break “snaplatch”, lift Perspex cover, press element

Colour Red

Input Voltage 9-33V DC

Quiescent Current 0mA

Alarm Current Typical 35mA (maximum 51mA)

Alarm Load 470 Ω resistor

Operating Temperature -20°C to 50°C

Max Humidity 95% RH non-condensing

IP Rating IP65

Size 87 x 87 x 70mm

Weight 198g

The Zeta conventional weatherproof manual

call point is an IP65 rated call point which

complies with EN54 part 11. It is resettable

and signals an alarm with a yellow flag

entering the window area and a red alarm LED.

The call point comes complete with a protective Perspex cover as well as a “snaplatch” catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a Type B call point).

Features

Complies with EN54 part 11 Attractive design

Resettable element Protective cover

(30)

Zeta Conventional Explosion Proof

Manual Call Point

(ZT-BGU/WP/R & ZT-BGU/WP)

The Zeta conventional explosion proof manual

call point is manufactured from aluminium

with a built-in push button activator. The call

point is finished with red anti-corrosive epoxy

powder coating with 2 x 20mm cable entries.

This unit is equipped with a stainless steel

hammer and chain.

Two models are available; the ZT-BGU/WP/R with 470Ω built-in resistor for connection to a standard fire alarm system or the ZTBGU/WP for mains connection.

Model ZT-BGU/WP/R ZT-BGU/WP

Part No. 43-300/WP 43-305/WP

Contact Rating 10 Amp

Voltage Rating 500V AV

Build-in Resistor 470Ω N/A

IP Rating IP65

Earthling 2No M6 eternal & 1No M5 internal

Size TBC Weight 1.5kg 2 Nos.0.75″ET B R E AK G L ASS IN CASE OF F I R E 185mm 105mm 4 Holes - ø7 Hammer Chain

(31)

Miditone Conventional Electronic Sounder

(ZMDD/8R & ZMDD/8W)

The Miditone sounder is a small, high output

conventional sounder which designed to meet

the requirements of EN54 part 3 and is CE

marked.

The sounder is a compact unit that fits a standard European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 95dB @ 1m with volume control.

It is available in red or white to meet architectural requirements.

Features

Complies to EN54 part 3 95dB @ 1m sound output 8 Tone patterns

Flush or surface fixing

Model ZMDD/8R ZMDD/8W

Part No. 42-040 42-040A

Sound Output See current consumption table

Colour Red White

Operating Voltage 9-30V DC

Quiescent Current 0mA

Alarm Current @ 24V See current consumption table

Operating Temperature -10°C to 50°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH Non Condensing

IP Rating IP43

Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm)

Weight (with Back Box) 100g (150g)

DIL Switch Settings (SW4 N/A)

1 2 3 Tone Description dB Level Current (mA)

Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 97 (+/- 2dB) 21

On Off Off Alternating 554 and 440Hz 0.5s Each 95 (+/- 2dB) 17

Off On Off Continuous 660Hz 96 (+/- 2dB) 22

On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 94 (+/- 2dB) 17

Off Off On Intermittent 970Hz @ 0.5s On/Off 93 (+/- 2dB) 8-24

On Off On Continuous 970Hz 95 (+/- 2dB) 25.5

Off On On Sweep Positive 800-970Hz 99 (+/- 2dB) 25

(32)

Miditone Conventional Combined Electronic

Sounder & Flasher

(ZMDF/8R, ZMDF/8A, ZMDF/8B, ZMDF/8C & ZMDF/8G)

The Miditone combined sounder & flasher is a small, high output conventional sounder & flasher which is designed to meet the requirements of EN54 part 3 and is CE marked.

The device is a compact unit that fits a standard European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 95dB @ 1m with volume control. This is an ideal solution to upgrade an existing sounder to a combined sounder & flasher.

It is available with either a red, amber, blue, clear or green lens to meet architectural requirements.

Model ZMDF/8R ZMDF/8A ZMDF/8B ZMDF/8C ZMDF/8G

Part No. 42-024 42-024A 42-024B 42-02C 42-024G

Sound Output See current consumption table

Lens Colour Red Amber Blue Clear Green

Operating Voltage 17-30V DC

Quiescent Current 0mA

Alarm Current @ 24V See current consumption table

Operating Temperature -10°C to 50°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH non condensing

IP Rating IP43

Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm)

Weight (with Back Box) 112g (162g)

Features

Complies to EN54 part 3 95dB @ 1m sound output 8 tone patterns

Flush or surface fixing

DIL Switch Settings (SW4 N/A)

1 2 3 Tone Description dB LEVEL CURRENT (mA)

Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 102 (+/- 2dB) 35

On Off Off Alternating 554 and 440Hz 0.5s Each 100 (+/- 2dB) 27

Off On Off Continuous 660Hz 100 (+/- 2dB) 33

On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 98 (+/- 2dB) 26

Off Off On Intermittent 970Hz @ 0.5s On/Off 93 (+/- 2dB) 13 - 35

On Off On Continuous 970Hz 103 (+/- 2dB) 37

(33)

Securetone Conventional Electronic Sounder

(ZST/8R & ZST/8W)

The Securetone sounder is designed to be

aesthetically pleasing and unobtrusive. It has

an elegant round design and fits to its supplied

mounting plate with a bayonet action to avoid

unsightly screws.

It has 8 selectable tones with a volume adjust screw to set the required sound level.

This product is designed to meet the requirements of EN54 part 3 and is CE marked.

Features

8 selectable tones Volume control

Model ZST/8R ZST/8W

Part No. 42-004 42-004A

Sound Output 100dBA @ 1 metre

Colour Red White

Operating Voltage 10-30V DC

Quiescent Current 0mA

Alarm Current @ 24V 35mA MAX

Operating Temperature -0°C to 50°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH Non Condensing

IP Rating IP43

Size (including Plate) 100 x 100 x 75mm (100 x 100 x 85mm)

Weight (including Plate) 230g (260g)

85mm

(34)

Secure Light Xenon Flasher

(ZTSL6/R & ZTSL6/A)

The Secure Light Xenon Flasher range is

designed to provide a visual warning at alarm

condition.

Both red and amber versions are available with the lenses constructed of high-Impact and heat resistant ACRYREX. The case is made of high-impact resistant ABS plastic.

Features

Available in Red & Amber Fits onto a standard outlet box

Model ZST/8R ZST/8W

Part No. 42-035 42-038

Colour Red Amber

Flash Energy 3 Watt

Flash Frequency 60 times per minute

Operating Voltage 20-30V DC

Quiescent Current 0mA

Alarm Current @ 24V 100mA MAX

Operating Temperature -30°C to 60°C

Minimum Continuous Temperature 0°C

Maximum Humidity 95% RH Non Condensing

IP Rating IP54

Size 97 x 100mm

Weight (including Plate) 231g

97mm

(35)

Maxitone Conventional Sounder and

Combined Sounder & Flasher

(ZMT/8R, ZMT/8W & ZMTF/8R)

The Maxitone sounder is an ideal alternative

to fire bells and for external use. It is housed

in an attractive horn comprises of flame

retardant ABS. Eight selectable tones and

volume control are featured to meet most

requirements.

The Maxitone is also available with transparent polycarbonate front which will provide both visual and audible alarm.

Model ZMT/8R ZMT/8W ZMTF/8R

Part No. 42-001 42-001A 42-032

Sound Output See current consumption table

Colour Red White Red

Operating Voltage 17-30V DC

Quiescent Current 0mA

Alarm Current @

24V See current consumption table

Operating

Temperature -20°C to 60°C

Minimum Continuous

Temperature 0°C

Maximum Humidity 95% RH non condensing

IP Rating IP65 Size 124 x 130 x 100mm Weight 357g 120mm 126mm 107mm

DIL SWITCH SETTINGS (SW4 N/A)

1 2 3 Tone Description dB Level Current (mA)

Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 101 (+/- 2dB) 27 On Off Off Alternating 554 and 440Hz 0.5s Each 98 (+/- 2dB) 20

Off On Off Continuous 660Hz 101 (+/- 2dB) 27

On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 98 (+/- 2dB) 19 Off Off On Intermittent 970Hz @ 0.5s On/Off 98 (+/- 2dB) 20

On Off On Continuous 970Hz 103 (+/- 2dB) 29.3

Off On On Sweep Positive 800-970Hz 103 (+/- 2dB) 38 On On On Alternating 800 and 970Hz @ 0.25s Each 102 (+/- 2dB) 35

Features

High output 8 selectable tones Volume control

(36)

Zeta Conventional Fire Alarm Bells

(ZTB6B, ZTB8B/230, ZTB8B & ZTB8B/WP)

The Zeta motorised fire alarm bells combine

styling and functional efficiency. They

incorporate a low power rotary centrifugal

mechanism, which gives a high sound output

with low current consumption at 24V dc.

The bells are available in 2 sizes; 6″ (152mm) and 8″ (203mm). These sizes suit a wide variety of installations. There is a 230V ac version of the 6″ bell, and a 24V dc Weatherproof version of the 8″ bell.

Features

Low current

Universally accepted fire evacuation signal

Model ZTB6B ZTB8B/230 ZTB8B ZTB8B/WP

Part No. 41-003 41-004 41-005 41-006

Supply Voltage 18-30V dc 200-250V AC 18-30V dc

Diameter 6″ (152mm) 8″ (203mm)

Quiescent Current 25mA 28mA

Nominal Output @ 1M 95dB(A) 97dB(A)

Dimensions 152 x 152 x 55mm 203 x 203 x 55mm Weight 860g 960g 1700g 1800g ZTB6B ZTB8B 152mm 55mm 55mm 152mm 203mm 203mm

(37)

Zeta Flame Proof Siren

(ZTSR/EXD24 & ZTSR/EXD230)

The Zeta flame proof siren is an explosion

proof siren available in either 24V or 230V

versions.

An intrinsically safe circuit is housed in the main chamber and it is duly wired up to terminal chamber through sealed bushes. The horn unit is placed on the main chamber cover and the output signals are taken through sealed coils. Neoprene ‘0’ rings are provided for the weather proof protection.

Model ZTSR/EXD24 ZTSR EXD230

Part No. 42-100/24 42-105/230

Type Of Protection Flame proof – Exd T6 IP 65 Area Classification Zone 1 & 2

Gas Groups Group I, II A, II B, II C

Apparatus

Standard IS - 2148

CMRI Certificate CMRI / TC / S / H388

Approvals CCE, DGFAS

Materials Cast Aluminium LM 6

Weight 5 Kg (approx.)

Size 170 (w) x 390 (h) x 240 (d) mm

IP Protection IP 65 to IS 13947 / 93

Finish Anti corrosive Epoxy – Powder Coated

Cable Entry 2 x ¾″ ET

Gasket Neoprene

Hardware Stainless Steel

Terminals 4 x 2.5 sq. mm (standard) 6 x 2.5 sq.

mm (for looping)

Voltage 24 V DC 230 V AC – 50 Hz

Output Current 600mA Peak. Galvanically Isolated

Power Rating 18 Watts

Sound Output 106 db 900 Hz On & Off alternatively at 1C/s

Earthing External: 2 Nos. - M6 Internal: 1 No. - M5

170mm 240mm

(38)

Zeta Flame Proof Gong Bell

(ZTB8B/EXD/24)

The Zeta flame proof gong bell is an explosion

proof gong bell with a terminal chamber.

A highly reliable electric circuit is housed inside to control the frequency of the gong operating spindle. The operating spindle and dish are made out of stainless steel thereby ensuring a long life.

The electric circuits are connected to terminals in the terminal chamber through nipple. The covers are provided with neoprene gaskets for weatherproof protection.

Model ZTB8B/EXD

Part No. 41-075

Type Of Protection Flame proof – Exd T6 IP 65

Area Classification Zone 1 & 2

Apparatus Standard IS - 2148

Material Cast Aluminium LM 6

Weight 3 Kg (approx.)

Size 225(w) x 285(h) x 160(d) mm

IP Protection IP 65 to IS 13947 / 93

Finish Anti Corrosive Epoxy – Powder coated

Cable Entry 1 X 3/4″ ET

Gasket Neoprene

Hardware Stainless steel

Voltage 24V DC or 110V / 230V AC – 50 Hz

Power Rating 12 Watt

Sound Output 112db

Terminals 4 x 4 mm²

Earthing External: 2 Nos – M6 Internal: 1 No. - M5

225mm 160mm

(39)

Zeta Magnetic Door Holders

(ZT-DR24 & ZT-DR240)

Model ZT-DR24 ZT-DR240

Part No. 50-001 50-002

Rated Voltage 24V DC 230V AC

Rated Current 65mA 6mA

Switch Through Aux Yes No

Needs Back EMF Diode Yes No

Holding Force 400 N

Size (Main Unit) 110 x 85 x 38mm

Dimensions (Keeper Plate) 55 x 55 x 50mm

Weight (Main Unit) 404g

Weight (Keeper Plate) 153g

The Zeta magnetic door holders are designed

to retain a fire door open against the force of

its own closing device. In the event of a fire,

the door holder magnet can be turned off by

the fire alarm, allowing the door to shut.

The manual release button is changeable from the base side to left or right. Cable entry is possible from rear side by means of enclosed exits from the base side, left or right.

An optional bracket is also available for floor or wall mounting (ZT-BR).

Features

Tested according to EN1155

(40)

Zeta Duct Unit

(ZT-DU, ZT-DU/12 & ZT-DU/230)

The Zeta duct unit allows air in a ventilation

duct to be monitored for smoke via a smoke

detector mounted externally in a sealed

chamber. The unit comes supplied with 2

sampling probes (one in & one out) which are

mounted through the duct in the centre of the

air flow.

There are 3 versions of the unit

available which are as follows;

ZT-DU – enclosure supplied with a Fyreye common base (FE-CB) allowing either a conventional or addressable Fyreye detector to be connected and wired as part a system.

ZT-DU/12 – enclosure c/w Fyeye base and relay board with form C relay outputs for alarm and for fault which requires 12V power supply.

ZT-DU/230 - enclosure c/w Fyeye base and relay board with form C relay outputs for alarm and for fault which requires 230V power supply.

Please note for reliable smoke detection the air speed in the duct must be at least 2.5m/s.

Features

Fire and Fault relays

Option for latching or non-latching Manual reset (latching option)

Model ZT-DU ZT-DU/12 ZT-DU/230

Part No. 48-011A 48-011B 48-011C

Supply Voltage N/A 12V 230V

Stand by current N/A 46mA (From 12v supply)

Alarm current N/A 86mA (From 12v supply)

Fault current N/A 26mA (From 12v supply)

Indications N/A Power, fault & alarm

Outputs N/A 1 x fault relay & 1 x alarm relay

Size 190 x 227 x 70mm

Weight 728g 989g

Direction of Airflow Duct Wall

(41)

Premier Power Pack EN 54-4 Power Supply

with LCD Screen

(PP-2/12, PP-5/17)

The Premier Power Pack Power supply uses an

innovative design that allows the engineer to

view system status through the on board LCD

screen. The screen can display several power

supply parameters, including output voltage,

and output current.

The power supply itself uses a 3 state charger which uses BOOST, FLOAT, and PULSE modes, depending on the state of the battery.

The PSU will disconnect the batteries under mains fail condition, when the batteries are fully discharged to prevent damage to the batteries.

The PSU will also monitor the battery for high internal resistance, and signal a fault if that condition is detected.

Screen Information

System Normal Screen

Z E T A A L A R M S Y S T E M S P R E M I E R P O W E R - P A C K R A T I N G 3 0 V D C 2 . 0 A S Y S T E M N O R M A L

Screen 1 - Main Information

M A I N S : O K B A T T S : O K V ( A ) = 2 9 . 5 V ( B ) = 2 9 . 5 C U R R E N T 0 . 1 2 A M P S

Screen 2 - Battery Info

B A T T E R Y I M P : 0 . 0 0 3 7 C H A R G E R V O L T : 2 5 . 4 5 V C H A R G E T Y P E : B O O S T B A T T E R Y S T A T E : G O O D Screen 3 - Misc. E A R T H : 2 . 4 4 7 V G O O D C H A R G E R C I R C U I T : O K B A D B A T T E R Y L V L X . X R

Screen 4 - Software Information

S o f t w a r e P S U : 2 V 0 0 S o f t w a r e L C D : 2 V 0 0 Model PP-2/12 PP-5/17 Part No. 46-300 46-305 Input Voltage 170-264V AC 47-63 Hz

Output Voltage 28V DC Nominal 28V DC Nominal

Power Rating 75W 150W

Efficiency 79% 86%

Total Power

Output 2.0 Amp 5.0 Amp

Power Supply

Outputs 2 Fused Outputs 2 Fused Outputs

Maximum Current

Per Output 0.625mA 2.0 Amps

Battery Charging

Current 750mA 920mA

Fault Relay Rating SELV 1A SELV 1A

IP Rating IP30 IP30

(42)

Batteries

(Z20201, Z20301, Z20651, Z21251 & Z21751)

As fire alarm systems are life safety systems,

they must have a battery backup to ensure full

functionality is maintained in the event of a

mains failure. All parts of the system (including

auxiliary power supplies) must have a battery

backup.

All the batteries stocked are 12V meaning that 2 batteries are required for a 24V systems. The standard capacities available are 2.2Ah, 3.2Ah, 7Ah, 12Ah and 17Ah.

It is important to choose the correct battery size for the system load to give the required standby time (usually 24 or 48 hours).

Model Z20201 Z20301 Z20651 Z21251 Z21751

Part No. 46-002 46-100 46-003 46-105 46-004

Type Sealed lead acid

Voltage 12V DC

Capacity 2.2 Ah 3.2 Ah 7.2 Ah 12 Ah 17 Ah

Size 178 x 34 x 65mm 132 x 59 x 65mm 151 x 65 x 98mm 150 x 98 x 103mm 178 x 75 x 168mm

Weight 1.0kg 1.25kg 2.5kg 3.5kg 5.8kg

Battery Calculation

To calculate the required battery backup, we use the

equation:-Battery Size (Standby time in Amp Hours) = 1.25 x [(TALM x IALM) + (TSBY x ISBY)] Where:

TALM = Maximum time in hours required for the alarm [½ hour is most common time]

IALM = Total Alarm Current in amps for all alarm devices connected to the alarm circuits

TSBY = Standby time in hours for the system after mains failure [normally 24, 48 or 72 hr]

ISBY = Quiescent current in amps of control panel in fault condition [because of mains failure] PLUS all loop devices

(43)
(44)

Tel: +44 (0) 1792 455 175 Fax: +44 (0) 1792 455 176 E-mail: info@zetaalarmsystems.com Detection House 72-78 Morfa Road Swansea SA1 2EN

References

Related documents

In a surprise move, the Central Bank of Peru (BCRP) reduced its benchmark interest rate by 25 basis points (bps) to 3.25% in mid-January following disappointing economic growth data

Some qualifying countries have also experienced strong growth in foreign direct investment aimed at taking advantage of AGOA with positive spin-offs for increased employment

2 Percentage endorsement rates for items from the DISCO PDA measure stratified by group ( “substantial” PDA features, “some” PDA features and the rest of the sample).. N

18 th Sunday in Ordinary Time Saint Rose of Lima Parish Parroquia Santa Rosa de Lima.. August

[r]

1 2 3 4 5 6 7 8 supply present remote output general fault power supply fault system fault repeater fault sounder status auxiliary output status output delays test remote

An important source for proposing that single women’s sexual and reproductive choices are influenced by their desire to build relationships and attain a certain place in

Other factors that favor good performance in adult cochlear implant candi- dates include lip-reading ability and residual hearing before implantation (patients with some hearing in