AS/NZS 1668.1:1998

(Incorporating Amendment No. 1)

Australian/New Zealand Standard

The use of ventilation and

airconditioning in buildings

Part 1: Fire and smoke control in

multi-compartment buildings

A S /N ZS 1668 .1:1 998

(2)

AS/NZS 1668.1:1998

This Joint Australian/New Zealand Standard was prepared by Joint Technical Committee ME-062, Ventilation and Airconditioning. It was approved on behalf of the Council of Standards Australia on 12 June 1998 and on behalf of the Council of Standards New Zealand on 9 June 1998.

This Standard was published on 5 November 2008.

The following are represented on Committee ME-062:

Air Conditioning and Mechanical Contractors Association of Australia Air Conditioning and Refrigeration Equipment Manufacturers association of Australia

Australasian Fire Authorities Council Australian Building Codes Board

Australian Institute of Building Surveyors Australian Institute of Environmental Health

Australian Institute of Refrigeration, Air Conditioning and Heating Chartered Institution of Building Services Engineers

Department of Contract and Management Services, W.A. FPA Australia

Institution of Refrigeration Heating and Airconditioning Engineers. New Zealand Insurance Council of Australia

Metal Trades Industry Association of Australia Plastics and Chemicals Industry Association Property Council of Australia

Thermal Insulation Contractors Association of Australia

Keeping Standards up-to-date

Standards are living documents which reflect progress in science, technology and systems. To maintain their currency, all Standards are periodically reviewed, and new editions are published. Between editions, amendments may be issued. Standards may also be withdrawn. It is important that readers assure themselves they are using a current Standard, which should include any amendments which may have been published since the Standard was purchased.

Detailed information about joint Australian/New Zealand Standards can be found by visiting the Standards Web Shop at www.standards.com.au or Standards New Zealand web site at www.standards.co.nz and looking up the relevant Standard in the on-line catalogue.

Alternatively, both organizations publish an annual printed Catalogue with full details of all current Standards. For more frequent listings or notification of revisions, amendments and withdrawals, Standards Australia and Standards New Zealand offer a number of update options. For information about these services, users should contact their respective national Standards organization.

We also welcome suggestions for improvement in our Standards, and especially encourage readers to notify us immediately of any apparent inaccuracies or ambiguities. Please address your comments to the Chief Executive of either Standards Australia or Standards New Zealand at the address shown on the back cover.

This Standard was issued in draft form for comment as DR 96503.

(3)

AS/NZS 1668.1:1998

(Incorporating Amendment No. 1)

Australian/New Zealand Standard

The use of ventilation and

airconditioning in buildings

Part 1: Fire and smoke control in

multi-compartment buildings

COPYRIGHT

© Standards Australia/Standards New Zealand

All rights are reserved. No part of this work may be reproduced or copied in any form or by any means, electronic or mechanical, including photocopying, without the written permission of the publisher.

Jointly published by Standards Australia, GPO Box 476, Sydney, NSW 2001 and Standards New Zealand, Private Bag 2439, Wellington 6020

ISBN 0 7337 2078 1

Originated in Australian as AS 1668.1—1974. Final Australian edition AS 1668.1—1991.

Jointly revised and designated AS/NZS 1668.1:1998. Reissued incorporating Amendment No. 1 (November 2002).

(4)

AS/NZS 1668.1:1998 2

PREFACE

This Standard was prepared by the Joint Standards Australia/Standards New Zealand Committee M-062, Ventilation and Airconditioning, to supersede AS 1668.1—1991, The use of mechanical ventilation and air-conditioning in buildings, Part 1: Fire and smoke control.

This Standard incorporates Amendment No. 1 (November 2002). The changes required by the Amendment are indicated in the text by a marginal bar and amendment number against the clause, note, table, figure or part thereof affected.

There is a considerable body of fire research which indicates that when a fire occurs in a multi-compartment building, the smoke from the fire is a far greater hazard to occupant safety than the fire itself, i.e.,

(a) Smoke obscures vision, preventing occupants from finding safe escape routes. (b) Smoke hinders the fire brigade in its search and rescue operations.

(c) Smoke can kill by asphyxiation or by poisoning people well before the temperature of the fire or smoke causes injury.

The fundamental purpose of this document is, therefore, life safety. Its objective is to provide standardized minimum requirements for mechanical air-handling and mechanical smoke control systems for use by designers, installers, inspectors and regulators of these systems. The Standard does not identify those buildings in which smoke control systems or pressurization systems are required. This is covered in the Building Code of Australia (BCA) or the New Zealand Building Code Handbook and approved documents, as applicable.

The first edition of AS 1668.1, published in 1974, prescribed a smoke control system intended to restrict the movement of smoke by way of airconditioning and ventilation ducting within a multistorey office building. This philosophy did not address smoke movement in a building by way of paths other than the air-handling system. Since the original publication, the Standard has changed, the zone pressurization system was added and the Standard has been applied (correctly and incorrectly) to buildings other than multistorey offices.

The objective of the Standard has also been expanded to limit smoke spread in a building by way of paths other than simply the ductwork. This revision looks deeper into the application of the Standard within buildings with varied uses, offers designers more options to find solutions for particular building types and further clarifies the intended application of the Standard.

The main technical changes made in this edition can be summarized as follows:

(i) Five particular methods of active smoke control have been included, with a table indicating which one The Standard has been linked to AS 1670.1.

(ii) More comprehensive testing clauses have been included.

(iii) Requirements for power and indication wiring and smoke detection for system control have been revised.

(iv) Requirements for non-electrical control systems have been added.

(v) Recommendations on reliability have been included because of concerns over the long-term operational capabilities of highly complex systems.

(vi) Protection of small exhaust duct penetrations in fire compartmentalization walls may now be by subduct rather than by fire dampers due to damper maintenance problems.

(5)

3 AS/NZS 1668.1:1998 The terms ‘normative’ and ‘informative’ have been used in this Standard to define the application of the appendix to which they apply. A ‘normative’ appendix is an integral part of a Standard, whereas an ‘informative’ appendix is only for information and guidance. Statements expressed in mandatory terms in notes to tables are deemed to be requirements of this Standard. Figures provided in this Standard are informative.

This Standard incorporates a Commentary on some of the clauses. The Commentary directly follows the relevant Clause, is designated by ‘C’ preceding the clause number and is printed in italics in a panel. The Commentary is for information only and does not need to be followed for compliance with the Standard.

(6)

AS/NZS 1668.1:1998 4

CONTENTS

Page SECTION 1 GENERAL 1.1 SCOPE ... 7 1.2 SYSTEM OBJECTIVES ... 7 1.3 APPLICATION ... 10

1.4 NEW DESIGNS AND INNOVATIONS ... 10

1.5 REFERENCED DOCUMENTS ... 11

1.6 DEFINITIONS ... 12

1.7 ACRONYMS... 16

SECTION 2 SECTION2AIR-HANDLING SYSTEMS—GENERAL REQUIREMENTS 2.1 SCOPE OF SECTION ... 17

2.2 DUCTWORK ... 17

2.3 PLENUMS AND CASINGS ... 18

2.4 AIR DAMPERS... 18

2.5 AIR FILTERS ... 19

2.6 ELECTRIC HEATERS... 20

2.7 ELECTRICAL INSTALLATION... 20

SECTION 3 FIRE PROTECTION OF OPENINGS 3.1 SCOPE OF SECTION ... 21

3.2 GENERAL ... 21

3.3 OPENINGS IN WALLS ... 21

3.4 OPENINGS IN FLOORS ... 22

3.5 FIRE-RESISTANT LIGHTWEIGHT STRUCTURES ... 24

3.6 SUBDUCTS ... 24

3.7 SMOKE-SPILL SYSTEMS... 27

3.8 INDIVIDUAL AIR-HANDLING SYSTEMS... 28

SECTION 4 SMOKE CONTROL SYSTEMS—GENERAL REQUIREMENTS 4.1 SCOPE OF SECTION ... 35

4.2 LOCATION OF EXTERNAL OPENINGS ... 35

4.3 DIRECTION OF SMOKE-SPILL AIRFLOW UNDER SMOKE-CONTROL CONDITIONS... 36

4.4 LOCATION OF SMOKE-SPILL SYSTEM INLETS ... 36

4.5 HEAT EXCHANGE EQUIPMENT... 36

4.6 NOISE ... 37

4.7 FIRE DOORS’ PRESSURE DIFFERENTIALS ... 37

4.8 SMOKE-SPILL FAN... 37

4.9 INITIATION OF SMOKE CONTROL SYSTEMS ... 38

4.10 AUTOMATIC SMOKE DETECTION FOR SYSTEM CONTROL ... 38

4.11 OTHER FIRE SAFETY SYSTEMS AND SYSTEM CONTROL ... 42

4.12 ELECTRICAL INSTALLATION... 46

4.13 CONTROL AND INDICATION ... 48

4.14 NON-ELECTRICAL CONTROL SYSTEMS ... 53

4.15 OPERATING INSTRUCTIONS... 53

4.16 TESTING ... 54

4.17 NOISE ... 55

4.18 TEST SCHEDULE ... 55

4.19 TEST RESULTS ... 55

(7)

5 AS/NZS 1668.1:1998

Page

SECTION 5 MISCELLANEOUS SYSTEMS

5.1 SCOPE OF SECTION ... 56

5.2 APPLICATION ... 56

5.3 EXHAUST SYSTEMS ... 56

5.4 SUPPLY AIR SYSTEMS ... 57

5.5 CAR PARK VENTILATION SYSTEMS... 57

SECTION 6 SYSTEM SHUTDOWN 6.1 SCOPE OF SECTION ... 61

6.2 SHUTDOWN SYSTEM ARRANGEMENT ... 61

6.3 GENERAL REQUIREMENTS ... 61

SECTION 7 AIR PURGE SYSTEMS 7.1 SCOPE OF SECTION ... 62

7.2 AIR PURGE SYSTEM ARRANGEMENT ... 62

7.3 PERFORMANCE CRITERIA ... 62

7.4 SMOKE-SPILL FAN... 62

7.5 RETURN AIR FAN... 63

7.6 SUPPLY AIR FAN... 63

7.7 DAMPERS ... 63

7.8 OPERATION UNDER FIRE MODE ... 63

SECTION 8 ZONE PRESSURIZATION SYSTEMS 8.1 SCOPE OF SECTION ... 70

8.2 ZONE PRESSURIZATION SYSTEM ARRANGEMENT... 70

8.3 PERFORMANCE CRITERIA ... 70

8.4 SMOKE-SPILL SYSTEM ... 71

8.5 SUPPLY AIR ... 72

8.6 AIR RELIEF AND MAKE-UP... 73

8.7 OPERATION UNDER FIRE CONDITIONS ... 74

8.8 INDIVIDUAL PLANTS INCORPORATING COMMON SHAFTS ... 74

8.9 LIFT SHAFT AIR RELIEF ... 75

SECTION 9 FIRE-ISOLATED EXIT PRESSURIZATION 9.1 SCOPE OF SECTION ... 84

9.2 FIRE-ISOLATED EXIT PRESSURIZATION SYSTEM ARRANGEMENT... 84

9.3 PERFORMANCE REQUIREMENTS ... 84

9.4 SYSTEM ARRANGEMENTS ... 86

9.5 HORIZONTAL FIRE-ISOLATED EXIT PRESSURIZATION... 90

9.6 AIR RELIEF... 91

9.7 OTHER SERVICES ... 91

SECTION 10 LIFT SHAFT PRESSURIZATION SYSTEM 10.1 SCOPE OF SECTION ... 92

10.2 LIFT SHAFT PRESSURIZATION SYSTEM ARRANGEMENT... 92

10.3 PERFORMANCE REQUIREMENTS ... 92

10.4 GENERAL REQUIREMENTS ... 92

SECTION 11 KITCHEN HOOD EXHAUST SYSTEMS 11.1 SCOPE AND APPLICATION... 96

11.2 SYSTEM REQUIREMENTS ... 96

(8)

AS/NZS 1668.1:1998 6

Page

APPENDICES

A SMOKE CONTROL SYSTEM APPLICATION ... 99

B HEALTH CARE BUILDINGS... 101

C SMOKE CONTROL IN LABORATORIES, CORRECTIONAL FACILITIES AND INDUSTRIAL PREMISES ... 107

D RELIABILITY ... 109

E WIRING SYSTEMS RATING ... 111

F SMOKE CONTROL SYSTEM COMMISSIONING TESTS ... 113

(9)

7 AS/NZS 1668.1:1998

COPYRIGHT

STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND

Australian/New Zealand Standard

The use of ventilation and airconditioning in buildings

Part 1: Fire and smoke control in multi-compartment buildings

S E C T I O N 1 G E N E R A L

1.1 SCOPE

This Standard sets out the minimum requirements for the design, construction, installation and commissioning of mechanical ventilation and airconditioning systems for fire and smoke control in multi-compartment buildings. This Standard also includes provisions that are applicable to single compartment buildings. Five specific methods of smoke control are defined and the appropriate requirements specified for each.

The Standard does not include requirements for smoke control systems utilizing exhaust from above the hot layer. Requirements for the maintenance of smoke control systems are also not included.

NOTE: AS 1851.6 outlines management procedures for maintaining the fire and smoke control features of air-handling systems.

1.2 SYSTEM OBJECTIVES

Systems designed in accordance with this Standard are intended to restrict smoke spread into areas within a building, via the following:

(a) Fire-isolated exits, ramps and passageways.

(b) Principal evacuation routes (e.g., public corridors) leading to a safe place (where practicable).

(c) Adjacent fire/smoke compartments via principal connecting paths such as stairs, lift and service shafts, airconditioning ducts, ventilation ducts and ceiling plenums. (d) Throughout the building via minor paths such as structural joints, gaps, cracks and

building services penetrations.

For the specified airflows and pressure differentials, systems are required to cope with a single fire event. Some systems are required to incorporate controls that will respond to more than one fire event. Systems that achieve the specified air velocities or pressure differentials for more than one fire event are considered to exceed the minimum requirements of this Standard.

(10)

This is a free preview. Purchase the entire publication at the link below:

Looking for additional Standards? Visit SAI Global Infostore

Subscribe to our Free Newsletters about Australian Standards® in Legislation; ISO, IEC, BSI and more Do you need to Manage Standards Collections Online?

Learn about LexConnect, All Jurisdictions, Standards referenced in Australian legislation Do you want to know when a Standard has changed?

Want to become an SAI Global Standards Sales Affiliate? Learn about other SAI Global Services:

LOGICOM Military Parts and Supplier Database

Metals Infobase Database of Metal Grades, Standards and Manufacturers Materials Infobase Database of Materials, Standards and Suppliers Database of European Law, CELEX and Court Decisions

Need to speak with a Customer Service Representative - Contact Us

This is a free 9 page sample. Access the full version at http://infostore.saiglobal.com.

AS/NZS 1668.1:1998, The use of ventilation and

airconditioning in buildings Fire and smoke control

in multi-compartment buildings

References

Related documents

TO: Long Term Care Facilities with Real Estate Tax Rates RE: 2001 REAL ESTATE TAX COST DOCUMENTATION In order to set the real estate tax portion of the capital rate, it

There are two buttons for switching between message view and log view, as shown as number five in Figure 3.16. Message view is shown in Figure.. Messages are used when the alarm

Samples of virus-infected pumpkin plants were collected in mid-July 2001 from naked-seeded and hulled oil pumpkins, patty pan, zucchini and summer squash, at three different

[7] Pranita Chavan, “ Superheated Steam Temperature control in Thermal Power Plant Using Fuzzy Logic Controller “,International Journal of Advance Foundation And Research

This paper investigated recommendation techniques that include content-based recommendation technique, collaborative (social) filtering technique, hybrid recommendation

Those authorities who have had to increase their council tax to mitigate the flawed funding system that Government has initially created and rolled forward year on year have seen

Each entity in the system model has specific strengths that we wish to exploit on behalf of distributed appli- cations: (i) the application initiator is best for holding private

Queensland Motorways have issued unpaid toll notices, final overdue toll notices and demand notices to the registered owner of [***KVD], as payment was not received for