• No results found

Duct Static Pressure Calculation

N/A
N/A
Protected

Academic year: 2021

Share "Duct Static Pressure Calculation"

Copied!
6
0
0

Loading.... (view fulltext now)

Full text

(1)

Static Pressure:

A fan must overcome resistance when pushing air from the discharge of the fan through the duct to some final outlet. This resistance is known as static pressure. Static pressure in a typical duct run is caused by the velocity of the air, type of duct material, elbows/fittings, dampers, diffusers, etc.

Fan static pressure is measured in inches of water gauge

To calculate static pressure, you must the ductwork system configuration. See link for an example on how to calculate static pressure

Static pressure is the measure of the potential energy of a unit of air in the particular cross section of a duct. Air pressure on the duct wall is considered static. Imagine a fan blowing into a completely closed duct; it will create only static pressure because there is no air flow through the duct. A balloon blown up with air is a similar case in which there is only static pressure. If you increase the static pressure in a duct such as with a reducer, the static pressure will decrease and the velocity pressure will increase.

Total Pressure

Consists of the pressure the air exerts in the direction of flow (Velocity Pressure) plus the pressure air exerts perpendicular to the plenum or container through which the air moves. (static pressure) In other words:

PT = PV + PS PT = Total Pressure PV = Velocity Pressure PS = Static Pressure

The equal friction method of sizing ducts is easy and straightforward to use

The equal friction method of sizing ducts is often preferred because it is quite easy to use. The method can be summarized to

1. Compute the necessary air flow volume (m

3

/h, cfm) in every room and branch of

the system

2. Use

1)

to compute the total air volume (m

3

/h, cfm) in the main system

3. Determine the maximum acceptable airflow velocity in the main duct

4. Determine the major pressure drop in the main duct

5. Use the major pressure drop for the main duct as a constant to determine the duct

sizes throughout the distribution system

6. Determine the total resistance in the duct system by multiplying the static

resistance with the equivalent length of the longest run

7. Compute balancing dampers

1. Compute the air volume in every room and branch

Use the actual heat, cooling or air quality requirements for the rooms and calculate the required air volume - q.

2. Compute the total volume in the system

(2)

Make a simplified diagram of the system like the one above.

Use 1) to summarize and accumulate the total volume - qtotal - in the system.

Note! Be aware that maximum load conditions almost never occurs in all of the rooms at the same time. Avoid over-sizing the main system by multiplying the accumulated volume with a factor less than one (This is probably the hard part - and for larger systems sophisticated computer-assisted indoor climate calculations are often required).

3. Determine the maximum acceptable airflow velocity in the main ducts

Select the maximum velocity in the main duct on basis of the application environment. To avoid disturbing noise levels - keep maximum velocities within experienced limits:

comfort systems - air velocity 4 to 7 m/s (13 to 23 ft/s)

industrial systems - air velocity 8 to 12 m/s (26 to 40 ft/s)

high speed systems - air velocity 10 to 18 m/s (33 to 60 ft/s)

Use the maximum velocity limits when selecting the size of the main duct.

4. Determine the static pressure drop in main duct

Use a pressure drop table or similar to determine the static pressure drop in the main duct.

5. Determine the duct sizes throughout the system

Use the static pressure drop determined in 4) as a constant to determine the ducts sizes throughout the system. Use the air volumes calculated in 1) for the calculation. Select the duct sizes with the pressure drop for the actual ducts as close to the main duct pressure drop as possible.

6. Determine the total resistance in the system

Use the static pressure from 4) to calculate the pressure drop through the longest part of the duct system. Use the equivalent length which is

the actual length + additional lengths for bends, T's, inlets and outlets

7. Calculate balancing dampers

Use the total resistance in 6) and the volume flow throughout the system to calculate necessary dampers and the theoretical pressure loss through the dampers.

Note about the Equal Friction Method

The equal friction method is straightforward and easy to use and gives an automatic reduction of the air flow velocities throughout the system. The reduced velocities are in general within the noise limits of the application environment.

The method can increase the numbers of reductions compared to other methods, and often a poorer pressure balance in the system require more adjusting dampers. This may increase the system cost compared to other methods.

Example - Equal Friction Method

The equal friction method can be done manual or more or less semi automatic with a spreadsheet as shown in the table below.

(3)

The table is based on the diagram above. Air flow and friction loss from a diagram is added. Minor pressure loss coefficients must be summarized for for the actual applications.

The pressure loss in each path is summarized on the right and pressure loss is added manually in the dampers to balance the system.

The ductwork of ventilation systems are often sized with either the Velocity, the

Constant Pressure Loss (or Equal Friction Loss) - or the Static Pressure Recovery

Methods

The design of the ductworks in ventilation systems are often done by using the

Velocity Method

Constant Pressure Loss Method (or Equal Friction Method)

Static Pressure Recovery Method

The Velocity Method

Proper air flow velocities for the application considering the environment are selected. Sizes of ducts are then given by the continuity equation like:

A = q / v (1) where

A = duct cross sectional area (m2) q = air flow rate (m3/s)

v= air speed (m/s)

Alternatively in Imperial units Ai = 144 qi / vi (1b)

where

A = duct cross sectional area (sq.in.) q = air flow rate (cfm)

v= air speed (fpm)

A proper velocity will depend on the application and the environment. The table below indicate commonly used velocity limits:

(4)

Type of Duct

Comfort Systems

Industrial Systems

High Speed Systems

m/s

ftm

m/s

ftm

m/s

ftm

Main ducts

4 - 7

780 - 1380

8 - 12

1575 - 2360

10 - 18

1670 - 3540

Main branch

ducts

3 - 5

590 - 985

5 - 8

985 - 1575

6 - 12

1180 - 2360

Branch ducts

1 - 3

200 - 590

3 - 5

590 - 985

5 - 8

985 - 1575

(5)

The Constant Pressure Loss Method (or Equal Friction Loss Method)

A proper speed is selected in the main duct close to the fan. The pressure loss in the main duct are then used as a template for the rest of the system. The pressure (or friction) loss is kept at a constant level throughout the system. The method gives an automatic velocity reduction through the system. The method may add more duct cross sectional changes and can increase the number of components in the system compared to other methods.

The Static Pressure Recovery Method

(6)

With the static pressure recovery method the secondary and branch ducts are selected to achieve more or less the same static pressure in front of all outlets or inlets. The major advantage of the method are more common conditions for outlets and inlets. Unfortunate the method is complicated to use and therefore seldom used.

References

Related documents

Recall that Binary Iterative Hard Thresholding (BIHT) is a greedy, iterative algorithm meant for the recovery of sparse signals from one-bit measurements.. At each iteration

• Functions include radio resource management, admission control, scheduling, enforcement of negotiated uplink QoS, cell information broadcast, ciphering/deciphering of user

○ If BP elevated, think primary aldosteronism, Cushing’s, renal artery stenosis, ○ If BP normal, think hypomagnesemia, severe hypoK, Bartter’s, NaHCO3,

Newby indicated that he had no problem with the Department’s proposed language change.. O’Malley indicated that the language reflects the Department’s policy for a number

Results suggest that the probability of under-educated employment is higher among low skilled recent migrants and that the over-education risk is higher among high skilled

The purpose of article 1525 is to protect co-debtors by establishing in their favour a presumption that they are jointly liable for their common debt. To overcome the presumption,

Acknowledging the lack of empirical research on design rights, our paper wishes to investigate the risk of piracy and the perceptions of the registered and unregistered design

cherish sanitary testimonials directly from wakaya perfection products of our product manufacturers use anything coming in.. Reset link to a sanitary napkins, is actually