TABLE OF CONTENTS TABLE OF CONTENTS

1. Technical specification 1. Function and application 2. Technical parameters

2. Heating / cooling module CoolBreeze

1. Power input and output characteristics of the unit 2. CoolBreeze cooling output characteristics 3. CoolBreeze heating output characteristics 4. Acoustic parameters

5. Leakage

6. Heat recovery efficiency 7. VAC scheme

3. Wiring diagram

4. Installation requirements

1. Connection of ventilation pipes 2. Installation

5. Energy label

6. Dimensional drawings

7. Dependence of air flow and external pressure 8. CoolBreeze pressure loss

Version 1.7 EN

(4)

1

1 . . Technical specification Technical specification

1

1 .. 1 1 . . F u n ct ion a n d a p p lica t ion F u n ct ion a n d a p p lica t ion

The Futura heat recovery unit represents HVAC equipment designed for controlled ventilation and treatment of the indoor environment. It ensures heat and humidity recovery, filters supplied air, helps maintain optimum indoor humidity, and provides after-cooling by means of an integrated, fully automatic by-pass in summer, in the night mode. The unit is equipped with an enthalpy exchanger to utilize the latent heat from humidity.

U n i t l o c a t i o n U n i t l o c a t i o n

The heat recovery unit is installed vertically on the wall, in a room with a guaranteed minimal temperature of +10 °C (+50 °F). Sufficient handling space shall be provided in front of the equipment for trouble-free access, maintenance and servicing throughout the entire duration of its operation.

U n i t b o d y

U n i t b o d y The internal structure of the heat recovery unit is made of monolithic EPP (expanded polypropylene) without thermal bridges.

E n t h a l p y E n t h a l p y e x c h a n g e r

e x c h a n g e r Enthalpy counter-current exchanger with humidity recovery control.

F i l t r a t i o n F i l t r a t i o n

The heat recovery unit contains two filters: the F7 filter at the air supply as well as the air extraction. The necessity to replace filters is indicated automatically and depends on the outside air quality of the location where the device is used (approximately once every 2 - 6 months). The filtration can be supplemented with an optional accessory in the form of a carbon filter, which is inserted directly into the unit under the air supply filter.

C o n n e c t i n g d u c t

C o n n e c t i n g d u c t The device is equipped with 4 EPP ∅ 150 mm (5.9") flanges. EPP ducts are required at both the air inlet and outlet to prevent the possibility of unwanted condensation occurring inside the inlet and outlet ducts.

D r y i n g a t D r y i n g a t e x t r e m e l y l o w e x t r e m e l y l o w o u t d o o r o u t d o o r t e m p e r a t u r e t e m p e r a t u r e

Drying is activated when the outdoor temperature is lower than -20 °C (-4 °F) for more than 16 minutes.

Drying stops when the outdoor temperature is higher than -18 °C (-0.4 °F). Low outdoor temperature and Caution is displayed on the control panel. After drying is finished, ventilation and filter check are blocked, boost ventilation is limited to 2 minutes, and the unit continues to run in circulation mode.

E l e c t r i c a l E l e c t r i c a l c o n n e c t i o n

c o n n e c t i o n Power socket 230 V / 50 Hz with separate fuse 16 A type B.

C o o l B r e e z e C o o l B r e e z e E l e c t r i c a l E l e c t r i c a l c o n n e c t i o n c o n n e c t i o n

The CoolBreeze add-on module requires c o n n e c t i o n o f t h e o u t d o o r c o n d e n s a t i o n u n i t t o t h ec o n n e c t i o n o f t h e o u t d o o r c o n d e n s a t i o n u n i t t o t h e m a i n s w i t h a f i x e d 2 3 0 V / 5 0 H z , t y p e B 1 6 A f u s e a n d a 3 0 0 m A r e s i d u a l c u r r e n t c i r c u i t m a i n s w i t h a f i x e d 2 3 0 V / 5 0 H z , t y p e B 1 6 A f u s e a n d a 3 0 0 m A r e s i d u a l c u r r e n t c i r c u i t b r e a k e r

b r e a k e r . Alternatively, preparation for later installation of the CoolBreeze module can be made.

C o n t r o l C o n t r o l

Integration in the MyJABLOTRON mobile application, which supports easy control of all user functions and settings. It enables remote monitoring, system administration and provides automatic alerts for error conditions and dirty filter replacement. Standard supply includes one wall-mounted control panel with an integrated CO2 sensor.

(5)

1

1 .. 2 2 . . Tech n ica l p a ra m et ers Tech n ica l p a ra m et ers

The Futura heat recovery unit comes in two power output variants.

D es crip t ion

D es crip t ion MM LL

Air flow 50-250 m3 (1770-8830 cubic feet)/h 100-350 m3 (3530-12360 cubic feet)/h

Model identification brand Futura M Futura L

Specific energy consumption (SEC) in kWh/(m2.a) for each applicable climate zone and each applicable

SEC class

A+ A+

Dimensions (height x width x depth) 835 x 995 x 522 mm (32.9" x 39.2" x 20.6") 835 x 995 x 522 mm (32.9" x 39.2" x 20.6")

Weight 47 kg (104 lbs) 47.5 kg (105 lbs)

Declared typology bidirectional bidirectional

Drive type variable speed drive variable speed drive

Heat recovery system type recuperative recuperative

Heat recovery efficiency 91.8 %* 91.4 %*

Acoustic power level Lwa 46 dBa** 46 dBa**

Reference flow 175 m3/h*** (6180 cubic feet per hour) 245 m3/h*** (8652 cubic feet per hour)

Reference pressure difference 50 Pa*** 50 Pa***

SPI 0.34 W(m3/h)*** 0.33 W(m3/h)***

Electric power input of the fan including motor control equipment at

max. flow and max. pressure

230 W 320 W

Power input of electric post-heater 0 -350 W, continuously regulated 0 -350 W, continuously regulated Maximum input incl. electrical post-

heater 580 W 670 W

Condensate condensate drain, HT pipe 32 mm (1.26"), siphon

condensate drain, HT pipe 32 mm (1.26"), siphon

Electric connection 230 V / 50 Hz, 16 A; connection to electric mains via power socket

230 V / 50 Hz, 16 A; connection to electric mains via power socket Operational range without

preheating -19 °C do +45 °C (-2 °F - 113 °F) -19 °C do +45 °C (-2 °F - 113 °F)

Fans 2× EBM Papst with integrated electronics

and air flow regulation

2× EBM Papst with integrated electronics and air flow regulation

(6)

D es crip t ion

D es crip t ion MM LL

Cooling / heating output of complete set including exchanger heat recovery (Futura + CoolBreeze)

1.5 kW - 3.8 kW / 4.9 kW**** 1.7 kW - 4.4 kW / 4.9 kW****

Annual electricity consumption (AEC) (in kWh/m2 electric power/year)

„average“, „hot“, „cold“) at reference flow

2.26/1.81/7.63 2.20/1.75/7.57

Annual heat savings (AHS) (in kWh/m2 of primary energy/year) for

individual climate zones („average“,

„hot“, „cold“) at reference flow

47/92/21 47/92/21

Exchanger enthalpy counter-current exchanger with

humidity recovery control

enthalpy counter-current exchanger with humidity recovery control

Summer functions fully automatic by-pass controlled by the temperature setpoint

fully automatic by-pass controlled by the temperature setpoint

Control

Integration in the MyJABLOTRON mobile application, which supports easy control of

all user functions and settings. It enables remote monitoring, system administration

and provides automatic alerts for error conditions and dirty filter replacement.

Standard supply includes one wall-mounted control panel with an integrated CO2 sensor.

Integration in the MyJABLOTRON mobile application, which supports easy control of

all user functions and settings. It enables remote monitoring, system administration

and provides automatic alerts for error conditions and dirty filter replacement.

Standard supply includes one wall-mounted control panel with an integrated CO2 sensor.

Optional equipment

CoolBreeze enthalpy heating / cooling module, forced extraction (boost) buttons

with operation indication; Rh, SQA, CO2 sensors, VAC material and distribution

elements

CoolBreeze enthalpy heating / cooling module, forced extraction (boost) buttons

with operation indication; Rh, SQA, CO2 sensors, VAC material and distribution

elements

* According to Czech norm ČSN EN 308

** According to Czech norm ČSN EN ISO 3744

*** According to Commission Regulation (EU) No. 1253/2014

**** Cooling output varies depending on the relative humidity and difference between indoor and outdoor temperature.

**** Heating output varies depending on the relative humidity and difference between indoor and outdoor temperature.

ANY CHANGES RESULTING FROM TECHNICAL DEVELOPMENT ARE RESERVED. WE RESERVE THE RIGHT TO CHANGE THE CONTENTS OF THE MANUAL ANY TIME WITHOUT PRIOR NOTICE.

(7)

2

2. . Heating / cooling module CoolBreeze Heating / cooling module CoolBreeze

D es crip t ion

D es crip t ion O u t d oor u n itO u t d oor u n it I n d oor u n itI n d oor u n it

Dimensions (height x width x depth) 540 x 660 x 290 mm (21.3" x 26" x 11.4") 364 x 254 x 481 mm (14.3" x 10" x 18.9")

Weight 23 kg (51 lbs) 6 kg (13.2 lbs)

Power input Cooling mode 460 W, heating mode 660 W

Refrigerant piping Min. 5 m (16.4 ft), max. 20 m (66 ft). The outdoor unit is pre-filled to 15 m pipe. In case of extension add 20 g/m pipe. Maximum height difference shall be 15 m (49 ft).

Electrical connection Power supply 230 V / 50 Hz with separate 16 A fuse, type B and 300 mA residual current device.

2

2 .. 1 1 . . Power in p u t a n d ou t p u t ch a ra ct erist ics of t h e u n it Power in p u t a n d ou t p u t ch a ra ct erist ics of t h e u n it

Figure 1: Power input [W] (red) and air flow [m3/h] (blue) at external pressure 100 [Pa] (green)

(8)

2

2 .. 2 2 . . CoolBreez e coolin g ou t p u t ch a ra ct erist ics CoolBreez e coolin g ou t p u t ch a ra ct erist ics

Figure 2: CoolBreeze cooling output characteristics

Measured at 34 °C (93 °F) outdoor temperature and 55 % relative humidity, and 25 °C (77 °F) indoor temperature and 65 % relative humidity.

1. Cooling output of ventilation relative to outdoor environment with Futura L 2. Cooling output of ventilation relative to outdoor environment with Futura M 3. Cooling output of ventilation relative to interior with Futura L

4. Cooling output of ventilation relative to interior with Futura M

(9)

2

2 .. 3 3. . CoolBreez e h ea t in g ou t p u t ch a ra ct erist ics CoolBreez e h ea t in g ou t p u t ch a ra ct erist ics

Figure 3: CoolBreeze heating output characteristics

Measured at 5 °C (41 °F) outdoor temperature and 70 % relative humidity, and 21 °C (70 °F) indoor temperature and 50 % relative humidity.

1. Heating output of ventilation relative to outdoor environment with Futura L 2. Heating output of ventilation relative to outdoor environment with Futura M 3. Heating output of ventilation relative to interior with Futura L

4. Heating output of ventilation relative to interior with Futura M

(10)

2

2 .. 4 4 . . Acou st ic p a ra m et ers Acou st ic p a ra m et ers

F ilt ra t ion F ilt ra t ion

Use Supply and extraction

Type Stringing

Class F7

Dimensions 328 x 309 x 48 mm (12.9" x 12.2" x 1.9")

A cou s t ic p ow er lev el L ( d B ) * A cou s t ic p ow er lev el L ( d B ) *

F req u en cy [ H z]

F req u en cy [ H z] T ot a lT ot a l 6363 12 512 5 2 5 02 5 0 5 0 05 0 0 1k1k 2 k2 k 4 k4 k 8 k8 k

Ai r s u p p l y

Ai r s u p p l y 5 1 ,65 1 ,6 4 1 ,64 1 ,6 4 4 ,44 4 ,4 2 7 ,62 7 ,6 2 2 ,02 2 ,0 2 9 ,12 9 ,1 1 5 ,91 5 ,9 1 0 ,41 0 ,4 2 3 ,82 3 ,8 Ai r e x t r a c t i o n

Ai r e x t r a c t i o n 5 2 ,05 2 ,0 4 2 ,14 2 ,1 4 5 ,04 5 ,0 2 7 ,92 7 ,9 2 2 ,42 2 ,4 2 9 ,52 9 ,5 1 6 ,51 6 ,5 1 0 ,81 0 ,8 2 4 ,62 4 ,6 T o t h e e n v i r o n m e n t

T o t h e e n v i r o n m e n t 5 2 ,05 2 ,0 4 2 ,14 2 ,1 4 5 ,04 5 ,0 2 7 ,92 7 ,9 2 2 ,42 2 ,4 2 9 ,52 9 ,5 1 6 ,51 6 ,5 1 0 ,81 0 ,8 < 1 0 < b >< 1 0 < b >

with F7 filters and silencers installed and at air flow of 245 m3/h and 50 Pa

(11)

2

2 .. 5 5 . . L ea ka g e L ea ka g e

Figure. 4: Internal leakage (blue) and external leakage (red) compared to certification limit (green)

1. Internal leakage 2. External leakage 3. Limit

2

2 .. 6 6. . Hea t recovery ef f icien cy Hea t recovery ef f icien cy

Figure 5: Heat recovery efficiency [%] at air flow [m3/h]

(12)

2

2 .. 7 7 . . VAC sch em e VAC sch em e

Figure 6: VAC scheme

D e s c r i p t i o n o f V AC s c h e m e : D e s c r i p t i o n o f V AC s c h e m e :

1) – F7 filter outdoor air

2) – bypass flap controlled by actuator 3) – enthalpy exchanger

4) – supply fan

5) – integrated post heater 6) – exhaust fan

7) – CoolBreeze indoor evaporator/condenser 8) – F7 filter extracted air

9) – expansion valve

10) – CoolBreeze outdoor evaporator/condenser 11) – 4-way valve

12) – compressor

13) – circulation flap controlled by actuator

I n p u t / o u t p u t c o l o r d e s c r i p t i o n : I n p u t / o u t p u t c o l o r d e s c r i p t i o n :

(13)

3

3 . . Wiring diagram Wiring diagram

Figure 7: Wiring diagram of 1-3 control panels, 0-8 CO2 sensors, outdoor temperature NTC sensor, boost buttons and programmable inputs

1. Alfa control panel, 1 - 8 pcs.

2. VarioBreeze – room-by-room ventilation button, 1 - 16 pcs.

3. CO2 sensor, 1 - 8 pcs.

4. VarioBreeze – room-by-room ventilation flap, 1 - 64 pcs.

5. NTC outdoor temperature sensor 6. Inputs and outputs

(14)

4

4. . Installation requirements Installation requirements

4

4 .. 1 1 . . Con n ect ion of ven t ila t ion p ip es Con n ect ion of ven t ila t ion p ip es

B - Outdoor air intake ∅ 150 inner /∅ 210 outer EPP pipes

A - Exhaust air ∅ 150 inner /∅ 210 outer EPP pipes

C - Supply air ∅ 150 SONOCUT silencer

D - Extracted air ∅ 150 SONOCUT silencer

The air inlet and outlet openings must remain free and clear! It is necessary to install silencers at the air supply and air extract in the length of approx. 1.5 m (5 ft). Note: It is necessary to leave 10 mm (0.4") gap under the door in all rooms with ventilation.

4

4 .. 2 2 . . In st a lla t ion In st a lla t ion

C o n d e n s a t e d r a i n c o n n e c t i o n C o n d e n s a t e d r a i n c o n n e c t i o n

In the heat exchanger, the exhausted air is cooled by the supplied air causing moisture condensation. The resulting condensed water is drained towards the siphon. The condensate drain connection is located at the bottom side of the heat recovery unit. A siphon, which is connected to the sewerage system, must be mounted onto the coupling of the condensate drain connection (HT 32 mm (1.26") drain pipe).

C o n d e n s a t e m u s t b e a l l o w e d t o f r e e l y f l o w o u t o f t h e h e a t r e c o v e r y u n i t b y g r a v i t y ! C o n d e n s a t e m u s t b e a l l o w e d t o f r e e l y f l o w o u t o f t h e h e a t r e c o v e r y u n i t b y g r a v i t y !

Re c o m m e n d e d t o p o l o g y o f c o n n e c t i n g p e r i p h e r a l s t o RS - 4 8 5 b u s Re c o m m e n d e d t o p o l o g y o f c o n n e c t i n g p e r i p h e r a l s t o RS - 4 8 5 b u s

This RS-485 bus is intended to connect only the peripherals of the Futura heat recovery unit. The bus is four-wire, with a 24 V supply and a maximum total current of 500 mA. The power supply is resistant to overload or short circuit.

1

2

4

(15)

1. Control panels and CO2 sensors

2. Installation box JA-190PL and JA-110Z-B hub 3. Connected via RS485

4. Room-by-room ventilation flaps – supply 5. Room-by-room ventilation flaps – exhaust Re c o m m e n d e d c a b l e

Re c o m m e n d e d c a b l e

Four-wire twisted-pair cable, eg. Unitronic PAAR LiYCY 2 × 2 × 0.34 – 0.5 mm2 or J-Y(St)Y 2 × 2 × 0.8 mm2. It is possible to use UTP or STP cable.

The cable must not run parallel to low or high voltage power lines. Occasional crossing is fine.

B u s t e r m i n a t i n g r e s i s t o r s RS - 4 8 5 B u s t e r m i n a t i n g r e s i s t o r s RS - 4 8 5

The terminating resistor 120 Ω is connected to the heat recovery unit. It is recommended to connect a second terminating resistor to the most remote control panel or sensor. For more convenient wiring, a Jablotron JA-110Z-B RS-485 bus splitter and JA-190PL box can be used. In the case of a large number of devices and a long wiring in a star connection, a suitable hub must be used.

E n t h a l p y c o o l i n g / h e a t i n g m o d u l e C o o l B r e e z e E n t h a l p y c o o l i n g / h e a t i n g m o d u l e C o o l B r e e z e

The CoolBreeze add-on module requires c o n n e c t i o n o f t h e o u t d o o r c o n d e n s a t i o n u n i t t o t h e m a i n s w i t h a f i x e d 2 3 0 V / 5 0 H z ,c o n n e c t i o n o f t h e o u t d o o r c o n d e n s a t i o n u n i t t o t h e m a i n s w i t h a f i x e d 2 3 0 V / 5 0 H z , t y p e B 1 6 A f u s e a n d a 3 0 0 m A r e s i d u a l c u r r e n t c i r c u i t b r e a k e r

t y p e B 1 6 A f u s e a n d a 3 0 0 m A r e s i d u a l c u r r e n t c i r c u i t b r e a k e r . Alternatively, preparation for later installation of the CoolBreeze module can be made.

The internal evaporator of the CoolBreeze module is connected to the outdoor unit with a 4 x 0 .7 5 m m 4 x 0 .7 5 m m 22 communication cable. The refrigerant piping should be 6/10 mm2. A m i n i m u m c o o l a n t p i p e l e n g t h o f 5 m (1 6 .4 f t ) a n d a m a x i m u m o f 1 5 m (4 9 f t ) m u s t b eA m i n i m u m c o o l a n t p i p e l e n g t h o f 5 m (1 6 .4 f t ) a n d a m a x i m u m o f 1 5 m (4 9 f t ) m u s t b e g u a r a n t e e d .

g u a r a n t e e d .

5

5 . . Energy label Energy label

2017 1254/2014

46

dB

I

II

3 JABLOTRON LIVING TECHNOLOGY CZ s.r.o.

Futura

A+

A B C D E F G

A

+

250 m /h

2017 1254/2014

46

dB

I

II

350 m

3

/h

JABLOTRON LIVING TECHNOLOGY CZ s.r.o.

Futura

A+

A B C D E F G

A

+

Figure 9: Futura M / Futura L

(16)

6

6 . . Dimensional drawings Dimensional drawings

Ma i n d i m e n s i o n s i n c l . C o o l B r e e z e m o d u l e Ma i n d i m e n s i o n s i n c l . C o o l B r e e z e m o d u l e

133 3x243

830

910

1274

169 6

73 10

111 247

364 260

1

2

3

4

5 6

(17)

20018

59

444

60

33

524

13

14 15 16 17

(18)

1. Condensate drain connection from Futura

2. Groove (diameter 22 mm) for CoolBreeze condensate hose 3. Condensate drain connection from CoolBreeze

4. When installing, keep space of at least 330 mm (distance for fitting the EPP elbow).

5. Refrigerant inlet / outlet for CoolBreeze

6. When installing CoolBreeze, use a flange from the Futura unit

7. When installing, keep space of at least 370 mm for the condensate drain connection 8. DN 32 hose

9. HL138 siphon – FUTURA 10. Sewer connection

11. T piece HT 32

12. STY-517-1 siphon (CoolBreeze)

13. When installing, keep space of at least 500 mm for filters exchange 14. Ambient air

15. Waste air 16. Fresh air 17. Indoor air

Mo u n t i n g d i m e n s i o n s f o r w a l l m o u n t i n g Mo u n t i n g d i m e n s i o n s f o r w a l l m o u n t i n g

666600

(19)

7

7. . Dependence of air flow and external pressure Dependence of air flow and external pressure

F u t u r a M F u t u r a M

Figure 10: Dependence of air flow [m3/h] and external pressure [Pa] - Futura M

F u t u r a L F u t u r a L

Figure 11: Dependence of air flow [m3/h] and external pressure [Pa] - Futura L

(20)

8

8. . CoolBreeze pressure loss CoolBreeze pressure loss

Figure 12: CoolBreeze pressure loss [Pa] at air flow [m3/h]

(21)
(22)
(23)
(24)

References

Related documents

 Jumper closed and button pressed for longer than six seconds – causes restoring of manufacturer setting of communication protocol, i.e. sets Modbus RTU

es así que mujeres como ana maría, de “al final del círculo”, o Herminia, de “Futuro prometido”, se atrevie- ron a enfrentar al sistema patriarcal; sin embargo, este sistema

Section 51.62 (relating to vendor goods and services reimbursement) applies to HCBS provided as part of the Consolidated, P/FDS and Adult Autism Waivers and when a provider provides

Based on the rugged HTS2035SMD humidity / temperature sensor, HTM2500LF is a dedicated humidity and temperature transducer designed for OEM applications where a

Prepare the CIP tank for cleaning by adding the recommended cleaners to the tank as outlined in charts above while re- circulating and heating within the tank Circulate into

2: Comparison of downy mildew resistance QTL LOD peaks obtained for pathogen populations from India mapped on LG1 of the newly constructed genetic linkage map based on cross

The sensor has got a PI controller for heating and cooling (depending on temperature) and for ventilation (depending on air humidity) and it can emit a warning to the bus as soon as

NIF utilizes a suite of commercial Computer Aided Design (CAD), Analysis, and Data Management software applications for the three dimensional virtual definition