• No results found

Active Chilled Beam System Design & Layout

N/A
N/A
Protected

Academic year: 2021

Share "Active Chilled Beam System Design & Layout"

Copied!
79
0
0

Loading.... (view fulltext now)

Full text

(1)

Active Chilled Beam

System Design & Layout

Salt Lake City, UT ASHRAE Chapter December 2013

Nick Searle

(2)

Contents

• Active Chilled Beam Basics

• Design Considerations

• Air System Design & Humidity Control

• Water System Design

• Heating with Active Beams

• Controls

(3)

Fan Energy Use in Buildings

“Energy Consumption Characteristics of Commercial Building HVAC Systems” publication prepared for U.S. Department of Energy

0 0.5 1 1.5 2 2.5 3 3.5 4 4.5

Central VAV Central CAV Packaged CAV

D e s ig n L o a d K W /S F Chiller/Compressor Supply & Return Fans Chilled Water Pump Condenser Water Pump Cooling Tower Fan Condenser Fan 0 1 2 3 4 5 6 7

Central VAV Central CAV Packaged CAV

E n e rg y U s e K W h /S F

(4)

Water = Efficient Transport

¾” diameter water pipe 10” 1 Ton of Cooling requires 550 CFM of air or 4 GPM of water

(5)

Active Chilled Beams

1980 1990 2000 2010

Chilled Ceilings Passive Chilled Beams Active Chilled Beams

• Higher space loads

• Higher occupant densities • Combined ventilation/cooling

preferred

• Integration into fiber tile ceilings required

(6)

Active Chilled Beam 0 Operation Principle

Suspended ceiling Primary air plenum

Primary air nozzles

Heat exchanger

1 Part Primary Air

(7)

Heat Removal Ratio

70% of sensible heat removed by chilled beam

water coil Airflow

requirement reduced by 70%

(8)
(9)

Active Chilled Beams 0 System Highlights

• Very high cooling capacity

‒ Up to 100 BTUH/FT2 floor space

‒ Up to 1500 BTUH per LF

• Integrated cooling, ventilation and heating

‒ All services in the ceiling cavity

• Suitable for integration into all ceiling types

(10)

Active Chilled Beams 0 System Highlights

• Significant space savings

‒ Smaller ductwork saves space in shafts, plant rooms and ceiling

• Can be installed tight up against the slab

‒ Reduced floor to floor heights

‒ Reduced construction costs on new buildings

• Low noise levels • Low maintenance

(11)

Energy Savings 0 Compared to VAV

Source Technology Application % Saving*

US Dept. of Energy Report (4/2001) Beams/Radiant Ceilings General 25A30

ASHRAE 2010 Technology Awards Passive Chilled Beams Call Center 41

ACEE Emerging Technologies Report (2009) Active Chilled Beams General 20

ASHRAE Journal 2007 Active Chilled Beams Laboratory 57

SmithGroup Active Chilled Beams Offices 24

*Compared to VAV

“Energy Consumption Characteristics of Commercial Building HVAC Systems” publication prepared for U.S. Department of Energy

(12)
(13)
(14)

9 ’A 1 0 ” 1 2 ’A 0 ”

Space Savings

(15)
(16)

Space Savings

8 ’A 0 ” 9 ’A 1 0 ”

(17)

E x p o s e d C h ill e d B e a m s 6 F lo o rs A ll A ir H V A C S y s te m 5 F lo o rs

Space Savings

(18)

ACTIVE CHILLED BEAM DESIGN

CONSIDERATIONS

(19)

Building Suitability

Building Characteristics that favor Active Chilled Beams

• Zones with moderateAhigh sensible load densities

‒ Where primary airflows would be significantly higher than needed for ventilation

‒ Sensible Heat Ratio’s (SHR) of 0.8 and above

• Buildings most affected by space constraints

‒ Hi – rises, existing buildings with induction systems

• Zones where the acoustical environment is a key design criterion

• Laboratories where sensible loads are driving airflows as opposed to air change rates

(20)

Building Suitability

Characteristics that less favor Active Chilled Beams

• Buildings with operable windows or “leaky” construction

‒ Beams with drain pans could be considered ‒ Building pressurization control should be used

• Zones with relatively low sensible load densities

• Zones with relatively low sensible heat ratios and low ventilation air requirements

• Zones with high filtration requirements for the reA circulated room air

(21)

SHR’s for Typical Spaces

SHR Range

Auditoriums, Theaters 0.65 - 0.75

Apartments 0.8 - 0.95

Banks, Court Houses, Municipal Buildings 0.75 - 0.9

Churches 0.65 - 0.75

Dining Halls 0.65 - 0.8

Computer Rooms 0.8 - 0.95

Cocktail Lounges, Bars, Taverns, Clubhouses, Nightclubs 0.65 - 0.8

Jails 0.8 - 0.95

Hospital Patient Rooms, Nursing Home, Patient Rooms 0.75 - 0.85

Kitchens 0.6 - 0.7

Libraries, Museums 0.8 - 0.9

Malls, Shopping Centers 0.65 - 0.85

Medical/Dental Centers, Clinics and Offices 0.75 - 0.85 Motel and Hotel Public Areas 0.75 - 0.9

Motel and Hotel Guest Rooms 0.8 - 0.95

Police Stations, Fire Stations, Post Offices 0.75 - 0.9

Precision Manufacturing 0.8 - 0.95

Restaurants 0.65 - 0.8

Residences 0.8 - 0.95

Retail, Department Stores 0.65 - 0.9

Other Shops 0.65 - 0.9

School Classrooms 0.65 - 0.8

(22)

Role of the Primary Air

• Ventilate the occupants according to ASHRAE 62A 2004

• Handle all of the latent load in the space

‒ Primary air is only source of latent heat removal

• Create induction through chilled beam

(23)

Primary Air Design

• Central AHU sized to handle:

‒ sensible and latent cooling/heating of the ventilation air ‒ portion of the sensible internal cooling/heating loads

AND

‒ all of the internal and infiltration latent loads

• Primary air delivered continuously to the chilled beams

‒ VAV primary air can be considered for the perimeter if the sensible loads are high

• Chilled beam water coils provide additional sensible cooling/heating to control zones

(24)

Primary Air Temperature 0 Cooling

55°F or Lower 65°F or Higher

• Reduces or eliminates reheat

• Ideal for labs or hospitals with code required minimum air changes

• More or longer beams

required in some applications • Reduces lengths/quantities of

beams

• Good for office buildings with high perimeter loads

• Often used with VAV in

applications with high sensible loads

Air must be suitably dehumidified whatever

the dry bulb temp is!

(25)

Room Neutral Air

• Sensible recovery device (downstream of coil) • Desiccant dehumidification units

(26)

Reducing Primary Air Temperature

Active Chilled Beams

Primary Air Pressure Primary Air Flow Rate Supply Air Flow Rate Supply Air Temp Out (Cooling) Primary Air Sensible Cooling Secondary Air Sensible Cooling Nett Unit Sensible Cooling Chilled Water Flow Rate

Qty Unit TAG Zone Name Unit Model 2 or 4 Pipe Coil Nominal Length (feet) PPA(Inch w.c.) QPA(CFM) QSA

(CFM) tSAout(°F) qPAs(Btuh) qSCAs(Btuh) qs(Btuh) QSCHW

(GPM)

2 ACBA1 1 DADANCO ACB50 2 8 0.7 105 529 59.3 2281 6770 9051 1.3

Room Design Primary Air Secondary Chilled Water Secondary Hot Water Elevation Feet

% Propylene Glycol

Cooling 75°F 50% RH 55°F 80% RH 58°F 110°F 0 0 Heating 70°F 50% RH 55°F 83% RH

Typically 25% + more chilled beams required when using 65°F primary air

Active Chilled Beams Primary Air Pressure Primary Air Flow Rate

Supply Air Flow Rate Supply Air Temp Out (Cooling) Primary Air Sensible Cooling Secondary Air Sensible Cooling Nett Unit Sensible Cooling Chilled Water Flow Rate Water Pressure Drop Qty Unit TAG Zone Name Unit Model 2 or 4 Pipe Coil

Nominal Length

(feet)

PPA(Inch

w.c.) QPA(CFM) QSA(CFM) tSAout(°F) qPAs(Btuh) qSCAs(Btuh) qs(Btuh)

QSCHW (GPM) SCHW pressure drop (Feet w.c.)

3 ACBA1 1 DADANCO ACB50 2 8 0.5 70 359 59.4 760 5325 6085 1.1 7.9

Room Design Primary Air Secondary Chilled Water Secondary Hot Water Elevation Feet % Propylene Glycol % Ethylene Gylcol

Cooling 75°F 53% RH 65°F 70% RH 58°F 70°F 0 0 0 Heating 70°F 50% RH 107°F 83% RH

(27)

Latent Load Calculation

• The amount of cooling required to remove the moisture from the air

Q

L

= 0.68 x q x ∆w

gr

or QL = 4,840 x q x ∆ w

lb

Where A

QL= latent heat (Btuh)

q = air volume flow (cfm)

∆ wgr = humidity ratio difference (grains water/lb dry air)

(28)

Dehumidification Air for 1 Person 0 200BTUH

0 5 10 15 20 25 30 35 40 45 44 45 46 47 48 49 50 51 52 P ri m a ry a ir f lo w ( C F M )

Primary air dew point (°F)

55% RH 52% RH 50% RH 30% less air Room Design Condition

(29)

Supply Water Temperature Safety Margin

Climatic Ceilings by “Energie”

Passive Chilled Beams + 1°F Active Chilled Beams A 2.9 °F Do not design below room dew point!

(30)

Condensation – Radiant Panel Test

Condensation after 8.5 hours on a chilled surface

intentionally held 7.8°F colder than the space DPT. Not one droplet fell under these

conditions

Chilled Ceilings in Parallel with Dedicated Outdoor Air Systems: Addressing the Concerns of Condensation, Capacity, and Cost Stanley A. Mumma, Ph.D., P.E.

(31)

• Building was designed for 80 BTUH/ft2 perimeter load

• Actual load in building use was 40 BTUH/ft2

Parameter Proposed in design Actual observed load

Area (Sq.ft) 200 200

Sensible Load (Btuh) 16,000 8,000

Latent Load (Btuh) 400 400

Minimum Outside Air (CFM) 40 40

Quantity of ACB’s 2 2

(32)

• Chilled beams selected for double actual required primary air to achieve overestimated load

• Primary air providing 65% of the total sensible cooling of the actual load

2 x beams at 115 CFM

(33)

• Therefore if load drops to 65% no waterside cooling will occur

• If load drops below 65% space will overcool unless reheat is used

(34)

• Assumptions on building materials performance

• Equipment loads that never eventuate

• Use of generic performance data

• Use of safety factors

• Lack of familiarity with load calculation software

(35)

Exclude loads:A

Outside air load

Plenum gain

Fan motor gain

Duct losses

Location Sensible Zone Load

North 25A30 Btuh/Sq.ft

East 35A45 Btuh/Sq.ft

South 30A40 Btuh/Sq.ft

West 40A50 Btuh/Sq.ft

Interior 15A20 Btuh/Sq.ft

If loads exceed these values review closely

(36)
(37)

CHW System Design Options

• Secondary loop

‒ Tap into district CHW loop

‒ Heat exchanger into return – no GPM demand ‒ Can increase main plant efficiency

• Dedicated chiller & DX

‒ Dehumidification by DX AHU

‒ Significantly increased COP A 11+

• Twin chillers

‒ One for AHU’s – 6 COP

(38)

Mixing Valve

S T

Secondary chilled water supply to beams Secondary chilled water return Supply temperature monitor Primary chilled water supply Primary chilled water return SCHW Pump 45°F 58°F 64°F T Primary chilled water return

(39)

Secondary Loop

S

T

Secondary chilled water supply to beams Secondary chilled water return Supply temperature monitor Primary chilled water supply Primary chilled water return Heat Exchanger SCHW Pump 54°F 45°F 58°F 64°F T

(40)

Dedicated Chiller

T

To chilled beam zones

Bypass Valve Chilled water pump Dedicated chiller 11+ COP Cooling Tower Geothermal Loop Geothermal Heat Pump 64°F 58°F

(41)

District Chilled Water Loops

• No demand in district loop GPM • Increases main chiller plant COP

Tap into return pipe with heat exchanger and secondary loop

(42)

Reverse Return Pipe Design

S

(43)
(44)
(45)

Advantages of 20Pipe Beams Versus 40Pipe

• Higher coil performance

‒ 4 pipe performance is compromised ‒ 75% Cooling (12 pipes)

‒ 25% Heating (4 pipes)

• Fewer or shorter beams

• Lower hot water temperatures

‒ 90°F for 2 pipe ‒ 130°F for 4 pipe

(46)

Boiler Efficiency 0 Lower Hot Water Temp

• Hot water typically 90A130°F

• Reduce boiler energy consumption by maximizing efficiency of a

condensing boiler through very low return water temperatures

• Use of water to water heat pumps

(KN boiler efficiency chart courtesy of Hydrotherm)

(47)

20Pipe Beams and Terminal Heating

S S T Terminal Heating Coil 2APipe Active Chilled Beams Chilled Water Supply

Chilled Water Return Hot Water Supply

(48)
(49)
(50)
(51)

Airside Control

• Constant volume air

‒ Reduces cost

‒ Maintains constant control of humidity ‒ Guarantees minimum fresh air delivery

• Monitor room dew point

‒ Use small quantity of high quality sensors ‒ Do not use RH sensors

‒ Locate sensors in room not in ceiling

• Reduce primary moisture content to control room RH

(52)

Waterside Control

• Variable water flow

‒ Pressure independent control

• Two position valves or modulating valves

• 6Away valves can be used on 4 pipe into 2 pipe chilled beams

• Reschedule or shut off SCHW only if primary moisture content cannot reduced

(53)

Waterside Control Sequence

71 72 73 74 75 76 R o o m T e m p e ra tu re ( °F ) Time D e a d Z o n e D e a d Z o n e SCHW ON SCHW OFF SCHW ON SCHW OFF HW ON

(54)

Typical Start Up Control Sequence

• Dry out cycle before engaging SCHW pumps

• Setback primary air humidity ratio

• ONLY initiate pumps when room dew point is within design limits

(55)

Condensation and Dew Point Sensors

Drip sensor

Condensation sensor Dew point sensor

(56)

ACTIVE BEAM SYSTEM DESIGN

COST CONTROL

(57)

First Cost Control

• Many projects still designed with far to many beams

‒ Caused by confusing selection software or low performance beams

• 4Apipe system designs are costly

‒ 2Apipe system with terminal heating or 6Away valves reduce cost

• Mechanical contractors unfamiliar with system

(58)

PEX Piping Significantly Reduces Costs

• 70% reduced pipe material cost

‒ $0.60 v’s $1.95 per linear foot

• Reduced labor, much faster installation

‒ No torches or soldering, no glue

• Longevity – 50 year life expectancy

‒ No corrosion

• Dampens water rushing noise and water hammer noise • Does not require insulation

• Plenum rated systems available

(59)

Active Chilled Beam

Selection & Layout

(60)
(61)

ACB Selection & Layout Tips

• Select beams for minimum possible primary air

• 0.4 – 0.7” w.c. typical airside beam ∆P

• Be aware of airside/waterside cooling ratio

‒ Maximize waterside cooling

• Chilled beams throw more air than VAV diffusers

‒ Be wary of air velocities

(62)

ACB Selection & Layout Tips

• Careful positioning near walls & columns

‒ Can interfere with beam if too close

• Chilled beams positioned closer than 6’ centers may not cool correctly

‒ Minimum 2 x tile spacing rule of thumb

• Use manufacturers selection software

(63)

Tips to Minimize Primary Air Flow

• Be wary of overrating cooling loads • Use low temperature primary air

‒ 45 – 48°F is possible but beam must be internally insulated

• Locate beams along perimeter to increase output

‒ Use a higher on coil temperature when beams are positioned along perimeter

‒ This additional capacity is often overlooked

(64)

DOAS with Booster Fans

A + A + Outdoor Air DEDICATED OUTDOOR AIR UNIT

A A

FAN BOOSTERS

Return Air Return Air

ACTIVE CHILLED BEAM ZONES ACTIVE CHILLED BEAM ZONES

(65)

LAYOUT EXAMPLE

@ OFFICE BUILDING @

(66)

Building With Exterior Cellular Offices

Office 1 35 BTUH/ft2 12’ 12’ Office 2 35 BTUH/ft2 Office 3 50 BTUH/ft2 Office 5 30 BTUH/ft2 Office 6 30 BTUH/ft2 TOTAL AREA 2,520 FT2 Office 7 30 BTUH/ft2 Office 4 30 BTUH/ft2 Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 1 144 ft2 15 CFM 7200 BTUH 288 BTUH 3000 BTUH Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 1 144 ft2 15 CFM 5040 BTUH 288 BTUH 2500 BTUH Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 1 144 ft2 15 CFM 5040 BTUH 288 BTUH 2500 BTUH Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 1 144 ft2 15 CFM 4320 BTUH 288 BTUH 2100 BTUH Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 1 144 ft2 15 CFM 4320 BTUH 288 BTUH 2100 BTUH Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 1 144 ft2 15 CFM 4320 BTUH 288 BTUH 2100 BTUH Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 1 144 ft2 15 CFM 4320 BTUH 288 BTUH 2100 BTUH Occupants: Area: Ventilation: Cooling: Latent load: Heating Load: 15 1,512 ft2 170 CFM 30,240 BTUH 3024 BTUH 0 BTUH Office 8 20 BTUH/ft2

(67)

ACB Design Parameters

• Room Conditions:

‒ 75°F db/53% RH ‒ 70°F db winter

• Primary Air Conditions:

‒ 55°F db/51.6 wb (48.7 DP) – Summer & Winter

• Chilled Water

‒ 57°F versus a 56.5°F room dewpoint (53% RH)

• Warm Water

(68)
(69)

ACB Layout

12’ 12’ Office 5 Office 6 TOTAL AREA 2,520 FT2 Office 7 Office 4 DOAS Max. O/A 485 CFM S/A R/A VAV V A V A C B A1 A C B A2 ACBA3 A C B A8 b A C B A8 a A C B A8 f A C B A8 e

ACBA4 ACBA5 ACBA6 ACBA7

PRIM. AIR Min. 15 CFM Max. 35 CFM PRIM. AIR Min. 15 CFM Max. 35 CFM PRIM. AIR Min. 15 CFM Max. 45 CFM PRIM. AIR Min. 15 CFM Max. 25 CFM PRIM. AIR Min. 15 CFM Max. 25 CFM PRIM. AIR Min. 15 CFM Max. 25 CFM PRIM. AIR Min. 15 CFM Max. 25 CFM

PRIM. AIR 270 CFM Min. 105 CFM

Max. 215 CFM Max. 270 CFM Office 1 35 BTU’sAHR/FT2 Office 2 35 BTU’sAHR/FT2 Office 3 50 BTU’sAHR/FT2 30 BTU’sA HR/FT2 30 BTU’sA HR/FT2 30 BTU’sA HR/FT2 30 BTU’sA HR/FT2 Internal Offices 20 BTU’sAHR/FT2 A C B A8 d A C B A8 c Min. 170 CFM Min. O/A 275 CFM

(70)

Beam Layout Notes

• 1Away beam in the perimeter offices

‒ Captures solar load, increases beam output ‒ Higher onAcoil temperature

‒ Free’s up ceiling space for lighting ‒ Works well for heating

• Interior office

‒ 2Away throw beams

‒ Check velocity between colliding airstreams ‒ Minimum of 1 beam per 300 ft2

(71)

10Way Perimeter Beam

• Increased on coil temp • Increased cooling output • Less primary air required

(72)
(73)
(74)
(75)

VAV Reheat Design Parameters

• Room Conditions:

‒ 75°F db/50% RH ‒ 70°F db winter

• Primary Air Conditions:

‒ 55°F db/55 wb – Summer & Winter

• Chilled Water

‒ 45°F

• Hot Water

(76)

VAV Layout

Office 1 35 BTU’sAHR/FT2 12’ 12’ Office 2 35 BTU’sAHR/FT2 Office 3

50 BTU’sAHR/FT2 Office 5 Office 6

TOTAL AREA 2,520 FT2 Office 7 Office 4 AHU O/A 275 CFM S/A R/A VAV 7 V A V IO MAX 232 CFM MIN 63 CFM MAX 232 CFM MIN 63 CFM MIN 63 CFM MAX 332 CFM MAX 199 CFM MIN 50 CFM MAX 199 CFM MAX 199 CFM MAX 199 CFM MIN 50 CFM MIN 50 CFM MIN 50 CFM MIN 304 CFM MAX 1,394 CFM VAV 6 VAV 5 VAV 4 V A V 2 V A V 1 Internal Offices 20 BTU’sAHR/FT2 30 BTU’sA HR/FT2 30 BTU’sA HR/FT2 30 BTU’sA HR/FT2 30 BTU’sA HR/FT2 E/A 275 CFM Max. 2986 CFM Min. 693 CFM

(77)

VAV ACB+DOAS

• Total Air System Size

‒ 565 CFM

• Airflow @ Max Turndown

‒ 275 CFM

• Max. Airflow

‒ 0.22 CFM/FT2

• Min. Average Airflow

‒ 0.11 CFM CFM/FT2

• Airflow @ 60% Load

‒ 0.11 CFM FT2

• Total Air System Size

‒ 2986 CFM

• Airflow @ Max Turndown

‒ 693 CFM

• Max. Airflow

‒ 1.18 CFM/FT2

• Min. Average Airflow

‒ 0.27 CFM CFM/FT2

• Airflow @ 60% Load

‒ 0.71 CFM FT2

Summary Comparison

(78)
(79)

References

Related documents

Small Turbine Heat Recovery Unit Water In Hot Water Absorption Chiller Chilled Water Return Chilled Water Supply Cooling Tower Electricity Output Fuel Input Exhaust

Heated and Chilled Plasterboard Ceiling, clipped-in heat conducting profile Suspension channel as primary and secondary grid, heating/cooling technology clipped-in by means of

A device whose primary purpose is the transfer of heat energy between two fluids at different temperature is named a heat exchanger. A heat exchanger may be defined as equipment

The main objective of the study is to configure the size of heat exchanger for cooling of turbine air intake using chilled water from steam absorption chiller to

Safety Valve Flash Recovery Vessel Strainer Float & Thermostatic Steam Trap Strainer Heat Exchanger Pressure Powered Pump To Condensate Return Vacuum Breaker Cool Return

The second supply connection is a mix of water from the primary part of the heat exchanger and the return flow from the heat distribution system (e.g. baseboard convectors).

The impact of heat load strength and positioning on the indoor environment generated by diffuse ceiling air supply and chilled beam with radial swirl jet was

Fully closed single primary water circuit Exhaust gas heat exchanger in primary circuit PHE between primary and secondary circuits Auto heat output modulation. Auto heat