PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for
Design Conditions WB (F) RH (%)
ROOM HEAT Ambient 75.00 20.00
ROOM SENSIBLE HEAT Room 63.00 50.00
Solar Gain - Glass Difference -
-Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF) = 0.30 Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF) = 0.70
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person 30.00 No = 6.00 = 180.00 Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt 0.33 Sqft x 160.97 = 53.12 Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM) = 1.00
Skylight SqFt x F x 0.00 CFM Cu.ft 1,609.65 x 1.00 x1/60 = 26.83 Solar & Transmission Gain - Walls & Roof
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window x cfm/window = 0.00 Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00 Wall - E SqFt x F x 0.00 Open Doors x cfm/door = 0.00 Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.00 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) = All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (F) = 53.50 Partition 300.80 SqFt x 30.00 F x 0.32 2,887.68
Ceiling 160.96 SqFt x 30.00 F x 0.16 772.61 (Room DB - ADP) x CF = 15.05 Floor 160.96 SqFt x 30.00 F x 0.16 772.61 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08 = 1,202.19 CFM Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat = 565.03 L/s
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY Lighting 160.97 SqFt x 0.75 W/SqFt x 3.41 409.14 3.01
Equipments 160.97 SqFt x 2.48 W/SqFt x 3.41 1,363.94 Power 0.00 kW/Hpx 0.00 0.00
17,763.98 5-10% 1,776.40
19,540.38 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.33 TR
Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00 933.91 cfm Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00 2,025.60 2.5 - 5% 101.28
2,126.88 2.00
EFFECTIVE ROOM TOTAL HEAT 21,667.26 OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 27,201.18
1 - 3% 816.04 28,017.21 TONS=GRAND TOTAL HEAT/12000 2.33
G+5 BUILDING HEAT LOAD 1st floor Right side
Laxmi nagar , New delhi. HALL
XYZ 160.97
Item Area or Quantity
Sun Gain or Temp. Diff. Factor Btu/Hour
ABC 10.00 1,609.65 CFM Ventilation W Summer DB (F) SH Gr/Lb 110.00 75.00 75.00 66.00 35.00 9.00
GRAND TOTAL HEAT
CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise
Sub Total Factor
Effective Room Sensible Heat
Sub Total Factor Effective Room Latent Heat
Factor
TR = 3.01 CFM =1202.19
PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N 0.00 SqFt x 0.00 F x 0.00 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat
Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) All Glass 0.00 SqFt x 35.00 F x 0.65 0.00 Selected ADP (F) Partition 147.40 SqFt x 30.00 F x 0.32 1,415.04
Ceiling 54.31 SqFt x 30.00 F x 0.16 260.69 (Room DB - ADP) x CF
Floor 54.31 SqFt x 30.00 F x 0.16 260.69 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 20.00 CFM x 35.00 T.Diff x 1.08 756.00 Dehumidified Rise x 1.08 Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY Lighting 54.32 SqFt x 2.20 W/SqFt x 3.41 407.47 1.37
Equipments 54.32 SqFt x 11.04 W/SqFt x 3.41 2,044.78
Power 0.00 kW/Hpx 0.00 0.00
8,655.86 5-10% 865.59
9,521.45
1.00
SENSIBLE HEAT CAPACITY XYZG+5 BUILDING HEAT LOAD Laxmi nagar , New delhi.
Item Area or Quantity
Sun Gain or Temp. Diff. Factor Btu/Hour
ABC
W
CFM Ventilation
CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise
Sub Total Factor
ROOM LATENT HEAT Grand Sensible Heat Infiltration 20.00 CFM x 9.00 Gr/Lb x 0.68 122.40 12,000.00
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48 People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
1,682.88 2.5 - 5% 84.14
1,767.02
2.00
EFFECTIVE ROOM TOTAL HEAT 11,288.48
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80
3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12
4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 16,822.40
1 - 3% 504.67 17,327.07
TONS=GRAND TOTAL HEAT/12000 1.44
Effective Room Latent Heat
Factor GRAND TOTAL HEAT
Sub Total Factor
7.41 7.33 Area 54.3153 WB (F) RH (%) 75.00 20.00 63.00 50.00 - -= 0.30 Contact Factor (CF = 1 - BF) = 0.70 30.00 No = 6.00 = 180.00 0.33 Sqft x 54.32 = 17.92 Air Change Per Hour (CFM) = 1.00
543.15 x 1.00 x1/60 = 9.05 x cfm/window = 0.00 Revolving Doors (People) x cfm/door = 0.00 x cfm/door = 0.00
x cfm/ft = 0.00
0.00 Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = =
= 52.00
(Room DB - ADP) x CF = 16.10
DEHUMIDIFIED Cfm (AIR QUANTITY) Effective Room Sensible Heat
Dehumidified Rise x 1.08 = 547.59 CFM = 257.37 L/s TOTAL HEAT CAPACITY
SENSIBLE HEAT CAPACITY
54.32
1st floor Right side DIMENSION
DINING 10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY 543.15 Summer DB (F) SH Gr/Lb 110.00 75.00 TR = 1.37 75.00 66.00 35.00 9.00 CFM Ventilation CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise
= 1.44 TR ACCEPT THIS TR 577.57 cfm ACCEPT THIS CFM
PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S 59.10 SqFt x 43.00 F x 0.48 1,219.82
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat
Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (F) Partition 101.60 SqFt x 30.00 F x 0.32 975.36
Ceiling 148.68 SqFt x 30.00 F x 0.16 713.66 (Room DB - ADP) x CF
Floor 148.68 SqFt x 30.00 F x 0.16 713.66 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08 Outside Air 60.00 CFM x 35.00 T.Diff x 0.3x 1.08 680.40
Internal Heat
People 2.00 Nos. x 245.00 Btu/Hour Per Person 490.00 TOTAL HEAT CAPACITY Lighting 148.68 SqFt x 0.40 W/SqFt x 3.41 204.57 2.48
Equipments 148.68 SqFt x 2.35 W/SqFt x 3.41 1,193.48
Power 0.00 kW/Hpx 0.00 0.00
14,237.76 5-10% 1,423.78
15,661.54
1.00
SENSIBLE HEAT CAPACITY XYZG+5 BUILDING HEAT LOAD Laxmi nagar , New delhi.
Item Area or Quantity
Sun Gain or Temp. Diff. Factor Btu/Hour
ABC
W
CFM Ventilation
CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise
Sub Total Factor
ROOM LATENT HEAT Grand Sensible Heat Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00
Outside Air 60.00 CFM x 9.00 Gr/Lb x BFx0.68 110.16 People 2.00 Nos. x 205.00 Btu/Hour Per Person 410.00 985.28 2.5 - 5% 49.26
1,034.54
2.00
EFFECTIVE ROOM TOTAL HEAT 16,696.08
OUTSIDE AIR HEAT
Sensible 60.00 CFM x 35.00 F(TD) x CF x 1.08 1,587.60
3.00
Latent 60.00 CFM x 9.00 Gr/Lb x CF x 0.68 257.04
4.00
OUTSIDE AIR TOTAL HEAT 1,844.64 Notes:
GRAND SUB-TOTAL HEAT 18,540.72
1 - 3% 556.22 19,096.94
TONS=GRAND TOTAL HEAT/12000 1.59
Effective Room Latent Heat
Factor GRAND TOTAL HEAT
Sub Total Factor
10.5 14.16 Area 148.68 WB (F) RH (%) 75.00 20.00 63.00 50.00 - -= 0.30 Contact Factor (CF = 1 - BF) = 0.70 30.00 No = 2.00 = 60.00 0.33 Sqft x 148.68 = 49.06 Air Change Per Hour (CFM) = 1.00
1,486.80 x 1.00 x1/60 = 24.78 x cfm/window = 0.00 Revolving Doors (People) x cfm/door = 0.00 x cfm/door = 0.00
x cfm/ft = 0.00
0.00 Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = =
= 54.15
(Room DB - ADP) x CF = 14.60
DEHUMIDIFIED Cfm (AIR QUANTITY) Effective Room Sensible Heat
Dehumidified Rise x 1.08 = 993.59 CFM = 466.99 L/s TOTAL HEAT CAPACITY
ACCEPT THIS TR
SENSIBLE HEAT CAPACITY
148.68
1st floor Right side DIMENSION
BEDROOM 10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY 1,486.80 Summer DB (F) SH Gr/Lb 110.00 75.00 CFM Ventilation CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise
75.00 66.00
35.00 9.00
CFM =993.59 TR = 2.48
= 1.59 TR
PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E 40.00 SqFt x 12.00 F x 0.65 312.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E 101.60 SqFt x 29.00 F x 0.48 1,414.27 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat
Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (F) Partition 161.60 SqFt x 30.00 F x 0.32 1,551.36
Ceiling 172.19 SqFt x 30.00 F x 0.16 826.49 (Room DB - ADP) x CF
Floor 172.19 SqFt x 30.00 F x 0.16 826.49 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 56.00 CFM x 35.00 T.Diff x 1.08 2,116.80 Dehumidified Rise x 1.08 Outside Air 120.00 CFM x 35.00 T.Diff x 0.3x 1.08 1,360.80
Internal Heat
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY Lighting 172.19 SqFt x 0.58 W/SqFt x 3.41 340.99 2.06
Equipments 172.19 SqFt x 2.61 W/SqFt x 3.41 1,534.41
Power 0.00 kW/Hpx 0.00 0.00
12,173.61 5-10% 1,217.36
13,390.97
1.00
SENSIBLE HEAT CAPACITY Sub TotalFactor
Effective Room Sensible Heat
CFM Ventilation
CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise W ABC Item Area or Quantity Sun Gain or Temp. Diff. Factor Btu/Hour
XYZ
G+5 BUILDING HEAT LOAD Laxmi nagar , New delhi.
ROOM LATENT HEAT Grand Sensible Heat Infiltration 56.00 CFM x 9.00 Gr/Lb x 0.68 342.72 12,000.00
Outside Air 120.00 CFM x 9.00 Gr/Lb x BFx0.68 220.32 People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00 1,383.04 2.5 - 5% 69.15
1,452.19
2.00
EFFECTIVE ROOM TOTAL HEAT 14,843.16
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 35.00 F(TD) x CF x 1.08 3,175.20
3.00
Latent 120.00 CFM x 9.00 Gr/Lb x CF x 0.68 514.08
4.00
OUTSIDE AIR TOTAL HEAT 3,689.28 Notes:
GRAND SUB-TOTAL HEAT 18,532.44
1 - 3% 555.97 19,088.42
TONS=GRAND TOTAL HEAT/12000 1.59
Effective Room Latent Heat
Factor GRAND TOTAL HEAT
Sub Total Factor
12.16 14.16 Area 172.1856 WB (F) RH (%) 75.00 20.00 63.00 50.00 - -= 0.30 Contact Factor (CF = 1 - BF) = 0.70 30.00 No = 4.00 = 120.00 0.33 Sqft x 172.19 = 56.82 Air Change Per Hour (CFM) = 1.00
1,721.86 x 1.00 x1/60 = 28.70 x cfm/window = 0.00 Revolving Doors (People) x cfm/door = 0.00 x cfm/door = 0.00
x cfm/ft = 0.00
0.00 Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = =
= 53.50
(Room DB - ADP) x CF = 15.05
DEHUMIDIFIED Cfm (AIR QUANTITY) Effective Room Sensible Heat
Dehumidified Rise x 1.08 = 823.86 CFM = 387.21 L/s TOTAL HEAT CAPACITY
ACCEPT THIS TR
SENSIBLE HEAT CAPACITY
CFM =823.86 TR = 2.06 75.00 66.00 35.00 9.00 CFM Ventilation CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise Summer
DB (F) SH Gr/Lb
110.00 75.00
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY 1,721.86
172.19
1st floor Right side DIMENSION
= 1.59 TR
PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for
Design Conditions WB (F) RH (%)
ROOM HEAT Ambient 75.00 20.00
ROOM SENSIBLE HEAT Room 63.00 50.00
Solar Gain - Glass Difference -
-Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF) = 0.30 Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF) = 0.70
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person 30.00 No = 6.00 = 180.00 Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt 0.33 Sqft x 160.97 = 53.12 Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM) = 1.00
Skylight SqFt x F x 0.00 CFM Cu.ft 1,609.65 x 1.00 x1/60 = 26.83 Solar & Transmission Gain - Walls & Roof
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window x cfm/window = 0.00 Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00 Wall - E SqFt x F x 0.00 Open Doors x cfm/door = 0.00 Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.00 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) = All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (F) = 53.25 Partition 218.30 SqFt x 30.00 F x 0.32 2,095.68
Ceiling 160.97 SqFt x 30.00 F x 0.16 772.63 (Room DB - ADP) x CF = 15.23 Floor 160.97 SqFt x 30.00 F x 0.16 772.63 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08 = 1,135.39 CFM Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat = 533.63 L/s
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY Lighting 160.97 SqFt x 0.75 W/SqFt x 3.41 409.14 2.84
Equipments 160.97 SqFt x 2.48 W/SqFt x 3.41 1,363.94 Power 0.00 kW/Hpx 0.00 0.00
16,972.03 5-10% 1,697.20
18,669.23 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.26 TR
Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00 904.00 cfm Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00 2,025.60 2.5 - 5% 101.28
2,126.88 2.00
EFFECTIVE ROOM TOTAL HEAT 20,796.11 OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 26,330.03
1 - 3% 789.90 27,119.93 TONS=GRAND TOTAL HEAT/12000 2.26
Effective Room Latent Heat
Factor GRAND TOTAL HEAT
CFM =1135.39 Sub Total
Factor
Effective Room Sensible Heat
Sub Total Factor TR = 2.84 75.00 66.00 35.00 9.00 CFM Ventilation CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise W Summer DB (F) SH Gr/Lb 110.00 75.00 ABC 10.00 1,609.65 Item Area or Quantity Sun Gain or Temp. Diff. Factor Btu/Hour
XYZ 160.97
G+5 BUILDING HEAT LOAD 1st floor Right side
PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N 0.00 SqFt x 0.00 F x 0.00 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat
Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) All Glass 0.00 SqFt x 35.00 F x 0.65 0.00 Selected ADP (F) Partition 156.60 SqFt x 30.00 F x 0.32 1,503.36
Ceiling 61.20 SqFt x 30.00 F x 0.16 293.76 (Room DB - ADP) x CF
Floor 61.20 SqFt x 30.00 F x 0.16 293.76 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 20.00 CFM x 35.00 T.Diff x 1.08 756.00 Dehumidified Rise x 1.08 Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY Lighting 61.20 SqFt x 1.96 W/SqFt x 3.41 409.04 1.39
Equipments 61.20 SqFt x 9.80 W/SqFt x 3.41 2,046.00
Power 0.00 kW/Hpx 0.00 0.00
8,813.12 5-10% 881.31
9,694.43
1.00
SENSIBLE HEAT CAPACITY Sub TotalFactor
Effective Room Sensible Heat
CFM Ventilation
CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise W ABC Item Area or Quantity Sun Gain or Temp. Diff. Factor Btu/Hour
XYZ
G+5 BUILDING HEAT LOAD Laxmi nagar , New delhi.
ROOM LATENT HEAT Grand Sensible Heat Infiltration 20.00 CFM x 9.00 Gr/Lb x 0.68 122.40 12,000.00
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48 People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
1,682.88 2.5 - 5% 84.14
1,767.02
2.00
EFFECTIVE ROOM TOTAL HEAT 11,461.45
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80
3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12
4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 16,995.37
1 - 3% 509.86 17,505.23
TONS=GRAND TOTAL HEAT/12000 1.46
Effective Room Latent Heat
Factor GRAND TOTAL HEAT
Sub Total Factor
7.5 8.16 Area 61.2 WB (F) RH (%) 75.00 20.00 63.00 50.00 - -= 0.30 Contact Factor (CF = 1 - BF) = 0.70 30.00 No = 6.00 = 180.00 0.33 Sqft x 61.20 = 20.20 Air Change Per Hour (CFM) = 1.00
612.00 x 1.00 x1/60 = 10.20 x cfm/window = 0.00 Revolving Doors (People) x cfm/door = 0.00 x cfm/door = 0.00
x cfm/ft = 0.00
0.00 Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = =
= 52.00
(Room DB - ADP) x CF = 16.10
DEHUMIDIFIED Cfm (AIR QUANTITY) Effective Room Sensible Heat
Dehumidified Rise x 1.08 = 557.54 CFM = 262.04 L/s TOTAL HEAT CAPACITY
SENSIBLE HEAT CAPACITY
CFM =557.54 TR = 1.39 75.00 66.00 35.00 9.00 CFM Ventilation CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise Summer
DB (F) SH Gr/Lb
110.00 75.00
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY 612.00
61.20
1st floor Right side DIMENSION
= 1.46 TR ACCEPT THIS TR 583.51 cfm ACCEPT THIS CFM
PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W 164.00 SqFt x 20.00 F x 0.65 2,132.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof
Wall - N 105.00 SqFt x 27.00 F x 0.48 1,360.80 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S 0.00 SqFt x 0.00 F x 0.00 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat
Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) All Glass 20.00 SqFt x 35.00 F x 0.65 455.00 Selected ADP (F) Partition 181.60 SqFt x 30.00 F x 0.32 1,743.36
Ceiling 148.68 SqFt x 30.00 F x 0.16 713.66 (Room DB - ADP) x CF
Floor 148.68 SqFt x 30.00 F x 0.16 713.66 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 38.00 CFM x 35.00 T.Diff x 1.08 1,436.40 Dehumidified Rise x 1.08 Outside Air 60.00 CFM x 35.00 T.Diff x 0.3x 1.08 680.40
Internal Heat
People 2.00 Nos. x 245.00 Btu/Hour Per Person 490.00 TOTAL HEAT CAPACITY Lighting 148.68 SqFt x 0.40 W/SqFt x 3.41 204.57 1.95
Equipments 148.68 SqFt x 2.35 W/SqFt x 3.41 1,193.48
Power 0.00 kW/Hpx 0.00 0.00
11,123.34 5-10% 1,112.33
12,235.67
1.00
SENSIBLE HEAT CAPACITY Sub TotalFactor
Effective Room Sensible Heat
CFM Ventilation
CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise W ABC Item Area or Quantity Sun Gain or Temp. Diff. Factor Btu/Hour
XYZ
G+5 BUILDING HEAT LOAD Laxmi nagar , New delhi.
ROOM LATENT HEAT Grand Sensible Heat Infiltration 38.00 CFM x 9.00 Gr/Lb x 0.68 232.56 12,000.00
Outside Air 60.00 CFM x 9.00 Gr/Lb x BFx0.68 110.16 People 2.00 Nos. x 205.00 Btu/Hour Per Person 410.00 752.72 2.5 - 5% 37.64
790.36
2.00
EFFECTIVE ROOM TOTAL HEAT 13,026.03
OUTSIDE AIR HEAT
Sensible 60.00 CFM x 35.00 F(TD) x CF x 1.08 1,587.60
3.00
Latent 60.00 CFM x 9.00 Gr/Lb x CF x 0.68 257.04
4.00
OUTSIDE AIR TOTAL HEAT 1,844.64 Notes:
GRAND SUB-TOTAL HEAT 14,870.67
1 - 3% 446.12 15,316.79
TONS=GRAND TOTAL HEAT/12000 1.28
Effective Room Latent Heat
Factor GRAND TOTAL HEAT
Sub Total Factor
10.5 14.16 Area 148.68 WB (F) RH (%) 75.00 20.00 63.00 50.00 - -= 0.30 Contact Factor (CF = 1 - BF) = 0.70 30.00 No = 2.00 = 60.00 0.33 Sqft x 148.68 = 49.06 Air Change Per Hour (CFM) = 1.00
1,486.80 x 1.00 x1/60 = 24.78 x cfm/window = 0.00 Revolving Doors (People) x cfm/door = 0.00 x cfm/door = 0.00
x cfm/ft = 0.00
0.00 Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = =
= 54.30
(Room DB - ADP) x CF = 14.49
DEHUMIDIFIED Cfm (AIR QUANTITY) Effective Room Sensible Heat
Dehumidified Rise x 1.08 = 781.87 CFM = 367.48 L/s TOTAL HEAT CAPACITY
ACCEPT THIS TR
SENSIBLE HEAT CAPACITY
CFM =781.87 TR = 1.95 75.00 66.00 35.00 9.00 CFM Ventilation CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise Summer
DB (F) SH Gr/Lb
110.00 75.00
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY 1,486.80
148.68
1st floor Right side DIMENSION
= 1.28 TR
PROJECT FLOOR
LOCATION SPACE REFERENCE
CLIENT AREA ( SqFt)
CONSULTANT Height (Ft)
Volume (CuFt) Estimate for Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E 20.00 SqFt x 12.00 F x 0.65 156.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E 86.60 SqFt x 29.00 F x 0.48 1,205.47 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat
Roof 0.00 SqFt x 0.00 F x 0.00 0.00
Transmission Gain - Except Walls & Roof Indicated ADP (F) All Glass 20.00 SqFt x 35.00 F x 0.65 455.00 Selected ADP (F) Partition 201.60 SqFt x 30.00 F x 0.32 1,935.36
Ceiling 129.63 SqFt x 30.00 F x 0.16 622.20 (Room DB - ADP) x CF
Floor 129.63 SqFt x 30.00 F x 0.16 622.20 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 38.00 CFM x 35.00 T.Diff x 1.08 1,436.40 Dehumidified Rise x 1.08 Outside Air 120.00 CFM x 35.00 T.Diff x 0.3x 1.08 1,360.80
Internal Heat
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY Lighting 129.63 SqFt x 0.77 W/SqFt x 3.41 340.99 1.78
Equipments 129.63 SqFt x 3.47 W/SqFt x 3.41 1,534.44
Power 0.00 kW/Hpx 0.00 0.00
10,648.86 5-10% 1,064.89
11,713.75
1.00
SENSIBLE HEAT CAPACITY Sub TotalFactor
Effective Room Sensible Heat
CFM Ventilation
CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise W ABC Item Area or Quantity Sun Gain or Temp. Diff. Factor Btu/Hour
XYZ
G+5 BUILDING HEAT LOAD Laxmi nagar , New delhi.
ROOM LATENT HEAT Grand Sensible Heat Infiltration 38.00 CFM x 9.00 Gr/Lb x 0.68 232.56 12,000.00
Outside Air 120.00 CFM x 9.00 Gr/Lb x BFx0.68 220.32 People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00 1,272.88 2.5 - 5% 63.64
1,336.52
2.00
EFFECTIVE ROOM TOTAL HEAT 13,050.27
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 35.00 F(TD) x CF x 1.08 3,175.20
3.00
Latent 120.00 CFM x 9.00 Gr/Lb x CF x 0.68 514.08
4.00
OUTSIDE AIR TOTAL HEAT 3,689.28 Notes:
GRAND SUB-TOTAL HEAT 16,739.55
1 - 3% 502.19 17,241.74
TONS=GRAND TOTAL HEAT/12000 1.44
Effective Room Latent Heat
Factor GRAND TOTAL HEAT
Sub Total Factor
12.16 10.66 Area 129.6256 WB (F) RH (%) 75.00 20.00 63.00 50.00 - -= 0.30 Contact Factor (CF = 1 - BF) = 0.70 30.00 No = 4.00 = 120.00 0.33 Sqft x 129.63 = 42.78 Air Change Per Hour (CFM) = 1.00
1,296.26 x 1.00 x1/60 = 21.60 x cfm/window = 0.00 Revolving Doors (People) x cfm/door = 0.00 x cfm/door = 0.00
x cfm/ft = 0.00
0.00 Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = =
= 53.25
(Room DB - ADP) x CF = 15.23
DEHUMIDIFIED Cfm (AIR QUANTITY) Effective Room Sensible Heat
Dehumidified Rise x 1.08 = 712.39 CFM = 334.82 L/s TOTAL HEAT CAPACITY
ACCEPT THIS TR
SENSIBLE HEAT CAPACITY
CFM =712.39 TR = 1.78 75.00 66.00 35.00 9.00 CFM Ventilation CFM Infiltration
Supply CFM from Machine
Apparatus Dew Point (ADP)
Dehumidified Rise Summer
DB (F) SH Gr/Lb
110.00 75.00
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY 1,296.26
129.63
1st floor Right side DIMENSION
= 1.44 TR
ROOMS TR CFM TR CFM BEDROOM 1.25 501.85 1.92 771.95 DINING 1.42 571.71 1.408 563.5 HALL 1.81 727.12 2.22 890.07 MASTER BEDROOM 1.33 533.15 1.75 703.57 TOTAL TR 7.31 TR TOTAL CFM 2333.83 CFM ROOMS TR CFM TR CFM BEDROOM 1.43 572 2.25 900 DINING 1.6 640 1.63 655.44 HALL 2.39 956 3.16 1267.87 MASTER BEDROOM 1.44 576 1.78 712 ROOMS TR CFM TR CFM BEDROOM 1.18 472 1.78 713.39 DINING 1.6 640 1.64 656 HALL 1.4 560 1.95 782 MASTER BEDROOM 1.43 572 1.81 726 TOTAL TR IN RHS IN 1ST FLOOR 17.0259 TOTAL CFM IN RHS IN 1ST FLOOR 5357.111 TOTAL TR IN 1ST FLOOR 32.2159 TR TOTAL CFM IN 1ST FLOOR 10056.33 CFM 128.8636 TR 40225.32 CFM TOTAL TR 1-5th floor 160.6636 TR total cfm 1-5th floor 50189.32 CFM TOTAL TR UPTO 4TH FLOOR
TOTAL CFM UPTO 4TH FLOOR
G+5 BUILDING HEAT LOAD 1ST FLOOR
CALCULATED DEHUMIDIFIED
LEFT TOP FLAT IN 1ST FLOOR (3)
RIGHT TOP
CALCULATED DEHUMIDIFIED
G+5 BUILDING HEAT LOAD 5th FLOOR
LEFT TOP
LEFT BOTTOM FLAT IN 1ST FLOOR (4) ROOMS TR CFM TR CFM BEDROOM 1.7 680.8 1024.25 2.56 DINING 1.45 582.7 574.54 1.43 HALL 1.36 547.8 858.87 2.14 MASTER BEDROOM 1.385 554.09 694.63 1.73 TOTAL TR 7.88 TR TOTAL CFM 2365.39 CFM ROOMS TR CFM TR CFM HALL 2.5 1000 3.37 348.02 DINING 1.45 580 1.44 577.92 BEDROOM 1.53 612 2.41 966.29 MASTER BEDROOM 1.37 548 1.67 671.46 ROOMS TR CFM TR CFM BEDROOM 1.2 480 1.74 696.53 DINING 1.47 588 1.41 565.62 HALL 1.32 528 1.59 639.14 MASTER BEDROOM 1.6 640 2.1 840 31.8 TOTAL CFM IN 5TH FLOOR 9964
G+5 BUILDING HEAT LOAD 1ST FLOOR
CALCULATED
RIGHT BOTTOM
CALCULATED DEHUMIDIFIED
TOTAL TR IN 5TH FLOOR
DEHUMIDIFIED
G+5 BUILDING HEAT LOAD 5th FLOOR
LEFT BOTTOM