• No results found

BFP Basics

N/A
N/A
Protected

Academic year: 2021

Share "BFP Basics"

Copied!
30
0
0

Loading.... (view fulltext now)

Full text

(1)



© A B B S w it z e rl a n d L td . -1 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Technology and Solutions

Protection and Substation Automation

Topic:

BREAKER

FAILURE

PROTECTION

APPLICATION

BASICS

BASICS

(2)



© A B B S w it z e rl a n d L td . -2 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Topic Objectives

r

Fault condition in a power grid

r

Protection zones

r

System behavior in case of breaker failure situation

r

BFP solutions

r

BFP application

(3)



© A B B S w it z e rl a n d L td . -3 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W B u s b a r Busbar L in e T ra n s fo rm e r G e n e ra to r -T ra n s fo rm e r BB

Fault Condition in a Power Grid

Protection zones

(4)



© A B B S w it z e rl a n d L td . -4 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W B u s b a r

Fault Condition in a Power Grid

Busbar Fault

(5)



© A B B S w it z e rl a n d L td . -5 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Fault Condition in a Power Grid

Busbar Fault

G

(6)



© A B B S w it z e rl a n d L td . -6 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Fault Condition in a Power Grid

Busbar Fault

G

- Breaker Failure

- solution

⇒ trip command to all

surrounding CBs by

a remote tripping command

a tripping command via the intertripping system

(7)



© A B B S w it z e rl a n d L td . -7 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W L in e

Fault Condition in a Power Grid

Line Fault

(8)



© A B B S w it z e rl a n d L td . -8 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Fault Condition in a Power Grid

Line Fault

G

(9)



© A B B S w it z e rl a n d L td . -9 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Fault Condition in a Power Grid

Line Fault

G

- Breaker Failure

- solution

⇒ trip command to all

surrounding CBs by

a remote tripping command

a tripping command via the intertripping system

(10)



© A B B S w it z e rl a n d L td . -1 0 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W Tra n s fo rm e r

Fault Condition in a Power Grid

Transformer or Generator - Transformer Fault

(11)



© A B B S w it z e rl a n d L td . -1 1 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Fault Condition in a Power Grid

G

(12)



© A B B S w it z e rl a n d L td . -1 2 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Transformer or Generator - Transformer Fault

Fault Condition in a Power Grid

G

- Breaker Failure

- solution

⇒ trip command to all

surrounding CBs by

a remote tripping command

a tripping command via the intertripping system

(13)



© A B B S w it z e rl a n d L td . -1 3 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

How is it possible to

detect a non operating

circuit breaker (= Circuit

Breaker Failure)

???

(14)



© A B B S w it z e rl a n d L td . -1 4 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

1.

supervision of the

feeder current (with

an overcurrent criteria)

after a tripping

command

OR

2.

supervision of the

CB auxiliary contacts

after a tripping command

OR

3.

supervision of the

feeder current (with

the BBP measurement algorithm)

after a

tripping command (only applicable if

the BFP is installed in the BBP system)

- BBP unbalancing

(15)



© A B B S w it z e rl a n d L td . -1 5 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W feeder current

t ~ higher than the highest possible CB opening time + arc extinguish time

Breaker Failure Protection Solutions

solution 1:

t2 ~120 ms re-trip to faulty CB (coil 1 & 2) trip to the surrounding CBs by • intertripping & • remote tripping CB opening coil trip to CB from protection device BFP t1 ~120 ms

&

I >

the trip from the protection device is called „Starting BFP“

(16)



© A B B S w it z e rl a n d L td . -1 6 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W CB closed

t ~ higher than the highest possible CB opening time + arc extinguish time

Breaker Failure Protection Solutions

solution 2:

t2 ~120 ms re-trip to faulty CB (coil 1 & 2) trip to the surrounding CBs by • intertripping & • remote tripping CB opening coil trip to CB from protection device t1 ~120 ms

&

BFP

the trip from the protection device is called „Starting BFP“

(17)



© A B B S w it z e rl a n d L td . -1 7 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Breaker Failure Protection Solutions

solution 3:

re-trip to faulty CB (coil 1 & 2) &

remote trip inter-tripping CB opening coil trip to CB from protection device x BFP CB x t1 ~120 ms t2 ~120 ms BBP BFP CB y CB x CB y trip to CB from protection device y

&

B F P l o g ic feeder current BFP logic ∆I = 0 IF I = I F

(18)



© A B B S w it z e rl a n d L td . -1 8 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

An advanced BFP (& BBP)

system offers all 3 solutions

!!!

Which solution must be used

for which application

???

(19)



© A B B S w it z e rl a n d L td . -1 9 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Breaker Failure Protection Solutions

standard BFP application (most common used)

for line, transformer, generator, generator- transformer, reactors and coupler CBs

for all voltage levels and switchgear configurations

overcurrent settable independently for all feeders (depending on the minimum feeder short current)

operation independent on the CB auxiliary contacts (aux. contacts are a week part of the protection chain)

for single, double and three phase auto- reclosure (tripping), (phase segregated starting inputs)

for detection of evolving faults (phase segregated timers for t1)

remote tripping signal settable after timer 1 or timer 2

advanced trip- redirection functionality in case of CB SF6 underpressure condition

not applicable for very low fault currents (e.g. generator reverse power function) -> solution 2

(20)



© A B B S w it z e rl a n d L td . -2 0 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Breaker Failure Protection Solutions

solution 1:

re-trip to faulty CB (coil 1 & 2) trip to the surrounding CBs by intertripping IR Start R & I > ≥ 1 t1 IS Start S & I > ≥ 1 t1 IT Start T & I > ≥ 1 t1 Start R S T ≥ 1 t2 remote tripping Trip Redirection set t1 & t2 to 10ms

(21)



© A B B S w it z e rl a n d L td . -2 1 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

advanced trip redirection functionality

remote tripping settable after t1

or t2

phase segregated timers for the detection of evolving faults

p h a s e s e g re g a te d s ta rt in g in p u ts f o r s in g le a n d d o u b le p o le a u to r e c lo s u re

Breaker Failure Protection Solutions

solution 1:

re-trip to faulty CB (coil 1 & 2) trip to the surrounding CBs by intertripping IR Start R & I > ≥ 1 t1 IS Start S & I > ≥ 1 t1 IT Start T & I > ≥ 1 t1 Start R S T ≥ 1 t2 remote tripping Trip Redirection set t1 & t2 to 10ms

(22)



© A B B S w it z e rl a n d L td . -2 2 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Breaker Failure Protection Solutions

applicable for very low fault currents (e.g. generator reverse power function)

remote tripping signal settable after timer 1 or timer 2

advanced trip- redirection functionality in case of CB SF6 underpressure condition

very good addition to solution 1

no overcurrent (fault current) supervision

the starting signal must be switch off by the CB “OFF” aux. contact to prevent an unwanted trip

operation dependent on the CB auxiliary contacts (aux. contacts are a week part of the protection chain)

not applicable for single and double phase auto- reclosure (tripping)

not applicable for detection of evolving faults

(23)



© A B B S w it z e rl a n d L td . -2 3 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Breaker Failure Protection Solutions

solution 2 in addition to solution 1:

re-trip to faulty CB (coil 1 & 2) trip to the surrounding CBs by intertripping IR Start R & I > ≥ 1 t1 IS Start S & I > ≥ 1 t1 IT Start T & I > ≥ 1 t1 External Start BFP t1 Start R S T ≥ 1 t2 remote tripping Trip Redirection set t1 & t2 to 10ms

(24)



© A B B S w it z e rl a n d L td . -2 4 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W cu rr e n t in d e p e n d e n t s ta rt in g i n p u t

Breaker Failure Protection Solutions

solution 2 in addition to solution 1:

re-trip to faulty CB (coil 1 & 2) trip to the surrounding CBs by intertripping IR Start R & I > ≥ 1 t1 IS Start S & I > ≥ 1 t1 IT Start T & I > ≥ 1 t1 External Start BFP t1 Start R S T ≥ 1 t2 remote tripping Trip Redirection set t1 & t2 to 10ms

(25)



© A B B S w it z e rl a n d L td . -2 5 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Breaker Failure Protection Solutions

applicable as basic BBP coupler functionality for the detection of faults between coupler CB and CT (coupler function - CB reclaim time)

not applicable for line, transformer, generator, generator- transformer, reactors feeders in HV systems

overcurrent (fault current) supervision depending on the BBP differential current setting (high short current required)

functionality depending on the BBP

not applicable for single and double phase auto- reclosure (tripping)

not applicable for detection of evolving faults

the starting signal must be switch off by the CB “OFF” aux. contact to prevent an unwanted trip to the CB after timer 1

operation dependent on the CB auxiliary contacts (aux. contacts are a week part of the protection chain)

no trip- redirection functionality in case of CB SF6 underpressure condition

remote tripping signal fixed to timer 1

(26)



© A B B S w it z e rl a n d L td . -2 6 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W c o u p le r fu n c ti o n

Breaker Failure Protection Solutions

Coupler function:

CB opening coil Input Current signal CB open

≥ 1

t

≥ 1

CT bypass C B r e c la im ti m e ~ 1 2 0 m s IF trip BBP Zone 1 inter-tripping Zone 2 B B P Z o n e 2 ∆I = 0 I = I F Zone 2 Zone 1

&

(27)



© A B B S w it z e rl a n d L td . -2 7 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

Breaker Failure Protection Application

Transformer, Transformer- Generator, Reactor feeder and coupler:

G

IR Start R & I > ≥ 1 t1 IS Start S & I > ≥ 1 t1 IT Start T & I > ≥ 1 t1 External Start BFP t1 ≥ 1 Trip Redirection set t1 & t2 to 10ms BFP CBx CBx G/T Prot. I T & I G ( 8 7 T & 8 7 G ) R e v e rs e P o w e r (3 2 ) Start RST 3 Phase trip “CB closed” aux. contacts

(28)



© A B B S w it z e rl a n d L td . -2 8 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W Start RST 3 Phase trip Start R Start S Start T single Phase trip

Breaker Failure Protection Application

Line feeder with single phase auto reclosure:

IR & I > ≥ 1 t1 IS & I > ≥ 1 t1 IT & I > ≥ 1 t1 External Start BFP t1 ≥ 1 Trip Redirection set t1 & t2 to 10ms BFP CBx CBx Line Prot. O C ( 5 1 ) Z < & D E F ( 2 1 & 6 7 N ) AR Syn

(29)



© A B B S w it z e rl a n d L td . -2 9 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W C B i s b lo c k e d s in c e S F 6 g a s p re s s u re t o e x ti n g u is h t h e a rc i s t o l o w Start RST 3 Phase trip Start R Start S Start T single Phase trip

Breaker Failure Protection Application

Trip Redirection in case of CB SF6 Underpressure :

IR & I > ≥ 1 t1 IS & I > ≥ 1 t1 IT & I > ≥ 1 t1 External Start BFP t1 ≥ 1 Trip

Redirection set t1 & t2

to 10ms BFP CBx CBx Line Prot. O C ( 5 1 ) Z < & D E F ( 2 1 & 6 7 N ) AR Syn

(30)



© A B B S w it z e rl a n d L td . -3 0 B F P _ b a s ic s / 2 0 0 3 -0 4 -0 1 / R W

References

Related documents

Most of research works on water distribution network (WDN) focused on the condition or performance of water systems creating a gap between municipal goals and public expectations. It

Table 9: World Recent Past, Current &amp; Future Analysis for Psoriasis Drugs by Drug Administration Route - Systemic Drugs and Topical Drugs Markets Independently Analyzed with

In conjunction with a selection of initiatives such as the Global Women South- South Digital Inclusion initiative supported by the First Lady of Panama,

Teaching practice incorporates appropriate modeling of the target language, both spoken and written; the design, implementation and evaluation of lessons and units of work

As mentioned in the introduction, in order to maintain some semblance with the now normative positioning of the letters, signs and trumps on the Tree of Life, I have decided to link

February 2014 Dinner Meeting The CSCE Younger Members Group will be releasing their Twitter page soon.. An email will be sent with the handle name when everything is up

• Coastal Commission LCP Planning Grant Program: $1 million available for updating and certifying LCPs; may include updates to address impacts of climate change and sea-level

A 55-year-old male presents to the clinic with a palpable anterior neck mass that moves on swallowing. The mass is 5cm x 5cm, hard in consistency and confined to the left