technical data air conditioning systems RXS E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

N/A
N/A
Protected

Academic year: 2021

Share "technical data air conditioning systems RXS E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air"

Copied!
30
0
0

Loading.... (view fulltext now)

Full text

(1)

Split

Sky Air

air

c

o

nd

itio

nin

g

sy

ste

m

s

FBQ-B8V1-B8V3B

RXS20-25-35E

(single phase)

Split Heat Pump

Condensing Units

(2)

1

1

• Split Sky Air • Outdoor Units

1

(3)

1

2

• Split Sky Air • Outdoor Units

2

NOMINAL INPUT

RXS20E2V1B RXS25E2V1B RXS35E2V1B

For combination indoor units + outdoor units Indoor Units FTXS20D3VMW FTXS25D3VMW FTXS35D3VMW Cooling

capacity MinimumStandard kWkW 1.22.0 1.22.5 1.23.4

Maximum kW 2.6 3.0 3.8

Heating

capacity MinimumStandard kWkW 1.22.7 1.23.4 1.24.0

Maximum kW 4.1 4.5 5.0

Nominal input Cooling Minimum kW 0.30 0.3 0.30

Standard kW 0.48 0.6 1.00 Maximum kW 0.82 0.8 1.22 Heating Minimum kW 0.29 0.29 0.29 Standard kW 0.65 0.83 1.08 Maximum kW 1.29 1.34 1.55 For combination indoor units + outdoor units EER Nominal 4.17 4.17 3.40 COP Nominal 4.15 4.10 3.70 Energy Labeling Directive Cooling A A Heating A A

Annual energy consumption kWh 240 300 500

Indoor Units FTXS20D3VML FTXS25D3VML FTXS35D3VML

Cooling

capacity MinimumStandard kWkW 1.22.0 1.22.5 1.23.4

Maximum kW 2.6 3.0 3.8

Heating

capacity MinimumStandard kWkW 1.22.7 1.23.4 1.24.0

Maximum kW 4.1 4.5 5.0

Nominal input Cooling Minimum kW 0.30 0.3 0.30

Standard kW 0.48 0.6 1.00 Maximum kW 0.82 0.8 1.22 Heating Minimum kW 0.29 0.29 0.29 Standard kW 0.65 0.83 1.08 Maximum kW 1.29 1.34 1.55 For combination indoor units + outdoor units EER Nominal 4.17 4.17 3.40 COP Nominal 4.15 4.10 3.70 Energy Labeling Directive Cooling A A Heating A A

Annual energy consumption kWh 240 300 500

Indoor Units FDXS25EAVMB FDXS35EAVMB

Cooling

capacity MinimumStandard kWkW 1.32.4 1.43.4

Maximum kW 3.0 3.8

Heating

capacity MinimumStandard kWkW 1.33.2 1.44.0

Maximum kW 4.5 5.0

Nominal input Cooling Standard kW 0.69 1.09

Heating Standard kW 0.91 1.18 For combination indoor units + outdoor units EER Nominal 3.48 3.12 COP Nominal 3.52 3.39 Energy Labeling Directive Cooling A B Heating B C

Annual energy consumption kWh 345 545

(4)

1

2

• Split Sky Air • Outdoor Units

3

Cooling

capacity MinimumStandard kWkW 1.22.5 1.23.5

Maximum kW 3.0 3.8

Heating

capacity MinimumStandard kWkW 1.23.4 1.44.0

Maximum kW 4.5 5.0

Nominal input Cooling Minimum kW 0.30 0.30

Standard kW 0.65 1.13 Maximum kW 0.86 1.26 Heating Minimum kW 0.29 0.29 Standard kW 0.98 1.23 Maximum kW 1.49 1.85 For combination indoor units + outdoor units EER Nominal 3.85 3.10 COP Nominal 3.47 3.25 Energy Labeling Directive Cooling A B Heating B C

Annual energy consumption kWh 325 565

Indoor Units FFQ25B8V1B FFQ35B8V1B

Cooling

capacity Standard kW 2.5 3.4

Heating

capacity Standard kW 3.2 4.0

Nominal input Cooling Standard kW 0.73 1.10

Heating Standard kW 0.92 1.20 For combination indoor units + outdoor units EER Nominal 3.42 3.09 COP Nominal 3.48 3.33 Energy Labeling Directive Cooling A B Heating B C

Annual energy consumption kWh 365 550

Indoor Units FBQ35B8V1

Cooling

capacity Standard kW 3.4

Heating

capacity Standard kW 4.0

Nominal input Cooling Standard kW 1.17

Heating Standard kW 1.22 For combination indoor units + outdoor units EER Nominal 2.91 COP Nominal 3.28 Energy Labeling Directive Cooling C Heating C

Annual energy consumption kWh 585

Indoor Units FHQ35BVV1B

Cooling

capacity MinimumStandard kWkW 1.43.4

Maximum kW 3.7

Heating

capacity MinimumStandard kWkW 1.24.0

Maximum kW 5.0

Nominal input Cooling Standard kW 1.05

Heating Standard kW 1.11 For combination indoor units + outdoor units EER Nominal 3.24 COP Nominal 3.60 Energy Labeling Directive Cooling A Heating B

(5)

1

2

• Split Sky Air • Outdoor Units

4

Casing Colour Ivory White

Dimensions Unit Height mm 550 550 550

Width mm 765 765 765 Depth mm 285 285 285 Packing Height mm 589 617 617 Width mm 882 882 882 Depth mm 363 363 363 Weight Unit kg 30 32 32 Packed Unit kg 35 38 38 Heat

Exchanger Dimensions LengthNr of Rowsmm 8281 8052 8052

Fin Pitch mm 1.4 1.4 1.4

Nr of Stages 24 24 24

Tube type Hi-Xa(7)

Fin Type Waffle fin

Treatment Anti-corrosion treatment (PE)

Fan Type Propeller

Quantity 1 1

Air Flow Rate (nominal at 230V) Cooling m³/min 36.2(H) - 25.7(L) 33.5(H) - 23.4(L) 33.5(H) - 23.4(L) Heating m³/min 32.6(H) - 30.6(L) 30.2(H) - 28.3(L) 30.2(H) - 28.3(L) Motor Quantity 1 1 1 Model D238-28 Motor Speed

(nominal) CoolingHeating rpmrpm 860(H) - 620(L)860(H) - 810(L) 860(H) - 620(L)860(H) - 810(L)

Fan Motor Output W 50 50 50

Compressor Quantity 1 1 1

Motor Model 1YC23NXD#C

Type Hermetically sealed swing compressor

Motor

Output W 600 600 600

Operation

Range Cooling Min

°CDB -10 -10 -10

Max °CDB +46 +46 +46

Heating Min °CWB -15 -15 -15

Max °CWB +20 +20 +20

Sound Level

(nominal) Cooling Sound Power dBA 61(H) 61(H) 62(H)

Sound

Pressure dBA 46(H) - 43(L) 46(H)- 43(L) 47(H) - 44(L)

Heating Sound

Pressure dBA 47(H) - 44(L) 62(H) 48(H) - 45(L)

Sound Level

(Night quiet) Sound Pressure dBA 47(H) - 44(L)

Refrigerant Type R-410A

Charge kg 0.8 1.0 1.0

Refrigerant Oil Type FVC50K

(6)

1

2

• Split Sky Air • Outdoor Units

5

connections (OD) Gas Diameter (OD) mm 9.5 9.5 9.5 Drain Diameter (OD) mm 18 18 18

Piping Length Maximum m 20 20 20

Chargele ss m 10 10 Additional Refrigerant Charge kg/m 0.02/>10m Installation height difference Maximum m 15 15 15

Heat Insulation Both liquid and gas pipes Both liquid and gas pipes

Standard

Accessories ItemQuantity 1 Installation manual1 1

Item Drain plug Drain plug

Quantity 1 1

Notes Nominal cooling capacities are based on : indoor temperature : 270CDB, 190CWB, outdoor temperature : 350CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.

2-3 ELECTRICAL SPECIFICATIONS

RXS20E2V1B RXS25E2V1B RXS35E2V1B

Power Supply Name V1

Phase 1 1 1 Frequency Hz 50 50 50 Voltage V 220-240 Current Nominal running current (RLA) Cooling (A) A 2.44 3.14 4.42 Heating (A) A 3.34 3.94 4.72

Starting current (cooling/

heating) A 3.7 4.3 5.1

Z-max List No requirements

Maximum Running Current A 3.33/4.13 4.61/4.91

Wiring

connections For Power Supply Quantity 3 3 3

For connection

(7)

1

4

• Split Sky Air • Outdoor Units

7

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FTXS20D3VMW/L RXS20E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 40 2.3 23 0.20 40 0.14 2.1 2.0 3D055006

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

Representative unit combination Power supply Comp. OFM IFM

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FTXS25D3VMW/L RXS25E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 48.5 3.0 23 0.22 40 0.14 2.8 2.7 3D055008

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

(8)

1

4

• Split Sky Air • Outdoor Units

8

FLXS25BAVMB RXS25E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 50 3.2 23 0.16 34 0.34 3.1 2.9 3D055010B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

Representative unit combination Power supply Comp. OFM IFM

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FDXS25EAVMB RXS25E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 54.5 3.5 23 0.16 62 0.5 3.3 3.2 3D055010B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

(9)

1

4

• Split Sky Air • Outdoor Units

9

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FFQ25B8V1B RXS25E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 55 3.7 23 0.16 55 0.6 3.5 3.4 3D055010B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

Representative unit combination Power supply Comp. OFM IFM

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FTXS35D3VMW/L RXS35E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 75 4.3 23 0.22 40 0.14 4.1 3.9 3D055009

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

(10)

1

4

• Split Sky Air • Outdoor Units

10

FLXS35BAVMB RXS35E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 82 4.8 23 0.22 34 0.38 4.6 4.4 3D055011B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

Representative unit combination Power supply Comp. OFM IFM

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FDXS35EAVMB RXS35E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 78 4.7 23 0.22 62 0.5 4.5 4.3 3D055011B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

(11)

1

4

• Split Sky Air • Outdoor Units

11

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FBQ35B8V1 RXS35E2V2B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 80 5.1 23 0.16 65 0.5 4.9 4.7 3D055011B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

Representative unit combination Power supply Comp. OFM IFM

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FCQ35B8V1 RXS35E2V2B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 78 4.8 23 0.16 45 0.6 4.5 4.3 3D055011B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

(12)

1

4

• Split Sky Air • Outdoor Units

12

FFQ35B8V1B RXS35E2V2B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 79 4.8 23 0.16 55 0.6 4.6 4.4 3D055011B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

Representative unit combination Power supply Comp. OFM IFM

Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA FHQ35BVV1B RXS35E2V1B 50 - 22050 - 230 50 - 240 Max. 50Hz 264V Min. 50Hz 198V 9.75 10 76 4.5 23 0.22 62 0.6 4.3 4.1 3D055011B

SYMBOLS

MCA

: Min. Circuit Amps (A)

MFA

: Max. Fuse Amps (A)

RHz

: Rated operating frequency (Hz)

RLA

: Rated Load Amps (A)

OFM

: Outdoor Fan Motor

IFM

: Indoor Fan Motor

FLA

: Full Load Amps (A)

W

: Rated motor output (W)

NOTES

1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWB

Outdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%

3. Select wire size based on the larger value of MCA.

4. Instead of fuse, use circuit breaker.

5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on

the document title of your choice.

(13)

1

5

• Split Sky Air • Outdoor Units

13

Cooling 50Hz 220-240V BF 0.21

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 9.4

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055032

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(14)

1

5

• Split Sky Air • Outdoor Units

14

BF 0.24

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 9.4

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055033

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(15)

1

5

• Split Sky Air • Outdoor Units

15

Cooling 50Hz 220-240V BF 0.32

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 9.2

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055037

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(16)

1

5

• Split Sky Air • Outdoor Units

16

BF 0.17

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 8.7

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055042

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(17)

1

5

• Split Sky Air • Outdoor Units

17

Cooling 50Hz 220-240V BF 0.24

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 9

Indoor Outdoor temperature (°CWB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055487

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(18)

1

5

• Split Sky Air • Outdoor Units

18

BF 0.24

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 9.7

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055034

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(19)

1

5

• Split Sky Air • Outdoor Units

19

Cooling 50Hz 220-240V BF 0.35

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 9.8

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055039

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(20)

1

5

• Split Sky Air • Outdoor Units

20

BF 0.17

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 8.7

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055043

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(21)

1

5

• Split Sky Air • Outdoor Units

21

Cooling 50Hz 220-240V BF 0.15

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 11.5

Indoor Outdoor temperature (°CWB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055493

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(22)

1

5

• Split Sky Air • Outdoor Units

22

BF 0.16

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 14

Indoor Outdoor temperature (°CWB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055491

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(23)

1

5

• Split Sky Air • Outdoor Units

23

Cooling 50Hz 220-240V BF 0.25

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 10

Indoor Outdoor temperature (°CWB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055489

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(24)

1

5

• Split Sky Air • Outdoor Units

24

BF 0.20

Indoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40

(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 13

Indoor Outdoor temperature (°CDB)

EDB -10 -5 0 6 10

(°C) TC PI TC PI TC PI TC PI TC PI

3D055046

SYMBOLS

AFR: Air flow rate (m3/min)

BF: Bypass factor

EWB: Entering wet bulb temp. (°C)

EDB: Entering dry bulb temp. (°C)

TC: Total capacity (kW)

SHC: Sensible heating capacity (kW)

PI: Power input (kW)

NOTES

1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m

(2) Level difference: 0 m

(25)

1

6

• Split Sky Air • Outdoor Units

25

3D041800H

RXS20-35E2V1B

Minimum space for air passage Wall height on air outlet side =less than 1200

Drain outlet

(I.D.J 15.9 hose for connection)

Handle

Wiring inlet

Gas stop valve (J 12.7 CuT) Liquid stop valve (J 6.4 CuT)

Service port

Outdoor air thermistor Brand name label

4 x holes for anchor bolts (M8 or M10)

Name plate

In case of removing stop valve cover

(26)

1

6

• Split Sky Air • Outdoor Units

26

(27)

1

7

• Split Sky Air • Outdoor Units

27

3D047315D

RXS20E2V1B

Outdoor temperature thermistor Heat exchanger Propeller fan Liquid stop valve Field piping Field piping Gas stop valve

Compressor Refrigerant flow

Cooling Heating Discharge pipe thermistor Heat exchanger thermistor Muffler with filter

Motor operated valve Muffler with

filter

Outdoor unit

Muffler

Muffler

Four way valve normally: OFF Accumulator Muffler with filter 3D047316E

RXS25-35E2V1B

Outdoor temperature thermistor Heat exchanger Propeller fan Liquid stop valve Field piping Field piping Gas stop valve Compressor Refrigerant flow Cooling Heating Discharge pipe thermistor Heat exchanger thermistor Muffler with filter Motor operated valve Muffler with filter Outdoor unit Muffler Muffler

Four way valve normally: OFF

Accumulator

Muffler with filter

(28)

1

8

• Split Sky Air • Outdoor Units

28

3D041707H R : Protective earth C74,C75 C94,C95,C100 : Capacitor DB1,DB2 : Diode bridge FU1,FU2,FU3 : Fuse

IC11 : Solid state relay

IPM1 : Intelligent power module

L : Live L1 : Coil L1R : Reactor M1C : Compressor motor M1F : Fan motor MRCW,MRM10,MRM20 : Magnetic relay N : Neutral

PCB1,PCB2 : Printed circuit board

Q1L : Overload protector R1T,R2T,R3T,R12T : Thermistor S10,S11,S20 S30,S40,S70 S80,S90,S91 HC3,HC4,HL3,HN3: Connector

g

Field wiring Indoor Outdoor (outdoor) (Condenser) (discharge)

SA1 : Surge arrester

V1,V2,V3 : Varistor

X1M : Terminal strip

Y1E : Electronic expansion valve coil

Y1R : Reversing solenoide valve coil

Z1C,Z2C : Ferrite core

In case of cooling

only type In case of heatpump type

NOTE

(29)

1

9

• Split Sky Air • Outdoor Units

29

4D052971C Octav e ban d soun d pressur e level

Octave band center frequency (Hz)

approximate threshold hearing for

continuous noise

NOTES

1 Measure in anechoic room

2 Operation noise differs with operation and ambient conditions.

3 The operation noise measuring method is in accordance with JISC9612

Legend 50Hz, 220-240V Location of microphone 3D052971C Octav e ban d soun d pressur e level

Octave band center frequency (Hz)

approximate threshold hearing for

continuous noise

NOTES

1 Measure in anechoic room

2 Operation noise differs with operation and ambient conditions.

3 The operation noise measuring method is in accordance with JISC9612

Legend 50Hz, 220-240V Location of microphone 4D052972C Octav e ban d soun d pressur e level

Octave band center frequency (Hz)

RXS35E2V1B (Cooling)

approximate threshold hearing for

continuous noise

NOTES

1 Measure in anechoic room

2 Operation noise differs with operation and ambient conditions.

3 The operation noise measuring method is in accordance with JISC9612

Legend 50Hz, 220-240V Location of microphone 3D052972C Octav e ban d soun d pressur e level

Octave band center frequency (Hz)

RXS35E2V1B (Heating)

approximate threshold hearing for

continuous noise

NOTES

1 Measure in anechoic room

2 Operation noise differs with operation and ambient conditions.

3 The operation noise measuring method is in accordance with JISC9612

Legend 50Hz, 220-240V

(30)

1

10

• Split Sky Air • Outdoor Units

30

3D039536J Outdoo rtemp .(°CDB) Pull-dow n period Indoor temp. (°CWB) Notes:

The graphs are based on the following conditions: + Equivalent piping length 7.5 m

+ Level difference 0 m

+ Air flow rate high

Cooling Heating Indoor temp. (°CDB) Outdoo rtemp .(°CWB) Continuou s operation Continuou s operation (-15 °CDB)

References

Related documents

In trials where the testing stimulus was partially or fully visible, we did not observe a significant dependency of the discrimination accuracy (aver- aged across stimuli

manning documents, a computer with internet access and a calculator, and a standardized Excel spreadsheet, develop an accurate and justifiable training budget to the nearest

Often, a dysregulation of the balance between Treg and Tconv cells in these tissues can cause a loss of tissue function and pathological effects: a depletion of Treg

In a split-system central air conditioner, an outdoor metal cabinet contains the condenser and compressor, and an indoor cabinet contains the evaporator.. In many split-system air

Commissioner of Internal Revenue ...G.R.. AFP Retirement and Separation Benefits

According to The National Institute on Drug Abuse, effective addiction treatment involves five steps which are detoxification, behavioral counseling, medication, evaluation

The question, “Can a single project be called a program?” leads to a discussion about similarities and differences in the management coordination of component entities

This study examines the hedonic (HED) and utilitarian (UT) value of digital games (hence games) and their influence on product recommendation among active game