Digital indicator model DI10 GB

14023439.01 • V1.0 • 10/2011

Digital indicator model DI10

for panel mounting or wall mounting

Operating instructions

(2)

GB Operating instructions model DI10 page 1 - 36

© 2010 WIKA Alexander Wiegand SE & Co. KG All rights reserved.

WIKA® is a registered trademark in various countries.

Prior to starting any work, read the operating instructions!

Keep for later use!

(3)

Contents

1 General information ...4

2 Safety ...5

2.1 Intended use ...5

2.2 Personnel qualification ...7

2.3 Special hazards ...7

2.4 Labelling / Safety marks ...8

3 Specifications ...9

4 Design and function ... 11

4.1 Short description ... 11

4.2 Scope of delivery ... 11

5 Transport, packaging and storage ... 12

5.1 Transport ... 12

5.2 Packaging ... 12

5.3 Storage ... 12

6 Commissoning, operation ... 13

6.1 Mounting ... 13

6.2 Electrical connection ... 14

6.3 Function and operation description ... 17

6.4 Setting up the device ... 18

6.5 Extended parameterization ... 21

6.6 Functional principle of the setpoints ... 27

6.7 Default values ... 28

7 Maintenance and cleaning ... 30

7.1 Maintenance ... 30

7.2 Cleaning ... 30

8 Faults ... 30

9 Dismounting, return and disposal ... 31

9.1 Dismounting ... 31

9.2 Return... 32

9.3 Disposal ... 32

10 Appendix: Declaration of conformity ... 33

(4)

1 General information

1 General information

 The instrument described in the operating instructions has been designed and manufactured using state-of-the-art technology.

All components are subject to stringent quality and environmental criteria during production. Our management systems are certified to ISO 9001.

 These operating instructions contain important information on handling the instrument. Working safely requires that all safety instructions and work instructions are observed.

 Observe the relevant local accident prevention regulations and general safety regulations for the instrument's range of use.

 The operating instructions are part of the instrument and must be kept in the immediate vicinity of the instrument and readily accessible to skilled personnel at any time.

 Skilled personnel must have carefully read and understood the operating instructions, prior to beginning any work.

 The manufacturer's liability is void in the case of any damage caused by using the product contrary to its intended use, non-compliance with these operating instructions, assignment of insufficiently qualified skilled personnel or unauthorised modifications to the instrument.

 The general terms and conditions, contained in the sales documentation, shall apply.

 Subject to technical modifications.

 Further information:

- Internet address: www.wika.de / www.wika.com - Relevant data sheet: AC 80.06

- Application consultant: Tel.: (+49) 9372/132-0 Fax: (+49) 9372/132-406

E-Mail: [email protected]

(5)

2 Safety

Explanation of symbols WARNING!

... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.

Information

... points out useful tips, recommendations and information for efficient and trouble-free operation.

DANGER!

...identifies hazards caused by electric power. Should the safety instructions not be observed, there is a risk of serious or fatal injury.

2 Safety

WARNING!

Before installation, commissioning and operation, ensure that the appropriate instrument has been selected in terms of measuring range, design and specific measuring conditions.

Non-observance can result in serious injury and/or damage to equipment.

Further important safety instructions can be found in the individual chapters of these operating instructions.

2.1 Intended use

The device is designed for the evaluation and display of current loop signals.

With the setpoints, it is possible to perform simple control tasks (only possible for devices with setpoints).

(6)

2 Safety

Please read the following safety advice and the assembly before installation and keep it for future reference.

If the instrument is transported from a cold into a warm environment, the formation of condensation may result in the instrument malfunctioning. Before putting it back into operation, wait for the instrument temperature and the room temperature to equalise.

Notes on installation

 There must be no magnetic or electric fields in the vicinity of the device, e.g. due to transformers, mobile phones or electrostatic discharge.

 Do not install inductive consumers (relays, solenoid valves etc.) near the device and suppress any interference with the aid of RC spark extinguishing combinations or free-wheeling diodes.

 Keep input, output and supply lines separate from one another and do not lay them parallel with each other. Position “go” and “return lines”

next to one another. Where possible use twisted pair. So, you receive best measuring results.

 Screen off and twist sensor lines. Do not lay current-carrying lines in the vicinity. Connect the screening on one side on a suitable potential

equaliser (normally signal ground).

 The device is not suitable for installation in areas where there is a risk of explosion.

 Any electrical connection deviating from the connection diagram can endanger human life and/or can destroy the equipment.

 The terminal area of the devices is part of the service. Here electrostatic discharge needs to be avoided. Attention! High voltages can cause dangerous body currents.

 Galvanic insulated potentials within one complex need to be placed on a appropriate point (normally earth or machines ground). So, a lower disturbance sensibility against impacted energy can be reached and dangerous potentials, that can occur on long lines or due to faulty wiring, can be avoided.

The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.

(7)

2 Safety

2.2 Personnel qualification

WARNING!

Risk of injury should qualification be insufficient!

Improper handling can result in considerable injury and damage to equipment.

 The activities described in these operating instructions may only be carried out by skilled personnel who have the qualifications described below.

 Keep unqualified personnel away from hazardous areas.

Skilled electrical personnel

Skilled electrical personnel are understood to be personnel who, based on their technical training, knowledge of measurement and control technology and on their experience and knowledge of country-specific regulations, current standards and directives, are capable of carrying out work on electrical systems and independently recognising and avoiding potential hazards.

The skilled electrical personnel have been specifically trained for the work environment they are working in and know the relevant standards and regulations.

The skilled electrical personnel must comply with current legal accident prevention regulations.

2.3 Special hazards

DANGER!

Danger of death caused by electric current.

Upon contact with live parts, there is a direct danger of death.

 Electrical instruments may only be installed and mounted by skilled electrical personnel.

 Operation using a defective power supply unit (e.g. short circuit from the mains voltage to the output voltage) can result in life-threatening voltages at the instrument!

WARNING!

Do NOT use this product as safety or emergency stopping device, or in any other application where failure of the product could result in personal injury or material damage.

(8)

2 Safety

2.4 Labelling / Safety marks

Product label

Explanation of symbols

Before mounting and commissioning the instrument, ensure you read the operating instructionns!

CE, Communauté Européenne

Instruments bearing this mark comply with the relevant European directives.

(9)

3 Specifications

3 Specifications

Specifications

Display

Principle 7-segment LED, red, 4-digit

Character size 14 mm

Indication range -1999 … +9999

Display rate 0.1….10 sec

Memory Flash memory (independent of power supply), data retension > 100 years

Input Number and type 1 current input 4…20 mA

Accuracy ± 0.3 % ± 1 Digit

Measuring time 0.1…10 sec

Voltage drop approx. DC 5.1 V, max. 150 mW

{approx. DC 8.0 V for option with switching outputs, max. 200 mW}

Power supply Not required, since the indicator is powered by the 4…20 mA loop

Electrical connection plug-in terminal, wire cross-section up to 2.5 mm²

{Switching outputs}

Number and type 2 PhotoMOS outputs, potential free max. AC/DC 30 V, max. 0.4 A Display

Material PC polycarbonate, black

Ingress protection Front: IP 65, rear: IP 00

Dimensions 96 x 48 x 45 mm (w x h x d) including plug-in terminals

Mounting snap-in screw element for wall thickness up to 3 mm

{Wall mounting enclosure}

Material ASA, black, PG gland

Ingress protection IP 65

Dimensions 160 x 90 x 60 mm (w x h x d) Cable gland Cable diameter: 4.0…8.0 mm

Mounting fixing holes for screws

(10)

3 Specifications

Permissible ambient conditions

Operating temperature 0…60 °C Storage temperature -20…80 °C

Humidity 0…80 % relative humidity, non-condensing CE conformity

EMC directive 2004/108/EC, EN 61326 emission (group 1, class B) and interference immunity (industrial application)

{ } Items in curved brackets are optional extras for additional price.

For further specifications see WIKA data sheet AC 80.06 and the order documentation.

Operating elements

(11)

4 Design and function

4 Design and function

4.1 Short description

The device is designed for the evaluation and display of current loop signals (4…20 mA). With the setpoints, it is possible to perform simple control tasks (only possible for devices with setpoints).

The configuration of the device is done with an intuitive menu navigation. The 14 mm characters allow a good read-out of the measuring values.

4.2 Scope of delivery

The scope of delivery is:

Indicator for panel mounting:

 Indicator

 2 fixing elements

 Seal

 Operating instructions

Indicator for wall mounting:

 Indicator

 Operating instructions

Cross-check scope of delivery with delivery note.

(12)

5 Transport, packaging and storage

5 Transport, packaging and storage

5.1 Transport

Check instrument for any damage that may have been caused by transport.

Obvious damage must be reported immediately.

5.2 Packaging

Do not remove packaging until just before mounting. Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for repair).

5.3 Storage

Permissible conditions at the place of storage:

 Storage temperature: -20 ... +80 °C

 Humidity: 0 ... 80 % relative humidity (no condensation)

Avoid exposure to the following factors:

 Direct sunlight or proximity to hot objects

 Mechanical vibration, mechanical shock (putting it down hard)

 Soot, vapour, dust and corrosive gases

 Potentially explosive environments, flammable atmospheres Store the instrument in its original packaging in a location that fulfils the conditions listed above. If the original packaging is not available, pack and store the instrument as described below:

1. Wrap the instrument in an antistatic plastic film.

2. Place the instrument, along with shock-absorbent material, in the packaging.

3. If stored for a prolonged period of time (more than 30 days), place a bag, containing a desiccant, inside the packaging.

WARNING!

Before storing the instrument (following operation), remove any residual media. This is of particular importance if the medium is hazardous to health, e.g. caustic, toxic,

carcinogenic, radioactive, etc.

(13)

6 Commissoning, operation

6 Commissoning, operation

Please read the safety instructions and installation instructions in chapter 2 before installation and keep this user manual for future reference.

6.1 Mounting

Indicator for panel mounting:

1. After removing the fixing elements, insert the device.

2. Check the seal to make sure it fits securely.

3. Click the fixing elements back into place and tighten the clamping screws by hand. Then use a screwdriver to tighten them another half a turn.

CAUTION! The torque should not exceed 0.1 Nm!

(14)

6 Commissoning, operation Indicator for wall mounting:

Fasten the wall mounting enclosure with adequate material (screws) at the four mounting holes.

Screws are not part of scope of delivery. Please use screws according to the material of the wall, where you want to install the enclosure.

For electrical connection pass the cable through the high-strength cable gland.

Close the enclosure with the attached screws and fasten the screw nut of the cable gland. So ingress protection IP 65 is reached.

6.2 Electrical connection

device without setpoints

(15)

6 Commissoning, operation device with setpoints

For devices with switching outputs please use measuring input Irel+.

Connection examples

The examples show devices with setpoints.

a) Current loop device in combination with a transmitter in current loop technique:

b) Current loop device in combination with another measuring input with low burden:

(16)

6 Commissoning, operation

c) Current loop device in combination with a 3-wire sensor:

d) Current loop device in combination with a 4-wire sensor:

e) Current loop device with activated outputs DC 24 V (upto 0.4 A)

(17)

6 Commissoning, operation

6.3 Function and operation description

Operation

The operation is divided into two different levels.

 Menu Level: Here it is possible to navigate between the individual menu items.

 Parameterization level: The parameters stored in the menu item can be parameterized here.

Functions that can be adjusted or changed are always indicated with a flashing of the display. Adjustments made at the parameterization level should be always confirmed by pressing the [P] key to save them.

However, the display automatically saves all adjustments and then switches to operation mode if no further keys are pressed within 10 seconds.

Level Button Description

Menu level

Change to parameterization level with the relevant parameters.

For navigation at the menu level.

Parameterization level

To confirm the changes made at the parameterization level.

To change the value or setting.

Example:

(18)

6 Commissoning, operation

6.4 Setting up the device

Switching on

Once the installation is complete, you can start the device by applying the current loop. Check beforehand once again that all the electrical connections are correct.

Starting sequence

For 1 second during the switching-on process, the segment test (8 8 8 8) is displayed, followed by an indication of the software type and, after that, also for 1 second, the software version. After the start-up sequence, the device switches to operation/display mode.

Standard parameterization

To be able to parameterize the display, press the [P] key in operating mode for 1 second. The display then changes to the menu level with the first menu item tYPE.

Menu level Parameterization level

tYPE

Selection of the input signal, tYPE:

4-20 SEnS

There are two measuring input options for the current loop: 4- 20 mA as works calibration (without application of the sensor signal) and SEnS as sensor calibration (with the sensor applied). Confirm the selection with [P] and the display switches back to the menu level.

(19)

6 Commissoning, operation

Menu level Parameterization level

End

Setting the measuring range end value, END:

8 8 8 8

nOCA CAL

Set the end value from the smallest to the highest digit with [] [] and confirm each digit with [P]. A minus sign can only be parametrized on the highest value digit. After the last digit, the display switches back to the menu level.

If SEnS was selected as the input option, you can only select between nOCA and CAL. With nOCA, only the previously set display value is taken over, and with CAL, the device takes over both the display value and the analogue input value.

OFFS

Setting the measuring range start/offset value, offs:

8 8 8 8

nOCA CAL

Enter the start/offset value from the smallest to the highest digit [] [] and confirm each digit with [P]. After the last digit the display switches back to the menu level.

If SEnS was selected as the input option, you can only select between nOCA and CAL. With nOCA, only the previously set display value is taken over, and with CAL, the device takes over both the display value and the analogue input value.

(20)

6 Commissoning, operation

Menu level Parameterization level

dot

Setting the decimal point, dot:

0 0.0 0.00 0.000

The decimal point on the display can be moved with [] [] and confirmed with [P]. The display then switches back to the menu level again.

SEC

Setting the display time, SEC:

0.1 0.9 dann 1.0 10.0

The display time is set with [] []. The display moves up in increments of 0.1 up to 1 second and in increments of 1.0 to 10.0 seconds. Confirm the selection by pressing the [P]

button. The display then switches back to the menu level again.

run

Activation / deactivation of the programming lock and completion of the standard parameterization, run:

ULOC LOC

With the aid of the [] [] keys, you can choose between the deactivated key lock ULOC (works setting) and the activated key lock LOC. Make the selection with [P]. After this, the display confirms the settings with "- - - -", and automatically switches to operating mode.

If LOC was selected, the keyboard is locked. To get back into the menu level, you must press [P] for 3 seconds in operating mode. You must now enter the CODE (works setting 1 2 3 4) that appears using the [] [] keys plus [P] to unlock the keyboard. FAIL appears if the input is wrong.

(21)

6 Commissoning, operation

6.5 Extended parameterization

By pressing the [] & [] buttons during standard parameterization for one second, the display switches to the extended parameterization mode.

Operation is the same as in standard parameterization.

Menu level Parameterization level

EndA

Rescaling the measuring input values, EndA:

8 8 8 8

With the aid of this function, you can rescale the input value of 4-20 mA (works setting) without applying a measuring signal.

If sensor calibration has been selected, these parameters are not available.

OFFA

Rescaling the measuring input values, OFFA:

8 8 8 8

With the aid of this function, you can rescale the input value of 4-20 mA (works setting) without applying a measuring signal.

If sensor calibration has been selected, these parameters are not available.

tArA

Setting the tare /offset value, tArA:

0 0 0 0

The given value is added to the linerarized value. In this way, the characteristic line can be shifted by the selected amount.

(22)

6 Commissoning, operation

Menu level Parameterization level

ZErO

Zero point tranquilization, ZErO:

0 0

With zero point tranquilization, a value range around zero can be preselected at which the display shows zero. If, for

example, a 10 is set, the display would show a zero in the range from -10 to +10 and continue below it with -11 and above it with +11.

tASt

MIN/MAX value inquiry - Assignment of key functions, tAST:

EHEr LI.12 no

Here, you can enter for the operating mode either a MIN/MAX value inquiry or a threshold value correction on the arrow keys.

If the MIN/MAX memory is activated with EHEr, the measured MIN/MAX values will be saved during operation and can be called up via the arrow keys [] []. The values are lost if the device is restarted.

If the threshold value correction LI.1 is selected, the limit values can be changed during operation without hindering the operating procedure.

If no is parameterized, the arrow keys [] [] have no function in operating mode.

FLAS

Flashing of display, FLAS:

LI-1 LI-2 LI.12 no

Here, flashing of the display can be added as an extra alarm function, either to the first limit value (select: LI-1), the second limit value (select: LI-2) or to both limit values (select: LI.12).

With no (works setting), no flashing is assigned at all.

(23)

6 Commissoning, operation

6.5.1 Limit values, limits, hysteresis Menu level Parameterization level

LI-1

Limit values / Limits, LI-1:

0 0 0 0

For both limit values, two different values can be

parameterized. With this, the parameters for each limit value are called up one after the other.

HY-1

Hysteresis for limit values, HY-1:

0 0 0 0

For both limit values, a hysteresis function exists that reacts according to the functional principle (operating current / quiescent current).

Fu-1

Function if display falls below / exceeds limit value, Fu-1:

HIgH Louu (Low)

To indicate if the value falls below the lower limit value, Louu can be selected (LOW = lower limit value) and if it goes above the upper limit value, HIgH can be selected (HIgH = upper limit value). LOW corresponds to the quiescent current principle and HIgH to the operating current principle.

(24)

6 Commissoning, operation

Menu level Parameterization level

LI-2

Limit value /Limits, LI-2:

0 0 0 0

For both limit values, two different values can be

parameterized. With this, the parameters for each limit value are called up one after the other.

HY-2

Hysteresis for limit values, HY-2:

0 0 0 0

For both limit values, a hysteresis function exists that reacts according to the functional principle (operating current / quiescent current).

Fu-2

Function if display falls below / exceeds limit value, FU-2:

HIgH Louu (Low)

To indicate if the value falls below the lower limit value, Louu can be selected (LOW = lower limit value) and if it goes above the upper limit value, high can be selected (HIGH = upper limit value). LOW corresponds to the quiescent current principle and HIGH to the operating current principle.

(25)

6 Commissoning, operation Menu level Parameter-Ebene

CodE

Setting the code, CODE:

1 2 3 4

With this setting, it is possible to select an individual code (works setting 1 2 3 4) for locking the keyboard. To

locl/release the key, proceed according to menu item run.

(26)

6 Commissoning, operation

6.5.2 Additional setpoints Menu level Parameter-Ebene

SPCt

Setpoints - Number of additional setpoints, SPCt:

0

In addition to the start and end value, 8 extra setpoints can be defined to linearize non-linear sensor values. Only the

activated setpoint parameters are displayed.

dIS1

Display values for setpoints dIS1 … dIS8:

8 8 8 8 nOCA CAL

Under this parameter the value of the setpoints is defined.

With sensor calibration, as with end value/offset, you will be asked at the end whether a calibration should be made.

InP1

Analogue values for setpoints INP1 … INP8:

0 0 0 0

The setpoints are only displayed with the works calibration (4- 20 mA). Here, the desired analogue values can be freely selected. The input of constantly rising analogue values must be carried out by the customer/user.

(27)

6 Commissoning, operation

6.6 Functional principle of the setpoints

Operating current The setpoint S1-S2 is off below the threshold and on reaching the threshold.

Quiescent current The setpoint S1-S2 is on below the threshold and switched off on reaching the threshold.

Alarms / optical setpoint display

An activated setpoint can be optically indicated by flashing of the 7-segment display.

Functional principle of the alarms

Threshold Threshold/limit value for switch over

Hysteresis Width of the window between the thresholds Operating principle Operating current / quiescent current

(28)

6 Commissoning, operation

6.7 Default values

Reset to default values

To return the unit to a defined basic state, a reset can be carried out to the default values. The indicator must be in “ULOC” mode. An accidental reset during operation is avoided..

The following procedure should be used:

 Switch off the power supply

 Press button [P]

 Switch on loop current (approx. 3.8 mA) and press [P]-button until

„- - - -“ is shown in the display.

With reset, the default values of the program table are loaded and used for subsequent operation. This puts the unit back to the state in which it was supplied.

Caution! All application-related data are lost.

(29)

6 Commissoning, operation

Default values

PN Parameter Menu items Default

0 tYPE 4-20 SEnS SEnS

1 End -1999 to 9999 2000

2 OFFS -1999 to 9999 0400

3 dot 0000 to 0.000 0

13 SEC 0.1 bis 10.0 1.0

50 run ULOC LOC ULOC

1 bin OFFA -19.99 to 99.99 04.00

2 bin EndA -19.99 to 99.99 20.00

4 tArA -1999 to 9999 0000

5 ZErO 00 to 99 00

6 tASt No EHtr LI.12 No

59 FLAS No LI-1 LI-2 LI12 no

61 LI-1 -1999 to 9999 0800

62 HY-1 0000 to 9999 0000

63 Fu-1 Louu HIgH HIgH

71 LI-2 -1999 to 9999 1200

72 HY-2 0000 to 9999 0000

73 Fu-2 Louu HIgH HIgH

51 CodE 0000 to 9999 1234

100 SPCt 0 to 8 0

101 A dIs1 -1999 to 9999

101 B InP1 -1999 to 9999

102 A dIs2 -1999 to 9999

102 B InP2 -1999 to 9999

103 A dIs3 -1999 to 9999

103 B InP3 -1999 to 9999

104 A dIs4 -1999 to 9999

104 B InP4 -1999 to 9999

105 A dIs5 -1999 to 9999

105 B InP5 -1999 to 9999

106 A dIs6 -1999 to 9999

106 B InP6 -1999 to 9999

107 A dIs7 -1999 to 9999

107 B InP7 -1999 to 9999

108 A dIs8 -1999 to 9999

108 B InP8 -1999 to 9999

(30)

8 Faults

7 Maintenance and cleaning

7.1 Maintenance

This instrument is maintenance-free.

Repairs must only be carried out by the manufacturer.

7.2 Cleaning

CAUTION!

 Before cleaning, correctly disconnect the instrument from the mains.

 Clean the instrument with a moist cloth.

 Electrical connections must not come into contact with moisture.

For information on returning the instrument see chapter "9.2 Return".

8 Faults

Fault Solution

The display of the device is dark Check the current loop current of the device.

Please contact the manufacturer if errors of this kind occur.

The device shows 4 bars in the upper part of the display

Displayed overflow at exceedance of display/measuring range

The device shows 4 bars in the lower part of the display

Displayed overflow at undershooting of display/measuring range

The device shows „Err2“ (Error 2) During parameterization current <

3,5 mA

(31)

9 Dismounting, return and disposal CAUTION!

If faults cannot be eliminated by means of the measures listed above, the instrument must be shut down immediately, and it must be ensured that pressure and/or signal are no longer present, and it must be prevented from being

inadvertently put back into service.

In this case, contact the manufacturer.

If a return is needed, please follow the instructions given in chapter "9.2 Return".

9 Dismounting, return and disposal

WARNING!

Residual media in dismounted instruments can result in a risk to persons, the environment and equipment. Take sufficient precautionary measures.

9.1 Dismounting

To dismount the instrument, do the following steps:

Indicator for panel mounting:

1. Open the clamping screws and remove the fixing elements.

2. Remove the instrument and seal from panel cutout.

Indicator for wall mounting:

For dismounting the indicator open the four fastening screws of the enclosure and remove it.

(32)

9 Dismounting, return and disposal

9.2 Return

WARNING!

Strictly observe when shipping the instrument:

All instruments delivered to WIKA must be free from any kind of hazardous substances (acids, bases, solutions, etc.).

When returning the instrument, use the original packaging or a suitable transport package.

Enclose the completed return form with the instrument.

The return form is available on the internet:

www.wika.de / Service / Return

9.3 Disposal

Incorrect disposal can put the environment at risk.

Dispose of instrument components and packaging materials in an

environmentally compatible way and in accordance with the country-specific waste disposal regulations.

(33)

10 Appendix: Declaration of conformity

10 Appendix: Declaration of conformity

(34)

10 Appendix: Declaration of conformity

(35)

10 Appendix: Declaration of conformity

(36)

WIKA global

WIKA subsidiaries worldwide can be found online at www.wika.com.

WIKA Alexander Wiegand SE & Co. KG Alexander-Wiegand-Straße 30

63911 Klingenberg • Germany Tel. (+49) 9372/132-0

Fax (+49) 9372/132-406 E-Mail [email protected] www.wika.de

References

Related documents

Enhancements included embedding additional JavaScript to control overriding methods from the report layout page to the report viewer page, and controlling the look of the MRV pages

Those grants are part of five ongoing demonstration projects, centered on the following research topics: Follow-up Services (described here), Achieving Scale, Institutional Models

Any amount by which an option premium exceeds the option’s intrinsic value can be considered time (or extrinsic) value. Trading Limit - See Limit and Position Limit..

In the tube agglutination technique, the object is to use the agglutination reaction to determine the titer of antibodies in a serum sample.. The titer is a measure of the amount

dummies, best bets daily, vegas betting odds on the super bowl 2014, betting lines on nfl games, free online gambling slot machines, honda classic betting tips 2013, pro betting

14 Western Southland Invercargill Hunting &amp; Fishing, 100 tgts Trophy Match Sporting Clays in conjunction with CLUB CHAMPIONSHIPS. At

There will be an optional service charge of 12.5% on all table service and all prices are inclusive of V.A.T.. There is a minimum spend of £10.00 on any debit or credit

Changes in service use before and following an inpatient rehabilitation stay were examined using quantitative outcome measures that included: (1) the number of admissions to