PRESENTATION ON
DESIGN AND COMPARISON OF FLAT SLAB USING
IS 456 – 2000 AND ACI 318 – 08
PRESENTED BY
TUSHAR MANOJ MADAMWAR
(11001063)
GUIDED BY
DR. K. N. KADAM
CONTENTS
1. INTRODUCTION
2. ADVANTAGES OF FLAT SLAB
3. LITERATURE REVIEW
4. DESIGNOF FLAT SLAB USING IS 456-2000
5. DESIGN OF FLAT SLAB USING ACI 318-08
6. RESULT AND COMPARISION
INTRODUCTION
DEFINATION-Slab and column without beams
COMPONENTS
- Drops-increase shear strength against punching.
Advantages of Flat Slab
1.
Flexibility in room layout
2.Saving in building height
3.Shorter construction time
4.Ease of installation
5.
Pre-fabricated welded mesh
6.Buildable score
PROBLEM STATEMENT
Design a flat slab of size 6.6m×5.6m using direct design method by IS
456-2000 and ACI 318-08 .It is subjected to live load of 7.75 kN/m
2.The
grade of steel used is Fe 415. The exposure condition is mild. Height of
floor is 4m.size of column is 400mm × 400mm.
DESIGN OF FLAT SLAB USING IS 456-2000
Column Strip
A design strip having a width of 0.25l2 not greater than 0.25l1 on each side of column center-line.
For longer span=1.4m (not greater than 1.65) For shorter span=1.65m(not greater than 1.4)
Middle strip
A design strip bounded on each of its opposite sides by the column strip. For longer span=2.8m
For shorter span=3.8m
Panel
The part of a slab bounded on-each of its four sides by the line of a Column or center-lines of adjacent-spans.
Drop
The drops when provided shall be rectangular in plan and have a length in each direction not less than one- third of the panel length in that direction
For longer span =2.2m For shorter span=1.866m Provide drop of 2.2m×2.2m
Column Head
For longer span=1.65m For shorter span=1.4 Adopting 1.3m
Depth of Flat Slab
The thickness of the flat slab up to spans of 10 m shall be generally controlled by considerations of span ( L ) to effective depth ( d ) ratios given as below:
Cantilever 7; simply supported 20; Continuous 26 For longer span=260mm
For shorter span= 220mm
Loads acting on slab
Dead load(𝑊𝑑1)=0.285× 25=6.25kN/m2
Floor finish(𝑊𝑑2)=1.45kN/m2
Live load(𝑊𝑙)=7.75kN/m2
Total design moment on slab
Mo=𝑾𝒍𝒏
𝟖
Mo=total moment
W = design load on an area l1 l2
ln = clear span extending from face to face of columns, capitals, brackets or walls, but not less than 0.65 l1
l1 = length of span in the direction of Mo.
l2 = length of span transverse to l1.
A=𝝅
𝟒 𝒅𝟐= 𝜋
4 1.32 = 1.152𝑚
Clear span along long span =ln =6.6-1
2 (1.152)-1
2(1.152)=5.448 >4.29
(Should not be less than 0.65 l1 )
Clear span along long span =ln =5.6-1
2 (1.152)-1
2(1.152)=4.44 >3.64
Total Design Load
For longer span(l n=5.448 m , l2 =5.6 m)= W = w l 2 l n =471.36kN For shorter span(l n=4.44 m , l2 =6.6 m)=W = w l2 ln= 452.74k N
Absolute Sum of Negative and Positive Moments
For longer span=Mo=𝑤𝑙𝑛
8 =
471.36×5.448
8 = 320.99 𝑘𝑁
For shorter span=Mo=𝑊𝑙𝑛
8 = 452.74×4.44 8 = 251.2 𝑘𝑁
Stiffness Calculations
stiffness coefficient=ac=𝑘𝑐 𝑘𝑠 =1.39Distribution of Bending Moment Across
The Panel Width
Longer Span
1.Column strip
Negative B.M at exterior support=−121.34𝑘𝑁𝑚 positive span B.M =90𝑘𝑁𝑚
Negative span BM at interior support =-166.5 kNm
2.Middle strip
Negative BM at exterior support =0𝑘𝑁𝑚 Positive span BM =59.96𝑘𝑁𝑚
Effective Depth of The Slab
Maximum positive BM occurs in the column strip (long span) = 90.91 kNm factored moment = 1.50 x 90.91 = 136.36 kNm
Mo= 0.138fck 𝑏𝑑2 = (𝑏 = 2800𝑚𝑚
d= 136.36×106
0.138×20×2800 𝑀20 𝑔𝑟𝑎𝑑𝑒 𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒
d=132.83 mm ≅140 mm
Using 12 mm ∅ (diameter) main bars. Overall thickness of slab =140+15+ 12
2 =161 mm ≅170 mm
Depth (along longitudinal direction) =170-15-12
2 = 150𝑚𝑚
Shear In Flat Slab
The critical section for shear shall be at a distance d/2 from the periphery of the column/capital/ drop panel, perpendicular to the plane of the slab
Check for shear stress developed in slab
The critical section for shear for the slab will be at a distance d/2 from the face of drop. Perimeter of critical section =4× 2340=9340mm
Vo=1.5× 15.45 × 𝐿1 × 𝐿2 − 2.34 (2.34) =729.78kN Nominal shear stress =Tv=𝑉𝑢
𝑏𝑑 =
729.78×103
9340×140 = 0.55𝑁/𝑚𝑚2
shear strength of concrete =Tc=0.25 𝑓𝑐𝑘=0.25 20 =1.1N/𝑚𝑚2 Permissible shear stress =𝑇𝑣 < 𝑘𝑠𝑇𝑐
Ks=(0.5+𝛽𝑐) ,βc=0.848 Ks=1.348 > 1
Reinforcement
Longer span
Negative exterior reinforcement: 𝑀𝑢=0.87 𝑓𝑦Ast 𝑑 − 0.42𝑥𝑢
1.5× 121.34 × 106 = 0.87 × 415 × 𝐴𝑠𝑡 𝑑 − 0.42 × 0.48 × 150
DESIGN OF FLAT SLAB USING ACI 318-08
Drop of flat slabs
Drop panel shall extend in each direction from centerline of support a distance not less than one-sixth the span length measured from center -to center of supports in that direction.
Span of panel in longer direction = 16.76 ft length of drop panel=1
6 × 16.76 × 2=5.58ft
With half width on either side of the center line of support = 0.85 m Thickness of drop =1
4 × 6 = 1.5 𝑖𝑛 = 38.1𝑚𝑚
Thickness of the slab
the minimum thickness shall be in accordance with (a) Slabs without drop panels as ... 5 in. (b) Slabs with drop panels as defined... 4 in.
Depth of the slab from deflection criteria =𝑙𝑛
36 (the yield stress 𝑓𝑦𝑖=60,000psi,≅ 415𝑁/𝑚𝑚2
Minimum depth of slab=max of (16.76×12
36 ,
14.22×12
36 )=max of (5.58in,4.74in)=5.58in
Providing a slab of thickness 6 in or 152.4 mm.
Design strips
Column strip is a design strip with a width on each side of a column centerline equal to 0.25 l2 or 0.25 l1,
whichever is less.
Middle strip is a design strip bounded by two column strips.
Designed Load on Slab
Dead load on the slab = 6
12 × 150 = 75𝑝𝑠𝑓 = 3.6𝑘𝑁/𝑚3
Live load on the slab = 161.80 psf = 7.75 KN /m2
Design load on the slab = (1.2 x 7.5 + 1.6 x 161.80) = 348.88 » 350 psf= 16. 765 KN /m2
Total factored static moment for a span
Mo=𝑾𝒖𝒍𝟐𝒍𝒏
𝟐
𝟖
Wu=load per unit area acting on the slab panel
ln=Clear span ln shall extend from face to face of columns, capitals ,brackets, or walls. Value of ln shall not be
less than 0.65 l1 .
l2=When the span adjacent and parallel to an edge is being considered, the distance from edge to panel centerline shall be substituted for l2 .
In an interior span, total static moment Mo shall be distributed as follows: Negative factored moment ...0.65
Positive factored moment ...0.35 Mo= 350
8×1000 × 170762 × 14.22 = 174.75𝑓𝑡 − 𝑘𝑖𝑝𝑠 = 237𝑘𝑁𝑚
Negative design moment = 237 x 0. 65 = 154 ft-kips = 208.89 kNm Positive design moment = 237 x 0.35 = 83.00 ft -kips = 113.22 kNm
Bending moment for column strip
Negative moment for column strip = 75 % of total negative moment in the pannel = 0.75 x 154.00 = 115.50 ft -kips = 157.66 KNm
Positive moment for column strip = 60 % of total positive moment in the panel. = 0.60 x 83.00 = 49.8 ft -kips = 67.977 KNm
Max moment (+ve or –ve ) along shorter span = 72.18 ft -kips Max moment (+ve or –ve) along longer span = 115.50 ft –kips
Shear Provision
For flat slabs Vc =Nominal shear strength of concrete, Vc Shall be smallest of the
following: [Where βc is the ratio of long side to short side of the column,
concentrated load or reaction area and where as is 40 for interior columns, 30 for
edge columns,20 for corner columns] Vc== 2 + 4 𝛽𝑐 𝑓𝑐 ′𝑏 𝑜𝑑 Vc== 2 + 𝑎𝑏𝑠𝑑 0 𝑓𝑐 ′𝑏 𝑜𝑑 Vc=4 𝑓𝑐′𝑏𝑜𝑑
Vu= factored shear, acting at distance d/2 from face of the support. (assuming column of size 400 mm by 400 mm)
Vu=350 16.76 × 14.22 − 1.31 + 0.5 1.31 + 0.5 =350 238.32 − 1. . 812 =82265.365 lb=365.91kN
𝑓𝑐′𝑏𝑜𝑑= 4000 × 4 × 21.72 × 6 = 32968.64𝑙𝑏 (𝛽𝑐 = 1.17) The nominal stress of concrete will be smallest of the following
Vc== 2 + 4
1.17 × 32968.64 = 178650.57 𝑙𝑏
Vc== 2 + 40×6
4×21.72 × 32968.64 = 157010.87 𝑙𝑏
Vc= 𝑓𝑐′𝑏𝑜𝑑=4× 32968.64 = 131874.56 𝑙𝑏 Vc > Vu section safe in punching shear \safe.
Reinforcement
For negative moment in column strip
R= 𝑀𝑢 𝑏(324) = 115.5×103 16.22×32.4=219.77 Reinforcement ratio = 0.00375 Area of reinforcement = 0.00375 x 16.22 x 6 x 12 = 4.38 in2/ft
Results and Comparisons
CODE IS 456 -2000 ACI 318-08
Shape of test specimen for concrete strength (mm) Cube 150x150x150 Cylinder 152.4x304.8 Grade of concrete(N/mm²) 20 20 Grade of steel (N/mm²) 415 413.7 Negative moment (KN-m) 188.5 208.89 Positive moments (KN-m) 90 113.22 Area of reinforcement(mm²) 4290 2829
Thickness of slab for Serviceability criteria(mm)
170 150
Conclusions
By comparing with different codes we concluded that ACI 318 code is more effective in designing of flat slabs.
As per Indian code we are using cube strength but in international standards cylinder strength is used which gives higher strength than cube.
Drops are important in increasing the shear strength of the slab.
Flat slabs enhance resistance to punching failure at the junction of concrete slab & column.
By incorporating heads in slab, we are increasing rigidity of slab.
Conclusions
The negative moment’s section shall be designed to resist the larger of the two interior negative design moments for the span framing into common supports.
According to Indian standard (IS 456) for RCC code has recommended characteristic strength of concrete as 20, 25, and 30 and above 30 for high strength concrete. For design purpose strength of concrete is taken as 2/3 of actual strength this is to compensate the difference between cube strength and actual strength of concrete in structure. After that we apply factor of safety of 1.5. So in practice Indian standard actually uses 46% of total concrete characteristic strength. While in International practice is to take 85% of total strength achieved by test and then apply factor of safety which is same as Indian standard so in actual they use 57% of total strength.
References
Bureau of Indian Standards, New Delhi, “IS 456:2000, Plain and Reinforced
Concrete - Code of Practice”, Fourth Revision, July (2000).
American Concrete Institute, “ACI 318-08, Building Code Requirements for
Structural Concrete and Commentary”, January (2008).
Dr. V. L. Shaha & Dr. S. R. Karve “Limit State Theory and Design of Reinforced Concrete” Sixth edition
Amit A. Sathwane , R. S. Deoalate (IJERA)“Analysis and Design of Flat Slab and Grid Slab and Their cost omparision”