• No results found

Relay Setting Study

N/A
N/A
Protected

Academic year: 2021

Share "Relay Setting Study"

Copied!
160
0
0

Loading.... (view fulltext now)

Full text

(1)

X Gas Field Development (Phases

Gas Field Development (Phases

CONTRACT NO.

PROJECT

COMPANY

SITE

0

Rev.

DOCUMENT

Doc. No. :

Gas Field Development (Phases X

)

CONTRACT NO.

PROJECT

COMPANY

23/05/08

Date

X

Project No. :

DOCUMENT

No.

RELAY SETTING

STUDY

Doc. No. :

NC-)

RELAY SETTING

: ONS

: X

(PHASES

FROM MPC

: X

: X

Issued for

Description

GAS FIELD DEVELOPMENT

PHASES

ONSHORE FACILITIES

Project No. : ONS-09-0

132kV TEMPORARY POWER

RELAY SETTING

NC-RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

RELAY SETTING

ONS-09-0-CO

X GAS FIELD DEVELOPMENT

(PHASES X)

FROM MPC

X

X GAS FIELD

Issued for Approval

Description

GAS FIELD DEVELOPMENT

PHASES X,

ONSHORE FACILITIES

0-CO-4127

32kV TEMPORARY POWER

FROM MPC

RELAY SETTING

-6340S-550-1600

RELAY SETTING

(CT2000:5)

1600-0004

)

RELAY SETTING

CO-4127

GAS FIELD DEVELOPMENT

)-132kV TEMPORARY POWER

FROM MPC

GAS FIELD

Approval

Hir.

ORIGI

GAS FIELD DEVELOPMENT –

,

ONSHORE FACILITIES

32kV TEMPORARY POWER

FROM MPC

RELAY SETTING STUDY

1600-0004

Rev. No. :

RELAY SETTING STUDY

GAS FIELD DEVELOPMENT

132kV TEMPORARY POWER

Hir.

S.M.K.

ORIGI

PRPD

Doc. Class :

32kV TEMPORARY POWER

FROM MPC

STUDY(CT2000:5)

Sh. No.

0

STUDY

132kV TEMPORARY POWER

S.M.K.

S.M.K.

PRPD

CHKD

Scale :

32kV TEMPORARY POWER

(CT2000:5)

No. :

1 of

Page 1

132kV TEMPORARY POWER

A.F.

APP’

D

CONT. APPRD.

Scale : NTS

of 158

Rev. 0

1 of 158

ONT. PPRD.

0

(2)

PAGE

REV

Doc. No. :

REV PAGE

RELAY SETTING

STUDY

Doc. No. :

NC-TABULATION OF REVISED PAGES

REV PAGE

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

TABULATION OF REVISED PAGES

PAGE

REV

RELAY SETTING

(CT2000:5)

1600-0004

TABULATION OF REVISED PAGES

PAGE

Rev. No. :

TABULATION OF REVISED PAGES

REV PAGE

0

(3)

X Gas Field Development (Phases

Gas Field Development (Phases

1. INTRODUCTION

2. SCOPE

3. SYSTEM DESCRIPTIO

3.1.Reference Documents

3.2.System Analysis Software

3.3. Electrical System Representation

4. CALCULATION CRITERIA

5. LOAD FLOW AND FAULT

6. RELAY TYPE AND LOCAT

7. RELAY SETTINGS

8. RESULTS

9. TRANSIENT ACTIONS

9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY

9.2 TRANSIENTS CHECKS

10.0 OTHER PARAMETERS TO BE SET

10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR

10.2 INRUSH CURRENT SETTINGS

11. CONCLUSIONS

Doc. No. :

Gas Field Development (Phases X

)

1. INTRODUCTION

3. SYSTEM DESCRIPTIO

3.1.Reference Documents

System Analysis Software

3.3. Electrical System Representation

CALCULATION CRITERIA

LOAD FLOW AND FAULT

RELAY TYPE AND LOCAT

RELAY SETTINGS

8. RESULTS

9. TRANSIENT ACTIONS

9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY

9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY

9.1.2 Under voltage, Bus Transfer

TRANSIENTS CHECKS

10.0 OTHER PARAMETERS TO BE SET

10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR

10.2 INRUSH CURRENT SETTINGS

. CONCLUSIONS

RELAY SETTING

STUDY

Doc. No. :

NC-)

3. SYSTEM DESCRIPTION AND INPUT DATA

3.1.Reference Documents

System Analysis Software

3.3. Electrical System Representation

CALCULATION CRITERIA

LOAD FLOW AND FAULT RESULTS

RELAY TYPE AND LOCATIONS

9. TRANSIENT ACTIONS

9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY

9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY

9.1.2 Under voltage, Bus Transfer

TRANSIENTS CHECKS

10.0 OTHER PARAMETERS TO BE SET

10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR

10.2 INRUSH CURRENT SETTINGS

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

TABLE OF CONTENTS

N AND INPUT DATA

System Analysis Software

3.3. Electrical System Representation

3.3.1.Network Topology

3.3.2. Network Parameters and Data

RESULTS

9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY

9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY

9.1.2 Under voltage, Bus Transfer

10.0 OTHER PARAMETERS TO BE SET

10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR

10.2 INRUSH CURRENT SETTINGS

RELAY SETTING

(CT2000:5)

1600-0004

)

TABLE OF CONTENTS

3.3.1.Network Topology

3.3.2. Network Parameters and Data

9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY

9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY

9.1.2 Under voltage, Bus Transfer

10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR

Rev. No. :

TABLE OF CONTENTS

3.3.1.Network Topology

3.3.2. Network Parameters and Data

9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY

9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY

10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR

0

3.3.2. Network Parameters and Data

9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY

9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY

Page 3

9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY SIMULATION

3 of 158

SIMULATION

(4)

A.I.1 GAS

A.I.2 INPUT DATA

A.I.3LOAD FLOW

A.I.4SHORT CIRCUIT ANALYSIS

A.I.5 DYNAMIC STUDIES

A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK

A.I.7 INTENDED STUDY SYSTEM

APPENDIX I

STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT

A.I.1 GAS PLANT ELECTRICAL NETWORK REPRESENTATION

A.I.2 INPUT DATA

A.I.3LOAD FLOW

A.I.4SHORT CIRCUIT ANALYSIS

A.I.5 DYNAMIC STUDIES

A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK

A.I.7 INTENDED STUDY SYSTEM

Doc. No. :

APPENDIX I

STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT

PLANT ELECTRICAL NETWORK REPRESENTATION

A.I.4SHORT CIRCUIT ANALYSIS

A.I.5 DYNAMIC STUDIES

A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK

A.I.7 INTENDED STUDY SYSTEM

RELAY SETTING

STUDY

Doc. No. :

NC-STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT

PLANT ELECTRICAL NETWORK REPRESENTATION

A.I.4SHORT CIRCUIT ANALYSIS

A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK

A.I.7 INTENDED STUDY SYSTEM

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT

PLANT ELECTRICAL NETWORK REPRESENTATION

A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK

RELAY SETTING

(CT2000:5)

1600-0004

STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT

PLANT ELECTRICAL NETWORK REPRESENTATION

A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK

Rev. No. :

STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT

A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK

0

(5)

X Gas Field Development (Phases

-Attachments

NC-6340S

NC-6340S

Gas Field Development (Phases

Attachments

6340S-550-1600-0004

6340S-550-1600-0004

Doc. No. :

Gas Field Development (Phases X

)

Attachments

0004-RELAY SETTING STUDY

0004-RELAY SETTING STUDY

RELAY SETTING

STUDY

Doc. No. :

NC-)

RELAY SETTING STUDY

RELAY SETTING STUDY

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

RELAY SETTING STUDY-AT01(CT2000:5)

RELAY SETTING STUDY-AT02(CT2000:5)

RELAY SETTING

(CT2000:5)

1600-0004

)

(CT2000:5)

(CT2000:5)

Rev. No. :

0

Page 5

5 of 158

(6)

1.

INTRODUCTION

The phase

hydrocarbon fluid by the sub

of

The Temporary Electrical Power required for phases

Mobi

transformer.

Six generators that are connected to the

that contains 132kV cable and 13

The

2. SCOPE

The objective of this document is to do relay settings and coordination analysis for temporary supply

the

in document

The results of this study provide the exact settings of the

must be

3. SYSTEM DESCRIPTION AND INPUT DATA

3.1.

DW 6340S 120 1633 0001

NC 6340S 120 1634 0001

NC 6340S 999 1630 0020

NC

VP 6340S 1600 LG 0001 077

NC 6340S 550 1600 001

NC 6340S 550 1600 002

NC 6340S 550 1600 003

NC 6340S 550 1600 005

SLD 6340S 550 1600 0002

INTRODUCTION

The phases X

hydrocarbon fluid by the sub

of X city.

The Temporary Electrical Power required for phases

Mobin Petrochemical Complex through 132

transformer.

Six generators that are connected to the

that contains 132kV cable and 13

The temporary supply relay setting

SCOPE

The objective of this document is to do relay settings and coordination analysis for temporary supply

the 33KV outgoing to the

in document VP 6340S 1600 LG 0001 077

The results of this study provide the exact settings of the

must be tuned before commissioning of the plant.

SYSTEM DESCRIPTION AND INPUT DATA

Reference Documents

DW 6340S 120 1633 0001

NC 6340S 120 1634 0001

NC 6340S 999 1630 0020

NC 6340S 999 1630 0021

VP 6340S 1600 LG 0001 077

NC 6340S 550 1600 001

NC 6340S 550 1600 002

NC 6340S 550 1600 003

NC 6340S 550 1600 005

SLD 6340S 550 1600 0002

Doc. No. :

INTRODUCTION

X within the

hydrocarbon fluid by the sub

The Temporary Electrical Power required for phases

n Petrochemical Complex through 132

Six generators that are connected to the

that contains 132kV cable and 13

temporary supply relay setting

The objective of this document is to do relay settings and coordination analysis for temporary supply

33KV outgoing to the Gas plant relays that are coordinated

VP 6340S 1600 LG 0001 077

The results of this study provide the exact settings of the

tuned before commissioning of the plant.

SYSTEM DESCRIPTION AND INPUT DATA

Reference Documents

DW 6340S 120 1633 0001

NC 6340S 120 1634 0001

NC 6340S 999 1630 0020

6340S 999 1630 0021

VP 6340S 1600 LG 0001 077

NC 6340S 550 1600 001

NC 6340S 550 1600 002

NC 6340S 550 1600 003

NC 6340S 550 1600 005

SLD 6340S 550 1600 0002

RELAY SETTING

STUDY

Doc. No. :

NC-within the X Gas Field Development project

hydrocarbon fluid by the sub-marine pipelines. The refinery is located at

The Temporary Electrical Power required for phases

n Petrochemical Complex through 132

Six generators that are connected to the

that contains 132kV cable and 132/33kV transformer.

temporary supply relay setting and coordination studies are described in this document.

The objective of this document is to do relay settings and coordination analysis for temporary supply

Gas plant relays that are coordinated

VP 6340S 1600 LG 0001 077

The results of this study provide the exact settings of the

tuned before commissioning of the plant.

SYSTEM DESCRIPTION AND INPUT DATA

General Single Line Diagram

Electrical Load Summary

Short Circuit and Load Flow Study

Dynamic Stability Study

VP 6340S 1600 LG 0001 077 (Issued with no name)

Switching Overvoltage Study

Load Flow Study

Short Circuit Study

Motor Starting Study

Single Line Diagram

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

Gas Field Development project

marine pipelines. The refinery is located at

The Temporary Electrical Power required for phases

n Petrochemical Complex through 132kv underground cable line and a 132kV/33

Six generators that are connected to the X National grid are assumed to supply electric power through circuit

2/33kV transformer.

and coordination studies are described in this document.

The objective of this document is to do relay settings and coordination analysis for temporary supply

Gas plant relays that are coordinated

VP 6340S 1600 LG 0001 077.

The results of this study provide the exact settings of the

tuned before commissioning of the plant.

SYSTEM DESCRIPTION AND INPUT DATA

General Single Line Diagram

Electrical Load Summary

Short Circuit and Load Flow Study

Dynamic Stability Study

(Issued with no name)

Switching Overvoltage Study

Load Flow Study made by TOM

Short Circuit Study made by T

Motor Starting Study

Single Line Diagram

RELAY SETTING

(CT2000:5)

1600-0004

Gas Field Development project

marine pipelines. The refinery is located at

The Temporary Electrical Power required for phases X Gas Plant shall be supplied from Power Plan

v underground cable line and a 132kV/33

National grid are assumed to supply electric power through circuit

2/33kV transformer.

and coordination studies are described in this document.

The objective of this document is to do relay settings and coordination analysis for temporary supply

Gas plant relays that are coordinated by another vendor and made available to us

The results of this study provide the exact settings of the concerned

SYSTEM DESCRIPTION AND INPUT DATA

General Single Line Diagram

Electrical Load Summary

Short Circuit and Load Flow Study

Dynamic Stability Study

(Issued with no name)

Switching Overvoltage Study made by TOM

made by TOM

made by TOM

made by TOM

Rev. No. :

Gas Field Development project are designed to process the incoming

marine pipelines. The refinery is located at X Village, about 270 km South

Gas Plant shall be supplied from Power Plan

v underground cable line and a 132kV/33

National grid are assumed to supply electric power through circuit

and coordination studies are described in this document.

The objective of this document is to do relay settings and coordination analysis for temporary supply

by another vendor and made available to us

concerned relays of the temporary supply

Short Circuit and Load Flow Study

made by TOM

OM

made by TOM

0

designed to process the incoming

X Village, about 270 km South

Gas Plant shall be supplied from Power Plan

v underground cable line and a 132kV/33kV, 100MVA power

National grid are assumed to supply electric power through circuit

and coordination studies are described in this document.

The objective of this document is to do relay settings and coordination analysis for temporary supply

by another vendor and made available to us

of the temporary supply

designed to process the incoming

X Village, about 270 km South East

Gas Plant shall be supplied from Power Plan

, 100MVA power

National grid are assumed to supply electric power through circuit

The objective of this document is to do relay settings and coordination analysis for temporary supply up to

by another vendor and made available to us

of the temporary supply which

designed to process the incoming

East

Gas Plant shall be supplied from Power Plant of

, 100MVA power

National grid are assumed to supply electric power through circuit

up to

by another vendor and made available to us

(7)

X Gas Field Development (Phases

3.2.

PASHA (Power Apparatus and System Homological Analysis), Version

studies. The software is product of TOM and serving the electrical utilities and the industries

years worldwide.

3.3.

Single line diagram

view of the overall electrical network represented in the present studies.

Gas plant is analyzed and equalized in Appendix I.

line diagram as represented in

Documents

Here,

loads are

induction motor loads are summed and represented as equivalent m

bars.

detailed representation of GAS PLANT electrical systems.

Figure 2 shows the electrical network representation whe

PLANT is represented inside the network, please see also drawing

6340S 550 1600 000

represented

are selected such that the

comes from the overall

documentation and reportings easiear.

In

and the

Therefore, they are included in the representation of the electrical networks as

report the neighboring factories are

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

side of the external plants cannot

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

all the motor fault contribu

shown in

Gas Field Development (Phases

System Analysis Software

PASHA (Power Apparatus and System Homological Analysis), Version

studies. The software is product of TOM and serving the electrical utilities and the industries

years worldwide.

Electrical System Representation

3.3.1. Network Topology

Single line diagram

view of the overall electrical network represented in the present studies.

Gas plant is analyzed and equalized in Appendix I.

line diagram as represented in

Documents NC 6340S 999 1630 0020

Here, 11 KV motor loads are represented separately based on their dynamic models.

loads are also

induction motor loads are summed and represented as equivalent m

bars. Static loads are lumped represented on their appropriate locations.

detailed representation of GAS PLANT electrical systems.

Figure 2 shows the electrical network representation whe

PLANT is represented inside the network, please see also drawing

6340S 550 1600 000

represented as

are selected such that the

comes from the overall

documentation and reportings easiear.

n fault and relay coordination studies

and their contributions

Therefore, they are included in the representation of the electrical networks as

report the neighboring factories are

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

side of the external plants cannot

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

all the motor fault contribu

shown in EXTERNAL

Doc. No. :

Gas Field Development (Phases X

)

System Analysis Software

PASHA (Power Apparatus and System Homological Analysis), Version

studies. The software is product of TOM and serving the electrical utilities and the industries

years worldwide.

Electrical System Representation

Network Topology

Single line diagram of the involving

view of the overall electrical network represented in the present studies.

Gas plant is analyzed and equalized in Appendix I.

line diagram as represented in

NC 6340S 999 1630 0020

KV motor loads are represented separately based on their dynamic models.

also represented separately based on their dynamic models

induction motor loads are summed and represented as equivalent m

Static loads are lumped represented on their appropriate locations.

detailed representation of GAS PLANT electrical systems.

Figure 2 shows the electrical network representation whe

PLANT is represented inside the network, please see also drawing

6340S 550 1600 0001 at the end of this report inside appendix I.

as equivalent induction motor

are selected such that the

comes from the overall loads and

documentation and reportings easiear.

fault and relay coordination studies

ir contributions in device

Therefore, they are included in the representation of the electrical networks as

report the neighboring factories are

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

side of the external plants cannot

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

all the motor fault contributions to short circuit are congregated in the coupled bus.

EXTERNAL area in Figure 2.

RELAY SETTING

STUDY

Doc. No. :

NC-)

System Analysis Software

PASHA (Power Apparatus and System Homological Analysis), Version

studies. The software is product of TOM and serving the electrical utilities and the industries

Electrical System Representation

of the involving plants are

view of the overall electrical network represented in the present studies.

Gas plant is analyzed and equalized in Appendix I.

line diagram as represented in drawing

NC 6340S 999 1630 0020,

KV motor loads are represented separately based on their dynamic models.

represented separately based on their dynamic models

induction motor loads are summed and represented as equivalent m

Static loads are lumped represented on their appropriate locations.

detailed representation of GAS PLANT electrical systems.

Figure 2 shows the electrical network representation whe

PLANT is represented inside the network, please see also drawing

at the end of this report inside appendix I.

equivalent induction motor

are selected such that the static power requirment

loads and induction motors existing i

documentation and reportings easiear. The

fault and relay coordination studies we need to consider the maximum planed and in operation fault level

in device setting studies. The neighboring factories play important rule in this regard.

Therefore, they are included in the representation of the electrical networks as

report the neighboring factories are called

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

side of the external plants cannot be closed together.

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

tions to short circuit are congregated in the coupled bus.

area in Figure 2.

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

PASHA (Power Apparatus and System Homological Analysis), Version

studies. The software is product of TOM and serving the electrical utilities and the industries

plants are used to

view of the overall electrical network represented in the present studies.

Gas plant is analyzed and equalized in Appendix I. For the purpose of the equalization, the Gas Plant, single

drawing DW 6340S 120 1633 0001

, NC 6340S 999 1630 002

KV motor loads are represented separately based on their dynamic models.

represented separately based on their dynamic models

induction motor loads are summed and represented as equivalent m

Static loads are lumped represented on their appropriate locations.

detailed representation of GAS PLANT electrical systems.

Figure 2 shows the electrical network representation whe

PLANT is represented inside the network, please see also drawing

at the end of this report inside appendix I.

equivalent induction motors and loads

power requirment and the dynamic behaviour

induction motors existing i

The Gas plant

we need to consider the maximum planed and in operation fault level

studies. The neighboring factories play important rule in this regard.

Therefore, they are included in the representation of the electrical networks as

called External plants

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

be closed together.

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

tions to short circuit are congregated in the coupled bus.

RELAY SETTING

(CT2000:5)

1600-0004

)

PASHA (Power Apparatus and System Homological Analysis), Version

studies. The software is product of TOM and serving the electrical utilities and the industries

used to produce the study power system. Figure 1

view of the overall electrical network represented in the present studies.

For the purpose of the equalization, the Gas Plant, single

DW 6340S 120 1633 0001

NC 6340S 999 1630 002

KV motor loads are represented separately based on their dynamic models.

represented separately based on their dynamic models

induction motor loads are summed and represented as equivalent m

Static loads are lumped represented on their appropriate locations.

detailed representation of GAS PLANT electrical systems.

Figure 2 shows the electrical network representation where the static and dynamic equivalent of the GAS

PLANT is represented inside the network, please see also drawing

at the end of this report inside appendix I.

and loads. The parameters of the equivalent induction motors

and the dynamic behaviour

induction motors existing i

Gas plant equivalent is shown in

we need to consider the maximum planed and in operation fault level

studies. The neighboring factories play important rule in this regard.

Therefore, they are included in the representation of the electrical networks as

xternal plants. The external plants are represented by their

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

be closed together. Maximum fault current contribution

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

tions to short circuit are congregated in the coupled bus.

Rev. No. :

PASHA (Power Apparatus and System Homological Analysis), Version 2008, was used for performing the

studies. The software is product of TOM and serving the electrical utilities and the industries

produce the study power system. Figure 1

view of the overall electrical network represented in the present studies.

For the purpose of the equalization, the Gas Plant, single

DW 6340S 120 1633 0001 is represented

NC 6340S 999 1630 0021 are used to provide the required data.

KV motor loads are represented separately based on their dynamic models.

represented separately based on their dynamic models. Other 6KV motors and

induction motor loads are summed and represented as equivalent motor loads on

Static loads are lumped represented on their appropriate locations. Please refer to appendix I for

re the static and dynamic equivalent of the GAS

PLANT is represented inside the network, please see also drawing DW 6340S 550 1600 0002

at the end of this report inside appendix I. The dynamic loads

. The parameters of the equivalent induction motors

and the dynamic behaviour

induction motors existing in the Gas Plant.

valent is shown in GASEQUAL

we need to consider the maximum planed and in operation fault level

studies. The neighboring factories play important rule in this regard.

Therefore, they are included in the representation of the electrical networks as

. The external plants are represented by their

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

aximum fault current contribution

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

tions to short circuit are congregated in the coupled bus.

0

, was used for performing the

studies. The software is product of TOM and serving the electrical utilities and the industries

produce the study power system. Figure 1

For the purpose of the equalization, the Gas Plant, single

is represented in PASHA software.

are used to provide the required data.

KV motor loads are represented separately based on their dynamic models. Some of 6

Other 6KV motors and

otor loads on their corresponding bus

Please refer to appendix I for

re the static and dynamic equivalent of the GAS

DW 6340S 550 1600 0002

The dynamic loads of this plant

. The parameters of the equivalent induction motors

and the dynamic behaviour of the load matches those

n the Gas Plant. Equalization, makes

GASEQUAL area in Figure 2.

we need to consider the maximum planed and in operation fault level

studies. The neighboring factories play important rule in this regard.

Therefore, they are included in the representation of the electrical networks as it is shown in Figure 2. In this

. The external plants are represented by their

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars o

aximum fault current contributions

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

tions to short circuit are congregated in the coupled bus. The external plants are

Page 7

, was used for performing the

studies. The software is product of TOM and serving the electrical utilities and the industries for twenty three

produce the study power system. Figure 1 shows a

For the purpose of the equalization, the Gas Plant, single

in PASHA software.

are used to provide the required data.

Some of 6 KV motor

Other 6KV motors and 400 V

their corresponding bus

Please refer to appendix I for

re the static and dynamic equivalent of the GAS

DW 6340S 550 1600 0002

,

and

DW

of this plant

. The parameters of the equivalent induction motors

of the load matches those

Equalization, makes

area in Figure 2.

we need to consider the maximum planed and in operation fault level

studies. The neighboring factories play important rule in this regard.

shown in Figure 2. In this

. The external plants are represented by their

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

transformer of these plants is also considered in the studies. This is because the bus bars on 20KV or 33KV

s of these plants

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

The external plants are

7 of 158

, was used for performing the

for twenty three

hows a

For the purpose of the equalization, the Gas Plant, single

in PASHA software.

are used to provide the required data.

KV motor

400 V

their corresponding bus

Please refer to appendix I for

re the static and dynamic equivalent of the GAS

DW

of this plant are

. The parameters of the equivalent induction motors

of the load matches those

Equalization, makes

area in Figure 2.

we need to consider the maximum planed and in operation fault levels

studies. The neighboring factories play important rule in this regard.

shown in Figure 2. In this

. The external plants are represented by their

lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming

or 33KV

of these plants

are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore

The external plants are

(8)

The existence of the connection of

This is shown in Figure 2

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of th

represented in this report.

The box

feeds

motor

11KV

As mentioned the equalization is just made to simplify the reporting, the actual

considered inside the Gas plant

The existence of the connection of

This is shown in Figure 2

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of th

represented in this report.

The box RELAY

feeds the various substations

motors of the Gas plant

11KV area.

As mentioned the equalization is just made to simplify the reporting, the actual

considered inside the Gas plant

Doc. No. :

The existence of the connection of

This is shown in Figure 2 in

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of th

represented in this report.

RELAY is introduced inside the

the various substations

s of the Gas plant is also considered. The selected equivalent motors are intdicated in Figure 2 in

As mentioned the equalization is just made to simplify the reporting, the actual

considered inside the Gas plant

RELAY SETTING

STUDY

Doc. No. :

NC-The existence of the connection of MOB

in GRID area. The

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of th

is introduced inside the

the various substations inside the Gas plant. The bahaviour of 33KV relays protecting the

is also considered. The selected equivalent motors are intdicated in Figure 2 in

As mentioned the equalization is just made to simplify the reporting, the actual

considered inside the Gas plant but it does not included in the reports.

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

MOBIN power generation plant to

. The detailed representation of the X

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of th

is introduced inside the Gas plant equivalent to consider for the outgoing 33KV relays

inside the Gas plant. The bahaviour of 33KV relays protecting the

is also considered. The selected equivalent motors are intdicated in Figure 2 in

As mentioned the equalization is just made to simplify the reporting, the actual

but it does not included in the reports.

RELAY SETTING

(CT2000:5)

1600-0004

power generation plant to

detailed representation of the X

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of th

Gas plant equivalent to consider for the outgoing 33KV relays

inside the Gas plant. The bahaviour of 33KV relays protecting the

is also considered. The selected equivalent motors are intdicated in Figure 2 in

As mentioned the equalization is just made to simplify the reporting, the actual

but it does not included in the reports.

Rev. No. :

power generation plant to X National GRID

detailed representation of the X national power grid is already

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of th

Gas plant equivalent to consider for the outgoing 33KV relays

inside the Gas plant. The bahaviour of 33KV relays protecting the

is also considered. The selected equivalent motors are intdicated in Figure 2 in

As mentioned the equalization is just made to simplify the reporting, the actual

but it does not included in the reports.

0

National GRID is also considered.

national power grid is already

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

network which includes the 63KV of the Esfahan is used to provide the equivalent of the power grid as

Gas plant equivalent to consider for the outgoing 33KV relays

inside the Gas plant. The bahaviour of 33KV relays protecting the

is also considered. The selected equivalent motors are intdicated in Figure 2 in

As mentioned the equalization is just made to simplify the reporting, the actual 33KV relays behavior is also

is also considered.

national power grid is already

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the

e power grid as

Gas plant equivalent to consider for the outgoing 33KV relays that

inside the Gas plant. The bahaviour of 33KV relays protecting the 11KV

is also considered. The selected equivalent motors are intdicated in Figure 2 in

relays behavior is also

is also considered.

national power grid is already

represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the X

e power grid as

that

11KV

is also considered. The selected equivalent motors are intdicated in Figure 2 in

(9)

X Gas Field Development (Phases

Figure 1: The overall view of the study system

Gas Field Development (Phases

Figure 1: The overall view of the study system

Doc. No. :

Gas Field Development (Phases X

)

Figure 1: The overall view of the study system

RELAY SETTING

STUDY

Doc. No. :

NC-)

Figure 1: The overall view of the study system

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

Figure 1: The overall view of the study system

RELAY SETTING

(CT2000:5)

1600-0004

)

Rev. No. :

0

Page 9

9 of 158

(10)

Figure 2: The study system

Figure 2: The study system

Doc. No. :

Figure 2: The study system

RELAY SETTING

STUDY

Doc. No. :

of this report

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

of this report; Gas plant equivalent (Appedix I) is introduced

RELAY SETTING

(CT2000:5)

1600-0004

; Gas plant equivalent (Appedix I) is introduced

Rev. No. :

; Gas plant equivalent (Appedix I) is introduced

0

(11)

X Gas Field Development (Phases

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

which includes the drawn equipment data on system

Table 1

dynamic loads are represented with type

8000000

appenix I.

Table 2 shows the system parameters after base conversion.

considered equal to 14.3 km per phase.

Appendix I.

Gas Field Development (Phases

3.3.2. Network Parameters and Data

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

which includes the drawn equipment data on system

Table 1 contain

dynamic loads are represented with type

8000000 to 89

appenix I.

Table 2 shows the system parameters after base conversion.

considered equal to 14.3 km per phase.

Appendix I.

Doc. No. :

Gas Field Development (Phases X

)

Network Parameters and Data

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

which includes the drawn equipment data on system

contains the base DATA

dynamic loads are represented with type

8999999. For the detailed data base of the Gas plant equipment please refer to Table I.1 of

Table 2 shows the system parameters after base conversion.

considered equal to 14.3 km per phase.

RELAY SETTING

STUDY

Doc. No. :

NC-)

Network Parameters and Data

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

which includes the drawn equipment data on system

base DATA for equipment parameters

dynamic loads are represented with type

For the detailed data base of the Gas plant equipment please refer to Table I.1 of

Table 2 shows the system parameters after base conversion.

considered equal to 14.3 km per phase.

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

which includes the drawn equipment data on system

for equipment parameters

dynamic loads are represented with types 9000 to 9030 and those lumped loads are represented with type

For the detailed data base of the Gas plant equipment please refer to Table I.1 of

Table 2 shows the system parameters after base conversion.

considered equal to 14.3 km per phase. For GAS PLANT deta

RELAY SETTING

(CT2000:5)

1600-0004

)

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

which includes the drawn equipment data on system base.This is selected

for equipment parameters of the equivalent study system

to 9030 and those lumped loads are represented with type

For the detailed data base of the Gas plant equipment please refer to Table I.1 of

Table 2 shows the system parameters after base conversion. The length of 132KV temporary cable is

For GAS PLANT detailed input data please refer to Table I.2 of

Rev. No. :

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

base.This is selected to be

of the equivalent study system

to 9030 and those lumped loads are represented with type

For the detailed data base of the Gas plant equipment please refer to Table I.1 of

The length of 132KV temporary cable is

iled input data please refer to Table I.2 of

0

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

to be 10MVA.

of the equivalent study system

to 9030 and those lumped loads are represented with type

For the detailed data base of the Gas plant equipment please refer to Table I.1 of

The length of 132KV temporary cable is

iled input data please refer to Table I.2 of

Page 11

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

of the equivalent study system. The equivalent

to 9030 and those lumped loads are represented with type

For the detailed data base of the Gas plant equipment please refer to Table I.1 of

The length of 132KV temporary cable is

iled input data please refer to Table I.2 of

11 of 158

The data are provided in two groups. One is from PASHA data bases which contains the fundamental data

of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages

. The equivalent

to 9030 and those lumped loads are represented with types

For the detailed data base of the Gas plant equipment please refer to Table I.1 of

The length of 132KV temporary cable is

iled input data please refer to Table I.2 of

(12)

CABLE SIZE 1(500) 1(400) 1(800)

Used for Tie connections and those not

known

Note : RATING MVA IS

Doc. No. :

CABLE Type MANUFACT. FICT FICT FICT

Note : RATING MVA IS OBTAINED FROM CABLE CURRENT CAPACITY, RATINGS ARE

RELAY SETTING

STUDY

Doc. No. :

NC-Table 1

P A S H A L IB . 33 6 15

OBTAINED FROM CABLE CURRENT CAPACITY, RATINGS ARE

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

Table 1 Data base for system equipment

CABLES AND LINES

R A T IN G M V A R A T IN G K V 100 33 5 6 160 15

OBTAINED FROM CABLE CURRENT CAPACITY, RATINGS ARE

RELAY SETTING

(CT2000:5)

1600-0004

Data base for system equipment

CABLES AND LINES DATA BASE

R A T IN G K V R E S IS T A N C E P U /K M

OBTAINED FROM CABLE CURRENT CAPACITY, RATINGS ARE

Rev. No. :

Data base for system equipment

DATA BASE

R E A C T A N C E P U /K M 0.0001 0.0001 0.0001

OBTAINED FROM CABLE CURRENT CAPACITY, RATINGS ARE THE PU BASES

0

S U S E P T A N C E P U /K M Z E R O PU BASES Z E R O S E Q U E N C E R E S IS T A N C E -P U /K M Z E R O Z E R O S E Q U E N C E R E A C T A N C E -P U /K M 0.0003 0.0003 0.0003

(13)

X Gas Field Development (Phases

R

A

T

IN

G

(

B

A

S

E

)

M

V

A

*400A grounding resistor considered,

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

Gas Field Development (Phases

R

A

T

IN

G

(

B

A

S

E

)

M

V

A

U

1

/U

2

K

V

/K

V

A grounding resistor considered,

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

Doc. No. :

Gas Field Development (Phases X

)

C

O

N

N

E

C

T

IO

N

T

Y

P

E

*

*

A grounding resistor considered,

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

RELAY SETTING

STUDY

Doc. No. :

NC-)

P

A

S

H

A

L

IB

.

! "" #

$%

%& '"

A grounding resistor considered,

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

TRANSFORMERS

R

E

S

IS

T

A

N

C

E

P

U

R

E

A

C

T

A

N

C

E

P

U

(

%& '"

)

%& '"

*+ "

,-% "'

%&

(

.+

! "" #

$%

%& '"

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

RELAY SETTING

(CT2000:5)

1600-0004

)

TRANSFORMERS DATA BASE

R

E

A

C

T

A

N

C

E

P

U

ZERO SEQUENCE

R

E

S

IS

T

A

N

C

E

P

U

*

(

%& '"

)

%& '"

*+ "

,-% "'

%&

.+

-

%& '"

! "" #

$%

%& '"

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

Rev. No. :

DATA BASE

ZERO SEQUENCE

R

E

S

IS

T

A

N

C

E

P

U

*

R

E

A

C

T

A

N

C

E

P

U

(

%& '"

)

%& '"

/

*+ "

,-% "'

%& '" %

%& '"

! "" #

$%

%& '"

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

0

MI

N

.

T

A

P

/

/

/

/

/

/

/

/

/

/

! "" #

$%

%& '"

/

**X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,

Page 13

T

A

P

S

T

E

P

MA

X

.

T

A

P

13 of 158

R

A

T

IO

D

V

T

y

p

e

o

r

M

A

N

U

F

A

C

T

.

/

T

y

p

e

o

r

M

A

N

U

F

A

C

T

.

(14)

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1

*0. 1 "

*0. 1

*0. 1 "

*0. 1

*0. 1 "

*0. 1

*0. 1 "

*0. 1 "

R A T E D KW

*0. 1 "

*0. 1 "

. 1 "

*0. 1 "

. 1 "

*0. 1 "

. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

*0. 1 "

. 1 "

*0. 1 "

*Driven Typ

Doc. No. :

P A S H A V O L T A G E LIB. KV

*Driven Type: Mechanical

RELAY SETTING

STUDY

Doc. No. :

NC-V O L T A G E B A S E KV MVA REAC T.

Mechanical Torque Formula=(A+B(1

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

MOTORS

MA G N E T IZ IN G REAC T.-PU R E S IS T .-P U

Torque Formula=(A+B(1

RELAY SETTING

(CT2000:5)

1600-0004

MOTORS DATA BASE

STATOR R E S IS T .-P U R E A C T -P U

Torque Formula=(A+B(1-s)+C(1-s)

2

)Tmo where A+B+C=1, B and C is written and s is slip.

Rev. No. :

DATA BASE

R E S IS T .-P U

)Tmo where A+B+C=1, B and C is written and s is slip.

0

ROTOR R E A C T .-P U

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*2

*2

*2

)Tmo where A+B+C=1, B and C is written and s is slip.

Type or Man ufac turer H ( S e c .) (t o ta l)

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*23

*2

*2

*2

)Tmo where A+B+C=1, B and C is written and s is slip.

OTHERS (t o ta l) (d ri v e n ) Driven TYPE*

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

(15)

X Gas Field Development (Phases

Gas Field Development (Phases

R A T E D MVA

*Driven Typ

Doc. No. :

Gas Field Development (Phases X

)

P A S H A V O L T A G E LIB. KV

Type: Mechanical Torque Formula=(A+B(1

RELAY SETTING

STUDY

Doc. No. :

NC-) B A S E MVA REAC

T.-nical Torque Formula=(A+B(1

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

)

LUMPED LOAD

MA G N E T IZ IN G REAC -PU R E S IS T .-P U

nical Torque Formula=(A+B(1

RELAY SETTING

(CT2000:5)

1600-0004

)

LUMPED LOADS DATA BASE

STATOR R E A C T -P U

nical Torque Formula=(A+B(1-s)+C(1-s)

2

)Tmo where A+B+C=1, B and C is written and s is slip.

Rev. No. :

DATA BASE

R E S IS T .-P U

)Tmo where A+B+C=1, B and C is written and s is slip.

0

ROTOR R E A C T .-P U % STATIC

)Tmo where A+B+C=1, B and C is written and s is slip.

Page 15

% STATIC Load H ( S e c .) (t o ta l)

)Tmo where A+B+C=1, B and C is written and s is slip.

15 of 158

OTHERS (t o ta l) (d ri v e n ) Driven TYPE*

4

4

4

4

4

4

4

4

4

(16)

PASHA

LIB.

RATED

POWER

MVA

*10A grounding resistor considered

X'd

RATED

POWER

TYPE

% .

"

. % .

"

Doc. No. :

A grounding resistor considered

DIRECT AXIS

'd

RATED

VOLTAGE

KV

% .

"

. % .

"

RELAY SETTING

STUDY

Doc. No. :

NC-A grounding resistor considered

DIRECT AXIS

X"d

RATED

PASHA

VOLTAGE

LIB.

RELAY SETTING

STUDY

(CT2000:5)

-6340S-550-1600

GENERATOR DATA BASE

"d

RESISTANCE

PU

RELAY SETTING

(CT2000:5)

1600-0004

GENERATOR DATA BASE

Xq

RESISTANCE REACTANCE

PU

Rev. No. :

GENERATOR DATA BASE

X'q

REACTANCE

PU

RESISTANCE

0

QUADRATURE AXES

X'q

'q

ZERO SEQUENCE

RESISTANCE-PU

5

5

QUADRATURE AXES

'q

X"q

ZERO SEQUENCE

REACTANCE

PU

QUADRATURE AXES

X"q

"q

H

REACTANCE-(SEC)

&

References

Related documents

Exempt form income tax if he is a non-resident citizen 53.Which of the following statement is correctb. The monetized value of unutilized vacation leave credits of ten (10) days or

Such a collegiate cul- ture, like honors cultures everywhere, is best achieved by open and trusting relationships of the students with each other and the instructor, discussions

Acknowledging the lack of empirical research on design rights, our paper wishes to investigate the risk of piracy and the perceptions of the registered and unregistered design

1 Select “Contacts” in the Skype Main Menu and press OK or ENTER7. 2 Select a contact from your contact list who is online and press OK or

countries or with the introduction of rail based infrastructure, this paper will consider whether and to what extent the value of residential land has increased in the area around

We assessed child feces disposal practices based on the wording used in the core questions of the WHO/UNICEF Joint Monitoring Programme on Water and Sanitation (JMP) [20]: ‘‘The

Comparing the quality of control system balancing two-wheel bicycle model using 4th- order reduction controller according to the new algorithm with the 4th-order reduction