SECTION: TITLE SHEET i OF i

BHAVANAGAR ENERGY COMPANY LIMITED, BHAVANAGAR

2 X 250 MW TPP

INITIALS SIGN INITIALS SIGN INITIALS SIGN INITIALS

SIGN

PPD. BY

KYP

-SD/-

-SD/-CKD. BY

GBK

-SD/-

-SD/-APP. BY

SVSP

-SD/-

-SD/-DATE

REV. NO

FILE NAME.: M2-2160.XLS

ISSUE

22.07.2010

TCE-M2-EL-CA-D-2160

TCE CONSULTING ENGINEERS LIMITED

CABLE SIZING CALCULATIONS

R3

CABLE SIZING CALCULATIONS

R1

R0

R2

(2)

By KYP Project 2 X 250 MW TPP

Date 22.07.2010 Doc No.

Chkd.GBK Client BECL, BHAVANAGAR Subject CABLE SIZING Date Job No. 5403A Office DB Dept. EL Sh. No. 1 of 2 Rev. No. 0

CABLE SIZING CALCULATION (6.6 kV H.V SIDE)

1 FEEDER DATA REMARKS

1.1 Incoming

1.2 Rating, 3 PH kVA

1.3 Voltage kV 6.600

1.4 Power Factor (p.f) 0.8

1.5 Efficiency (Effy) 0.9

1.6 Type of Earthing Earthed /

Unearthed Solidly Earthed. 1.7 (a) Current IFL kVA (Amp.)

3 * kV

(b) Current IFL kW (Motor) (Amp.) 3 * kV * Effy. * p.f

1.8

1.9 (a) 3 Phase - Fault Current (Ish) kA (b) Fault Clearing Time (t) ( Secs) 1.10 Estimated Length (L) m 1.11 Permissible Voltage drop (a) Running % (b) Starting %

2 LAYING CONDITIONS Tray/ Buried Duct Trench/ in

Air ground

2.1 Ambient Temperature Deg. C 45 0.86 2.2 Grouping / Spacing with other cables 1 2.3 Thermal Resistivity Deg.C cm /W 200 1.00 2.4 Depth of Burial mm 750 1.00 2.5 Overall Derating Factor ODF 0.860

3 TYPE OF CABLE TO BE USED

(To be Marked) Cu (Cond.)

3.1 PVC 75 112 3.2 XLPE (a) 22 / 33 kV 94 140 (b) 11 kV 94 140 (c) 6.6 kV 94 140 3.3 (d) 415V 94 140 4 CABLE SIZING

4.1 Based on Full Load Current

(a) Cable rating required (I / ODF) Amp.

(b) Cable for above rating Type No.of runs XLPE 1 CORE 2 4.2

(a) Sq. mm

TATA CONSULTING ENGINEERS LIMITED

Incoming / Outgoing & Designation

12000

1049.73

Type of Protection (CB / Fuse / MCB / MCCB) CB 40 0.5

Refer TCE design guide

500 5 15

Derating Refer cable Factor catalogue. Value of k (Amp./ sq.mm) Al (Cond.) 1220.61 Size (Sq.mm.) 800 Based on Short Circuit Current

(For breaker protected feeders only)

300.897 cond. of Area k t * Ish =

(3)

(b) Sq. mm 4.3 Estimated Cable Size

( Higher of 4.1 & 4.2 ) 5 CHECK FOR VOLTAGE DROP

5.1 Cable Size Sq. mm 5.2 R (at cond. temp) ohm/ph./kM

X ohm/ph./kM Load Angle 5.3

5.4

(Refer Note - 1 below) 5.5

YES

5.6 Sq. mm

800 6.0 RECOMMENDED CABLE SIZE Type

(Higher of 4.3 and 5.6)

XLPE 1 CORE

NOTE:

1) Load angle shall correspond to starting condition of Motor. For Contactor Controlled Feeder

(HT only) I2t of cable chosen shall

be 1.5*I2t of associated fuse -Sq. mm 400 800 0.047 0.091 36.86 % Drop 0.635 % Drop 4.572 Is the voltage drop within

permissible limits? (If not select higher size of cable and check for voltage drop)

Yes / No Cable Size considering Voltage

Drop

Size (Sq.mm) No. of Runs

800 2

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

FL

 10000 * kV L * ) Sin X + Cos R ( I * 3 STG  

(4)

By KYP Project 2 X 250 MW TPP

Date 22.07.2010 Doc No.

Chkd.GBK Client BECL, BHAVANAGAR Subject CABLE SIZING Date Job No. 5403A Office DB Dept. EL Sh. No. 1 of 2 Rev. No. 0

CABLE SIZING CALCULATION (6.6 kV H.V SIDE)

1 FEEDER DATA REMARKS

1.1 Incoming

1.2 Rating, 3 PH kVA

1.3 Voltage kV 6.600

1.4 Power Factor (p.f) 0.8

1.5 Efficiency (Effy) 0.9

1.6 Type of Earthing Earthed /

Unearthed Solidly Earthed. 1.7 (a) Current IFL kVA (Amp.)

3 * kV

(b) Current IFL kW (Motor) (Amp.) 3 * kV * Effy. * p.f

1.8

1.9 (a) 3 Phase - Fault Current (Ish) kA (b) Fault Clearing Time (t) ( Secs) 1.10 Estimated Length (L) m 1.11 Permissible Voltage drop (a) Running % (b) Starting %

2 LAYING CONDITIONS Tray/ Buried Duct Trench/ in

Air ground

2.1 Ambient Temperature Deg. C 45 0.86 2.2 Grouping / Spacing with other cables 1 2.3 Thermal Resistivity Deg.C cm /W 200 1.00 2.4 Depth of Burial mm 750 1.00 2.5 Overall Derating Factor ODF 0.860

3 TYPE OF CABLE TO BE USED

(To be Marked) Cu (Cond.)

3.1 PVC 75 112 3.2 XLPE (a) 22 / 33 kV 94 140 (b) 11 kV 94 140 (c) 6.6 kV 94 140 3.3 (d) 415V 94 140 4 CABLE SIZING

4.1 Based on Full Load Current

(a) Cable rating required (I / ODF) Amp.

(b) Cable for above rating Type No.of runs XLPE 3 CORE 1 4.2

(a) Sq. mm

TATA CONSULTING ENGINEERS LIMITED

Incoming / Outgoing & Designation

2500

218.69

Type of Protection (CB / Fuse / MCB / MCCB) CB 40 0.16

Refer TCE design guide

50 5 15

Derating Refer cable Factor catalogue. Value of k (Amp./ sq.mm) Al (Cond.) 254.29 Size (Sq.mm.) 185 Based on Short Circuit Current

(For breaker protected feeders only)

170.213 cond. of Area k t * Ish =

(5)

(b) Sq. mm 4.3 Estimated Cable Size

( Higher of 4.1 & 4.2 ) 5 CHECK FOR VOLTAGE DROP

5.1 Cable Size Sq. mm 5.2 R (at cond. temp) ohm/ph./kM

X ohm/ph./kM Load Angle 5.3

5.4

(Refer Note - 1 below) 5.5

YES

5.6 Sq. mm

185 6.0 RECOMMENDED CABLE SIZE Type

(Higher of 4.3 and 5.6)

XLPE 3 CORE

NOTE:

1) Load angle shall correspond to starting condition of Motor. For Contactor Controlled Feeder

(HT only) I2t of cable chosen shall

be 1.5*I2t of associated fuse -Sq. mm 185 185 0.21 0.0969 36.86 % Drop 0.065 % Drop -Is the voltage drop within

permissible limits? (If not select higher size of cable and check for voltage drop)

Yes / No Cable Size considering Voltage

Drop

Size (Sq.mm) No. of Runs

185 1

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

FL

 10000 * kV L * ) Sin X + Cos R ( I * 3 STG  

(6)

By KYP Project 2 X 250 MW TPP

Date 22.07.2010 Doc No.

Chkd.GBK Client BECL, BHAVANAGAR Subject CABLE SIZING Date Job No. 5403A Office DB Dept. EL Sh. No. 1 of 2 Rev. No. 0

CABLE SIZING CALCULATION (6.6 kV H.V SIDE)

1 FEEDER DATA REMARKS

1.1 Incoming

1.2 Rating, 3 PH kW

1.3 Voltage kV 6.600

1.4 Power Factor (p.f) 0.85

1.5 Efficiency (Effy) 0.95

1.6 Type of Earthing Earthed /

Unearthed Solidly Earthed. 1.7 (a) Current IFL kVA (Amp.)

3 * kV

(b) Current IFL kW (Motor) (Amp.) 3 * kV * Effy. * p.f

1.8

1.9 (a) 3 Phase - Fault Current (Ish) kA (b) Fault Clearing Time (t) ( Secs) 1.10 Estimated Length (L) m 1.11 Permissible Voltage drop (a) Running % (b) Starting %

2 LAYING CONDITIONS Tray/ Buried Duct Trench/ in

Air ground

2.1 Ambient Temperature Deg. C 45 0.86 2.2 Grouping / Spacing with other cables 1 2.3 Thermal Resistivity Deg.C cm /W 200 1.00 2.4 Depth of Burial mm 750 1.00 2.5 Overall Derating Factor ODF 0.860

3 TYPE OF CABLE TO BE USED

(To be Marked) Cu (Cond.)

3.1 PVC 75 112 3.2 XLPE (a) 22 / 33 kV 94 140 (b) 11 kV 94 140 (c) 6.6 kV 94 140 3.3 (d) 415V 94 140 4 CABLE SIZING

4.1 Based on Full Load Current

(a) Cable rating required (I / ODF) Amp.

(b) Cable for above rating Type No.of runs XLPE 3 CORE 1 4.2

(a) Sq. mm

TATA CONSULTING ENGINEERS LIMITED

Incoming / Outgoing & Designation

1500

162.50 Type of Protection (CB / Fuse / MCB / MCCB) CB

40 0.16

Refer TCE design guide

50 5 15

Derating Refer cable Factor catalogue. Value of k (Amp./ sq.mm) Al (Cond.) 188.95 Size (Sq.mm.) 95 Based on Short Circuit Current

(For breaker protected feeders only)

170.213 cond. of Area k t * Ish =

(7)

(b) Sq. mm 4.3 Estimated Cable Size

( Higher of 4.1 & 4.2 ) 5 CHECK FOR VOLTAGE DROP

5.1 Cable Size Sq. mm 5.2 R (at cond. temp) ohm/ph./kM

X ohm/ph./kM Load Angle 5.3

5.4

(Refer Note - 1 below) 5.5

YES

5.6 Sq. mm

185 6.0 RECOMMENDED CABLE SIZE Type

(Higher of 4.3 and 5.6)

XLPE 3 CORE

NOTE:

1) Load angle shall correspond to starting condition of Motor. For Contactor Controlled Feeder

(HT only) I2t of cable chosen shall

be 1.5*I2t of associated fuse -Sq. mm 185 185 0.21 0.089 36.86 % Drop 0.047 % Drop 0.340 Is the voltage drop within

permissible limits? (If not select higher size of cable and check for voltage drop)

Yes / No Cable Size considering Voltage

Drop

Size (Sq.mm) No. of Runs

185 3

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

FL

 10000 * kV L * ) Sin X + Cos R ( I * 3 STG  

(8)

By KYP Project 2 X 250 MW TPP

Date 22.07.2010 Doc No.

Chkd.GBK Client BECL, BHAVANAGAR Subject CABLE SIZING Date Job No. 5403A Office DB Dept. EL Sh. No. 1 of 2 Rev. No. 0

CABLE SIZING CALCULATION (6.6 kV H.V SIDE)

1 FEEDER DATA REMARKS

1.1 Incoming

1.2 Rating, 3 PH kW

1.3 Voltage kV 6.600

1.4 Power Factor (p.f) 0.85

1.5 Efficiency (Effy) 0.95

1.6 Type of Earthing Earthed /

Unearthed Solidly Earthed. 1.7 (a) Current IFL kVA (Amp.)

3 * kV

(b) Current IFL kW (Motor) (Amp.) 3 * kV * Effy. * p.f

1.8

1.9 (a) 3 Phase - Fault Current (Ish) kA (b) Fault Clearing Time (t) ( Secs) 1.10 Estimated Length (L) m 1.11 Permissible Voltage drop (a) Running % (b) Starting %

2 LAYING CONDITIONS Tray/ Buried Duct Trench/ in

Air ground

2.1 Ambient Temperature Deg. C 45 0.86 2.2 Grouping / Spacing with other cables 1 2.3 Thermal Resistivity Deg.C cm /W 200 1.00 2.4 Depth of Burial mm 750 1.00 2.5 Overall Derating Factor ODF 0.860

3 TYPE OF CABLE TO BE USED

(To be Marked) Cu (Cond.)

3.1 PVC 75 112 3.2 XLPE (a) 22 / 33 kV 94 140 (b) 11 kV 94 140 (c) 6.6 kV 94 140 3.3 (d) 415V 94 140 4 CABLE SIZING

4.1 Based on Full Load Current

(a) Cable rating required (I / ODF) Amp.

(b) Cable for above rating Type No.of runs XLPE 3 CORE 1 4.2

(a) Sq. mm

TATA CONSULTING ENGINEERS LIMITED

Incoming / Outgoing & Designation

350

37.92 Type of Protection (CB / Fuse / MCB / MCCB) CB

40 0.16

Refer TCE design guide

100 5 15

Derating Refer cable Factor catalogue. Value of k (Amp./ sq.mm) Al (Cond.) 44.09 Size (Sq.mm.) 35 Based on Short Circuit Current

(For breaker protected feeders only)

170.213 cond. of Area k t * Ish =

(9)

(b) Sq. mm 4.3 Estimated Cable Size

( Higher of 4.1 & 4.2 ) 5 CHECK FOR VOLTAGE DROP

5.1 Cable Size Sq. mm 5.2 R (at cond. temp) ohm/ph./kM

X ohm/ph./kM Load Angle 5.3

5.4

(Refer Note - 1 below) 5.5

YES

5.6 Sq. mm

240 6.0 RECOMMENDED CABLE SIZE Type

(Higher of 4.3 and 5.6)

XLPE 3 CORE

NOTE:

1) Load angle shall correspond to starting condition of Motor. For Contactor Controlled Feeder

(HT only) I2t of cable chosen shall

be 1.5*I2t of associated fuse -Sq. mm 185 185 0.21 0.089 36.86 % Drop 0.022 % Drop 0.159 Is the voltage drop within

permissible limits? (If not select higher size of cable and check for voltage drop)

Yes / No Cable Size considering Voltage

Drop

Size (Sq.mm) No. of Runs

185 1

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

FL

 10000 * kV L * ) Sin X + Cos R ( I * 3 STG  

(10)

By

KYP

Project

Date 22.07.2010

Doc No.

Chkd.GBK

Client

BECL, BHAVANAGAR

Subject

Date

Job No. 5403A

Office DB

Dept.

EL

Sh. No.

CABLE SIZING CALCULATION (6.6 kV H.V SIDE)

1 FEEDER DATA

1.1

Incoming

1.2 Rating, 3 PH

kVA

1.3 Voltage

kV

0.415

1.4 Power Factor (p.f)

0.8

1.5 Efficiency (Effy)

0.9

1.6 Type of Earthing

Earthed /

Unearthed

Solidly Earthed.

1.7 (a) Current I

FL

kVA

(Amp.)

3 * kV

(b) Current I

FL

kW (Motor)

(Amp.)

3 * kV * Effy. * p.f

1.8

1.9 (a) 3 Phase - Fault Current (Ish)

kA

(b) Fault Clearing Time (t)

( Secs)

1.10 Estimated Length (L)

m

1.11 Permissible Voltage drop (a) Running

%

(b) Starting

%

2 LAYING CONDITIONS

Tray/

Buried

Duct

Trench/

in

Air

ground

2.1 Ambient Temperature

Deg. C

45

2.2 Grouping / Spacing with other cables

2.3 Thermal Resistivity

Deg.C cm /W

200

2.4 Depth of Burial

mm

750

2.5 Overall Derating Factor

ODF

3 TYPE OF CABLE TO BE USED

(To be Marked)

Value of k (Amp./ sq.mm)

Al (Cond.)

50

0.16

500

5

15

1669.45

TATA CONSULTING ENGINEERS LIMITED

Incoming / Outgoing & Designation

1200

(11)

3.1 PVC

75

3.2 XLPE (a) 22 / 33 kV

94

(b) 11 kV

94

(c) 6.6 kV

94

3.3 (d) 415V

94

4 CABLE SIZING

4.1 Based on Full Load Current

(a) Cable rating required (I / ODF)

Amp.

(b) Cable for above rating

Type

XLPE 1 CORE

4.2

(a)

Sq. mm

(b)

Sq. mm

4.3 Estimated Cable Size

( Higher of 4.1 & 4.2 )

5 CHECK FOR VOLTAGE DROP

5.1 Cable Size

Sq. mm

5.2 R (at cond. temp)

ohm/ph./kM

X

ohm/ph./kM

Load Angle

5.3

5.4

(Refer Note - 1 below)

5.5

YES

2.931

% Drop

-0.0444

Is the voltage drop within

permissible limits? (If not select

higher size of cable and check for

voltage drop)

Yes / No

0.081

36.86

% Drop

For Contactor Controlled Feeder

(HT only) I

2

t of cable chosen shall

be 1.5*I

2

t of associated fuse

-Sq. mm

185

800

1854.94

Size (Sq.mm.)

1000

Based on Short Circuit Current

(For breaker protected feeders only)

212.766

cond.

of

Area

k

t

*

Ish

=

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

FL

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

STG

(12)

5.6

Sq. mm

185

6.0 RECOMMENDED CABLE SIZE

Type

(Higher of 4.3 and 5.6)

XLPE 3 CORE

NOTE:

1) Load angle shall correspond to starting condition of Motor.

Size (Sq.mm)

185

Cable Size considering Voltage

(13)

2 X 250 MW TPP

Doc No.

Subject

CABLE SIZING

1

of

2 Rev. No.

0

REMARKS

Solidly Earthed.

0.90

1

1.00

1.00

0.900

Cu (Cond.)

Value of k (Amp./ sq.mm)

50

0.16

Refer TCE design

guide

500

Refer cable

Factor

catalogue.

5

15

Derating

1669.45

1200

CB

(14)

112

140

140

140

140

No.of runs

10

-185

1854.94

212.766

(15)

No. of Runs

1

(16)

By

KYP

Project

Date 22.07.2010

Doc No.

Chkd.GBK

Client

BECL, BHAVANAGAR

Subject

Date

Job No. 5403A

Office DB

Dept.

EL

Sh. No.

CABLE SIZING CALCULATION (6.6 kV H.V SIDE)

1 FEEDER DATA

1.1

Incoming

1.2 Rating, 3 PH

kVA

1.3 Voltage

kV

6.600

1.4 Power Factor (p.f)

0.8

1.5 Efficiency (Effy)

0.9

1.6 Type of Earthing

Earthed /

Unearthed

Solidly Earthed.

1.7 (a) Current I

FL

kVA

(Amp.)

3 * kV

(b) Current I

FL

kW (Motor)

(Amp.)

3 * kV * Effy. * p.f

1.8

1.9 (a) 3 Phase - Fault Current (Ish)

kA

(b) Fault Clearing Time (t)

( Secs)

1.10 Estimated Length (L)

m

1.11 Permissible Voltage drop (a) Running

%

(b) Starting

%

2 LAYING CONDITIONS

Tray/

Buried

Duct

Trench/

in

Air

ground

2.1 Ambient Temperature

Deg. C

45

2.2 Grouping / Spacing with other cables

2.3 Thermal Resistivity

Deg.C cm /W

200

2.4 Depth of Burial

mm

750

2.5 Overall Derating Factor

ODF

3 TYPE OF CABLE TO BE USED

(To be Marked)

Value of k (Amp./ sq.mm)

Al (Cond.)

40

0.5

500

5

15

TATA CONSULTING ENGINEERS LIMITED

Incoming / Outgoing & Designation

11000

962.25

(17)

3.1 PVC

75

3.2 XLPE (a) 22 / 33 kV

94

(b) 11 kV

94

(c) 6.6 kV

94

3.3 (d) 415V

94

4 CABLE SIZING

4.1 Based on Full Load Current

(a) Cable rating required (I / ODF)

Amp.

(b) Cable for above rating

Type

XLPE 1 CORE

4.2

(a)

Sq. mm

(b)

Sq. mm

4.3 Estimated Cable Size

( Higher of 4.1 & 4.2 )

5 CHECK FOR VOLTAGE DROP

5.1 Cable Size

Sq. mm

5.2 R (at cond. temp)

ohm/ph./kM

X

ohm/ph./kM

Load Angle

5.3

5.4

(Refer Note - 1 below)

5.5

YES

Is the voltage drop within

permissible limits? (If not select

higher size of cable and check for

voltage drop)

Yes / No

% Drop

0.437

% Drop

-0.06

0.093

36.86

For Contactor Controlled Feeder

(HT only) I

2

t of cable chosen shall

be 1.5*I

2

t of associated fuse

-Sq. mm

400

630

1118.90

Size (Sq.mm.)

630

Based on Short Circuit Current

(For breaker protected feeders only)

300.897

cond.

of

Area

k

t

*

Ish

=

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

FL

10000

*

kV

L

*

)

Sin

X

+

Cos

R

(

I

*

3

STG

(18)

5.6

Sq. mm

630

6.0 RECOMMENDED CABLE SIZE

Type

(Higher of 4.3 and 5.6)

XLPE 1 CORE

NOTE:

1) Load angle shall correspond to starting condition of Motor.

Cable Size considering Voltage

Drop

Size (Sq.mm)

630

(19)

2 X 250 MW TPP

Doc No.

Subject

CABLE SIZING

1

of

2 Rev. No.

0

REMARKS

Solidly Earthed.

0.86

1

1.00

1.00

0.860

Cu (Cond.)

Derating

Refer cable

Factor

catalogue.

Value of k (Amp./ sq.mm)

40

0.5

Refer TCE design

guide

500

5

15

11000

962.25

CB

(20)

112

140

140

140

140

No.of runs

3

-400

1118.90

300.897

(21)

No. of Runs

3

References

Related documents

Usinagem Usinagem Simulação de Usinagem Chão de Fábrica Documentação Usinagem Recursos Human Produto Produto Engenharia Reversa Importação De dados Conserto geométrico Pré

Electrostatic precipitators are highly efficient filtration devices that minimally impede the flow of gases through the device, and can easily remove fine particulate matter such

Results from network meta-analysis for selective preventive intervention for Edinburgh Postnatal Depression Scale threshold score at 6

Female students had greater Social Jetlag at both time points; however, these differences were not significant (Table 7). Female students had.. significantly higher rates of

Additional information demonstrating major achievements in this area including: national recognition of faculty in professional association (e.g., President); editorships,

Este análisis se elaboró en torno al cisma existente en este ámbito entre la ha- bilidad y los modelos mixtos y en él se alegaba (en gran medida, como hacemos aquí) que el

sources, estimate water demand, design water demand, design structures for structures for water intake, treatm water intake, treatment, storage, and ent, storage,

Central Database Regular Filing Insu ran ce Co mpa ny Special Reports Supervisory activities: • Data analysis • Financial Condition Monitoring • Early Warning • On-Spot