TRANSFORMER
PROTECTION
TRANSFORMER FAULTS
EARTH FAULTS PHASE FAULTS
INTER TURN FAULTS CORE FAULTS
TANK FAULTS AND COOLING FAILURE TAP CHANGER FAULTS
TRANSFORMER ABNORMAL
OVERLOAD
Increase copper loss & Temperature rise
SYSTEM FAULTS OVERVOLTAGE OVERFLUXING
EARTH FAULT CURRENT DEPENDS ON
Method of Earthing
Impedance of the winding
TYPES OF EARTHING
EFFECTIVE EARTHING
Solid and low impedance earthed systems During Earth fault healthy phase voltage is
below 80% of nominal
TYPES OF EARTHING
NON - EFFECTIVE EARTHING
High resistance and Reactance earthed systems
Systems are subjected to high over voltage
Inter-turn Faults
Degradation of winding insulation due to lightning or switching 70 to 80% of the Transformer failuresCore Faults
Breakdown in the insulation b/w silicon steel
core lamination
Breakdown in the core bolt insulation
Causes excessive eddy currents to flow and
Tap Changer Faults
Due to
Flashovers
Selector or Divertor failure Contact failure
System Short Circuit
Transformer Fault Permitted
Reactance Current Duration (Sec)
4 25 2
5 20 3
6 16.6 4
7 14.2 5
Limited by self reactance Severe mechanical stress
Over Voltages
Transient Surge Voltage
Power frequency Voltage
Arise from switching & Lightning disturbances Cause interturn faults
Load throw off condition
Increase stress on the insulation Damage the core bolt and coil
OVERALL TRANSFORMER
PROTECTION REQUIREMENT
SENSITIVITY FOR INTERNAL FAULT
FASTER OPERATION FOR INTERNAL
FAULT
THROUGH FAULT STABILITY MAGNETIC INRUSH STABILITY OVER FLUXING STABILITY
OVER CURRENT AND EARTH FAULT HIGH IMPEDANCE DIFFERENTIAL BIASED DIFFERENTIAL
RESTRICTED EARTH FAULT
WINDING / OIL TEMPERATURE BUCHOLZ GAS
Biased Differential
CT error
Tap Changer variation Magnetizing Inrush
Through fault stability
Through fault stability - CT saturated condition Overfluxing Stability
OPERATE RESTRAIN | I1 - I2 | (A) | I1 + I2 | / 2 (A) 0.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 4.5 3.0 2.5 2.0 1.5 1.0 0.5 3.5 4.0
Measured Point under Maximum Load Highset Differential at 12x
(12A)
Supply
Figure 8. Restricted Earth Fault
R Y B SETTING RESISTOR SETTING RESISTOR METROSIL REF RELAY METROSIL REF RELAY R Y B K EARTHING RESISTOR IF IP
15 20 3 6 9 12 100 80 60 40
Earth Fault Current - IF
K - PERCENTAGE OF WINDING FROM NEUTRAL AT WHICH EARTH FAULT OCCURS
Primary Current - IP
CURRENT AS A MULTIPLE OF FULL LOAD
100 5 20 40 60 80 30 25 20 15 10
RESTRICTED EARTH FAULT RELAY
DIFFERENTIAL RELAY
FAULT SETTING - PERCENTAGE OF FULL LOAD
PERCENTAGE OF WINDING PROTECTED
Protection against Earth Faults Variation of Earth Fault Current with position (solidly earthed)
Protection Overview
Current amplitude correction (0.25 - 3.0)
Vector group compensation
Proven biased differential protection
Low or high impedance REF/SEF
Backup IDMTL and DTL overcurrent and earth fault
Overfluxing protection
4-stage Undervoltage / under-frequency load shedding
Neutral voltage displacement
Trip circuit supervision
Biased Differential Protection Settings
Differential, Initial setting (10 - 200% xIn)
Differential, Bias Slope (0 - 70%)
Setting > maximum percentage unbalance (tap mismatch, CT mismatch)
Differential, Bias Slope Limit (1-20 xIn)
Aids stability for heavy external faults accompanied by CT saturation
Setting > transformer maximum 3phase through fault current/2
Biased Differential Protection Settings
Differential, Highset (1-30 xIn)
Setting > max through fault, and Setting > max magnetizing inrush
Mag. Inrush Restraint Level (10-50% x Id)
Determines level of even harmonic that will cause relay to be inhibited
Single phase line diagram
Mag inrush detector RMS converter 5% of In Initial setting Bias slope Bias limit RMS converter RMS converter Inrush level 0.5 + -+ + -I1 I2 I1-12 I1+12 I1 + 12 2 Trip from other phases Other phase inhibits Inhibit enable Phase inhibit Trip -+ Restraint OperateBiased Differential Characteristic
Highset Differential Set to x7
O p er ate C u rr e nt (I 1 - I 2 ) Restraint Current ( |I1| + |I2| ) / 2 Initial Setting Bias Slope
Setting Bias Slope Limit Set at x4
RESTRAIN OPERATE 0 2 4 6 8 10 2 4 6 8
7.5 MVA; 66 / 11 KV; Dyn11; HVCT ratio = 100/1; LVCT ratio = 450/1;
HV full load current = 7.5MVA / (1.732 x 66KV)
= 65.61A
HV CT secondary current = (65.61 x 1) / 100
= 0.656A
LV full load current = 7.5MVA / (1.732 x 11KV)
= 393.65A
LV CT secondary current = (393.65 x 1) / 450
= 0.875A
Tap changer range = -10% to +10%
HV ICT multiplier = 1 / 0.656 = 1.52
LV ICT multiplier = 1 / 0.875 = 1.14
DUOBIAS - M Relay SETTINGS:
Initial setting = 20%
Bias setting = 20%
Bias slope = 4 x In
High set over current = 8 x In
HV ICT vector connection = Ydy0, 0
HV ICT multiplier = 1.52
LV ICT vector connection = Yd1, 30