• No results found

Electronically Signed

N/A
N/A
Protected

Academic year: 2021

Share "Electronically Signed"

Copied!
5
0
0

Loading.... (view fulltext now)

Full text

(1)

K 000 INITIAL COMMENTS K 000 KOOO LIFE SAFETY CODE 101:2000

The facility is not in substantial compliance with the Minimum Life Safety Code requirements as surveyed under CMS-2786R.

K 050 SS=C

NFPA 101 LIFE SAFETY CODE STANDARD Fire drills include the transmission of a fire alarm signal and simulation of emergency fire

conditions. Fire drills are held at unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Responsibility for planning and conducting drills is assigned only to competent persons who are qualified to exercise leadership. Where drills are conducted between 9:00 PM and 6:00 AM a coded announcement may be used instead of audible alarms.

18.7.1.2, 19.7.1.2

This STANDARD is not met as evidenced by:

K 050 4/7/16

Based on surveyor's review of facility records on 3/1/16, it was determined that the facility failed to ensure that fire drills were conducted at

unexpected times as evidenced by the following: A review of the facility's fire drill reports for the last 4 quarters revealed that 3rd. shift fire drills were conducted at varied times. Fire drills were conducted between 11:00 p.m. and 11:45 p.m. as indicated on fire drill reports dated 3/20/16 (11:45 p.m.), 12/31/15 (11:45 p.m.), 8/31/15 (11:00 p.m.) and 6/29/15 (11:00 p.m.).

NJAC 8:39-31.6b

Fire drills will be conducted at unexpected times under varying conditions

Any resident has the potential to be affected

The Administrator will in- service Maintenance Director/ Designee tol conduct fire drills at unexpected times under varying conditions

Administrator/Maintenance

Director/Designee will audit fire drills monthly x3.

LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE TITLE (X6) DATE

04/01/2016 Electronically Signed

Any deficiency statement ending with an asterisk (*) denotes a deficiency which the institution may be excused from correcting providing it is determined that other safeguards provide sufficient protection to the patients . (See instructions.) Except for nursing homes, the findings stated above are disclosable 90 days following the date of survey whether or not a plan of correction is provided. For nursing homes, the above findings and plans of correction are disclosable 14 days following the date these documents are made available to the facility. If deficiencies are cited, an approved plan of correction is requisite to continued program participation.

(2)

A. BUILDING 02

(X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: STATEMENT OF DEFICIENCIES

AND PLAN OF CORRECTION

(X3) DATE SURVEY COMPLETED PRINTED: 08/10/2017 FORM APPROVED (X2) MULTIPLE CONSTRUCTION B. WING _____________________________

DEPARTMENT OF HEALTH AND HUMAN SERVICES

CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO. 0938-0391

315259 03/04/2016

STREET ADDRESS, CITY, STATE, ZIP CODE NAME OF PROVIDER OR SUPPLIER

1180 ROUTE 22 WEST MANOR CARE MOUNTAINSIDE

MOUNTAINSIDE, NJ 07092

PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE

DEFICIENCY) (X5) COMPLETION DATE ID PREFIX TAG (X4) ID PREFIX TAG

SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION)

K 050 Continued From page 1 K 050

Results of the audits will be forwarded monthly to the Quality Assessment and Assurance Committee for review and action as appropriate.

The Quality Assessment and Assurance Committee will determine the need for further or continued action.

K 052 SS=C

NFPA 101 LIFE SAFETY CODE STANDARD A fire alarm system required for life safety shall be, tested, and maintained in accordance with NFPA 70 National Electric Code and NFPA 72 National Fire Alarm Code and records kept readily available. The system shall have an approved maintenance and testing program complying with applicable requirement of NFPA 70 and 72. 9.6.1.4, 9.6.1.7,

This STANDARD is not met as evidenced by:

K 052 4/7/16

Based on surveyor's interview and review of facility records on 3/1/16, it was determined that the facility failed to ensure that their fire alarm system was tested semiannually (6-month intervals) as evidenced by the following: A review of the facility's fire alarm system

inspection reports for period 3/15 to 3/16 revealed that the system was inspected only once as indicated by a report dated 12/28/15. The previous inspection of the fire alarm system was done on 1/20/15 according to a report provided by the facility. The facility was due for an inspection no later than 6/20/15. The facility was unable to provide a fire alarm system inspection report for this date. The facility's Administrator revealed in an interview on 3/2/16 at approximately 11:30 a.m. that the facility's fire alarm system was only inspected once within the last 12 months. NJAC 8:39-31.2e

Fire Alarm System has been scheduled for June 2016 to meet requirement semiannually (6 month intervals

Anyone in the facility has the potential to be affected.

Administrator/Maintenance Director will schedule Fire Alarm System inspections and have scheduled standing semi-annual June 2016 and December 2016 going forward and have scheduled standing semi-annual inspections.

Results of the inspections June 2016 and December 2016 will be forwarded to the Quality Assessment and Assurance Committee for review and action as appropriate.

(3)

K 052 Continued From page 2 K 052

The Quality Assessment and Assurance Committee will determine the need for further or continued action.

K 062 SS=E

NFPA 101 LIFE SAFETY CODE STANDARD Required automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested

periodically. 19.7.6, 4.6.12, NFPA 13, NFPA 25, 9.7.5

This STANDARD is not met as evidenced by:

K 062 4/7/16

Based on observation in the presence of the facility's Maintenance Director on 3/1/16 and 3/2/16, it was determined that the facility failed to maintain their automatic sprinkler system in safe operating condition as evidence by the following: A tour of the building revealed that automatic sprinkler heads were not free of obstructions. On 3/1/16 at 10:20 a.m., the surveyor observed a pile of personal clothing stored directly under a ceiling mounted sprinkler head in the wardrobe closet in resident room #209. The top of the clothing pile was touching the sprinkler head's spray deflector, thus obstructing its coverage and discharge pattern. On 3/2/16 at 1:20 p.m., the surveyor observed that the automatic sprinkler head in the kitchen's walk-in freezer was covered with an accumulation of dust. Also, the sprinkler heads glass tube was covered with a rust-like substance. The accumulated dust and rust-like substance could prevent the sprinkler head from quick and prompt activation when needed. NJAC 8:39-31.2(e)

The obstructed sprinkler system in room#209 has been corrected. The automatic sprinkler head in the kitchen’s walk-in freezer was replaced. Anyone in the facility has the potential to be affected.

Administrator/Maintenance Director will complete random checks of facility for sprinkler heads so that are free from obstruction and are maintained. Administrator/Maintenance

Director/Designee will randomly check sprinklers for obstructions and are maintained. Weekly x4 and monthly x3. Results of the audits will be forwarded monthly to the Quality Assessment and Assurance Committee for review and action as appropriate.

The Quality Assessment and Assurance Committee will determine the need for

(4)

A. BUILDING 02

(X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: STATEMENT OF DEFICIENCIES

AND PLAN OF CORRECTION

(X3) DATE SURVEY COMPLETED PRINTED: 08/10/2017 FORM APPROVED (X2) MULTIPLE CONSTRUCTION B. WING _____________________________

DEPARTMENT OF HEALTH AND HUMAN SERVICES

CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO. 0938-0391

315259 03/04/2016

STREET ADDRESS, CITY, STATE, ZIP CODE NAME OF PROVIDER OR SUPPLIER

1180 ROUTE 22 WEST MANOR CARE MOUNTAINSIDE

MOUNTAINSIDE, NJ 07092

PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE

DEFICIENCY) (X5) COMPLETION DATE ID PREFIX TAG (X4) ID PREFIX TAG

SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION)

K 062 Continued From page 3 K 062

further or continued action. K 147

SS=C

NFPA 101 LIFE SAFETY CODE STANDARD Electrical wiring and equipment shall be in accordance with National Electrical Code. 9-1.2 (NFPA 99) 18.9.1, 19.9.1

This STANDARD is not met as evidenced by:

K 147 4/7/16

Based on review of facility records on 3/1/16, it was determined that the facility failed to ensure that the building's electrical system was inspected annually by a licensed electrician as evidenced by the following:

A review of the electrical system inspection reports provided by the facility revealed that the system was last inspected in 2014 as indicated on a report dated 3/24/14. The facility did not have their electrical system inspected in 2015 and was unable to provide any additional information.

NJAC 8:39-31.6b

Electrical system was inspected on February 24rd 2016

Anyone in the facility has the potential to be affected.

Administrator/Maintenance Director will have electrical inspection annually by licensed electrician.

The Administrator /Maintenance Director schedule electrical inspection 3 months prior to annual requirement.

Copy of electrical inspection will be submitted to Quality Assessment and Assurance Committee review and action as appropriate.

The Quality Assessment and Assurance Committee will determine the need for further or continued action.

(5)

provision number and the identification prefix code previously shown on the CMS-2567 (prefix codes shown to the left of each requirement on the survey report form).

Y4 ITEM Y5 DATE Y4 ITEM Y5 DATE DATE Y5 ITEM Y4 ID Prefix Correction

Reg. # NFPA 101 Completed

LSC K0050 04/07/2016

ID Prefix Correction

Reg. # NFPA 101 Completed

LSC K0052 04/07/2016

ID Prefix Correction

Reg. # NFPA 101 Completed

LSC K0062 04/07/2016

ID Prefix Correction

Reg. # NFPA 101 Completed

LSC K0147 04/07/2016 ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC ID Prefix Correction Reg. # Completed LSC REVIEWED BY STATE AGENCY REVIEWED BY CMS RO REVIEWED BY (INITIALS) REVIEWED BY (INITIALS) DATE

DATE SIGNATURE OF SURVEYOR

TITLE DATE

DATE

FOLLOWUP TO SURVEY COMPLETED ON CHECK FOR ANY UNCORRECTED DEFICIENCIES. WAS A SUMMARY OF

UNCORRECTED DEFICIENCIES (CMS-2567) SENT TO THE FACILITY? YES NO 3/4/2016

References

Related documents

Most companies recruit for full-time and internship positions, but some indicate Co-Op as a recruiting priority, while not attending Professional Practice

public class XorSocket extends Socket { private final byte pattern;}. private InputStream in

COPIER TECHNOLOGY A NEW BEGINNING IN DIGITAL DICTATION SPEECH RECOGNITION TRANSCRIPTION SERVICES Professional Solutions... The digital dictation solution we offer is developed to

What are the driving factors leading companies to request sales tax outsourcing services:. • Complexity of returns at the local level of tax (County

We are now using the second part of our test database (see Figure 4 ) ; the boxpoints table which contains 3000 customer points, and the box table with 51 dierent sized bounding

With regard to more specialized practices of Agility, related to the piloting of a project, to communication or development, PUMA is based on the standards of

This section outlines the method to find the best allocation of n distinguishable processors to m dis- tinguishable blocks so as to minimize the execution time.. Therefore,

$1000 and a complimentary letter to Mary Patten for her heroic work in bringing the fast sailing clipper ship safely around the dangerous Cape Horn?. When Mary and Captain