Iso Floor Raised Floor System

Optimal modularity for Data Centers, Network Operation Centers, etc. in all seismic zones.

(2)

2

Bergvik company facts

• Bergvik was founded in 1970

• Iso Floor raised floors are used by customers such as Cingular, IBM,T-Mobile, Bell South, Digicel, MTN, Telmex, Vivo, American Movil,

Vodafone, Vodacom, Celtel, Areeva etc in more than 100 countries around the world

• Since 1993, Bergvik has been the sole global supplier of raised floors and seismic bracing to Ericsson, the world leading Telecom Network provider

• Subsidiary in the USA since 2000, customers like AT&T, Bell South, Internap, Hoganas, Rettenmeier etc have seen the advantages.

The fully automated 65,000 SF factory in Bergvik, Sweden

(3)

Secure raised floor solutions

for your Data Center

The right floor should be strong and modular

Bergvik, a world-renowned raised floor supplier, offers a series of raised flooring systems engineered for use in all seismic zones. Adapted to accommodate all types of equipment and designed with room to

expand, the Bergvik Iso Floor is a flexible, secure and cost competitive solution for your Data Center flooring needs.

Proven mechanical strength

Bergvik has developed and adapted a series of three different raised floor designs to

(4)

4

Cost saving features using Iso Floor

IT Perspective:

• Only 2 grounding lug points diagonally per room are needed to provide a high potential to the main ground bar.

(5)

Cost saving features using Iso Floor

IT Perspective:

• No additional steel substructures needed for heavy equipment like CRAC air conditioner units, UPS and Rectifiers since floor offers modular loading capabilities, making it easy to add pedestals and steel beams.

(6)

6

Cost saving features using Iso Floor

IT Perspective:

• Directional air grille panel option forcing more of the cold air directly onto the face of the equipment.

(7)

Cost saving features using Iso Floor

Infrastructure Perspective:

• All floor panels can be removed without effecting the structural-integrity and the stability of the floor.

(8)

8

Cost saving features using Iso Floor

Infrastructure Perspective:

• Open bottom access for the racks and cabinets can be provided using 1½ inch (38x38mm) square tubing bolted on top of the framework.

(9)

Cost saving features using Iso Floor

Infrastructure Perspective:

• More useable space between pedestals compared to conventional raised floors with 24” spacing.

(10)

10

Cost saving features using Iso Floor

Infrastructure Perspective:

• As an option we can provide the floor with stepless cable ladder brackets to reduce installation time.

(11)

Cost saving features using Iso Floor

Infrastructure Perspective:

• Optimization of Data Center floor space is possible due to the different panel size option. Up to 25% more equipment on the same room footprint.

(12)

12

Infrastructure Perspective:

• Using conventional raised floors, threaded rod tip protection is needed to secure heavy equipment.

(13)

Cost saving features using Iso Floor

Infrastructure Perspective:

(14)

14

Infrastructure Perspective:

• Using conventional raised floors, bridging is needed due to the set 24” spacing between pedestals.

(15)

Cost saving features using Iso Floor

Infrastructure Perspective:

• No bridging needed due to flexible spacing between pedestals. Even

heavy transformers or UPS can be transported and mounted by decreasing the space between pedestals.

(16)

16

Maximum cooling of Blade Servers can be achived

by using optional Bergvik solutions

(17)

Iso Floor design for seismic zone 1-2

Bergvik’s floor design for NEBS Zone 1– 2 offers the same stable construction as our base model but with additional

reinforcements to

accommodate a higher risk of seismic activity.

Strengthened with a 60 x 60 mm pedestal anchored to the sub-floor with steel plate connections between primary and secondary steel sections, the Iso Floor model fulfills the requirements for seismic

reliability according to NEBS. This floor has passed both calculated stress as well as

(18)

18

Iso Floor design for seismic zone 3-4

The Bergvik raised floor designed for NEBS Zone 3-4 is the most secure product on the market today. The addition of solid bracing frames anchored to the concrete sub-floor provides the strength and stability to withstand severe seismic activity.

This Bergvik raised floor system fulfills all the requirements for seismic reliability according to NEBS. The frames have passed both calculated stress as well as dynamic full-scale tests in

accordance with NEBS GR-63 and NEBS GR-2930.

Floor Heights available in 14-36 inch (350 to 910 mm). Seismic bracing frames integrated with the raised floor have pre-torqued cross bracing rods, therefore no tightening is needed following an earthquake.

(19)

Iso Floor accessories

Panel lifter

Steps, ramps, border fascia, guard rail Pre-cut panels for cable intake

(20)

20

High loads on standard panel with minimum

permanent deflection due to high e-module

Concentrated Load in aisle:

P = 1500 lbs (680 kg) gives 0.18” (4.7 mm) temporary deflection

P = 2000 lbs (908 kg) gives 0.24” (6.1 mm) temporary deflection

Permanent deflection after 5000 times = 0.004 inch (0.1 mm).

Rolling Load, CISCA Test:

P = 600 lbs (272 kg) using a 6” diam x 1.5” wide Alathane wheel.

Permanent deflection after 10000 passes = 0.009 inch (0.2 mm).

(21)

Standard panel construction and

panel options

Suitable for most applications, the standard panel consists of a 1½" (38 mm) high

density HD particleboard,

moisture-resistant quality V313. The bottom side is laminated with aluminum. Standard panels weigh only 22 lbs. Flame spread is 20

(class 1) in accordance with ASTM E84 / NFPA 266 / UL 723.

As an option we offer a high density, all non-combustible calcium sulphate panel if there are limitations on the amount of combustible materials to be used in

(22)

22

Bergvik Laminate finish

Decor: M335 Granite

• Extremely wear resistant

• Easy to clean – even the most difficult stains

• Direct-laminated without glue, which could work loose.

• Surface to ground resistivity: < 2x1011 Ohms at min 40% RH.

Other surface finishes such as vinyl,

linoleum or carpet tiles are available upon request.

Decor: A287 Oak

(23)

Tapered panel edges

Attractive, functional and safe

When floor panels are removed and other

surrounding panels shift (which will happen), the unique tapered panel edge design of the Iso Floor allows the removed panels to “self adjust” and go back flush to prevent tripping.

The thin edge trim gives the floor an aesthetically pleasing appearance by making the panel edges virtually

disappear into the flooring surface, while fully protecting the surface finish edge.

(24)

24

Features and Benefits:

• Iso Floor provide high lateral stability, meaning all panels can be removed without the risk of the floor shifting. The free-standing, high stability floor substructure doesn’t need walls for support, allowing you to only plan for the space needed today, with room to expand.

• 25% more room for equipment in your Network Center will save money on the real estate investment. This can be achieved by using Bergvik custom size panels in aisles.

• Up to 70% less pedestal supports than conventional raised floors will provide lots of space for wiring, cable ladders etc.

• Removal of all floor panels in equipment aisles are now possible since Bergvik produce custom size panels to your specification.

• Open bottom access and/or perforated aisle panels allows for maximum cooling of Server racks. Airflow grilles with built-in fans directly in front of server racks can also be provided as an option.

• Floor panel meets NFPA 75 chapter 5.4.2 for fire resistance. Flame spread is 20 (class 1). Test report can be provided upon request.

• The all-bolted floor structure is sufficiently grounded by only two (2) grounding wires attached in opposite corners of the floor mechanics.

(25)

Iso Floor Technical Data

The floor system in general

Gross weight: approx. 45 kg/m2 (9.3 lbs/sf)

Uniform distributed load, UDL: 5-50 kN/m2 (103-1030 lbf/sf) where 7.4 kN/m2 (150 lbf/sf) is

used as a standard value

Finished floor height, FFH: 350-1900 mm (14–75 inch). Higher than 900 mm, zone 0-2 only. Laminate floor panel specification

Material: 38 mm high density particle board, V313 moist resistant quality is standard Panel sizes: 600x600, 600x800, 600x400 mm (23.6” square, 23.6”x31.5”, 23.6”x15.8”) as

standard. Custom sizes available.

Surface finish: Bergvik direct laminate as standard. Optional surfaces available. 36x24 inch Perforated aisle panel: open area 0.78 sf (0.072 m2).

Electrical resistance: >500 kOhms and <2 x 1011 Ohms at RH min 40%.

Color pattern: M335 Granite laminate as standard. H817 Alder is optional. Wear resistance: 4,000-6,000 cycles according to EN 438-2:6 1991. Color fastness: >6 according to EN 438-2:16 1991.

Weight: 10 kg (22 lbs) for floor panel 600 x 600 mm (23.6” square). Flame spread: 20 In accordance with ASTM E84 or NFPA 266

Cleaning: With vacuum cleaner or dry mop. For difficult stains use citrus cleaner on a buffing pad.

NA Hoganas, PA, USA

SAS Flight Academy, Sweden

Bergvik is an innovative knowledge company specializing in raised floor systems and seismic bracing solutions tailored to our customer's applications.

For an Iso Floor Master Specification, please contact us or visit our website.

Bergvik North America, Inc

212 West Main Street, Suite 202-B Salisbury, MD 21801. USA

Bergvik Flooring AB

Box 46 Vannsätter

References

Related documents

Table 3: Absolute and relative averages of return position errors for the square-shaped closed-loop path of 65 m total length on horizontal terrain... The approximated total traveled

The objective of the paper is to show a different role of the grain boundary carbides on the SCC in oxidized acidic solution and simu- lated PWR primary water and to review the

• analysis of the “social capital dimensions” of the measures previously selected, by means of 6 questions related to the different dimensions of social capital

Axial gauge instrumental – allows for physical interpretation Here we discuss recalculation of the NLO evolution kernels real-real ones – [JHEP 1108 (2011) 012]. virtual-real ones

• The first exception was the experimental 0.6Nb- stabilised ferritic stainless steel (B:0.6Nb) at a strain of 1%, which was in sector 2 and at welding speeds of 6 and 3

This study explored the multicultural training practices within Pepperdine University’s PsyD program in clinical psychology and provided a template for other training programs

The following list includes some of the institutions that have accepted credits from Calvary Chapel Bible College or admitted students to graduate programs who have earned

If you are planning to sell your home and it does not already have at least two RCDs protecting all power points and lighting circuits, you will need to engage a licensed