Circular No. 47 1955

STATE OF ILLINOIS

WILLIAM G. STRATTON, Governor

H y d r o g e n Exchange Resin

ror

Steam P u r i t y Analysis

by

R. W. Lane, T. E. Larson and J. W. Pankey

Issued by

Department of Registration and Education

VERA M. BINKS, Director

State Water Survey Division

A. M. BUSWELL, Chief

(2)

Reprinted f r o m I N D U S T R I A L A N D ENGINEERING CHEMISTRY, V o l . 4 7 , Page 4 7 , J a n u a r y 1 9 5 5 C o p y r i g h t 1 9 5 5 b y the American Chemical Society a n d r e p r i n t e d b y permission o f the c o p y r i g h t owner

Hydrogen Exchange Resin

for Steam Purity Testing

R. W. LANE, T. E. LARSON, AND J. W. PANKEY

Illinois State Water Survey, Urbana, Ill.

I n t h e c o n d u c t i v i t y m e a s u r e m e n t o f c o n d e n s e d s t e a m for p u r i t y , i n a c c u r a c i e s . r e s u l t f r o m t h e p r e s e n c e o f c a r b o n d i o x i d e , a m m o n i a , a n d / o r v o l a t i l e a m i n e s . M e a s u r e m e n t o f c o n d u c t i v i t y a t a t m o s p h e r i c b o i l i n g p o i n t e l i m i n a t e s m a j o r i n t e r f e r e n c e b y c a r b o n d i o x i d e b u t o n l y m i n o r i n t e r f e r e n c e b y a m m o n i a a n d / o r a m i n e s . I f p r e t r e a t e d c o n d e n s a t e i s p a s s e d t h r o u g h a h y d r o g e n e x c h a n g e b e d , a m m o n i a , v o l a t i l e a m i n e s , a n d o t h e r c a t i o n s a r e r e p l a c e d b y h y d r o g e n i o n ; s u b s e q u e n t r e b o i l i n g e l i m i n a t e s t h e free c a r b o n d i o x i d e . T h e r e m a i n i n g a n i o n s a r e i n t h e f o r m o f a c i d s a n d are r e a d i l y a p p a r e n t b y t h e i r c o n d u c t -a n c e . T h i s m e t h o d p r o v i d e s -a r -a p i d , -a c c u r -a t e t e s t for s t e -a m p u r i t y t o i n d i c -a t e d e f i c i e n c i e s o f feed w a t e r ' t r e a t m e n t , o f b o i l e r d e s i g n , a n d o f p l a n t o p e r a t i o n , a n d l i m i t s o f s a f e f e e d w a t e r a n d b o i l e r s o l i d s c o n t r o l . I t a l s o d e t e c t s c o n d e n s e r l e a k a g e i f a m m o n i a o r v o l a t i l e a m i n e s are p r e s e n t i n s t e a m c o n d e n s a t e .

S

T E A M produced by the modern steam power plant must be of high purity in order to prevent damage to superheaters, turbines, and other power equipment. High maintenance costs can be expected when impure steam resulting from carry-over of boiler water solids is produced. Also, impure steam when em-ployed in processing may contribute to the contamination of manufactured goods.

By way of definition, steam quality (a measure of B.t.u. con-tent) refers to moisture content as H2O, whereas steam purity

refers to ingredients other t h a n H2O which might be present.

Whether the particular ingredients are desirable, unimportant,

or harmful need have no place in a basic definition. Likewise,.

causative factors need no place in the definition.

From an academic standpoint, any divergence of conductivity from 0.054 micromho per cm. at 25° C. should be an indication of the presence of impurities, whether they be gaseous or mineral. The object of all steam purity testing is to observe or record de-viations from a uniform recording of conductivity. T h e limits of impurities of various types have been neither completely identified nor quantitatively defined for various operating con-ditions. Pure steam or condensate or water meeting t h e above definition is not necessary and probably not desirable.

Steam impurities may be of the volatile class which includes silica, carbon dioxide, sulfur dioxide, ammonium, t h e volatile and filming amines, and oil, or of the nonvolatile class which includes mineral ingredients obtained from mist, spray, prime, or other causes.

Figure 1. C o n d u c t i v i t y M e a s u r e m e n t s S h o w i n g Effect of Varying P e r c e n t a g e s of M a k e - u p Water,

o n A m m o n i a C o n t e n t o f S t e a m

Figure 2. Equilibrium C o n s t a n t s for Carbon Dioxide, A m m o n i a , pH, and Conductivity Relationships

(3)

The presence of volatile impurities in steam and condensate is subject to the laws of chemical equilibria and is dependent pri-marily on rating, pressure, and boiler water concentrations. The design of boiler drum internals may also influence the resultant concentration of volatile compounds, particularly sulfur dioxide and silica, in steam to a greater or lesser degree. Also, steady state conditions in the boiler are proportionally upset by increas-ingly rapid changes in load. Sampling and testing procedures for the volatile components are usually of more specific interest at the particular points of potential harm.

Figure 3. Conductivity Measurements at P l a n t 21

The presence of nonvolatile impurities is not governed by chemical equilibria and may or may not be expected to be quan-titatively dependent on rating, pressure, or boiler water concen-tration but to a large extent is dependent on design and water treatment. Deviation from a uniform conductivity may be con-sidered as abnormal. Appropriate sampling and testing pro-cedures for the abnormal presence of nonvolatile impurities (carry-over) are of primary importance.

Steam purity measurements have, therefore, been found to be important in the design of boiler internal baffling, of steam puri-fiers, and of feed water treatment, as well as in the control of plant operating variables, such as water level, boiler load, firing practices, and feed water treatment.

During the past 30 years, measurements of steam purity have been made principally by calorimetric, gravimetric, and conduc-tometric methods {2, 4). The conducconduc-tometric method, however, is the most accepted method because it is the simplest, most sensitive, and speediest. Its main disadvantage has been the interference provided by gases, such as carbon dioxide, ammonia, and more recently, amines, which have significant conductivities when condensed.

This interference problem became acute in studies on steam purity at Illinois State. Institutions supplementing the Feed Water Treatment Service provided by the Illinois State Water Survey. In the institution type plant, a variable percentage of make-up water is employed from hour to hour. This produces a widely varying ammonia content in the steam. When the ammonia recycles through the plant system, the interpretation . of the recorded conductivity is further complicated. Such con-ductivity results at two plants are shown in Figure 1 and Figure 3.

The early tests used a modified Straub degasifier or constant temperature device to provide a simple control of the constant temperature required for conductivity measurement.

The steam was injected in the degasifier and condensed in a

vented chamber containing a cooling water coil. Sufficient cool-ing was provided to maintain a constant temperature of about 210° F. at atmospheric pressure. A single point strip chart recorder of 0-40 and 0-1200 micromho ranges was employed to measure the conductivity of the condensed steam. This in-strument, when employing an electrode with a cell constant of 0.1, recorded the conductivity in micromhos per centimeter, corrected to a temperature of 25° C. The advantages of this measurement of the conductivity at 210° F. were the accuracy and the simplicity of the temperature control of the condensate near the atmospheric boiling point of water.

This device, however, was found to be only partially efficient in the removal of ammonia.

Applying corrections for the ammonia and/or carbon dioxide • contents was found to be tedious, and inexact, because of the varying gas contents and the frequent analyses required. A new graph (Figure 2) employing the latest equilibrium constants

(6) was prepared for the carbon dioxide, ammonia, pH, and

con-ductivity relationships, but this also did not serve the purpose of simple interpretation of results.

The specific application of this chart is limited by the low con-fidence in the results of direct Nesslerization for ammonia (±0.1 p.p.m.) and by the lack of information on the temperature coeffi-cient of the individual ionic conductances as well as the equilib-rium constants, unless the tests are made at 25° C. Both of these limitations may be overcome in time.

The futile attempts to apply corrections for ammonia and car-bon dioxide interference led to a decision to remove the gas prior to the measurement of conductivity by incorporation of a hydrogen exchanger in the system, following the boiling point condensation. Subsequent reboiling was provided to remove remaining carbon dioxide at the more favorable low pH conditions resulting from the hydrogen exchange.

Although it was anticipated that carry-over conductivity due to hydroxide and carbonate would be lost by the ion exchange and reboiling processes, it was also recognized that the increased conductivity of the resultant hydrochloric and sulfuric acid would more than compensate for this loss and actually increase the sen-sitivity of the measurement. Calculations revealed that the 48 I N D U S T R I A L A N D E N G I N E E R I N G C H E M I S T R Y Vol. 47, No. 1

(4)

conductivity of the acids was about 3.3 times the conductivity of the corresponding sodium salts, and therefore more t h a n 5 0 % of the boiler solids would have to be of hydroxide and carbonate salts before any decrease in conductivity would result from the ion exchange.

F i g u r e 5 . C o n t i n u o u s p H M e a s u r e m e n t s F o l l o w i n g H y d r o g e n E x c h a n g e

The procedure proved to be successful (Figure 3). Since the gas contaminants were reduced to a minimum, any increase in conductivity was now attributed with certainty to be mineral carryover (5).

TEST METHODS

Saturated steam was sampled from institutional power plant boilers producing steam at the r a t e of 20,000 to 50,000 pounds per hour at 125 to 250 pounds per square inch pressure. Steam sampling nozzles were installed according to the A S M E specifica-tions (1). One-quarter inch copper and stainless steel tubing carried t h e steam from t h e nozzle to the stainless steel or brass degasifiers.

Following condensation in the constant temperature device, the condensate was passed through a 4-inch diameter bed of poly-styrene resin (0.04 cu. ft.) in the hydrogen cycle, then through a reboil chamber, where the temperature was brought back to

F i g u r e 6 . C o n d u c t i v i t y , p H , a n d Redox P o t e n t i a l M e a s u r e m e n t s F o l l o w i n g A p p l i c a t i o n o f S o d i u m

Sulfite t o Effluent f r o m V e n t e d C o n d e n s e r

Ion Exchange.

210° F. as in the original chamber. Sampling locations were provided for measuring the conductivity previous to and following the hydrogen exchange in order to determine t h e effectiveness of this process in removal of the interfering substances. Figure 4 shows the complete steam purity testing equipment.

In these tests, chemicals were fed with the boiler feed water direct to the boiler by means of a chemical feed p u m p or a pot feeder connected to the boiler feed line.

Considerable differences of opinion {1, 3, 8) have been reported as to proper sampling rates, so the authors chose a more or less average rate of 40 to 60 pounds per hour, in order to avoid liquid films and corrosive effects associated with the lower sampling rates and to avoid the excessive loss of condensate associated with higher sampling rates.

TEST RESULTS

As anticipated, continuous pH measurement following hydro-gen exchange also indicated steam purity (Figure 5).

T h e application of sodium sulfite to the effluent from the boiling point condenser provided parallel indications of its presence when measurements were made of conductivity, pH, and redox poten-tial (Figure 6).

At plant 21, cyclohexylamine was applied hourly with other

F i g u r e 7 . C o n d u c t i v i t y M e a s u r e m e n t s o f C y c l o h e x y l a m i n e T r e a t e d W a t e r before a n d a f t e r H y d r o g e n E x -c h a n g e T r e a t m e n t F i g u r e 8 . H y d r o g e n E x c h a n g e T r e a t m e n t P l u s R e b o i l E l i m i n a t e d Effects o f C y c l o h e x y l a m i n e , M o r p h o l i n e , a n d A m m o n i u m C h l o r i d e Used for C o n d e n s a t e p H C o n t r o l t o P r e v e n t C o r r o s i o n January 1955 I N D U S T R I A L A N D E N G I N E E R I N G C H E M I S T R Y 4 9

(5)

boiler feed water treatment by means of an electrically operated p u m p . Prior to the application of the hydrogen exchange proc-ess, the interpretation of t h e conductivity data would have in-dicated a serious boiler water carry-over problem. However, the ion exchange process eliminated this interference and indi-cated t h a t good steam purity was being provided (Figure 7).

At plant 24, ap-plication of cyclo-h e x y l a m i n e , mor-pholine, and ammo-nium chloride (9), chemicals normally employed for con-densate pH control for corrosion pre-v e n t i o n , repre-vealed t h a t the hydrogen e x c h a n g e process plus reboil elimi-nated the interfer-ence provided by t h e s e c h e m i c a l s (Figure 8).

Preliminary tests on the effect of oc-tadecylamine (7), a filming amine em-ployed to prevent

Figure 9. C o n d e n s a t e Analyzer E q u i p m e n t

condensate corrosion, indicate t h a t this amine, apparently due to its low solubility and ionization, does not appreciably influ-ence the conductivity results.

When these data were discussed with F. G. Straub, at the University of Illinois, he designed a small unit without temper-a t u r e control for testing condenstemper-ate to determine condenser letemper-ak-

leak-age in power plants employing ammonia or amines for conden-sate pH control (Figure 9). It was estimated that immediately after installation the results detected a 0 . 0 1 % condenser leakage (Lake Michigan water).

CONCLUSIONS

By combining the procedure of temperature control at the atmospheric boiling point and t h e hydrogen exchange proc-ess with reboiling, an easy foolproof method of testing steam purity has been developed. This method minimizes interference from carbon dioxide, ammonia, cyclohexylamine, and morpho-line; provides a simple temperature control; and detects boiler water carry-over by continuous conductivity, pH, or redox measurement.

LITERATURE CITED

(1) Am. Soc. Mech. Engrs., 29 W. 39th St., New York, Power Test Code, "Determination of Quality of Steam, Part I I , " 1940. (2) Am. Soc. Mech. Engrs., 29 W. 39th St., New York, Steam

Contamination Subcommittee of the Joint Research Com-mittee on Boiler Feedwater Studies, "Bibliography on Steam Contamination.''

(3) Am. Soc. Testing Materials, Committee D 1066-49T, "Tentative Method of Sampling Steam," 1949.

(4) Am. Soc. Testing Materials, Proc, 4 1 , 1261-1340 (1941). (5) Lane, R. W., Larson, T. E., and Pankey, J. W., Proc. 14th Ann.

Water Conf., Engrs. Soc. West. Perm., 119-39 (1953).

(6) Latimer, W. M., "Oxidation Potentials," Prentice Hall, New York, 1952.

(7) Maguire, J. J., IND. ENG. CHEM., 46, 994 (1954). (8) Place, P. B., Combustion, 23, 49-53 (April 1951).

(9) Proc. 14th Ann. Water Conf., Engrs. Soc. West. Penn., "Panel Discussion on Corrosion and Deposits in Condensate and Feedwater Systems" (1953).

RECEIVED for review March 29, 1954. ACCEPTED September 23, 1954

References

Related documents

tain lower delivery prices through volume discounts granted by operators. 32 Moreover, note that the prices of delivery operators are only one element in the overall delivery

Given that the station uses different presenters who may be non-native speakers of some of the target languages of the listeners of Mulembe FM newscasts, the

Tracings of electrocardiograms (lead V4) in patients with hyperkalemic familial periodic paralysis before and during spontaneous attacks of paralysis and after disappearance of

Acknowledging the lack of empirical research on design rights, our paper wishes to investigate the risk of piracy and the perceptions of the registered and unregistered design

Field experiments were conducted at Ebonyi State University Research Farm during 2009 and 2010 farming seasons to evaluate the effect of intercropping maize with

These questions included: (a) What factor(s) did the graduates perceive as most important to their success?, (b) To what degree of importance did the graduates perceive the impact

The Laotian Government highly evaluated the improvement of the quality of the clinical training implemented by this project. Highly comprehensive sustainability can be expected in