• No results found

M483CX manual air conditioner LG

N/A
N/A
Protected

Academic year: 2021

Share "M483CX manual air conditioner LG"

Copied!
51
0
0

Loading.... (view fulltext now)

Full text

(1)

LG

Multi Type Air Conditioner

SERVICE MANUAL

LG

CAUTION

website http://www.lgservice.com

e-mail http://www.lgeservice.com/techsup.html

• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.

• ONLY FOR AUTHORIZED SERVICE PERSONNEL.

MODEL: Indoor Unit: Wall Mounted Type

TMNC092DYAA

TMNC122DYAA

TMNC182D5AA

TMNC242D5AA

TMNC092TYAA

TMNC122TYAA

TMNC182T5AA

TMNC242T5AA

TMNH092DYAA

TMNH122DYAA

TMNH182D5AA

TMNH242D5AA

TMNH092TYAA

TMNH122TYAA

TMNH182T5AA

TMNH242T5AA

Outdoor Unit: T2UC182FAA

T2UC242FAA

T2UC362FAA

T2UC482FAA

T2UH242FAA

T2UH362FAA

T2UH482FAA

T2UH182FAA

(2)

2 Multi Air Conditioner

Multi Air Conditioner Service Manual

TABLE OF CONTENTS

Safety Precautions ...3

Product Specifications

...7

Dimensions ...9

Refrigeration Cycle Diagram ...12

Wiring Diagram ...13

Electronic Control Device ...14

Schematic Diagram ...17

Functions ...19

Operation Details ...22

Disassembly ...26

2-way, 3-way Valve ...29

Cycle Troubleshooting Guide

...33

Installation ...39

Flaring work and connection of piping

...42

Connecting the Cable Between Indoor Unit and Outdoor Unit

...47

(3)

Service Manual 3

Safety Precautions

Safety Precautions

To prevent injury to the user or other people and property damage, the following instructions must

be followed.

Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is

classified by the following indications.

Meanings of symbol used in this manual are as shown below.

WARNING

CAUTION

This symbol indicates the possibility of death or serious injury.

This symbol indicates the possibility of injury or damage.

WARNING

Installation

Be sure not to do.

Be sure to follow the instruction.

Do not use a defective or

underrated circuit breaker.

Use this appliance on a

dedi-cated circuit.

• There is risk of fire or electric shock.

Do not let the air conditioner

run for a long time when the

humidity is very high and a

door or a window is left open.

• Moisture may condense and wet or damage furniture.

Always ground the product.

• There is risk of fire or electric shock.

Install the panel and the cover

of control box securely.

• There is risk of fire or electric shock.

Always install a dedicated

cir-cuit and breaker.

• Improper wiring or installation may cause fire or electric shock

Use the correctly rated

break-er or fuse.

(4)

4 Multi Air Conditioner

Safety Precautions

Operational

Do not modify or extend the

power cable.

• There is risk of fire or electric shock.

Do not install, remove, or

re-install the unit by yourself

(customer).

• There is risk of fire, electric shock, explosion, or injury.

Be cautious when unpacking

and installing the product.

• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.

For installation, always

con-tact the dealer or an

Authorized Service Center.

• There is risk of fire, electric shock, explosion, or injury.

Do not install the product on a

defective installation stand.

• It may cause injury, accident, or dam-age to the product.

Be sure the installation area

does not deteriorate with age.

• If the base collapses, the air condition-er could fall with it, causing propcondition-erty damage, product failure, and personal injury.

Do not touch(operate) the

product with wet hands.

• There is risk of fire or electrical shock.

Do not place a heater or other

appliances near the power

cable.

• There is risk of fire and electric shock.

Do not allow water to run into

electric parts.

• It may cause There is risk of fire, fail-ure of the product, or electric shock.

(5)

Service Manual 5

Safety Precautions

Do not open the inlet grille of the product

dur-ing operation. (Do not touch the electrostatic

filter, if the unit is so equipped.)

• There is risk of physical injury, electric shock, or product fail-ure.

Be cautious that water could not enter the

product.

• There is risk of fire, electric shock, or product damage.

Do not store or use flammable gas or

com-bustibles near the product.

• There is risk of fire or failure of product.

If strange sounds, or smell or smoke comes

from product. Turn the breaker off or

discon-nect the power supply cable.

• There is risk of electric shock or fire.

(6)

6 Multi Air Conditioner

Operational

Safety Precautions

Use two or more people to lift

and transport the product.

• Avoid personal injury.

Use a soft cloth to clean. Do

not use harsh detergents,

sol-vents, etc.

• There is risk of fire, electric shock, or damage to the plastic parts of the prod-uct.

Do not touch the metal parts

of the product when removing

the air filter. They are very

sharp!

• There is risk of personal injury.

Do not step on or put anyting on the product.

(outdoor units)

• There is risk of personal injury and failure of product.

Do not insert hands or other objects through

the air inlet or outlet while the product is

oper-ated.

• There are sharp and moving parts that could cause personal injury.

CAUTION

Installation

Wa

x Thinner

check for gas (refrigerant)

leakage after installation or

repair of product.

• Low refrigerant levels may cause fail-ure of product.

Install the drain hose to

ensure that water is drained

away properly.

• A bad connection may cause water leakage.

Keep level even when

installing the product.

• To avoid vibration or water leakage.

(7)

Service Manual 7

Product Specifications

Product Specifications

Indoor Unit

Power Supply Ø,V,Hz r h / u t B y ti c a p a C g n il o o C y ti c a p a C Heating W kcal/hr r h / u t B W kcal/hr Current Normal running current A Fan Model

Fan Type

Motor Output W Air Flow Rate CMM(CFM) Capacitor µF/Vac Coil Tube Size (OD) mm(inch)

Fins per inch

No. of Rows & Column/No.

3 ± ) A ( B d ) L / M / H (l e v e L d n u o S Referigerant Referigerant Control ) h c n i( m m d i u q i L n o it c e n n o C g n i p i P ) h c n i( m m s a G ) s b l( g k r o o d n I t h g i e W t e N ) h c n i( m m D * H * W s n o is n e m i D ) h c n i( m m D * H * W n o is n e m i D g n ik c a P

Model TMNH092DYAA TMNH122DYAA d e t n u o m l l a W e p y t ti n u r o o d n I 1Ø, 220V, 60Hz 1Ø, 220V, 60Hz 0.27 0.20 CFF RP15C-1 WEILING RP15C-1 WEILING 42 8.4/7.6/6.4(296.5/268.3/225.9) 7/6/5(247.1/211.8/176.5) 0.9/400 20FPI S-FIN 2R 15C R-22 R-22 6.35(1/4) 12.7(1/2) 7/9 840*270*161 6.35(1/4) 9.52(3/8) 7/9 840*270*161 892*322*198 892*322*198 5 CFF 37 0.9/400 20FPI S-FIN 2R 15C 34/31/29 40/37/34 Thermistor 5 12,000 3,517 3,024 9,000 2,638 2,268 12,000 3,517 3,024 9,000 2,638 2,268

(8)

8 Multi Air Conditioner

Product Specifications

Note :

1. Capacities are based on the following conditions:

Cooling: - Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB - Outdoor Temperature 35°C(95°F) DB / 23.9°C(75°F) WB Piping Length - Interconnecting Piping Length 7.5m

- Level Difference of Zero.

2. Due to our policy of innovation some specifications may be changed without notification. 3. At least two indoor units should be connected.

Outdoor Unit

Unit T2UH182FAA T2UH242FAA

W 3077/ 3077 3517 / 3517 Btu/hr 10500 / 10500 12000 / 12000 W 3077/ 3077 3517 / 3517 Btu/hr 10500 / 10500 12000 / 12000 W 5275 / 5275 7034 Btu/hr 18,000 / 18,000 24,000 Power input (Cooling/heating) A+B W 1850/1650 2380/2420 Running current (Cooling/heating) A+B A 8.6/ 7.6 11/11.3 f,V,Hz 1,220,60 1,220,60 No. * mm2 3*2.5 3*2.5 No. * mm2 4*0.75 4*0.75 W/W 2.85 2.96 Btu/hr W 9.7 10.1 W/W 3.20 2.91 Btu/hr W 10.9 9.9 Capillary Capillary g(oz), type 1050, R22 A: 650 /B: 650 R22

Dimensions (W*H*D) Outdoor unit mm 801*555*262 870*655*320

Packing dimensions (W*H*D) Outdoor unit mm 960*610*384 1002*700*422

kg (lbs) 50 (110) 63 (139)

Rotary Rotary

1 2

QJ278KDF QK185KBK

LG LG

SUNISO 4GSI SUNISO 4GSI

MOTOR TYPE PSC PSC

Oil charge cc 410 350

Tube size (OD) inch (mm) 0.276 (7.0) 0.276 (7.0)

18 18 2R 24C 2R 28C Model YGK25-6A-9 KFD-60K11 No. of poles 6 6 CMM (CFM) 49 (1398) 40 (1142) Propeller Propeller

No. used / dia. EA / inch (mm) 1 / 18.1(460) 1 / 18.1(460) Side discharge Side discharge

RPM ±30 1020 880 dB +3(dB+1) 54(56) 54(56) Liquid A inch (mm) 1/4 (6.35) 1/4 (6.35) Gas A inch (mm) 3/8 (9.52) 1/2 (12.7) Liquid B inch (mm) 1/4 (6.35) 1/4 (6.35) Gas B inch (mm) 3/8 (9.52) 1/2 (12.7)

Max piping length total m 30 30

Std. Piping length m 7.5 7.5

m 15 / 7.5 15 / 7.5

Stuff Quantity (Set) 20FT/40FT/40FT(H) 80/168/192 65/138/156

Power supply Power supply cable Connecting cable Item Capacity (Cooling/heating) A (SY 9K) B (SY 9K ) A+B (9K+9K) EER cooling COP heating Refrigerant control Refrigerant charge Net weight Compressor Type Quantity Model name Maker Oil type

Outdoor coil FPI

No. of rows & columns

Noise level +3 SVC valves

Max. piping length per each room / elevation Outdoor Motor

Air circulation

Outdoor fan Type

(9)

Service Manual 9

Dimensions

Dimensions

Installation plate D H W m m W m m H m m D Model Dimension

Indoor Unit

TMN 122DYAA TMNH092DYAA 840 270 161 840 270 161 H

(10)

10 Multi Air Conditioner

Dimensions

Outdoor Unit

Model: T2UH182FAA

W D L1 L2 L9 L4 L3 H L10 L10 L10 L8 L7 L5 L6 801 m m W 555 m m H 262 m m D 339 m m 1 L 37 m m 2 L 543.6 m m 3 L 11.4 m m 4 L 591 m m 5 L 105 m m 6 L 105 m m 7 L 72.5 m m 8 L 74.5 m m 9 L 79 m m 0 1 L T2UH182FAA MODEL DIM Gas side 3-way valve Liquid side 2-way valve

(11)

Service Manual 11

Dimensions

Model : T2UH242FAA

W D L1 L2 L9 L4 L3 H L10 L10 L10 L8 Gas side 3-Way valve Liquid side 2-Way valve L7 L5 L6 870 m m W 655 m m H 0 2 3 m m D 0 7 3 m m 1 L 5 2 m m 2 L 630 m m 3 L 5 2 m m 4 L 6 4 5 m m 5 L 0 6 1 m m 6 L 0 6 1 m m 7 L 55 m m 8 L 80 m m 9 L 0 5 m m 0 1 L T2UH242FAA MODEL DIM

(12)

12 Multi Air Conditioner

Refrigeration Cycle Diagram

Refrigeration Cycle Diagram

T2UH182FAA / T2UH242FAA

12K

12K

A

B

Indoor Side Outdoor Side

A Comp B Comp Refrigerent Flow Cooling Heating

(13)

13

Service Manual

Wiring Diagram

Wiring Diagram

Indoor Unit

Outdoor Unit

T2UH242FAA

.

2

T2UH182FAA

.

1

FAN B/P1B/P2 B C EBY49965301 RD BRYL 2 BK WH 1 BLRD BL RD WH BL BKBL OR BL BL BL WH TB B C BL BR BR BR BR BK EBY49965302 3 4 TB L N

(14)

14 Multi Air Conditioner

Electronic Control Device

Electronic Control Device

Indoor Unit

• MAIN P.C.B ASM

• TOP VIEW

(15)

Service Manual

Electronic Control Device

Outdoor Unit

(16)

Multi Air Conditioner

Electronic Control Device

Display P.C.B ASM

(17)

Service Manual

Schematic Diagram

Schematic Diagram

Indoor Unit

42 28 1516 22 20 19 18 17 21 26 25 23 24 27 11121314 9 8 10 3433 32 29 30 31 38373635 414039 53 55 56 58 57 54 61 63 62 64 60 59 5 4 6 7 123 49 51 52 50 44 45 43 48 4746 FAN 12V COMP4WAY OUTDOOR FAN

L(AC) LOADCOMP4WAY

2. The unit of undefined capacitors is uF.

1. The unit of undefined resistance is ohm, 1/8W, 5%.

NOTE Direct type 12 3 PCB outside 12 Angle type CN-MOTOR 3 2 1 CN-4WAY SH-CAPACITOR 22 680 33 CN-12V 2 1 1 2 2 1 12V AC PART 3 TLP421(V4 BL) IC01L VOLTAGE GND DC LOW INT 4 1N4148 VOLTAGE GND 2 DC HIGH 300K1/2W NF01J40mH/1A 1IN4007 1N4007 D05J R03L 300K1/2W 27k1/6W D01L 1 R02L R01L 1N4007 5V 1N4007 D03J C02JMETAL FILM100nF/275V/436D D02J1N4007 D01J D04J 12V INDOOR FAN R01F 560 1/4W 100,1/2W 250V/T2A 100nF/275V/436D C01JMETAL FILM ZNR01JTVR10561 FUSE

RY- FAN RY-4 WAY

3 4 3 4 TLP762JF SM1L43 T1 R03F 1/2W 5 12 4 IC01F 3 TR01FTRAICS T2 METAL FILM100nF/275V/436D C01F TVR10561 120, 1/2W R04F ZNR01F COMPRESSOR 1 1 CN-N1 RY-COMPG4A-1A-E-LG 3 N AC220~240V50/60Hz L MOTOR 4 1 1 3 3 1 1 2 2 32 1 3 1 2(N)1(L) 2 TERMINAL 5 4 5 FAN MOTOR OUTDOOR 4-WAY 4 11 2 4 3 5 Vout GND Vcc RECEIVER DISPLAY C C AB B KTC3198-Y 1 1 11 20KR01P(2012) 10V 2 2 HVB 33 1 CN-HVB 1 Option HVB OUT 6 3 A0

A1 EEPROMM24C01-MN6T SGS-THOMSON 8PIN SOP TRAY EEPROM IIC

4 SCL SDA 5 GA2 12 8 Vcc 7 WP receiver 5 5 55 C13L SW(FORCE) 104 2 2 11 2 2 1 1 44 3 3 4 4 3 3 R01G~R04G 1 220 1/8W 7 7 6 6 7 7 6 6 8 8 8 8 CN-DISP1 KRA107S Q02G Q03GKRA107S 220uF SD Force + C12L 5V Q01GKRA107S 5V KID65004AF 9 IC01G 5V 5V 20KR02P(2012) OR4H OR6H OR5H Hi Med Low OR3H OR1H OR2H O/L F2 F 1 R26H R21H 5V d 5V s 1 s V d Force 20K R15L 5V C08D,AXIAL 103,50V A V A Vss0Vdd0 AVref R24H R23H R25H 12.1K, 1% R21H~R26H R22H 5V RESETAVdd C07D,AXIAL103,50V X2 X1 CRTL8.00MSOT CSTS0800MG03-T2 R01B1M OSC01B 2SC5343 R03G

OUTDOOR LED2SLEEPLED1OPERATION

A TIMER LED3 R02G R01G 3 3 2 2 3 3 2 2 6 6 44 55 6 6 5 5 4 4 LED4 R04G 77 7 7 11 6 16 15 14 1 2 3 13 12 4 5 12V 10 7 KID65004AF IC01M BL OR 4 5 RD 4 5 2 1 3 PK YL 2 1 3 STEPPING MOTOR (UP/DOWN) HVB OUT 15 2 8 16 9 1 13 14 3 4 INDOOR FAN COMP 10 11 12 5 6 7 UPD780023AGC-C NEC INT1INT0Vss1 BZ Q01L R11L,1/6W FAN 12 4 1 2 3 16 15 14 13 2 4 3 5 4WAY KID65004AF 8 7 5 6 9 10 11 IC02M 1 CN-L/R DC PART STEPPING MOTOR (LEFT/RIGHT) Option 1 INT RELAY CONNECTION CN-TH1 10K R05H R02H12.1K 1% R04H6.2K 1% 5V PIPE-TH R02F 11 44 33 22 ROOM-TH 50V 5V 3 10uF C02A IC01A 1 3.6V S7136 2 KIA7036P R05L56K R02A,4.7K CN-MOTOR 33 FAN INDOORMOTOR 34 R12L 5.1K receiver 680pF,50V 12K R04L,1/6W 5V C11L ,AXIAL 5V PKM13EPY-4002 R02E,20 R01E1K BZ01E IC01J DMR40 EE1916SLp=4.50mH,+-8%,40Khz 158T VOLTAGE GND DC LOW + 5V C04D C05D 10V SD 104,AXAIL50V 220 S78L05L 1W I IC01D O 7805 D01DUF4004 ZBF503D-TA-K TDK TP 12uH L01D,IMD 1/6W 104,AXIAL C03D R01D4.7K 50V 100uF C02D 25V 12V 28T 220UF C01D 25V SMPS 450V/SD 1N4937 DC HIGHVOLTAGE GND 100,1/6W R02J 50V C05J0.1uF100V RO1J27K1/4W,1% DO6J 1uF C04J LNK500P S D C + 10uF C03J NTC SCK-102 CI-B2012-100KJT R/TP 100nH L02D 2 4 5 5 4 3 1 3 1 2 12V 5V GND R14L 1K C01P,AXIAL,103,50V X RT X DD R01A,1K R03A,100 AXIAL C01A103 222,400V C06J,AXIAL + 1 2 1 2 33 12V CN-P/O + R01H,1/6W,10K R03H,1/6W,10K C14L C02H C01H R13L 100 1/4W 12V BL PK YL OR RD 8 PLASMA CHIP RXD TXD C03TCHIP R06H,1/6W,10K C03H 2 3 1 2 3 1 CN-TH2 6.2K R07H 1% 5V 11 3 3 22 77 6 6 5 5 44 CN-OPTION GND

OR1H (PIN 33) OR2H (PIN 32) OR3H (PIN 31) OR4H (PIN 30) OR5H (PIN 29)OR6H (PIN 28)

C01LAXIAL 3 3 CN-RF 5V 1 1 2 2

CHIP(104) or 10K ohm resistor

C01T R01T,1K,AXIAL CHIP(681) C02T 1 3 8 6 Metal film + LINK SWICH CN-4WAY CN-N2 CN-LIVE WIRE-N R02D C06D,AXIAL 4.7K,1/6W 102,400V WIRE-N 3 4 CN-LIVE PTC-HEATER RF Transmitter on artworking,Eyelet pattern

10M,1W,5% noise character increasing thing

R03J 103 103 103 YW396-03AV(WH) YW396-03AV(YL) 103 1K 102 or 10K ohm resistor AXIAL AXIAL 50V 50V AXIAL50V 50V 10350V CN-DISP2 CN-U/D CN-CENT SMD

BARE PCB:6870A90238A ASM PCB:6871A20572

DISPLAY BARE PCB : 6870A90240A DISPLAY ASM PCB : 6871A20574A

If CN-CENT don't use,this use resistor 10K(2012).

OR1H OR2HOR3H OR4H OR5H OR6H

PCB ASM : 6871A20577

If CN-RF don't use,this use resistor 10K(2012).

2UEW0.14

TIW0.25

Option : only This is applied the H/P SRAC.

P/no:6200JB8010P WRAC APPLIED

OPTION : noise character increasing thing

OPTION : noise character increasing thing

PWB:6870A90243A 10K 47K 47K 10K 47K 10K

Only no low temporature detection function.

10K+-5% 5K+-5% 15pF 15pF GLASS TYPE R11H R12H 5V 0J1H 0J2H 5V

OPTION : import or export operation option

R11H~R12H20K,2012 1-4 79T4-3 79T R04D0 ohm 0 ohm R03D C09Dopen C10Dopen

Anti Surge Res.

Anti Surge Res.

Anti Surge Res.

(18)

Schematic Diagram

(19)

Service Manual

Functions

Function of Indoor Unit

• Room temperature sensor. (THERMISTOR)

• Maintains the room temperature in accordance with the Setting Temp.

• Indoor fan is delayed for 5 seconds at the starting.

• Restarting is inhibited for approx. 3 minutes.

• High, Med, Low, Chaos

--- Lights up in operation --- Lights up in Sleep Mode

--- Lights up in Energy Saving Mode

--- Lights up in Defrost Mode(for Heating model)

--- Lights up in Compressor operation(for Cooling model)

• Intermittent operation of fan at low speed.

• The fan is switched to low(Cooling), med(Heating) speed. • The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.

• The fan is switched to intermittent or irregular operation • The fan speed is automatically switched from high to low speed.

• The louver can be set at the desired position or swing up and down automatically.

Wall mounted type

Operation ON/OFF by Remote controller

Sensing the Room Temperature

Room temperature control

Starting Current Control

Time Delay Safety Control

Indoor Fan Speed Control

Operation indication Lamps (LED)

OUT DOOR

Health Dehumidification Operation

Sleep Mode Auto Control

Natural Air Control by CHAOS Logic

Airflow Direction Control

(20)

Multi Air Conditioner

Functions

Healthy Dehumidification Operation Mode.( )

Remote Controller

Operation ON/OFF

Operation Mode Selection

Temperature Setting

JET COOL

Sleep Operation

Airflow Direction Control

(Cooling model only)

TEMPERATURE LOW HIGH

Cooling Operation Mode.( )

Heating Operation Mode.( )

Fan Operation Mode Energy Saving Mode Fan Speed Selection

(Low) (Med) (High) (CHAOS)

: Cancel Sleep Mode, Timer ON or Timer OFF

: 1, 2, 3, 4, 5, 6, 7, Off Timer

: Fan Operates without cooling or heating.

Cooling Down to 18°C

Up to 30°C

(21)

Service Manual 2

Function

Display Function

Self-diagnosis Function

• Cooling, Soft Dry, Fan

• Sleep Mode Operation Indicator

Energy Saving Mode Sleep Timer Indicator

Compressor on Indicator DOOROUT

Error Indicator

• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble. • Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table. • If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed. • After error occurrence, if error is released, error LED is also released simultaneously.

• To operate again on the occurrence of error code 12, be sure to pull out power cord and then re-insert. • Having or not of error code is different from Model.

l

e

d

o

M

g

n

i

l

o

o

C

3sec 3sec 3sec

(once)

Error Code

1

Error Display LED

(Indoor body operation LED) Error contents

• Indoor room temperature thermistor open/short • Indoor pipe temperature

thermistor open/short.

• Indoor Thermistor assembly check

SVC check point

(22)

2

Multi Air Conditioner

Operation Details

Operation Details

Function of Controls

• DISPL

AY

C/O Model Operation Indicator

• ON while in appliance operation, OFF while in appliance pause. •

Sleep Mode

Comp. Running Incidator •

Cooling Mode Operation

• When the intake air temperature reaches0.5 °C below the setting temp, the compressorand the outdoor fan stop.

• When itreaches0.5 °C above the setting temp, they start to operate again.

Compressor ON Temp Setting Temp+0.5°C

Compressor OFF Temp Setting Temp-0.5°C

• While in compressorrunning, operating with the speedset by the remote control. While in compressor

Health

• When the operation input by the remote control is received,the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.

26°C” Intake Air Temp 25°C

24°C” Intake Air Temp<26°C Intake Air Temp-1°C 18°C” Intake Air Temp<24°C Intake Air Temp-0.5°C

Intake Air Temp<18°C 18°C

• Whilethe intake air temp is between compressoron temp. and compressor temp.,10-min

Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. Setting Temp-0.5°C •

Energy Saving Mode

(23)

Operation Details

Airflow Speed Selection

• The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.

Sleep Timer Operation

• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli-ance operation, the operation of the appliappli-ance stops.

• While the appliance is on pause, the sleep timer mode cannot be input.

• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.

• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low.

• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.

Chaos Natural Wind Mode

• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.

Jet Cool Mode Operation (C/O Model)

• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C

• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then

operated in order that the air outflow could reach further.

Forced Operation

• Operation procedures when the remote control can't be used. • The operation will be started if the power button is pressed. • If you want to stop operation, re-press the button.

• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.

Heat pump Model Cooling Model

Room Temp. • 24°C 21°C ” Room Temp. < 24 °C Room Temp. < 21 °C

Operating mode Cooling Cooling Healthy Dehumidification Heating

Indoor FAN Speed High High High High

Setting Temperature 22°C 22°C 23°C 24°C

Test operation

During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-perature and resets in 18±1 minutes.

During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.

If you want to stop the operation, re-press the button.

(24)

Operation Details

Auto restart

In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.

Protection of the evaporator pipe from frosting

• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool-ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.

• When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.

Buzzer Sounding Operation

• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds. • When the appliance-pause key is input by the remote control, the long "beep—" sounds.

(25)

25

Service Manual

Operation Details

(26)

Disassembly

Disassembly

Indoor Unit

Disconnect the unit from power supply before mak-ing any checks.

Be sure the power switch is set to “OFF ”.

To remove the Grille from the Chassis.

• Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.

• Remove the securing screws.

• To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.

1. Before removing the control box, be sure to take out the wire screwed at the other end.

Earth Conductor

(27)

Disassembly

2. To remove the Control Box. • Remove securing screws.

• Pull the control box out from the chassis carefully.

3. To remove the Discharge Grille.

• Unhook the discharge grille and pull the discharge grille out from the chassis carefully.

4. To remove the Evaporator.

• Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).

Screw

• When repair, do not damage the Caution label.

(28)

Disassembly

• Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.

5. To remove the Motor Cover • Remove 2 securing screw.

• Pull the motor cover out from the chassis carefully.

6. To remove the Cross-Flow Fan

• Loosen the screw securing the cross-flow fan to the fan motor (do not remove).

• Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.

• Remove the left end of the cross-flow fan from the self-aligning bearing.

Motor cover

Bearing

Cross-flow fan

(29)

2-way, 3-way Valve

2-way, 3-way Valve

2-way Valve (Liguid Side) 3-way Valve (Gas Side)

Works Shaft position Shaft position Service port

Shipping Closed Closed Closed

(with valve cap) (with valve cap) (with cap)

Air purging Open Closed Open

(Installation) (counter-clockwise) (clockwise) (push-pin or with

vacuum pump)

Operation Open Open Closed

(with valve cap) (with valve cap) (with cap)

Pumping down Closed Open Open

(Transfering) (clockwise) (counter-clockwise) (connected

manifold gauge)

Evacuation Open Open Open

(Servicing) (with charging

cylinder)

Gas charging Open Open Open

(Servicing) (with charging

cylinder)

Pressure check Open Open Open

(Servicing) (with charging

cylinder)

Gas releasing Open Open Open

(Servicing) (with charging

cylinder) 3. 2. 1. 4. 5. 6. Flare nut To piping connection Open position Closed position Flare nut Valve cap To piping connection Open position Closed position Hexagonal wrench (4mm) To outdoor unit Pin Service port Service port cap To outdoor unit

Service Manual 29

(30)

2-way, 3-way Valve

Procedure

1. Confirm that both the gas side and liquid side valves are set to the open position.

- Remove the valve stem caps and confirm that the valve stems are in the raised position. - Be sure to use a hexagonal wrench to operate

the valve stems.

2. Operate the unit for 10 to 15 minutes.

3. Stop operation and wait for 3 minutes, then con-nect the manifold gauge to the service port of the gas side valve.

- Connect the hose of the gauge with the push pin to the service port.

4. Air purging of the charge hose.

- Open the Low-handle valve on the gauge slightly to air purge from the hose.

5. Set the liquid side valve to the closed position.

6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2

g. 7. Immediately set the gas side valve to the closed

position.

- Do this quickly so that the gauge ends up indi-cating 1kg/ g.

8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut.

- Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg*m/5.5kg*m) - Be sure to check for gas leakage.

Indoor unit Outdoor unit Liquid side Close Gas side 2-Way valve Open 3-Way valve manifold gauge Hi- handle (CLOSE) Low-handle (CLOSE)

(1) Pumping down

(31)

2-way, 3-way Valve

(2) Evacuation

(All amount of refrigerant leaked)

• Procedure

1. Confirm that both the liguid side valve and gas side valve are set to the opened position. 2. Connect the vaccum pump to the center hose of

the manifold gauge.

3. Connect the service port of the gas side valve to the low side of the gauge.

4. Connect power supply to outdoor unit. 5. Evacuation for approximately one hour.

- Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less).

6. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge nee-dle does not move(approximately 5 minutes after turning off the vacuum pump).

7. Disconnect the charge hose from the vacuum pump.

- Vacuum pump oil.

If the vacuum pump oil becomes dirty or deplet-ed,replenish as needed.

8. Mount the valve caps and the service port caps.

Indoor unit Outdoor unit Liquid side Close Gas side 2-Way valve Open 3-Way valve manifold gauge Vacuum pump Hi- handle (CLOSE) Low-handle (OPEN)

Service Manual 31

(32)

2-way, 3-way Valve

(3) Gas Charging

(After Evacuation)

• Procedure

1. Connect the gauge to the charging cylinder.

- Connect the charge hose which you disconnect-ed from the vacuum pump to the valve at the bottom of the cylinder.

- If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid.

2. Purge the air from the charge hose.

- Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.

3. Open the low handle on the gauge and charge the system with liquid refrigerant.

- If the system can not be charged with the speci-fied amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi-cient, wait approximately 1 minute and then repeat the procedure(pumping down-pin).

4. Immediately disconnect the charge hose from the gas side valve's service port.

- Stopping partway will allow the gas to be dis-charged.

- If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.

5. Mount the valve stem nuts and the service port nut.

- Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.) - Be sure to check for gas leakage.

Indoor unit Outdoor unit Liquid side Close Gas side 2-Way valve Open 3-Way valve manifold gauge Charging cylinder Hi- handle (CLOSE) Low-handle (OPEN) Check valve

This is different from previous procedures.

Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.

(33)

Cycle Troubleshooting Guide

Cycle Troubleshooting Guide

Trouble analysis

1. Check temperature difference between intake and discharge air and operating current.

All amount of refrigerant leaked out. Check refrigeration cycle.

Refrigerant leakage Clog of refrigeration cycle Defective compressor

Excessive amount of refrigerant

Normal

Notice:

Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Notice:

1. The suction pressure is usually 4.5~6.0 kg/cm2

G at normal condition.

2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.

Temp. difference : approx. 0°C

Current : less than 80% of

rated current

Temp. difference : approx. 8°C

Current : less than 80% of

rated current

Temp. difference : less than 8°C

Current : over the rated

current

Temp. difference : over 8°C Temp. Difference

Operating Current

Suction pressure Temperature

(Compared with (Compared with Cause of Trouble Description

the normal value) the normal value)

High Defective compressor Current is low.

Normal Excessive amount of High pressure does not quickly

refrigerant rise at the beginning of operation.

Insufficient amount of Current is low.

Lower Higher refrigerant(Leakage)

Clogging Current is low.

Higher

(34)

Cycle Troubleshooting Guide

Electronic Parts

Product does not operate at all.

(* Refer to Electronic Control Device drawing and Schematic diagram.)

Turn off Main Power

Turn on Main Power

Does "beeping" sound is made from the Indoor Unit?

Primarily, the operating condition of Micom is OK. Check the voltage of power (About AC 220V, 60Hz)

• Main power's voltage • Voltage applied to the unit

• Connecting method of Indoor/Outdoor connecting cable

• Check PWB Assembly - Fuse

- Pattern damage - Varistor(ZNR01J)

Check the connection housing for contacting • Connector related to CN-NI, RY-COMP NO.3 • Connector related to CN-MOTOR

• Connector contacting of Outdoor Fan/Compressor • Display PCB Assembly Check

Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector

Main PCB Board Operation Check Items • SMPS Transformer (Indoor unit) - Input Voltage - Output Voltage(C03D) • IC01D(7805) Output (Indoor/Outdoor unit)

• IC01A(KIA7036, Reset IC) OSC01B(8MHz)

• Replace Trans

• Replace IC01D

• Replace faulty parts - About AC220V/240V±10% - Check the power voltage

- About DC12V

• DC +5V

• Voltage of IC No.1,

(DC +4.5V over) and Soldering condition.

Content Remedy

NO YES

(After 10 seconds)

(35)

Cycle Troubleshooting Guide

The product is not operate with the remote controller.

Turn on Main Power

While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped.

Caused by other parts except the remote control Cause by the remote control

When the mark( ) is displayed in LCD screen, replace

battery. Check the contact of CN-DISP1 connector.

When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)

Check Display PCB Assembly

- Voltage between CN DISP1 - : DC +5V Check the connecting circuit between the remote controller

MICOM (No. ) - R16(1.5k) - IR LED - TR - R17(1Ω). or

MICOM (No. ) - R1(1.5k) - IR LED - TR - R2(1Ω).

Check point

• Check the connecting circuit between CN-DIS1 -R11L(100Ω) - C01A(100nF) - MICOM PIN

• Check Receiver Assembly

61

(36)

Cycle Troubleshooting Guide

Compressor/Outdoor Fan are unable to drive.

Turn on Main Power

Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least.

When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.

Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).

When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.

• Check the related circuit of RY-FAN.

• Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 25°C).

Turn off Main Power

• Check the electrical wiring diagram of outdoor side. • Check the abnormal condition for the component of

Compressor/Outdoor Fan Motor.

• Check the "open" or "short" of conmecting wires between indoor and outdoor.

Check Relay(RY - COMP) for driving compressor.

• When the power(About AC220V/240V) is applied to the connecting wire terminal support transferred to compressor, PWB Assembly is normal. • Check the circuit related to the relay.

Check point COMP ON COMP OFF Between Micom(No.

DC5V DC0V 59) and GND

Between IC01M(No. 15) Below DC 1V

About DC12V and GND (app)

(37)

Cycle Troubleshooting Guide

Check the TRIAC high speed operation by remote control. (The Indoor Fan Motor is connected)

Turn off Main power

Check the connection of CN-MOTOR

Check the Fan Motor

Check the Fuse(AC250V/T2A)

Turn ON Main Power

Check the related circuit of indoor Fan Motor.

• The pin NO 58 of Micom, and the part for driving TRIAC(the input and output signal of IC01M, PIN NO 1, 16)

• Check the pattern • Check the TRIAC

- TRIAC Open: Indoor Fan Motor never operate

- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.

When indoor Fan does not operate.

The voltage of PIN NO 1(orange) and 3(yellow) of CN-MOTOR.

About AC 180V over About AC 50V over

TRIAC is not damaged TRIAC Check

(38)

Cycle Troubleshooting Guide

• Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.

• If the regular torque is detected when rotating the Vertical Louver with hands Normal

• Check the connecting condition of CN-U/D Connector

• Check the soldering condition(on PWB) of CN-U/D Connector

If there are no problems after above checks

• Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver

When Vertical Louver does not operate.

Check the operating circuit of the Vertical Louver

• Confirm that there is DC +12V between pin (RED) of CN-U/D and GND.

• Confirm that there is a soldering short at following terminals. - Between , , and of MICOM

- Between , , and of IC01M - Between , , and of IC01M

60 61 62 63

(39)

Installation

Installation

Select the best Location

1. If an awning is built over the unit to prevent

direct sunlight or rain exposure, make sure

that heat radiation from the condenser is not

restricted.

2. Ensure that the spaces indicated by arrows

around front, back and side of the unit.

3. Do not place animals and plants in the path

of the warm air.

4. Take the air conditioner weight into account

and select a place where noise and vibration

are minimum.

5. Select a place so that the warm air and noise

from the air conditioner do not disturb

neighbors.

Rooftop Installations:

If the outdoor unit is installed on a roof

structure, be sure to level the unit. Ensure the

roof structure and anchoring method are

adequate for the unit location. Consult local

codes regarding rooftop mounting.

more than 20cm more than 70cm more than 20cm

Service Manual 39

(40)

Multi Air Conditioner

Installation

(41)

Service Manual

Installation

Piping Length and Elevation

Indoor Unit Capacity Pipe Size Rated Max Additional (Btu/h) Gas Liquid Length Length Refrigerant

• The maximun allowable level and piping length

18k 24k

Refrigerant Charge

Extra refrigerant = (Extended length - Rated length) x Additional refrigerant

7.5m A

B

7.5m Installation of the outdoor unit

on an upper position

Installation of the outdoor unit on a lower position A B 7.5m 7.5m Model [Outdoor unit] T2UH182FAA 7.5m 15m 15m - 30m (A+B) T2UH242FAA Standard length A,B

Max. piping length of each indoor unit

A B C

Max. total piping length

1/2"(12.7mm) 1/4"(6.35mm) 7.5 15

3/8"(9.52mm) 1/4"(6.35mm) 7.5 15 20g/m 30g/m

(42)

Flaring work and connection of piping

Flaring work and connection of piping

Flaring work

Flaring work

Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow-ing procedure.

Cut the pipes and the cable.

• Use the piping kit accessory or pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than the measured distance.

• Cut the cable 1.5m longer than the pipe length.

Check

• Compare the flared work with figure below.

• If flare is noted to be defective, cut off the flared sec-tion and re-flare it.

• Preparing the indoor unit's piping and drain hose for instal-lation through the wall.

• Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis. • Replace the plastic tubing holder in the original

position.(Optional)

• Carry out flaring work using flaring tool as shown below.

Burr removal

• Completely remove all burrs from the cut cross section of pipe/tube.

• Put the end of the copper tube/pipe in a downward direc-tion as you remove burrs in order to avoid dropping burrs into the tubing.

Putting nut on

• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)

Flaring work

• Firmly hold copper pipe in a die in the dimension shown in the table above.

Copper

pipe 90q Slanted Uneven Rough

Bar

Copper pipe Clamp handle

Red arrow mark Cone Yoke Handle Bar "A" Inclined

Inside is shiny without scratches Smooth all round

Even length all round Surface damaged Cracked Uneven thickness = Improper flaring = Drain hose Pipe Reamer Point down Flare nut Copper tube mm inch mm Ø6.35 1/4 0~0.5 Ø9.52 3/8 0~0.5 Ø12.7 1/2 0~0.5 Ø15.88 5/8 0~1.0 Ø19.05 3/4 1.0~1.3 Outside diameter A

Connection of piping -- Indoor

When install, make sure that the remaining parts must be removed clearly so as not to damage the pip-ing and drain hose, especially power cord and connecting cable.

(43)

Flaring work and connection of piping

Route the indoor tubing and the drain hose in the direction of rear right. Drain hose Connecting cable Vinyl tape(narrow) Connection pipe Connecting cable Vinyl tape

(wide) Wrap with vinyl tape

Indoor unit pipe

Pipe

Plastic bands Insulation material

Vinyl tape(narrow) Adhesive

Drain pipe

Indoor unit drain hose

Wrench Indoor unit tubing

Open-end wrench (fixed)

Connection pipe Flare nut

Indoor unit tubing Flare nut Pipes

Drain hose Connecting pipe Connecting cable Tape Drain hose

Insert the connecting cable into the indoor unit from the out-door unit through the piping hole.

• Do not connect the cable to the indoor unit.

• Make a small loop with the cable for easy connection later.

Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

NOTE: If the drain hose is routed inside the room, insulate

the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.

Indoor unit installation

• Hook the indoor unit onto the upper portion of the installa-tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa-tion plate by moving it left and right.

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(click-ing sound).

Connecting the pipings to the indoor unit and

drain hose to drain pipe.

• Align the center of the pipes and sufficiently tighten the flare nut by hand.

• Tighten the flare nut with a wrench.

• When extending the drain hose at the indoor unit, install the drain pipe.

Wrap the insulation material around the

con-necting portion.

•Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.

• Wrap the area which accommodates the rear piping hous-ing section with vinyl tape.

mm inch kg.m Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6

Outside diameter Torque

For right rear piping

(44)

Flaring work and connection of piping

• Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.

Connecting the pipings to the indoor unit and

the drain hose to drain pipe.

• Align the center of the pipes and sufficiently tighten the flare nut by hand.

• Tighten the flare nut with a wrench.

• When extending the drain hose at the indoor unit, install the drain pipe.

Wrap the insulation material around the

con-necting portion.

• Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.

Route the indoor tubing and the drain hose to

the required piping hole position.

Insert the piping, drain hose, and the

connect-ing cable into the pipconnect-ing hole.

Insert the connecting cable into the indoor unit.

• Don't connect the cable to the indoor unit.

• Make a small loop with the cable for easy connection later.

Indoor unit installation

• Hang the indoor unit from the hooks at the top of the instal-lation plate.

• Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.

Tape the drain hose and the connecting cable.

• Connecting cable

Drain pipe Connecting cable

Wrap with vinyl tape

Drain hose Pipe

Vinyl tape(wide)

Indoor unit tubing Flare nut Pipes

Installation plate

Spacer Indoor unit

8cm

Plastic bands Insulation material

Vinyl tape Adhesive

Drain hose

Indoor unit drain hose (narrow)

Wrench Indoor unit tubing

Connection pipe Flare nut

Open-end wrench (fixed)

For left rear piping

mm inch kg.m Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6

Outside diameter Torque

(45)

Flaring work and connection of piping

Installation Information (For left piping)

• Good case

For left piping. Follow the instruction below. • Press on the upper side of clamp. ( ) • Wrap the area which accommodates the rear piping

hous-ing section with vinyl tape.

Indoor unit installation

• Remove the spacer.

• Ensure that the hooks are properly seated on the installa-tion plate by moving it left and right.

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

• Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.

Reroute the pipings and the drain hose across

the back of the chassis.

Set the pipings and the drain hose to the back

of the chassis with the tubing holder.

• Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis. Vinyl tape(narrow) Connection pipe Connecting cable Indoor unit piping Pipe Vinyl tape

(wide) Wrap with vinyl tape

Drain hose Vinyl tape(narrow) Pipe Wrap with vinyl tape(wide) Piping for passage through piping hole Tubing holder Drain hose Connecting cable

• Unfold the tubing to downward slowly. ( )

• Bend the tubing to the left side of chassis.

(46)

Flaring work and connection of piping

Align the center of the pipings and sufficiently

tighten the flare nut by hand.

Finally, tighten the flare nut with torque wrench

until the wrench clicks.

• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. • Bad case

• Following bending type from right to left could cause problem of pipe damage.

Connection of the pipes-Outdoor

mm inch kg.m Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6

Outside diameter Torque

Outdoor unit

Gas side piping (Bigger diameter) Liquid side piping (Smaller diameter) Torque wrench

(47)

Connecting the cable between indoor unit and outdoor unit

Outdoor unit Terminal block Over 5mm Cover control Connecting cable Power cord Holder for power supply cord

Connection of the cable

1. Remove the cover control from the unit by loosening the screw.

Connect the wires to the terminals on the control board individually as the following.

2.Secure the cable onto the control board with the hold-er (clamphold-er).

3. screw.

4.Use a recongnized circuit breaker between the power source and the unit. A disconnection device to

ade-Connect the cable to the Indoor unit.

Connecting the cable between indoor unit and outdoor unit

(48)

Connecting the cable between indoor unit and outdoor unit

The power cord connected to the outdoor unit should be complied with the following specifications

(ETL recognized and CSA certified).

The power connecting cable connected to the indoor and outdoor unit should be complied with

the following specifications.

GN/YL 20mm GN/YL 20mm GN/YL 20mm 0.75 Cable Type(B) H07RN-F NORMAL CROSS -SECTIONAL AREA Grade (mm2) T2UH182FAA T2UH242FAA 2.5 2.5 Cable Type(B) H07RN-F H07RN-F NORMAL CROSS -SECTIONAL AREA Grade (mm2) T2UH182FAA T2UH242FAA

(49)

Exploded View and Replacement Parts List

Exploded View and Replacement Parts List

342800 263230 359011 131410 135316 135311 35211B 346810 135516 354210-1 W0CZZ 267110

Indoor Unit

Service Manual 49

135515 354210-2 352111 352116 352115 267110

(50)

53

Service Manual

Exploded View and Replacement Parts List

649950 554160 554160 349600 554031 546810 559010 447910 435301 430410 435511 W6640-1 349480 552203-1 552203-2 552203-3 552116 552111-1 W6640-2 552111-2 435512 437211 437212 268711-1 268711-2 263230

(51)

P/No.:

December, 2007 Printed in China

References

Related documents

2008 – 2013 Graduate Student Instructor, Screen Arts &amp; Cultures, University of Michigan 2006 – 2008 Teaching Assistant, Department of Film, York University... (Published

Because there are a number of insurance groups and individual companies that, for various reasons, have a small amount of direct written premium in a given market, prior reports

dration on MEG-14, an intrinsically disordered pro- tein (IDP), using synchrotron radiation circular dichroism (SRCD) spectroscopy, suggested that the MEG-14 protein gained

The sports installations that we deliver include natural sports pitches, such as those used for rugby, football and cricket; and synthetic and Multi Use Games Area (MUGA) pitches

In Scotland, under a somewhat paradoxical setting whereby the legal framework criminalises the way sex workers work, alongside a policy context that pivots on an understanding

• Set up MSOPIT and create an ultimate pit Set up MSOPIT and create an ultimate pit • Set up a model view to display your open Set up a model view to display your

potopului, şi din timpul potopului, pe care au învăţat-o de la fiii lui Noe, propovăduiau despre un Dumnezeu Creator al Totului şi despre sufletul nemuritor. Străbunul

transmission to humans in Goiás State and the Federal District of Brazil. Over 1,800 triatomines were caught inside or around houses in 95 municipalities of Goiás State during the