Restricted earthfault protection (PDIF, 87N)
Up to three instances available Low impedance type
Can be used on all directly or low impedance earthed windings Up to 4 three-phase CT inputs
RET 670 – Restricted Earthfault Protection
REF1-I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2 REFPDIF_87N
A B B P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Able to handle multiple circuit breaker applications as well as autotransformers in 1½ CB applications
RET 670 – Restricted Earthfault Protection
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2 I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Zero sequence differential protection with a percentage biased operate/restrain characteristic, plus an additional zero sequence current directional comparison criterion
Requires no current magnitude or phase correction, even when OLTC present
Insensitive to inrush and overexcitation currents Only danger is eventual CT saturation
A B B P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Three-section operate/restrain characteristic
Settings:
IdMin
Dependent on the magnitude of the bias current, the corresponding zone (section) of
P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Differential current – vector sum of the fundamental
frequency neutral current and the fundamental frequency residual current (calculated from the three line-side
fundamental frequency phase currents)
For multiple circuit breaker applications, the two contributing residual currents are internally summed to produce the
overall line-side residual current Idiff = IN + 3I0
I3PW1 = I3PW1CT1 + I3PW1CT2 I3PI3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
A B B P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Single circuit breaker applications – ordinary power trfrs
curr(x) = MAX [I3PW1CT1] curr(z) = IN
i.e. Ibias = MAX [curr(x); curr(z)]
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker applications-CTFactor
A factor to allow a sensitive function also at multi-breaker
arrangement where the rating in the bay is much higher than the rated current of the transformer winding.
CTFactor = Irated pri_CT / Irated_W
The CTFactor is generally chosen so that when 1pu primary
current flows through the CT, this would contribute a 1pu component to the bias calculation – e.g.
Irated pri_CT = 1000A
Irated_W = 500A
contribution to bias calculation = 1000 / (1000/500) = 500A Ibias (pu) = Ibias (pri A) / IBase, where IBase = Irated_W
Without CTFactor, a 1pu CT primary current would contribute a 1000A component to the bias calculation (i.e. 2pu)
A B B P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker applications – ordinary power trfrs
curr(a) = MAX [I3PW1CT1] / CTFactorPri1
curr(b) = MAX [I3PW1CT2] / CTFactorPri2
curr(x) = MAX [I3PW1CT1 + I3PW1CT2] curr(z) = IN
i.e. Ibias = MAX [curr(a); curr(b); curr(x); curr(z)]
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker applications
Applying the CTFactor gives a gain in the sensitivity for internal faults (by reducing the contribution to the bias from the T-side CTs), but still ensures adequate biasing for
A B B P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Single circuit breaker applications – autotransformers
curr(x) = MAX [I3PW1CT1] curr(y) = MAX [I3PW2CT1] curr(z) = IN
i.e. Ibias = MAX [curr(x); curr(y); curr(z)]
Note: set IBase = highest winding rated current, normally Irated_MV I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker applications – autotransformers
RET 670 – Restricted Earthfault Protection
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
A B B P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker autotransformer applications curr(a) = MAX [I3PW1CT1] / CTFactorPri1
curr(b) = MAX [I3PW1CT2] / CTFactorPri2
curr(c) = MAX [I3PW2CT1] / CTFactorSec1
curr(d) = MAX [I3PW2CT2] / CTFactorSec2
curr(x) = MAX [I3PW1CT1 + I3PW1CT2] curr(y) = MAX [I3PW2CT1 + I3PW2CT2] curr(z) = IN
i.e. Ibias = MAX [curr(a);…….curr(z)]
I3P
I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Directional criterion – external earth fault
RET 670 – Restricted Earthfault Protection
A (L1) B (L2) Ia =0 Ia =0 Ib =0 Ib =0 Ic =0 Ic =0 Uzs Uzs 3Io=3Izs1
Current in the neutral (IN) serves as a directional the same direction for both internal and external faults. reference because it has
180o out of phase for any external
earth fault.
Currents 3Io and IN are theoretically zone of protection
IN = -3I-3Izs1
zs voltage is max. at the earth fault zs voltage is max.
at the earth fault C (L3) a (L1) b (L2) c (L3) s o u r c e s o u r c e IN Izs1 Izs1 Izs1 ROA MTA For external fault
Restrain for external fault Reference is neutral current ROA IN Operate for internal fault 3I0
Relay Operate Angle (ROA)
A B B P ow er T ec hn ol og ie s A B , 20
07 currents 3Io and IN are approximately
in phase for an internal earth fault. A (L1) B (L2) C (L3) a (L1) b (L2) c (L2) Ia = 0 Ia = 0 Ib =0 Ib =0 Ic =0 Ic =0 Uz s
3Io = -3Izs2 reference because it hasserves as a directional
the same direction for both internal and external faults. Current in the neutral (IN)
serves as a directional reference because it has the same direction for both internal and external faults. zone of protection IN = - 3Izs1 Ifault power system contribution to fault current power system contribution to fault current s o u r c e s o u r c e
Return path for 3Izs2 Return path for 3Izs1
IN Izs2 Izs2 Izs2 Izs1 Izs1 Izs1 ROA MTA For internal fault
Restrain for external fault Reference is neutral current ROA IN Operate for internal fault 3I0
Restricted earthfault protection (PDIF, 87N)
Directional criterion – internal earth fault
RET 670 – Restricted Earthfault Protection
Relay Operate Angle (ROA)
Settable 60° to 90
The residual current 3I0and the
neutral current INare theoretically
equal in magnitude and 180 degrees
P ow er T ec hn ol og ie s A B , 20 07
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
2nd harmonic analysis / blocking
Required primarily to prevent unwanted operation on reactor
energizing due to possible line-side CT saturation caused by a high dc component of long duration.
The current through the neutral CT does not have the same dc-component, or the same amplitude, and consequently the risk of saturation in this CT is much less
The differential current that appears as a result of the saturation may be so high that it reaches the operate area of the characteristic
If the ratio between 2nd harmonic and fundamental exceeds 60%, the
A B B P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Overview of restricted earthfault protection function
RET 670 – Restricted Earthfault Protection
Directional check TRIP START & ≥1 IN > 50% of Idmin & 3I0 < 3% of Ibase 3I0 > 3% of Ibase
A directional check is only executed if The magnitude of the line-side residual
current (3I0) is at least 3% of IBase
start has been registered from the operate-restrain characteristic
P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Function block
RET 670 – Restricted Earthfault Protection
‘Analog’ quantity inputs
A B B P ow er T ec hn ol og ie s A B , 20 07
P ow er T ec hn ol og ie s A B , 20 07 Settings Settings group N1 Differential protection LowImpREF(PDIF,87N) Off; On
A B B P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Service values
P ow er T ec hn ol og ie s A B , 20 07
Restricted earthfault protection (PDIF, 87N)
Service values
A B B P ow er T ec hn ol og ie s A B , 20 07