LDCDP−EPC50ACU

.SR6

Ä.SR6ä

Software Manual

Industrial PC

ACU UPS software for Industrial PCs

(2)

,

Please read these instructions before you start working! Follow the enclosed safety instructions.

(3)

Validity information

These instructions are valid for

ƒ ACU UPS software for Lenze Industrial PCs

Trademark

Windows XPâ, Windows XPâ Embedded and Windowsâ Embedded Standard 2009 are registered

trademarks or trademarks of Microsoft Corporation in the USA and/or other countries.

Any additional trade names given in this documentation are trademarks of their corresponding owners.

Document history

Material number Version Description

13218873 1.0 11/2007 TD29 First edition 13303164 2.0 08/2009 TD29 Revision

13348913 3.0 08/2010 TD29 Extension by the description of software versions V3.x and V4.x

13411916 4.0 06/2012 TD29 Revision of ACU control register

.SR6 5.0 12/2015 TD09 Extension by the description of software version V5.x

0Fig. 0Tab. 0

I

Tip!

Information and auxiliary devices related to the Lenze products can be found in the download area at

(4)

Contents

i

1 Software Description . . . 5 1.1 Operating mode. . . 5 1.2 System Requirements . . . 5 1.3 Messages . . . 6

1.3.1 Message in case of a voltage failure . . . 6

1.3.2 Message after a change in ACU UPS state. . . 6

2 Software Operation . . . 7

2.1 Start and Close Software . . . 7

2.2 Open User Interface . . . 9

2.3 User Interface Dialogs . . . 10

2.3.1 Registry "ACU State" − Show UPS State . . . 10

2.3.2 Registry "ACU Control" − Configure UPS . . . 12

2.3.3 Registry "Time Set" − Time Before Shutdown . . . 14

2.3.4 Registry "Application"− Start External Programs . . . 15

2.3.5 Registry "Shutdown" − Force Shutdown . . . 15

2.3.6 Registry "LogFile" − View Program Messages . . . 16

(5)

Software description

Operating mode

1

1

Software Description

The industrial PC option "ACU UPS Control Unit" in combination with a battery/capacitor pack extends the industrial PC (IPC) by one UPS function.The ACU UPS software controls the behaviour of the IPC in this process as soon as the hardware identifies a supply voltage failure.

The ACU UPS control unit is a factory set pre−equipment if you chose this option when placing your purchase order. However, it can also be upgraded later on by Lenze service personnel.

If you purchased the preinstalled operating system on a storage medium at Lenze, the ACU UPS software is already installed and configured according to your hardware. Alternatively, you can find the software on the driver CD for your IPC. Then, install the

software as described in the chapter "Software Installation". (¶ 17

1.1 Operating mode

During the boot phase of the operating system, the ACU UPS is in a permanent buffer operation which means that it already provides protection against data loss in the boot phase, even before the ACU software has started.

The ACU software starts automatically after the operating system has been booted and monitorsthe voltage supply from the background until it is closed along with the operating system.

1.2 System Requirements

)

Note!

Software versions Vx.x must only be used in conjunction with specific devices and are incompatible.

ACU UPS version Device Operating system

V2.x IPC CPC 2700, EL 870−9700 or CS 5700−9700 with ACU UPS control unit

Windows XPâ or Windowsâ XP Embedded

V3.x L−force Controller 3241 C Windows XPâ or Windowsâ Embedded Standard 2009 V4.x IPC CPC 2800, EL 1800−9800 or CS

5800−9800 with ACU USV Control Unit

Windows XPâ or Windowsâ Embedded Standard 2009 V5.x IPC CPC 2800, EL 1800−9800 oder CS

5800−9800 mit ACU USV Control Unit

Windows Embedded Standard 7 P 64bit

(6)

Software description

Messages

Message in case of a voltage failure

1

1.3 Messages

1.3.1 Message in case of a voltage failure

In the case of a voltage failure, the ACU UPS takes charge of the IPC supply. The remaining

time to the IPC shutdown is displayed on the desktop. (¶ 14).

EPC50ACU−003

Fig. 1−1 Desktop message in the event of a voltage failure

1.3.2 Message after a change in ACU UPS state

Changes in ACU UPS state are indicated by a change in colour of the ACU symbol on the Windows task bar.

EPC50ACU−001

Fig. 1−2 Windows task bar with ACU UPS symbol

Legend:

Green: Battery/capacitor pack loaded and active

Yellow: Battery/capacitor pack is being loaded

Red: Indicates one or more of the following faults:

– ACU UPS is buffering the system

– Short circuit in the battery/capacitor pack – Battery/capacitor pack is not connected – Battery/capacitor pack is damaged

– Non−defined battery/capacitor packstatus – Charging connection of the ACU UPS is defective

(7)

Software operation

Start and Close Software

2

2

Software Operation

2.1 Start and Close Software

Start

After the IPC has been booted, the software starts automatically and then runs in the background. A symbol pops up in the information bar.

EPC50ACU−001

Fig. 2−1 Windows task bar with ACU UPS symbol

)

Note!

If an L−force Controller is delivered with ACU UPS but without a battery pack, the ACU UPS software is installed but UPS support is deactivated. In this case, there will be no ACU symbol in the information bar of the Windows task bar.

In the "ACU Control" registry, UPS support can be(¶ 12)activated and

deactivated.

Double−click the ACU symbol in the control panel to start the software manually.

EPC50ACU−011

(8)

Software operation

Start and Close Software

2

Close

Usually, the software is automatically closed by Windows.

If you want to close the software manually, right−click the ACU symbol in the information

bar of the Windows task bar and select Exit from the context menu.

EPC50ACU−002

Fig. 2−3 Windows task bar with opened context menu

ACU UPS V2.x: UPS functionality is switched off until it is switched on again via the context menu.

(9)

Software operation

Open User Interface

2

2.2 Open User Interface

)

Note!

For configuring the ACU software, administrator rights are required. Otherwise, only actual states can be displayed.

ƒ If you want to View ACU UPS Configuration, double−click the ACU symbol in the

information bar of the Windows task bar.

The ACU software dialog is displayed. The registries of this dialog show the ACU UPS software settings.

Various settings which affect software only can be made (e.g. the period of time from identifying a voltage failure to the shutdown of the IPC). Settings affecting the ACU UPS control unit hardware cannot be made.

EPC50ACU−005

Fig. 2−4 Example: ACU software dialog ACU UPS V2.x

ƒ If you want to Configure the ACU UPS Control Unit, double−click on the ACU symbol

in the Windows control panel.

The ACU software dialog is also displayed. Unlike the process described above, the ACU control registry is displayed as well which helps you configure the behaviour of the ACU UPS control unit in the case of a voltage failure.

EPC50ACU−004

Fig. 2−5 Example: ACU software dialog ACU UPS V2.x

Information on the registries of the user interface of the various ACU UPS versions is provided in the following chapter.

(10)

Software operation

User Interface Dialogs

Registry "ACU State" − Show UPS State

2

2.3 User Interface Dialogs

2.3.1 Registry "ACU State" − Show UPS State ACU USV V2.x:

Dialog Box Value Range Explanation

Type − Hardware Type

Power OK/Fail Input Voltage State; OK or Failure UPS On/Off On: UPS functionality activated

Buffer Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out.

Delay Time [s] 0 ... 240 s; infinite

Maximum period of time the industrial PC can be fed by the battery/capacitor pack, depending on the hardware. ACU State − Current ACU State Display

Firmware Version − Displays the current ACU firmware version

)

Note!

(11)

Software operation

User Interface Dialogs Registry "ACU State" − Show UPS State

2

ACU USV V3.x/V4.x/V5.x:

Dialog Box Value Range Explanation

Type − Hardware Type

Power OK/Fail Input Voltage State; OK or Failure UPS On/Off On: UPS functionality activated

Delay Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out.

Buffer Time 4 min.; infinite Maximum period of time the industrial PC can be fed by the battery/capacitor pack, depending on the hardware. ACU State − Current ACU State Display

Firmware Version − Displays the current ACU firmware version

)

Note!

(12)

Software operation

User Interface Dialogs

Registry "ACU Control" − Configure UPS

2

2.3.2 Registry "ACU Control" − Configure UPS

)

Note!

This registry is only shown when the ACU software has been called up via the system panel. It is not shown when the software is called up by double−clicking the symbol in the information bar of the Windows task bar.

ACU USV V2.x:

Dialog Box Value Range Explanation

Buffer Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out.

Delay Time 0 ... 240 s; infinite

Maximum period of time the industrial PC can be fed by the battery/capacitor pack, depending on the hardware.

Restart after Delay Time On/Off On: Restart or shutdown of the system when the delay time is up.

UPS Activated On/Off On: UPS support activated Off: UPS support deactivated

Auto off after shutdown On/Off On: The ACU UPS control unit is switched off right after the shutdown of the system. This function requires a system with ACPI support (ETX−CD).

Backlight off after Power Fail On/Off On: Deactivates the backlight of the TFT display in case of a voltage failure.

(13)

Software operation

User Interface Dialogs Registry "ACU Control" − Configure UPS

2

ACU USV V3.x:

Dialog Box Value Range Explanation

Delay Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out.

Buffer Time 4 min.; infinite Maximum period of time the industrial PC can be fed by the battery/capacitor pack, depending on the hardware. UPS Activated On/Off On: UPS support activated

Off: UPS support deactivated

ACU USV V4.x:

Dialog Box Value Range Explanation

Buffer Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out.

Delay Time 4 min.; infinite Maximum period of time the industrial PC can be fed by the battery/capacitor pack, depending on the hardware.

Restart after Delay Time On/Off On: Restart or shutdown of the system when the delay time is up.

UPS Activated On/Off On: UPS support activated Off: UPS support deactivated

Backlight off after Power Fail On/Off On: Deactivates the backlight of the TFT display in case of a voltage failure.

(14)

Software operation

User Interface Dialogs

Registry "Time Set" − Time Before Shutdown

2

ACU USV V5.x:

Dialog Box Value Range Explanation

Delay Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Voltage fluctuations are therefore filtered out.

Buffer Time 4 min.; infinite

Maximum period of time the industrial PC can be fed by the battery/capacitor pack, depending on the hardware.

Restart On/Off On: Restart or shutdown of the system when the delay time is up.

UPS Activated On/Off On: UPS support activated Off: UPS support deactivated

Backlight off after Power Fail On/Off On: Deactivates the backlight of the TFT display in the event of a voltage failure.

2.3.3 Registry "Time Set" − Time Before Shutdown ACU UPS Vx.x:

Dialog Box Value Range Explanation

(15)

Software operation

User Interface Dialogs Registry "Application"− Start External Programs

2

2.3.4 Registry "Application"− Start External Programs ACU UPS Vx.x:

While the ACU software counts down the seconds until the IPC is shut down after a voltage failure, an external program can be started.

Dialog Box Value Range Explanation

Executable Application − Path of the executable program file of the application [Browse] − Search executable program file

Execute Application On/Off On: The program file specified in "Executable Application" is executed.

2.3.5 Registry "Shutdown" − Force Shutdown ACU UPS Vx.x:

Dialog Box Value Range Explanation

Shutdown On/Off Default Setting

Force Shutdown On/Off If you are using the default setting and an application prompts you to make a user entry when shutting down the PC, the PC cannot be shut down automatically.

If the "Force Shutdown" option is activated, all programs are closed before the shutdown without considering feedbacks.

(16)

Software operation

User Interface Dialogs

Registry "LogFile" − View Program Messages

2

2.3.6 Registry "LogFile" − View Program Messages ACU UPS Vx.x:

All ACU software messages are recorded in the ACU.log file and can be viewed there.

Dialog Box Value Range Explanation

[Position Log File] − Select the folder the ACU.log file shall be written to. [Show Log File] − Display ACU.log File

)

Note!

The log file data is moved to the "ACU.bak" file when the file size reaches 64 KB so that the log file does not become too big.

If you delete the "ACU.log" log file through the Windows Explorerâ, a new log

file will be created as soon as a new log entry is available.

It may be impossible to write the log file if the software is run under a user account with restricted access rights and if a folder other than the

preconfigured folder has been assigned. So please ensure that the user account has the corresponding write permissions with regard to the log file folder.

If a write filter (EWF or FBWF) is used: The log file need not be in a write−protected area.

(17)

Software installation

3

3

Software Installation

The ACU UPS control unit software is a factory set pre−equipment if you chose this option when placing your purchase order and if you obtained the operating system via a Lenze storage medium.

In other cases, start the setup program on the program CD and follow the instructions of the setup assistent.

)

Note!

After the ACU UPS software has been reinstalled, UPS functionality is deactivated for versions V3.x/V4.x/V5.x and activated for version V2.x.

(18)

Q

References

Related documents

For each of the drug use outcomes (lifetime alcohol, cigarette, and marijuana use and number of seven drugs ever used), the equations first assess the differences by ethnic

Quality: We measure quality (Q in our formal model) by observing the average number of citations received by a scientist for all the papers he or she published in a given

The aim of this study was to evaluate the current vac- cination status of the HCWs in all of the Departments different from the Department for the Health of Women and Children of one

National Conference on Technical Vocational Education, Training and Skills Development: A Roadmap for Empowerment (Dec. 2008): Ministry of Human Resource Development, Department

Furthermore, while symbolic execution systems often avoid reasoning precisely about symbolic memory accesses (e.g., access- ing a symbolic offset in an array), C OMMUTER ’s test

All of the participants were faculty members, currently working in a higher education setting, teaching adapted physical activity / education courses and, finally, were

Teachers should communicate weekly assignments to students through email or Google Classroom and unlock at least a week’s worth of assignments in Courseware by no later than Friday

The redox state of 823 Cys residues was quantified using OxICAT in the mshC mutant under control and NaOCl stress as shown in the Voronoi redox treemaps (Fig.  6A–D , Tables  S3 ,