This book, "Electrical Installation Guide according to IEC International Standards", which is compiled and printed in English by Schneider Electric, facilitates utilization of the IEC 60364 series of international standards concerned with safety, guarding, control, performance and protection of circuits, together with fundamentals and rules of electrical installation design. Moreover, the book contains topics of extreme importance that cover wide fields of electric power systems and their installations in different facilities. This renders the book a useful reference to each engineer and specialist in the field and an easy guide to such international standards and their application.
SASO, in recognition of the guide's important and comprehensive electric installation content, has translated it into Arabic to enable researchers and specialists to benefit from it in Arabic, if they desire.
In its capacity as the body entrusted with issuing and approving Saudi standards, SASO attaches particular importance to verification of safety in electrical installation in buildings. SASO is also acting assiduously to complete work on the national regulations of electrical installation based upon IEC 60364 series of international standards which are adopted as Saudi standards. In view of the divergence of the items of such standards and the many technical options offered, issuing an application guide to these standards is extremely useful. To this effect, the Saudi national regulations of electrical installation in buildings will be used. The guide being introduced here, will be an important reference for "the electrical installation guide according to Saudi standards" as part of the Saudi national regulations of electrical installation in buildings.
Dr. Khaled Y. Al-Khalaf
Vice Chairman, Board of Directors and Director General, SASO
A. contents
A1B. general - installed power
1. methodology
B12. rules and statutory regulations
B32.1 definition of voltage ranges
B3table B1
standard voltages between 100 V and 1000 V (IEC 38-1983) B3
table B2
standard voltages above 1 kV and not exceeding 35 kV (IEC 38-1983) B3
2.2 regulations
B42.3 standards
B42.4 quality and safety of an electrical installation
B52.5 initial testing of an installation
B62.6 periodic check-testing of an installation
B6table B3
frequency of check-tests commonly recommended for an electrical installation B6
2.7 conformity (with standards and specifications) of equipment
used in the installation
B73. motor, heating and lighting loads
B83.1 induction motors
B8table B4
power and current values for typical induction motors B9
3.2 direct-current motors
B10table B6
progressive starters with voltage ramp B10
table B7
progressive starters with current limitation B10
3.3 resistive-type heating appliances and incandescent lamps
(conventional or halogen)
B11table B8
current demands of resistive heating and incandescent lighting (conventional or halogen)
appliances B11
3.4 fluorescent lamps and related equipment
B11table B10
current demands and power consumption of commonly-dimensioned fluorescent
lighting tubes (at 220 V/240 V - 50 Hz) B12
table B11
current demands and power consumption of compact fluorescent lamps
(at 220 V/240 V - 50 Hz) B12
3.5 discharge lamps
B13table B12
current demands of discharge lamps B13
4. power loading of an installation
B144.1 installed power (kW)
B144.2 installed apparent power (kVA)
B15table B13
estimation of installed apparent power B15
4.3 estimation of actual maximum kVA demand
B16table B14
simultaneity factors in an apartment block B16
table B16
factor of simultaneity for distribution boards (IEC 439) B17
table B17
factor of simultaneity according to circuit function B17
4.4 example of application of factors ku and ks
B17table B18
an example in estimating the maximum predicted loading of an installation
A
B. general - installed power
(continued)4. power loading of an installation
(continued)4.5 diversity factor
B184.6 choice of transformer rating
B18table B19
IEC-standardized kVA ratings of HV/LV 3-phase distribution transformers
and corresponding nominal full-load current values B18
4.7 choice of power-supply sources
B19C. HV/LV distribution substations
1. supply of power at high voltage
C11.1 power-supply characteristics of high voltage distribution networks
C1table C1
relating nominal system voltages with corresponding rated system voltages
(r.m.s. values) C2
table C2
switchgear rated insulation levels C3
table C3A
transformers rated insulation levels in series I (based on current practice other than
in the United States of America and some other countries) C3
table C3B
transformers rated insulation levels in series II (based on current practice in the United
States of America and some other countries) C4
table C4
standard short-circuit current-breaking ratings extracted from table X IEC 56 C4
1.2 different HV service connections
C111.3 some operational aspects of HV distribution networks
C132. consumers HV substations
C152.1 procedures for the establishment of a new substation
C153. substation protection schemes
C173.1 protection against electric shocks and overvoltages
C173.2 electrical protection
C22table C18
power limits of transformers with a maximum primary current not exceeding 45 A C25 table C19
rated current (A) of HV fuses for transformer protection according to IEC 282-1 C26 table C20
3-phase short-circuit currents of typical distribution transformers C27
3.3 protection against thermal effects
C313.4 interlocks and conditioned manœuvres
C314. the consumer substation with LV metering
C344.1 general
C344.2 choice of panels
C36table C27
standard short-circuit MVA and current ratings at different levels of nominal voltage C37
4.3 choice of HV switchgear panel for a transformer circuit
C384.4 choice of HV/LV transformer
C38table C31
categories of dielectric fluids C41
table C32
safety measures recommended in electrical installations using dielectric liquids
of classes 01, K1, K2 or K3 C42
5. a consumer substation with HV metering
C445.1 general
C445.2 choice of panels
C46D. low-voltage service connections
1. low-voltage public distribution networks
D11.1 low-voltage consumers
D1table D1
survey of electricity supplies in various countries around the world. D1 table D2 D6
1.2 LV distribution networks
D71.3 the consumer-service connection
D101.4 quality of supply voltage
D132. tariffs and metering
D14E. power factor improvement and harmonic filtering
1. power factor improvement
E11.1 the nature of reactive energy
E11.2 plant and appliances requiring reactive current
E21.3 the power factor
E21.4 tan
ϕ
E31.5 practical measurement of power factor
E41.6 practical values of power factor
E4table E5
example in the calculation of active and reactive power E4
table E7
values of cos ϕ and tan ϕ for commonly-used plant and equipment E4
2. why improve the power factor?
E52.1 reduction in the cost of electricity
E52.2 technical/economic optimization
E5table E8
multiplying factor for cable size as a function of cos ϕ E5
3. how to improve the power factor
E63.1 theoretical principles
E63.2 by using what equipment?
E73.3 the choice between a fixed or automatically-regulated bank
of capacitors
E84. where to install correction capacitors
E94.1 global compensation
E94.2 compensation by sector
E94.3 individual compensation
E107.1 transfert current and take-over current
7.2 types of faults involved in the transfer region
App C1-3
8. appendix 2␣ : ground-surface potential gradients
due to earth-fault currents
App C2-19. appendix 3␣ : vector diagram of ferro-resonance
A
E. power factor improvement and harmonic filtering
(continued)5. how to decide the optimum level of compensation
E115.1 general method
E115.2 simplified method
E11table E17
kvar to be installed per kW of load, to improve the power factor of an installation E12
5.3 method based on the avoidance of tariff penalties
E135.4 method based on reduction of declared maximum apparent
power (kVA)
E136. compensation at the terminals of a transformer
E146.1 compensation to increase the available active power output
E14table E20
active-power capability of fully-loaded transformers, when supplying loads at different
values of power factor E14
6.2 compensation of reactive energy absorbed by the transformer
E15table E24
reactive power consumption of distribution transformers with 20 kV primary windings E16
7. compensation at the terminals of an induction motor
E177.1 connection of a capacitor bank and protection settings
E17table E26
reduction factor for overcurrent protection after compensation E17
7.2 how self-excitation of an induction motor can be avoided
E18table E28
maximum kvar of P.F. correction applicable to motor terminals without risk
of self-excitation E19
8. example of an installation before and after
power-factor correction
E209. the effect of harmonics on the rating of a capacitor
bank
E219.1 problems arising from power-system harmonics
E219.2 possible solutions
E219.3 choosing the optimum solution
E22table E30
choice of solutions for limiting harmonics associated with a LV capacitor bank E22
9.4 possible effects of power-factor-correction capacitors
on the power-supply system
E2310. implementation of capacitor banks
E2410.1 capacitor elements
E2410.2 choice of protection, control devices, and connecting cables
E2511. appendix 1␣ : elementary harmonic filters
App E3-112. appendix 2␣ : harmonic suppression reactor
for a single (power factor correction)
capacitor bank
App E4-1F. distribution within a low-voltage installation
1. general
F1assumed levels of transient overvoltage possible at different points of a typical
installation F8
table F12
typical levels of impulse withstand voltage of industrial circuit breakers labelled
Uimp = 8 kV F8
table F18
compatibility levels for installation materials F13
3. safety and emergency-services installations,
and standby power supplies
F153.1 safety installations
F153.2 standby reserve-power supplies
F153.3 choice and characteristics of reserve-power supplies
F16table F21
table showing the choice of reserve-power supply types according to application
requirements and acceptable supply-interruption times F16
3.4 choice and characteristics of different sources
F17table F22
table of characteristics of different sources F17
3.5 local generating sets
F184. earthing schemes
F194.1 earthing connections
F19table F25
list of exposed-conductive-parts and extraneous-conductive-parts F20
4.2 definition of standardized earthing schemes
F214.3 earthing schemes characteristics
F234.4.1 choice criteria
F294.4.2 comparison for each criterion
F304.5 choice of earthing method - implementation
F314.6 installation and measurements of earth electrodes
F32table F47
resistivity (Ω-m) for different kinds of terrain F33
table F48
mean values of resistivity (Ω-m) for an approximate estimation of an earth-electrode
resistance with respect to zero-potential earth F33
5. distribution boards
F365.1 types of distribution board
F365.2 the technologies of functional distribution boards
F375.3 standards
F385.4 centralized control
F386. distributors
F396.1 description and choice
F396.2 conduits, conductors and cables
F41table F60
selection of wiring systems F41
table F61
erection of wiring systems F41
table F62
some examples of installation methods F43
table F63
designation code for conduits according to the most recent IEC publications F44 table F64
designation of conductors and cables according to CENELEC code for harmonized
cables F45
table F66
A
F. distribution within a low-voltage installation
(continued)7. external influences
F477.1 classification
F47table F67
concise list of important external influences (taken from Appendix A of IEC 364-3) F48
7.2 protection by enclosures: IP code
F49G. protection against electric shocks
1. general
G11.1 electric shock
G11.2 direct and indirect contact
G12. protection against direct contact
G22.1 measures of protection against direct contact
G22.2 additional measure of protection against direct contact
G33. protection against indirect contact
G43.1 measure of protection by automatic disconnection of the supply
G4table G8
maximum safe duration of the assumed values of touch voltage in conditions where
UL = 50 V G4
table G9
maximum safe duration of the assumed values of touch voltage in conditions where
UL = 25 V G4
3.2 automatic disconnection for a TT-earthed installation
G5table G11
maximum operating times of RCCBs (IEC 1008) G6
3.3 automatic disconnection for a TN-earthed installation
G6table G13
maximum disconnection times specified for TN earthing schemes (IEC 364-4-41) G7
3.4 automatic disconnection on a second earth fault in an IT-earthed
system
G8table G18
maximum disconnection times specified for an IT-earthed installation (IEC 364-4-41) G9
3.5 measures of protection against direct or indirect contact
without circuit disconnection
G104. implementation of the TT system
G134.1 protective measures
G13table G26
the upper limit of resistance for an installation earthing electrode which must not be
exceeded, for given sensitivity levels of RCDs at UL voltage limits of 50 V and 25 V G13
4.2 types of RCD
G144.3 coordination of differential protective devices
G155. implementation of the TN system
G185.1 preliminary conditions
G185.2 protection against indirect contact
G18table G42
correction factor to apply to the lengths given in tables G43 to G46 for TN systems G20 table G43
maximum circuit lengths for different sizes of conductor and
instantaneous-tripping-current settings for general-purpose circuit breakers G20 table G44
maximum circuit lengths for different sizes of conductor and rated currents for type B
circuit breakers G20
table G45
maximum circuit lengths for different conductor sizes and for rated currents of circuit
breakers of type C G21
6.2 protection against indirect contact
G25table G59
correction factors, for IT-earthed systems, to apply to the circuit lengths given
in tables G43 to G46 G28
6.3 high-sensitivity RCDs
G296.4 in areas of high fire-risk
G296.5 when the fault-current-loop impedance is particularly high
G307. residual current differential devices (RCDs)
G317.1 description
G317.2 application of RCDs
G31table G70
electromagnetic compatibility withstand-level tests for RCDs G32 table G72
means of reducing the ratio I∆n/lph (max.) G33
7.3 choice of characteristics of a residual-current circuit breaker
(RCCB - IEC 1008)
G34table G74
typical manufacturers coordination table for RCCBs, circuit breakers, and fuses G34
H. the protection of circuits and the switchgear
H1. the protection of circuits
1. general
H1-11.1 methodology and definitions
H1-1table H1-1
logigram for the selection of cable size and protective-device rating for a given circuit H1-1
1.2 overcurrent protection principles
H1-31.3 practical values for a protection scheme
H1-41.4 location of protective devices
H1-5table H1-7
general rules and exceptions concerning the location of protective devices H1-5
1.5 cables in parallel
H1-51.6 worked example of cable calculations
H1-6table H1-9
calculations carried out with ECODIAL software (Merlin Gerin) H1-8 table H1-10
example of short-circuit current evaluation H1-9
2. practical method for determining the smallest
allowable cross-sectional-area of circuit conductors
H1-102.1 general
H1-10table H1-11
logigram for the determination of minimum conductor size for a circuit H1-10
2.2 determination of conductor size for unburied circuits
H1-10table H1-12
code-letter reference, depending on type of conductor and method of installation H1-10 table H1-13
factor K1 according to method of circuit installation (for further examples refer
to IEC 364-5-52 table 52H) H1-11
table H1-14
correction factor K2 for a group of conductors in a single layer H1-11 table H1-15
correction factor K3 for ambient temperature other than 30 °C H1-12 table H1-17
case of an unburied circuit: determination of the minimum cable size (c.s.a.), derived
A
H. the protection of circuits and the switchgear
(continued)H1. the protection of circuits
(continued)2. practical method for determining the smallest
allowable cross-sectional-area of circuit conductors
(continued)2.3 determination of conductor size for buried circuits
H1-14table H1-19
correction factor K4 related to the method of installation H1-14 table H1-20
correction factor K5 for the grouping of several circuits in one layer H1-14 table H1-21
correction factor K6 for the nature of the soil H1-15
table H1-22
correction factor K7 for soil temperatures different than 20 °C H1-15 table H1-24
case of a buried circuit: minimum c.s.a. in terms of type of conductor; type of insulation;
and value of fictitious current I'z (I'z = Iz) H1-15
K
3. determination of voltage drop
H1-173.1 maximum voltage-drop limit
H1-17table H1-26
maximum voltage-drop limits H1-17
3.2 calculation of voltage drops in steady load conditions
H1-18table H1-28
voltage-drop formulae H1-18
table H1-29
phase-to-phase voltage drop ∆U for a circuit, in volts per ampere per km H1-18
4. short-circuit current calculations
H1-204.1 short-circuit current at the secondary terminals of a HV/LV
distribution transformer
H1-20table H1-32
typical values of Usc for different kVA ratings of transformers with HV windings i 20 kV H1-20 table H1-33
Isc at the LV terminals of 3-phase HV/LV transformers supplied from a HV system
with a 3-phase fault level of 500 MVA, or 250 MVA H1-20
4.2 3-phase short-circuit current (Isc) at any point within
a LV installation
H1-21table H1-36
the impedance of the HV network referred to the LV side of the HV/LV transformer H1-21 table H1-37
resistance, reactance and impedance values for typical distribution transformers
with HV windings i 20 kV H1-22
table H1-38
recapitulation table of impedances for different parts of a power-supply system H1-23 table H1-39
example of short-circuit current calculations for a LV installation supplied at 400 V
(nominal) from a 1,000 kVA HV/LV transformer H1-23
4.3 Isc at the receiving end of a feeder in terms of the Isc
at its sending end
H1-23table H1-40
Isc at a point downstream, in terms of a known upstream fault-current value
and the length and c.s.a. of the intervening conductors, in a 230/400 V 3-phase system H1-24
4.4 short-circuit current supplied by an alternator or an inverter
H1-255. particular cases of short-circuit current
H1-265.1 calculation of minimum levels of short-circuit current
H1-26table H1-49
maximum circuit lengths in metres for copper conductors (for aluminium, the lengths
must be multiplied by 0.62) H1-28
table H1-50
maximum length of copper-conductored circuits in metres protected by B-type
circuit breakers H1-29
6. protective earthing conductors (PE)
H1-326.1 connection and choice
H1-32table H1-59
choice of protective conductors (PE) H1-33
6.2 conductor dimensioning
H1-33table H1-60
minimum c.s.a.'s for PE conductors and earthing conductors
(to the installation earth electrode) H1-34
table H1-61
k factor values for LV PE conductors, commonly used in national standards
and complying with IEC 724 H1-34
6.3 protective conductor between the HV/LV transformer
and the main general distribution board (MGDB)
H1-35table H1-63
c.s.a. of PE conductor between the HV/LV transformer and the MGDB, in terms of transformer
ratings and fault-clearance times used in France H1-35
6.4 equipotential conductor
H1-357. the neutral conductor
H1-367.1 dimensioning the neutral conductor
H1-367.2 protection of the neutral conductor
H1-36table H1-65
table of protection schemes for neutral conductors in different earthing systems H1-37
H2. the switchgear
1. the basic functions of LV switchgear
H2-1table H2-1
basic functions of LV switchgear H2-1
1.1 electrical protection
H2-11.2 isolation
H2-1table H2-2
peak value of impulse voltage according to normal service voltage of test specimen H2-2
1.3 switchgear control
H2-22. the switchgear and fusegear
H2-42.1 elementary switching devices
H2-4table H2-7
utilization categories of LV a.c. switches according to IEC 947-3 H2-5 table H2-8
factor "n" used for peak-to-rms value (IEC 947-part 1) H2-5 table H2-13
zones of fusing and non-fusing for LV types gG and gM class fuses
(IEC 269-1 and 269-2-1) H2-7
2.2 combined switchgear elements
H2-93. choice of switchgear
H2-113.1 tabulated functional capabilities
H2-11table H2-19
functions fulfilled by different items of switchgear H2-11
A
H2. the switchgear
(continued)4. circuit breakers
H2-12table H2-20
functions performed by a circuit breaker/disconnector H2-12
4.1 standards and descriptions
H2-124.2 fundamental characteristics of a circuit breaker
H2-15table H2-28
tripping-current ranges of overload and short-circuit protective devices
for LV circuit breakers H2-16
table H2-31
Icu related to power factor (cos ϕ) of fault-current circuit (IEC 947-2) H2-17
4.3 other characteristics of a circuit breaker
H2-18table H2-34
relation between rated breaking capacity Icu and rated making capacity Icm at different power-factor values of short-circuit current, as standardized in IEC 947-2 H2-19
4.4 selection of a circuit breaker
H2-20table H2-38
examples of tables for the determination of derating/uprating factors to apply to CBs
with uncompensated thermal tripping units, according to temperature H2-21 table H2-40
different tripping units, instantaneous or short-time delayed H2-23 table H2-43
maximum values of short-circuit current to be interrupted by main and principal
circuit breakers (CBM and CBP respectively), for several transformers in parallel H2-25
4.5 coordination between circuit breakers
H2-27table H2-45
example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation H2-28 table H2-49
summary of methods and components used in order to achieve discriminative tripping H2-29
4.6 discrimination HV/LV in a consumer's substation
H2-32J. particular supply sources and loads
1. protection of circuits supplied by an alternator
J11.1 an alternator on short-circuit
J11.2 protection of essential services circuits supplied in emergencies
from an alternator
J41.3 choice of tripping units
J51.4 methods of approximate calculation
J6table J1-7
procedure for the calculation of 3-phase short-circuit current J6 table J1-8
procedure for the calculation of 1-phase to neutral short-circuit current J7
1.5 the protection of standby and mobile a.c. generating sets
J92. inverters and UPS
(Uninterruptible Power Supply units)
J102.1 what is an inverter?
J102.2 types of UPS system
J10table J2-4
examples of different possibilities and applications of inverters, in decontamination of supplies
and in UPS schemes J11
2.3 standards
J112.4 choice of a UPS system
J122.5 UPS systems and their environment
J14currents and c.s.a. of copper-cored cables feeding the rectifier, and supplying the load
for UPS system Maxipac (cable lengths < 100 m) J21
table J2-23
currents and c.s.a. of copper-cored cables feeding the rectifier, and supplying the load for UPS system EPS 2000 (cable lengths < 100 m). Battery cable data are also included J21 table J2-24
input, output and battery currents for UPS system EPS 5000 (Merlin Gerin) J22
2.9 choice of protection schemes
J232.10 complementary equipments
J243. protection of LV/LV transformers
J253.1
transformer-energizing in-rush current
J253.2 protection for the supply circuit of a LV/LV transformer
J253.3 typical electrical characteristics of LV/LV 50 Hz transformers
J26table J3-5
typical electrical characteristics of LV/LV 50 Hz transformers J26
3.4 protection of transformers with characteristics as tabled in J3-5
above, using Merlin Gerin circuit breakers
J26table J3-6
protection of 3-phase LV/LV transformers with 400 V primary windings J26 table J3-7
protection of 3-phase LV/LV transformers with 230 V primary windings J27 table J3-8
protection of 1-phase LV/LV transformers with 400 V primary windings J27 table J3-9
protection of 1-phase LV/LV transformers with 230 V primary windings J28
4. lighting circuits
J294.1 service continuity
J294.2 lamps and accessories (luminaires)
J30table J4-1
analysis of disturbances in fluorescent-lighting circuits J30
4.3 the circuit and its protection
J314.4 determination of the rated current of the circuit breaker
J31table J4-2
protective circuit breaker ratings for incandescent lamps and resistive-type heating
circuits J31
table J4-3
maximum limit of rated current per outgoing lighting circuit, for high-pressure discharge
lamps J32
table J4-4
current ratings of circuit breakers related to the number of fluorescent luminaires to be
protected J32
4.5 choice of control-switching devices
J33table J4-5
types of remote control J33
4.6 protection of ELV lighting circuits
J344.7 supply sources for emergency lighting
J355. asynchronous motors
J365.1 protective and control functions required
J36table J5-2
commonly-used types of LV motor-supply circuits J37
5.2 standards
J385.3 basic protection schemes: circuit breaker / contactor / thermal relay
J38table J5-4
A
J. particular supply sources and loads
(continued)5. asynchronous motors
(continued)5.5 maximum rating of motors installed for consumers supplied at LV
J43table J5-12
maximum permitted values of starting current for direct-on-line LV motors (230/400 V) J43 table J5-13
maximum permitted power ratings for LV direct-on-line-starting motors J43
5.6 reactive-energy compensation (power-factor correction)
J436. protection of direct-current installations
J446.1 short-circuit currents
J446.2 characteristics of faults due to insulation failure, and of protective
switchgear
J45table J6-4
characteristics of protective switchgear according to type of d.c. system earthing J45
6.3 choice of protective device
J45table J6-5
choice of d.c. circuit breakers manufactured by Merlin Gerin J46
6.4 examples
J466.5 protection of persons
J477. Appendix␣ : Short-circuit characteristics
of an alternator
App J1-1
L. domestic and similar premises and special locations
1. domestic and similar premises
L11.1 general
L11.2 distribution-board components
L21.3 protection of persons
L41.4 circuits
L6table L1-9
recommended minimum number of lighting and power points in domestic premises L6 table L1-11
c.s.a. of conductors and current rating of the protective devices in domestic
installations (the c.s.a. of aluminium conductors are shown in brackets) L7
2. bathrooms and showers
L82.1 classification of zones
L82.2 equipotential bonding
L102.3 requirements prescribed for each zone
L103. recommendations applicable to special installations
the study of an electrical installation
by means of this guide requires the
reading of the entire text in the order
in which the chapters are presented.
listing of power demands
The study of a proposed electrical installation necessitates an adequate understanding of all governing rules and regulations. A knowledge of the operating modes of power-consuming appliances, i.e. "loads" (steady-state demand, starting conditions, non-simultaneous operation, etc.) together with the location and magnitude of each load shown on a building plan, allow a listing of power demands to be compiled. The list will include the total power of the loads installed as well as an estimation of the actual loads to be supplied, as deduced from the operating modes.
From these data the power required from the supply source and (where appropriate) the number of sources necessary for an adequate supply to the installation, are readily obtained.
Local information regarding tariff structures is also required to permit the best choice of connection arrangement to the power-supply network, e.g. at high voltage or low voltage.
corresponding chapter
B - general - installed power
service connection
This connection can be made at: c High Voltage:
a consumer-type substation will then have to be studied, built and equipped. This substation may be an outdoor or indoor installation conforming to relevant standards and regulations (the low-voltage section may be studied separately if necessary). Metering at high-voltage or low-voltage is possible in this case
c Low Voltage:
the installation will be connected to the local power network and will (necessarily) be metered according to LV tariffs.
C - HV/LV distribution substations
D - low-voltage service connections
reactive energy
The compensation of reactive energy within electrical installations normally concerns only power factor improvement, and is carried out locally, globally or as a combination of both methods.
E - power factor improvement
LV distribution
The whole of the installation distribution network is studied as a complete system. The number and characteristics of standby emergency-supply sources are defined. Earth-bonding connections and neutral-earthing arrangements are chosen according to local regulations, constraints related to the power-supply, and to the nature of the installation loads.
The hardware components of distribution, together with distribution boards and cableways, are determined from building plans and from the location and grouping of loads.
The kinds of location, and activities practised in them, can affect their level of resistance to external influences.
F - distribution within a low-voltage installation
protection against electric shock
The system of earthing (TT, IT or TN) having been previously determined, it remains, in order to achieve protection of persons against the hazards of direct and indirect contact, to choose an appropriate scheme of protection.
B
circuits and switchgear
Each circuit is then studied in detail.
From the rated currents of the loads; the level of short-circuit current; and the type of protective device, the cross-sectional area of circuit conductors can be determined, taking into account the nature of the cableways and their influence on the current rating of conductors.
Before adopting the conductor size indicated above, the following requirements must be satisfied:
c the voltage drop complies with the relevant standard,
c motor starting is satisfactory,
c protection against electric shock is assured. The short-circuit current Isc is then
determined, and the Isc thermal and electro-dynamic withstand capability of the circuit is checked.
These calculations may indicate that a different conductor size than that originally chosen is necessary.
The performance required by the switchgear will determine its type and characteristics. The use of cascading techniques and the discriminative operation of fuses and tripping of circuit breakers are examined.
H1 - the protection of circuits
H2 - the switchgear
particular supply sources
and loads
Particular items of plant and equipment are studied:
c specific sources such as alternators or inverters,
c specific loads with special characteristics, such as induction motors, lighting circuits or LV/LV transformers, or
c specific systems, such as direct-current networks.
J - particular supply sources and loads
domestic and similar premises
and special locations
Certain premises and locations are subject to particularly strict regulations: the most common example being domestic dwellings.
L - domestic and similar premises and special locations
Ecodial 2.2 software
Ecodial 2.2 software* provides a complete conception and design package for LV installations, in accordance with IEC standards and recommendations.
The following features are included: c construction of one-line diagrams, c calculation of short-circuit currents, c calculation of voltage drops, c optimization of cable sizes,
c required ratings of switchgear and fusegear, c discrimination of protective devices, c recommendations for cascading schemes, c verification of the protection of persons,
c comprehensive print-out of the foregoing calculated design data.
three phase, four wire or three wire systems single phase, three wire systems nominal voltage (V) nominal voltage (V)
- 120/240
230/400(1)
-277/480(2)
-400/690(1)
-1000
-Low-voltage installations are governed by a number of regulatory and advisory texts, which may be classified as follows:
c statutory regulations (decrees, factory acts, etc.),
c codes of practice, regulations issued by professional institutions, job specifications, c national and international standards for installations,
c national and international standards for products.
2.1 definition of voltage ranges
IEC voltage standards and
recommendations
table B1: standard voltages between 100 V and 1000 V (IEC 38-1983).
1) The nominal voltage of existing 220/380 V and 240/415 V systems shall evolve towards the recommended value of 230/400 V. The transition period should be as short as possible, and should not exceed 20 years after the issue of this IEC publication. During this period, as a first step, the electricity supply authorities of countries having 220/380 V systems should bring the voltage within the range 230/400 V +6% -10% and those of countries having 240/415 V systems should bring the voltage within the range 230/400 V +10% -6%. At the end of this transition period the tolerance of 230/400 V ±10% should have been achieved; after this the reduction of this range will be considered. All the above considerations apply also to the present 380/660 V value with respect to the recommended value 400/690 V.
2) Not to be utilized together with 230/400 V or 400/690 V.
50 Hz and 60 Hz systems 60 Hz systems
series I series II (North American practice) highest voltage nominal system highest voltage nominal system for equipment (kV) voltage (kV) for equipment (kV) voltage (kV)
3.6(1) 3.3(1) 3((1) 4.40(1) 4.16(1) 7.2(1) 6.6(1) 6(1) - -12 11 10 - -- - - 13.2(2) 12.47(2) - - - 13.97(2) 13.2(2) - - - 14.52(1) 13.8(1) (17.5) - (15) - -24 22 20 - -- - - 26.4(2) 24.94(2) 36(3) 33(3) - - -- - - 36.5(2) 34.5(2) 40.5(3) - 35(3) -
-table B2: standard voltages above 1 kV and not exceeding 35 kV (IEC 38-1983).
* These systems are generally three-wire systems unless otherwise indicated. The values indicated are voltages between phases.
The values indicated in parentheses should be considered as non-preferred values. It is recommended that these values should not be used for new systems to be constructed in future.
1) These values should not be used for public distribution systems. 2) These systems are generally four-wire systems.
B
2.2 regulations
In most countries, electrical installations shall comply with more than one set of regulations, issued by National Authorities or by
recognised private bodies. It is essential to take into account these local constraints before starting the design.
2.3 standards
This Guide is based on relevant IEC standards, in particular IEC 364. IEC 364 has been established by medical and engineering experts of all countries in the world
comparing their experience at an international level. Currently, the safety principles of IEC 364 and 479-1 are the fundamentals of most electrical standards in the world. IEC - 38 Standard voltages
IEC - 56 High-voltage alternating-current circuit breakers IEC - 76-2 Power transformer - Part 2: Temperature rise
IEC - 76-3 Power transformer - Part 3: Insulation levels and dielectric tests IEC - 129 Alternating current disconnectors and earthing switches IEC - 146 General requirements and line commutated converters
IEC - 146-4 General requirements and line commutated converters - Part 4: Method of specifying the performance and test requirements of uninterruptible power systems
IEC - 265-1 High-voltage switches - Part 1: High-voltage switches for rated voltages above 1 kV and less than 52 kV
IEC - 269-1 Low-voltage fuses - Part 1: General requirements
IEC - 269-3 Low-voltage fuses - Part 3: Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household and similar applications) IEC - 282-1 High-voltage fuses - Part 1: Current limiting fuses
IEC - 287 Calculation of the continuous current rating of cables (100% load factor) IEC - 298 AC metal-enclosed switchgear and controlgear for rated voltages above 1kV
and up to and including 52 kV IEC - 364 Electrical installations of buildings
IEC - 364-3 Electrical installations of buildings - Part 3: Assessment of general characteristics
IEC - 364-4-41 Electrical installations of buildings - Part 4: Protection of safety - Section 41: Protection against electrical shock
IEC - 364-4-42 Electrical installations of buildings - Part 4: Protection of safety - Section 42: Protection against thermal effects
IEC - 364-4-43 Electrical installations of buildings - Part 4: Protection of safety - Section 43: Protection against overcurrent
IEC - 364-4-47 Electrical installations of buildings - Part 4: Application of protective measures for safety - Section 47: Measures of protection against electrical shock IEC - 364-5-51 Electrical installations of buildings - Part 5: Selection and erection of electrical
equipment - Section 51: Common rules
IEC - 364-5-52 Electrical installations of buildings - Part 5: Selection and erection of electrical equipment - Section 52: Wiring systems
IEC - 364-5-53 Electrical installations of buildings - Part 5: Selection and erection of electrical equipment - Section 53: Switchgear and controlgear
IEC - 364-6 Electrical installations of buildings - Part 6: Verification
IEC - 364-7-701 Electrical installations of buildings - Part 7: Requirements for special installations or locations - Section 701: Electrical installations in bathrooms IEC - 364-7-706 Electrical installations of buildings - Part 7: Requirements for special
installations or locations - Section 706: Restrictive conductive locations IEC - 364-7-710 Electrical installations of buildings - Part 7: Requirements for special
installations or locations - Section 710: Installation in exhibitions, shows, stands and funfairs
IEC - 420 High-voltage alternating current switch-fuse combinations
IEC - 439-1 Low-voltage switchgear and controlgear assemblies - Part 1: Types-tested and partially type-tested assemblies
IEC - 439-2 Low-voltage switchgear and controlgear assemblies - Part 2: Particular requirements for busbar trunking systems (busways)
IEC - 439-3 Low-voltage switchgear and controlgear assemblies - Part 3: Particular requirements for low-voltage switchgear and controlgear assemblies intended to be installed in places where unskilled persons have access for their use -Distribution boards
2.4 quality and safety of an electrical installation
Only by
c the initial checking of the conformity of the electrical installation,
c the verification of the conformity of electrical equipment,
c and periodic checking
can the permanent safety of persons and security of supply to equipment be achieved.
IEC - 787 Application guide for selection for fuse-links of high-voltage fuses for transformer circuit application
IEC - 831-1 Shunt power capacitors of the self-healing type for a.c. systems having a rated voltage up to and including 660 V. - Part 1: General - Performance, testing and rating - Safety requirements - Guide for installation and operation
B
2.6 periodic check-testing of an installation
In many countries, all industrial and commercial-building installations, together with installations in buildings used for public gatherings, must be re-tested periodically by authorized agents.
Table B3 shows the frequency of testing commonly prescribed according to the kind of installation concerned.
installations which require c locations at which a risk of degradation, annually
the protection of employees fire or explosion exists
c temporary installations at worksites c locations at which HV installations exist c restrictive conducting locations where mobile equipment is used
other cases every 3 years
installations in buildings according to the type of establishment
used for public gatherings, and its capacity for receiving the public,
2.5 initial testing of an installation
Before a power-supply authority will connect an installation to its supply network, strict pre-commissioning electrical tests and visual inspections by the authority, or by its appointed agent, must be satisfied. These tests are made according to local (governmental and/or institutional)
regulations, which may differ slightly from one country to another. The principles of all such regulations however, are common, and are based on the observance of rigorous safety rules in the design and realization of the installation.
IEC 364 and related standards included in this guide are based on an international consensus for such tests, intended to cover all the safety measures and approved installation practices normally required for domestic, commercial and (the majority of) industrial buildings. Many industries however have additional regulations related to a particular product (petroleum, coal, natural gas, etc.). Such additional requirements are beyond the scope of this guide.
The pre-commissioning electrical tests and visual-inspection checks for installations in buildings include, typically, all of the following: c insulation tests of all cable and wiring conductors of the fixed installation, between phases and between phases and earth, c continuity and conductivity tests of protective, equipotential and earth-bonding conductors,
c resistance tests of earthing electrodes with respect to remote earth,
c allowable number of socket-outlets per circuit check,
c cross-sectional-area check of all conductors for adequacy at the short-circuit levels prevailing, taking account of the associated protective devices, materials and installation conditions (in air, conduit, etc.), c verification that all exposed- and extraneous metallic parts are properly earthed (where appropriate),
c check of clearance distances in bathrooms, etc.
These tests and checks are basic (but not exhaustive) to the majority of installations, while numerous other tests and rules are included in the regulations to cover particular cases, for example: TN-, TT- or IT-earthed installations, installations based on class 2 insulation, SELV circuits, and special locations, etc.
The aim of this guide is to draw attention to the particular features of different types of installation, and to indicate the essential rules to be observed in order to achieve a satisfactory level of quality, which will ensure safe and trouble-free performance. The methods recommended in this guide, modified if necessary to comply with any possible variation imposed by a local supply authority, are intended to satisfy all pre-commissioning test and inspection requirements.
c
the standards organization concerned, or c by a certificate of conformity issued by a laboratory, or
c by a declaration of conformity from the manufacturer.
declaration of conformity
In cases where the equipment in question is to be used by qualified or experienced persons, the declaration of conformity provided by the manufacturer (included in the technical documentation) together with a conformity mark on the equipment concerned, are generally recognized as a valid attestation. Where the competence of the manufacturer is in doubt, a certificate of conformity can be obtained from an independent accredited laboratory.
mark of conformity
Conformity marks are inscribed on appliances and equipment which are generally used by technically inexperienced persons (for example, domestic appliances) and for whom the standards have been established which permit the attribution, by the standardization authority, of a mark of conformity (commonly referred to as a conformity mark).
certification of Quality
Assurance
A laboratory for testing samples cannot certify the conformity of an entire production run: these tests are called type tests. In some tests for conformity to standards, the samples are destroyed (tests on fuses, for example). Only the manufacturer can certify that the fabricated products have, in fact, the characteristics stated.
Quality assurance certification is intended to complete the initial declaration or certification of conformity.
As proof that all the necessary measures have been taken for assuring the quality of production, the manufacturer obtains certification of the quality control system which monitors the fabrication of the product concerned. These certificates are issued by organizations specializing in quality control, and are based on the international standard ISO 9000, the equivalent European standard being EN 29000.
These standards define three model systems of quality assurance control corresponding to different situations rather than to different levels of quality:
c model 3 defines assurance of quality by inspection and checking of final products, c model 2 includes, in addition to checking of the final product, verification of the
manufacturing process. This method applies, for example, to the manufacture of fuses where performance characteristics cannot be checked without destroying the fuse, c model 1 corresponds to model 2, but with the additional requirement that the quality of the design process must be rigorously scrutinized; for example, where it is not intended to fabricate and test a prototype
the standards define several
methods of quality assurance which
correspond to different situations
rather than to different levels of
quality.
B
current demand
The full-load current Ia supplied to the motor is given by the following formulae:
3-phase motor: Ia = Pn x 1,000 ex U x η x cos ϕ 1-phase motor: Ia = Pn x 1,000 U x η x cos ϕ where
Ia: current demand (in amps)
Pn: nominal power (in kW of active power) U: voltage between phases for 3-phase motors and voltage between the terminals for single-phase motors (in volts). A single-phase motor may be connected phase-to-neutral or phase-to-phase.
η: per-unit efficiency, i.e. output kW input kW cos ϕ: power factor, i.e. kW input
kVA input
an examination of the actual
apparent-power demands of different
loads: a necessary preliminary step
in the design of a LV installation.
The examination of actual values of apparent-power required by each load enables the establishment of: c a declared power demand which determines the contract for the supply of energy,
c the rating of the HV/LV transformer, where applicable (allowing for expected increases in load),
c levels of load current at each distribution board.
3.1 induction motors
the nominal power in kW (Pn) of a
motor indicates its rated equivalent
mechanical power output.
The apparent power in kVA (Pa)
supplied to the motor is a function of
the output, the motor efficiency and
the power factor.
Pa = Pn
η
cos
ϕ
motor-starting current
Starting current (Id) for 3-phase induction motors, according to motor type, will be: c for direct-on-line starting of squirrel-cage motors:
v Id = 4.2 to 9 In for 2-pole motors v Id = 4.2 to 7 In for motors with more than 2 poles (mean value = 6 In), where In = nominal full-load current of the motor, c for wound-rotor motors (with slip-rings), and for D.C. motors:
Id depends on the value of starting resistances in the rotor circuits: Id = 1.5 to 3 In (mean value = 2.5 In). c for induction motors controlled by speed-changing variable-frequency devices (for example: Altivar Telemecanique), assume that the control device has the effect of increasing the power (kW) supplied to the circuit motor (i.e. device plus) by 10%.
compensation of reactive-power
(kvar) supplied to induction
motors
The application of this principle to the operation of induction motors is generally referred to as "power-factor improvement" or "power-factor correction".
As discussed in chapter E, the apparent-power (kVA) supplied to an induction motor can be significantly reduced by the use of shunt-connected capacitors.
Reduction of input kVA means a corresponding reduction of input current (since the voltage remains constant). Compensation of reactive-power is particularly advised for motors that operate for long periods at reduced power.
it is generally advantageous for
technical and financial reasons to
reduce the current supplied to
induction motors. This can be
achieved by using capacitors without
affecting the power output of the
motors.
As noted above cos ϕ = kW input so that a kVA input
reduction in kVA input will increase (i.e. improve) the value of cos ϕ.
The current supplied to the motor, after power-factor correction, is given by: Ia x cos ϕ
cos ϕ'
where cos ϕ is the power factor before compensation and cos ϕ' is the power factor after compensation, Ia being the original current.
table of typical values
Table B4 shows, as a function of the rated nominal power of motors, the current supplied to them at different voltage levels
Note: the rated voltages of certain loads
listed in table B4 are still based on 220/380 V. The international standard is now (since
kW HP % 0.37 0.5 64 0.55 0.75 68 0.75 1 72 1.1 1.5 75 1.5 2 78 2.2 3 79 3 4 81 3.7 5 82 4 5.5 82 5.5 7.5 84 7.5 10 85 9 12 86 10 13.5 86 11 15 87 15 20 88 18.5 25 89 22 30 89 25 35 89 30 40 89 33 45 90 37 50 90 40 54 91 45 60 91 51 70 91 55 75 92 59 80 92 63 85 92 75 100 92 80 110 92 90 125 92 100 136 92 110 150 93 129 175 93 132 180 94 140 190 94 147 200 94 150 205 94 160 220 94 180 245 94 185 250 94 200 270 94 220 300 94 250 340 94 257 350 94 280 380 95 295 400 95 300 410 95 315 430 95 335 450 95 355 480 95 375 500 95 400 545 95 425 580 95 445 600 95 450 610 95 475 645 95 500 680 95 530 720 95 560 760 95 600 810 95 630 855 95 670 910 95 710 965 95 750 1020 95 800 1090 95 900 1220 95 1100 1500 95 kVA A A A A A A 0.73 0.79 3.6 1.8 1.03 0.99 0.91 0.6 0.75 1.1 4.7 2.75 1.6 1.36 1.21 0.9 0.75 1.4 6 3.5 2 1.68 1.5 1.1 0.79 1.9 8.5 4.4 2.6 2.37 2 1.5 0.80 2.4 12 6.1 3.5 3.06 2.6 2 0.80 3.5 16 8.7 5 4.42 3.8 2.8 0.80 4.6 21 11.5 6.6 5.77 5 3.8 0.80 5.6 25 13.5 7.7 7.1 5.9 4.4 0.80 6.1 26 14.5 8.5 7.9 6.5 4.9 0.83 7.9 35 20 11.5 10.4 9 6.6 0.83 10.6 47 27 15.5 13.7 12 8.9 0.85 12.3 - 32 18.5 16.9 13.9 10.6 0.85 13.7 - 35 20 17.9 15 11.5 0.86 14.7 - 39 22 20.1 18.4 14 0.86 19.8 - 52 30 26.5 23 17.3 0.86 24.2 - 64 37 32.8 28.5 21.3 0.86 28.7 - 75 44 39 33 25.4 0.86 33 - 85 52 45.3 39.4 30.3 0.86 39 - 103 60 51.5 45 34.6 0.86 43 - 113 68 58 50 39 0.86 48 - 126 72 64 55 42 0.86 51 - 134 79 67 60 44 0.86 57 - 150 85 76 65 49 0.86 65 - 170 98 83 75 57 0.86 70 - 182 105 90 80 61 0.87 74 - 195 112 97 85 66 0.87 79 - 203 117 109 89 69 0.87 94 - 240 138 125 105 82 0.87 100 - 260 147 131 112 86 0.87 112 - 295 170 146 129 98 0.87 125 - 325 188 162 143 107 0.87 136 - 356 205 178 156 118 0.87 159 - 420 242 209 184 135 0.87 161 - 425 245 215 187 140 0.87 171 - 450 260 227 200 145 0.87 180 - 472 273 236 207 152 0.87 183 - 483 280 246 210 159 0.87 196 - 520 300 256 220 170 0.87 220 - 578 333 289 254 190 0.87 226 - 595 342 295 263 200 0.88 242 - 626 370 321 281 215 0.88 266 - 700 408 353 310 235 0.88 302 - 800 460 401 360 274 0.88 311 - 826 475 412 365 280 0.88 335 - 900 510 450 400 305 0.88 353 - 948 546 473 416 320 0.88 359 - 980 565 481 420 325 0.88 377 - 990 584 505 445 337 0.88 401 - 1100 620 518 472 365 0.88 425 - 1150 636 549 500 370 0.88 449 - 1180 670 575 527 395 0.88 478 - 1250 710 611 540 410 0.88 508 - 1330 760 650 574 445 0.88 532 - 1400 790 680 595 455 0.88 538 - 1410 800 690 608 460 0.88 568 - 1490 850 730 645 485 0.88 598 - 1570 900 780 680 515 0.88 634 - 1660 950 825 720 545 0.88 670 - 1760 1000 870 760 575 0.88 718 - 1880 1090 920 830 630 0.88 754 - 1980 1100 965 850 645 0.88 801 - 2100 1200 1020 910 690 0.88 849 - - 1260 1075 960 725 0.88 897 - - 1350 1160 1020 770 0.88 957 - - 1450 1250 1100 830 0.88 1076 - - 1610 1390 1220 925 0.88 1316 - - 1980 1700 1500 1140 kvar kVA A A A A A A 0.93 0.31 0.62 2.8 1.4 0.8 0.77 0.71 0.47 0.93 0.39 0.87 3.8 2.2 1.3 1.1 1 0.72 0.93 0.48 1.1 4.8 2.8 1.6 1.3 1.2 0.88 0.93 0.53 1.6 7.2 3.7 2.2 2 1.7 1.3 0.93 0.67 2.1 10.3 5.2 3 2.6 2.2 1.7 0.93 0.99 3 13.7 7.5 4.3 3.8 3.3 2.4 0.93 1.31 4 18 9.9 5.7 5 4.3 3.3 0.93 1.59 4.8 22 11.6 6.6 6.1 5.1 3.8 0.93 1.74 5.2 22 12.5 7.3 6.8 5.6 4.2 0.93 1.80 7 31 17.8 10.3 9.3 8 5.9 0.93 2.44 9.5 42 24 13.8 12.2 10.7 7.9 0.93 2.4 11.3 - 29 16.9 15.4 12.7 9.7 0.93 2.6 12.5 - 32 18 16.4 13.7 10.5 0.93 2.50 13.6 - 36 20 19 17 13 0.93 3.37 18.3 - 48 28 25 21 16 0.93 4.12 22.4 - 59 34 30 26 20 0.93 4.89 26.6 - 69 41 36 31 23 0.93 5.57 30 - 79 48 42 36 28 0.93 6.68 36 - 95 55 48 42 32 0.93 7.25 39 - 104 63 54 46 36 0.93 8.12 44 - 117 67 59 51 39 0.93 8.72 47 - 124 73 62 55 41 0.93 9.71 53 - 139 79 70 60 45 0.93 11.10 60 - 157 91 77 69 53 0.93 11.89 64 - 168 97 83 74 56 0.93 10.98 69 - 182 105 91 80 62 0.93 11.66 74 - 190 109 102 83 65 0.93 13.89 88 - 225 129 117 98 77 0.93 14.92 93 - 243 138 123 105 80 0.93 16.80 105 - 276 159 137 121 92 0.93 18.69 117 - 304 176 152 134 100 0.93 20.24 127 - 333 192 167 146 110 0.93 23.84 149 - 393 226 196 172 126 0.93 24 151 - 398 229 201 175 131 0.93 25.55 160 - 421 243 212 187 136 0.93 26.75 168 - 442 255 221 194 142 0.93 27.26 172 - 452 262 230 196 149 0.93 29.15 183 - 486 281 239 206 159 0.93 32.76 206 - 541 312 270 238 178 0.93 33.79 212 - 557 320 276 246 187 0.93 30.78 229 - 592 350 304 266 203 0.93 33.81 252 - 662 386 334 293 222 0.93 38.44 286 - 757 435 379 341 259 0.93 39.45 294 - 782 449 390 345 265 0.93 42.63 317 - 852 483 426 378 289 0.93 44.80 334 - 897 517 448 394 303 0.93 45.66 339 - 927 535 455 397 306 0.93 47.98 356 - 937 553 478 421 319 0.93 51 379 - 1041 587 490 447 336 0.93 54 402 - 1088 602 519 473 350 0.93 57.1 424 - 1117 634 544 499 374 0.93 60.84 453 - 1183 672 578 511 388 0.93 64.60 481 - 1258 719 615 543 420 0.93 67.63 504 - 1325 748 643 563 431 0.93 68.50 509 - 1334 757 653 575 435 0.93 70.40 538 - 1410 804 691 610 459 0.93 72.26 566 - 1486 852 738 643 487 0.93 80.64 600 - 1571 899 781 681 516 0.93 85.12 634 - 1665 946 823 719 544 0.93 91.33 679 - 1779 1031 871 785 596 0.93 95.81 713 - 1874 1041 913 804 610 0.93 101.88 758 - 1987 1135 965 861 653 0.93 107.95 804 - - 1192 1017 908 686 0.93 114 849 - - 1277 1098 965 729 0.93 121.68 905 - - 1372 1183 1041 785 0.93 136.86 1019 - - 1523 1315 1154 875 0.93 167.35 1245 - - 1874 1609 1419 1079
B
3.2. direct-current motors
D.C. motors are mainly used for specific applications which require very high torques and/or variable speed control (for example machine tools and crushers, etc.).
Power to these motors is provided via speed-control converters, fed from 230/400 V 3-phase a.c. sources; for example, Rectivar 4 (Telemecanique).
The operating principle of the converter does not allow heavy overloading. The speed controller, the supply line and the protection are therefore based on the duty cycle of the motor (e.g. frequent starting-current peaks) rather than on the steady-state full-load current.
For powers i 40 kW, this solution is progressively replaced with a speed-changing variable-frequency device and an asynchronous motor. It is still used for gradual starters and/or retarders.
M
V power-supply network
In
Im
fig. B5: diagram of a low-power speed controller.
table B6: progressive starters with voltage ramp.
motor maximum power motor GRADIVAR catalogue number weight 220 V 380 V 415 V 440 V (60 Hz) In Ith kg kW kW kW kW A A 4 5.5 6 - 12 20 VR2-SA3171 3.30 - - - 6.5 12 20 VR2-SA3173 3.30 5.5 7.5 8 - 16 30 VR2-SA3211 5.10 - - - 8.5 16 30 VR2-SA3213 5.10 11 18.5 20 - 37 60 VR2-SA3281 5.50 - - - 21.5 37 60 VR2-SA3283 5.50 18.5 30 33 - 60 100 VR2-SA3361 5.50 - - - 35 60 100 VR2-SA3363 5.50 22 37 40 - 72 130 VR2-SA3401 5.60 - - - 42 72 130 VR2-SA3403 5.60 - 55 60 - 105 200 VR2-SA3441 11.00 - - - 63 105 200 VR2-SA3443 11.00
motor maximum power motor GRADIVAR catalogue number weight 220 V 380 V 415 V 440 V (60 Hz) In Ith kg kW kW kW kW A A 1.5 3 3.3 - 7 10 VR2-SA2121 1.95 - - - 3.5 7 10 VR2-SA2123 1.95 4 5.5 6 - 12 20 VR2-SA2171 3.10 - - - 6.5 12 20 VR2-SA2173 3.10 5.5 7.5 8 - 16 30 VR2-SA2211 4.90 - - - 8.5 16 30 VR2-SA2213 4.90 11 18.5 20 - 37 60 VR2-SA2281 5.30 - - - 21.5 37 60 VR2-SA2283 5.30 18.5 30 33 - 60 100 VR2-SA2361 5.30 - - - 35 60 100 VR2-SA2363 5.30 22 37 40 - 72 130 VR2-SA2401 5.40 - - - 42 72 130 VR2-SA2403 5.40 - 55 60 - 105 200 VR2-SA2441 10.00 - - - 63 105 200 VR2-SA2443 10.00
quoted by the manufacturer
(i.e. cos ø = 1).
the currents are given by:
c
3-phase case:
Ia = Pn*
e
x U
c
1-phase case:
Ia = Pn*
U
where U is the voltage between the
terminals of the equipment.
The currents are given by: c 3-phase case: Ia = Pn* ex U c 1-phase case: Ia = Pn* U
where U is the voltage between the terminals of the equipment.
Note: at the instant of switching on, the cold filament gives rise to a very brief but intense peak of current.
* Ia in amps; U in volts. Pn is in watts. If Pn is in kW, then multiply the equation by 1,000.
nominal current demand
power 1-phase 1-phase 3-phase 3-phase kW 127 V 230 V 230 V 400 V 0.1 0.79 0.43 0.25 0.14 0.2 1.58 0.87 0.50 0.29 0.5 3.94 2.17 1.26 0.72 1 7.9 4.35 2.51 1.44 1.5 11.8 6.52 3.77 2.17 2 15.8 8.70 5.02 2.89 2.5 19.7 10.9 6.28 3.61 3 23.6 13 7.53 4.33 3.5 27.6 15.2 8.72 5.05 4 31.5 17.4 10 5.77 4.5 35.4 19.6 11.3 6.5 5 39.4 21.7 12.6 7.22 6 47.2 26.1 15.1 8.66 7 55.1 30.4 17.6 10.1 8 63 34.8 20.1 11.5 9 71 39.1 22.6 13 10 79 43.5 25.1 14.4
table B8: current demands of resistive heating and incandescent lighting (conventional or halogen) appliances.
3.4. fluorescent lamps and related equipment
the power in watts indicated on the
tube of a fluorescent lamp does not
include the power dissipated in the
ballast.
the current is given by:
Ia =
Pballast + Pn
U x cos ø
If no power-loss value is indicated for
the ballast, a figure of 25% of Pn may
be used.
standard tubular fluorescent
lamps
The power Pn (watts) indicated on the tube of a fluorescent lamp does not include the power dissipated in the ballast.
The current taken by the complete circuit is given by:
Ia = Pballast + Pn U x cos ø
where U = the voltage applied to the lamp, complete with its related equipment. with (unless otherwise indicated): c cos ø = 0.6 with no power factor (PF) correction* capacitor,
c cos ø = 0.86 with PF correction* (single or twin tubes),
c cos ø = 0.96 for electronic ballast. If no power-loss value is indicated for the ballast, a figure of 25% of Pn may be used. Table B8 gives these values for different arrangements of ballast.
* "Power-factor correction" is often referred to as "compensation" in discharge-lighting-tube terminology.
B
arrangement of tube power current (A) at 220V/240 V tube lamps, starters power consumed PF not PF electronic length and ballasts (W) (1) (W) corrected corrected ballast (cm)
single tube with starter 18 27 0.37 0.19 60
36 45 0.43 0.24 120
58 69 0.67 0.37 150
single tube without 20 33 0.41 0.21 60
starter (2) with 40 54 0.45 0.26 120
external starting strip 65 81 0.80 0.41 150
twin tubes with starter 2 x 18 55 0.27 60
2 x 36 90 0.46 120
2 x 58 138 0.72 150
twin tubes without starter 2 x 40 108 0.49 120
single tube with 32 36 0.16 120
high frequency ballast 50 56 0.25 150
cos ø = 0.96
twin tubes with high- 2 x 32 72 0.33 120
frequency ballast 2 x 50 112 0.50 150
cos ø = 0.96
(1) Power in watts marked on tube.
(2) Used exclusively during maintenance operations.
table B10: current demands and power consumption of commonly-dimensioned fluorescent lighting tubes (at 220 V/240 V - 50 Hz).
compact fluorescent tubes
Compact fluorescent tubes have the same characteristics of economy and long life as classical tubes.
They are commonly used in public places which are permanently illuminated (for example: corridors, hallways, bars, etc.) and can be mounted in situations otherwise illuminated by incandescent lamps.
type of lamp lamp power current at power consumed 220/240 V
(W) (A)
globe lamps with 9 9 0.090
integral ballast 13 13 0.115 cos ø = 0.5 (1) 18 18 0.160 25 25 0.205 electronic lamps 9 9 0.070 cos ø = 0.95 (1) 11 11 0.090 15 15 0.135 20 20 0.155
lamps with type 5 10 0.185
starter single 7 11 0.175
only "U" form 9 13 0.170
incorporated cos ø ≈ 0.35 11 15 0.155
(no ballast) type 10 15 0.190
double 13 18 0.165
"U" form 18 23 0.220
cos ø ≈ 0.45 26 31 0.315
(1) Cos ø is approximately 0.95 (the zero values of V and I are almost in phase) but the power factor is 0.5 due to the impulsive form of the current, the peak of which occurs "late" in each half cycle.
table B11: current demands and power consumption of compact fluorescent lamps (at 220 V/240 V - 50 Hz).