• No results found

21 st Century Facilities

N/A
N/A
Protected

Academic year: 2021

Share "21 st Century Facilities"

Copied!
31
0
0

Loading.... (view fulltext now)

Full text

(1)
(2)

21

st

Century Facilities

• Facility Owners face tough challenges

– 24 X 7 reliability needed

– Non linear loads cause harmonics • VFD

• Computers

– Switching transients disrupt operations – Less customer support from Utilities – Pressure to hold energy costs down

– Compressed schedules for expanding facilities – Effect of EMF on computers and equipment

– How to expand facilities to meet customer needs cost effectively

(3)

Formula For Successful Facilities

• Facility Planning and Scheduling

• Engineering Design • Quality Installation • Acceptance Testing

• Regular and Complete Maintenance – Preventative Maintenance Testing

(4)

Testing for All Phases of Facility

Improvements

• Load analysis for facility improvements

• Trouble shooting and correction of problems • Acceptance Testing for New Projects

• Switchboards and/or Switchgear • Circuit Breakers

• Preventative Maintenance • Forensic Testing

(5)

Testing – Load Analysis

• Measuring existing loads with portable test equipment – 120V to 480V, 0 – 3000 Amps

– Recorded values

– Volts - Power Factor – Amps - KVA

– KW - KVAR – Measure harmonic distortion

– THD - Voltage & Current – Individual harmonics

• Measure loads for emergency generator sizing • Motor starting studies

(6)

CURRENT Trend Monitoring

48 54.75 61.5 68.25 75 48 54.75 61.5 68.25 75 10:50 AM 11:00 AM 11:10 AM 11:20 AM 11:30 AM 11:40 AM 11:50 AM 11/5/01 10:50:00 AM to 11/5/01 11:50:00 AM IAvg IA IB IC Trend Plot For Device: 3 Phase Current

(7)

Testing – Acceptance Testing

• Equipment Acceptance Testing

– Medium Voltage – Transformers – Switchgear – Cables – PFC – Air Switches – SF6 Circuit Breakers – Below 600V

– Switchboards and Switchgear – Motor Control Centers

(8)

Acceptance Testing Cont’d.

• Short Circuit and Coordination Studies

– Short Circuit Study verifies overcurrent protective

devices meet requirement for interrupting available fault current.

– Coordination Study graphically shows how overcurrent protective devices coordinate to have the CB closest to the fault open.

• Ground Resistance Testing

– 3 Point Fall of Potential Method

(9)

Transformer Testing

Oil Filled Transformers

• On Line, no shutdown

• Excellent analytical technique developed by IEEE to evaluate condition of transformer

• IEEE/ANSI C57 Distribution, Power and Regulating

Transformers. C57.104 is the Standard for Interpretation. • NFPA 70B

– Section 7-2.81 Oil Tests

(10)

Transformer Testing Cont.’d

• Mineral Oil is complex hydrocarbon molecular compound – At normal conditions it is very stable

– Heat, corona and arcing break molecule down to sub elements (combustible gases) (H2, CH4, etc.)

– Analysis of dissolved combustible gases gives the condition of the transformer.

– Trending of gases is very helpful in the analysis.

• DGA is one of the best ways to monitor the condition of the transformer and help the Owner plan repairs or

(11)

Infrared Thermography Scan

• Heat is the enemy for electrical equipment

• Heat breaks down electrical insulation • 10° C Rule = ½ life

• Infrared thermography scanning

– Looks at thermal image of switchgear, busbars, connections, cables, etc.

– Hot spots and irregularities are discovered by trained technicians

– Problem areas can be corrected before they cause shutdowns or cause fires.

• Scanning Saves Equipment

– Technician scanning is much faster that tightening all bolts. – Cannot see some circuit breaker problems without IR.

(12)

Infrared Thermography Scan

95.8°F 148.5°F 100 110 120 130 140 SP01 SP02 Spot 1 Temperature 154.7°F Spot 2 Temperature 93.9°F

Spot 1 Rise over Spot 2 60.84°F

(13)

Circuit Breaker Testing

• Contact Resistance

– Results vary with size and construction of circuit breaker • less than 100 microhms for medium voltage

– Contact resistance exposes problems not detectable with IR when there is little load current.

• Insulation Resistance – Phase to ground – Phase to phase • Functionality Tests – Close, Open – Trip

(14)

Circuit Breaker Testing Cont’d.

• Overcurrent Trip Point Calibration and Testing

– Secondary Injection Testing

– Electronic CB test sets for accurate testing • Square D

• Cutler Hammer • GE

• Siemens

• New Circuit Breakers with on-board secondary injection testing • Cutler Hammer 1150 Trip Unit

(15)

Cable Testing

– Medium Voltage (> 600 Volts)

• New Cables

– Insulation resistance testing using hi pot at manufacturer’s recommended values

– NETA use Table 10.6 of Acceptance Testing Specs. – Leakage current should be <10 micro Amps for new cables.

• Existing Cables

– Watch out! – Be careful what voltage you use on old cables.

– Conservative approach

• RMS X Square Root of 2 = Peak voltage • Use peak value as DC value

(16)

Relay Testing

• Relays are typically used on medium voltage systems

– Older electro mechanical style relays (typical single phase) – Newer models–microprocessor based, 1 Phase + 3 Phase

– Incorporate metering and relay tripping. – Programmable on site

– Fault analysis logging for retrieval • Short Circuit and Coordination Studies

– At least 50% of facilities are not coordinated • Poor maintenance

(17)

Power Quality -

Today’s Perspective

• The quality of power 30 years ago was not much of an issue – Linear Devices

• Today many devices disrupt and corrupt the quality of the power

– Utility Side

• Voltage Sags • Impulses

• Transient Disturbances • Loss of One Phase

(18)

Power Quality – Today’s Perspective

– Customer Side

• Switch mode power supplies (non-linear device) – Harmonic Distortion

– Overloaded neutrals – Transformer heating • SCR (non-linear device) • Loose wiring

(19)

PQ Testing

• Power Quality Analyzer – 3 phase microprocessor based analyzer that samples the voltage waveform 128 times per second. We set thresholds for voltages. By exceeding the thresholds, the machine is activated to record the “events” as they occur.

• Harmonic testing and analysis

– Measure voltage and current THD – Analyze individual harmonic values

• Engineering investigation of problem and surrounding power distribution system by power quality engineer.

(20)

Main Switchboard Voltage Sag

340.0A 170.0A 0.0A 350.0V 175.0V 0.0V 5.83 ms/div 0.00ns 116.67ms RMS Sag Disturbance Model 7100 M SWBD 11/22/01 07:57:32.98 AM Three Phase Wye

Vc Ic Channel Y1 Y2 Delta Channel Y1 Y2 Delta Time X1 X2 Delta Voltage 285.185 205.967 79.218 Current 277.037 200.082 76.955

(21)

Main SWBD Voltage Sag on Phase C-N

640.0A 0.0A -640.0A 500.0V 0.0V -500.0V 2.50 ms/div 0.00ns 50.00ms Impulse Disturbance Model 7100 M SWBD 11/22/01 07:57:32.98 AM

Three Phase Wye

(22)

Main SWBD Utility Capacitor

Switching Transient – Phase B-N

2.1KA 0.0A -2.1KA 500.0V 0.0V -500.0V 2.50 ms/div 0.00ns 50.00ms Impulse Disturbance Model 7100 M SWBD 12/03/01 09:48:07.93 AM

Three Phase Wye

(23)

Utility Capacitor

Switching Transient Phase B-N

2.3KA 0.0A -2.3KA 550.0V 0.0V -550.0V 2.50 ms/div 0.00ns 50.00ms Impulse Disturbance Model 7100 M SWBD 12/03/01 11:43:11.90 AM Three Phase Wye

Vb

Channel Y1 Y2 Delta

Channel Y1 Y2 Delta

Time X1 X2 Delta

(24)

Panel NEH1 Power Source

Switching Transient – Phase A-N

575.0A 0.0A -575.0A 650.0V 0.0V -650.0V 2.50 ms/div 0.00ns 50.00ms Impulse Disturbance Model 7100 Pnl NEH1 01/03/02 02:00:54.74 PM

Three Phase Wye

(25)

Panel NEH1 Power Source

Switching – Phase B-N

570.0A 0.0A -570.0A 700.0V 0.0V -700.0V 2.50 ms/div 0.00ns 50.00ms Impulse Disturbance Model 7100 Pnl NEH1 01/03/02 02:48:29.37 PM

Three Phase Wye

(26)

Harmonic Distortion – Voltage Waveform

50.0A 0.0A -50.0A 200.0V 0.0V -200.0V 833.33 us/div 0.00ns 16.67ms Snapshot Waveform Model 7100 PDU PnlD 01/17/02 01:06:45.97 PM Three Phase Wye 0.0% 0.5% 1.0% 60Hz 2940Hz Va Distortion: thd=1.41% Odd=1.36%

(27)

Harmonic Distortion - Current

50.0A 0.0A -50.0A 200.0V 0.0V -200.0V 833.33 us/div 0.00ns 16.67ms Snapshot Waveform Model 7100 PDU PnlD 01/17/02 01:06:45.97 PM Three Phase Wye 0.0% 16.0% 32.0% 60Hz 2940Hz Ia Distortion: thd=42.34% Odd=42.19%

(28)

How Do You Spot PQ Problems?

• Variable speed drives trip off line more than usual.

• Computer data errors that cannot be explained by hardware or software

• Lights flicker (not in a storm).

• Equipment power supplies have burned or damaged boards. • Transformers overheating.

• Circuit breaker nuisance tripping. • Motors overheating or failing easily.

• Voltages vary significantly from loose wiring. • Computer screens wave or are disrupted.

(29)

Power Quality and Facility

Maintenance Are Related

• Loose connections are one of the leading power quality problems

• Lack of coordination of overcurrent protection devices can cause blackouts that could have been avoided.

– Coordination Study – Short Circuit Study

• Preventative Maintenance

– Infrared thermography scan – looks for hot spots – Transformer Testing

– Oil Quality

– Dissolved Gas Analysis – Cable Testing

– Test Circuit Breakers

(30)

Conclusion

• Facilities today face tough problems:

– Harsh environments

– Power Quality Problems – Need for 24/7 Reliability – Compressed schedules

• A successful 21st Century Facility needs four solid legs to

stand on:

– Engineering Design – Quality Installation – Maintenance

(31)

Conclusion Cont’d.

• Excellent resources and standards from IEEE, NETA and NFPA for Testing and Maintenance

• A proper test is worth a thousand opinions. The right test equipment and experience will aid the Design Engineer in ensuring success for the Customer.

References

Related documents

MacIntyre &amp; Gardner (1991) concluded that anxiety in the foreign language context can have a negative effect on the language learning process. Similar results were revealed by the

Designed For Reliability Manufactured To Last iMeter 8 Advanced Power Quality Analyzer.. The iMeter 8 is CET’s Advanced PQ Analyzer designed for the compliance monitoring

4 RS-232: Use the left/right arrow keys to adjust communication baudrate (for communication with a PC). 5 Battery save: Use the up/down arrow keys to select the time after which

Alcohol or Drug Addiction Program  No,  federal  TANF  program  funds  cannot  be  used  for  medical  services,  except  for  pre‐pregnancy  family 

South Dakota State University Basic News Writing, 2010 Public Affairs Reporting, 2010 Basic News Writing, 2011 Journalism History, 2011 ADVISING.

The Trust will share safety lessons from the aggregated report across the local health economy with the Clinical Quality Review Group (via the SITREP report). Governance

After man sinned, how- ever, God had to go back to work, and that’s what this book is about: God’s restoration of THE BLESSING on mankind, where it belonged, through His

there are approximately 210 distinct cell types in the adult human body. Rehab Mamdouh 20.. Rehab Mamdouh 21 Structure of animal cell.. • An organelle is a specialized subunit