ARCHITECT IMMEDIATELY. 2. DO NOT SCALE DRAWINGS.

3. DIMENSIONS ARE TYPICALLY TO THE EXTERIOR FACE OF THE STUDS, CENTER OF STRUCTURAL COLUMN OR GRID LINE UNLESS NOTED OTHERWISE.

4. OPENINGS ARE DIMENSIONED TO FINISH FACE OF OPENING.

5. INSTALL FULLY RECESSED FIRE DEPARTMENT KEY SAFE ADJACENT TO FRONT DOOR ACCORDING TO REQUIREMENTS OF LOCAL AUTHORITY HAVING JURISDICTION.

6. FIRE PARTITIONS AND DEMISING WALLS TO EXTEND FROM TOP OF FLOOR TO UNDERSIDE OF ROOF SLAB ABOVE PER IBC 708.4 'CONTINUITY'

7. ALL WALL AND FLOOR ASSEMBLY PENETRATIONS AT RATED LOCATIONS REQUIRED FOR PIPES, CONDUIT, DUCTING, ETC. SHALL BE SEALED TO STOP PASSAGE OF FIRE AND/OR SMOKE WITH FIRE SAFING AND APPROVED SEALANT.

8. FIREBLOCKING SHALL CONSIST OF 2-INCH NOMINAL LUMBER OR TWO THICKNESSES OF 1-INCH NOMINAL LUMBER WITH BROKEN LAP JOINTS OR ONE THICKNESS OF 0.719-INCH WOOD STRUCTURAL PANEL WITH JOINTS BACKED BY 0.719-INCH WOOD STRUCTURAL PANEL OF ONE THICKNESS OF 0.75-INCH PARTICLEBOARD WITH JOINTS BACKED BY 0.75-INCH PARTICLEBOARD. GYPSUM BOARD, CEMENT FIBER BOARD, BATTS OR BLANKETS OF MINERAL WOOL, GLASS FIBER OR OTHER APPROVED MATERIALS INSTALLED IN SUCH A MANNNER AS TO BE SECURELY RETAINED IN PLACE SHALL BE PERMITTED AS AN ACCEPTABLE FIREBLOCK.

9. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES, AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS, AS FOLLOWS:

A. VERTICALLY AT THE CEILING AND FLOOR LEVELS. B. HORIZONTALLY AT INTERVALS NOT EXCEEDING 10'.

10. FIREBLOCKING SHALL BE PROVDED AT INTERCONNECTIONS BETWEEN CONCEALED VERTICAL STUD WALL OR PARTITION SPACES AND CONCEALED HORIZONTAL SPACES CREATED BY AN ASSEMBLY OF FLOOR JOISTS OR TRUSSES, AND BETWEEN CONCEALED VERTICAL AND HORIZONTAL SPACES SUCH AS OCCUR AT SOFFITS, DROP CEILINGS, COVE CEILINGS AND SIMILAR LOCATIONS.

11. FIREBLOCKING SHALL BE INSTALLED AT OPENINGS AROUND VENTS PIPES, DUCTS CHIMNEYS AND FIREPLACES AT CEILING AND FLOOR LEVELS, WITH AN APPROVED MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND THE PRODUCTS OF COMBUSTION. FACTORY-BUILT CHIMNEYS AND FIREPLACES SHALL BE FIREBLOCKED IN ACCORADANCE WITH UL 103 AND UL 127.

12. DRAFTSTOPPING - IN COMBUSTIBLE CONSTRUCTION, DRAFTSTOPPING SHALL BE INSTALLED TO SUBDIVIDE FLOOR/CEILING ASSEMBLIES.

13. DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN 0.5-INCH GYPSUM BOARD, 0.375-INCH WOOD STRUCTUAL PANEL, 0.375-INCH PARTICLEBOARD, 1-INCH NOMINAL LUMBER, CEMENT FIBERBOARD, BATTS, OR BLANKETS OF MINERAL WOOL OR GLASS FIBER OR OTHER APPROVED MATERIALS ADEQUATELY SUPPORTED. THE INTEGRITY OF DRAFTSTOPS SHALL BE MAINTAINED. 14. DRAFTSTOPPING - IN COMBUSTIBLE CONSTRUCTION, DRAFTSTOPPING SHALL BE INSTALLED TO

SUBDIVIDE THE ATTIC SPACES AND CONCEALED ROOF SPACES. VENTILATION OF CONCEALED ROOF SPACES SHALL BE MAINTAINED IN ACCORDANCE WITH 2018 I.B.C.

(01) SINGLE STOREFRONT (03) HM FLUSH

4" 4" 4" 10 " PE R SC H ED . PE R SC H ED .

DOOR TYPES

4" 4" 4" 10 " PE R SC H ED . 4" 4" 4" 10 " (02) DOUBLE STOREFRONT

FRAME TYPES

2" 2" 2" M A N U F. MANUF. (F1) STOREFRONT (F2) HM DOOR B-A200 4 B-A200 3 B-A200 2 B-A200 1

B-4

B-4

B-3

B-3

B-2

B-2

B-1

B-1

B-A

B-A

B-B

B-B

B-C

B-C

3,602 SF

PAD B

1 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 5 1/4" 19'-2" 4 3/4" 1'-8 1/4" 2'-4 1/4" 11'-6" 2'-6" 6'-0" 2'-4" 10'-6" 2'-6" 7'-0" 7' -0 " 10 '-4 1 /8 " 12 '-7 7 /8 " 2' -0 3 /8 " 22 '-6 1 /2 " 8' -0 " 5 1/ 4" 2' -0 " 1'-0" 2 B-A300 1 B-A300 01 02 03 04 05 W6A W6A W6B W6B W6B W6B W6B W6B W6B W6B W6B W6C W6C W6C W6C W6C W6C W6B W6A W6A W6A W6A W6A W6A W6A W6A 1002 TYP 309 2602 3301 TYP 601 TYP 803 801 2102 2'-5" TYP 803 TYP 601 TYP 2202 2103 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 7' -0 " 23 '-0 " 4' -9 3 /8 " 6' -7 3 /4 " 6' -7 3 /4 " 14 '-1 1 1/ 8" 2' -0 " 11'-6" 2'-6" 6'-0" 2'-4" 10'-6" 2'-6" 7'-0" 7' -0 " 10 '-4 1 /8 " 12 '-7 7 /8 " 2' -0 3 /8 " 20 '-5 1 /2 " 2' -1 " 8' -0 " 5 1/ 4" 2' -0 " 1'-0" 2'-5" 2101 1'-5" 11'-0" 4'-0" 11 1/2" 3'-4 3/8" 13'-2" 3'-5 5/8" 13'-2" 3'-4 3/8"11 1/2" 4'-0" 11'-0" 3'-5 5/8" 1' -5 " L I C E N S E D A RCHI TE CT ST AT E TA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

P

A

D

B

F

LO

O

R

P

LA

N

KEYNOTES

#

DESCRIPTION

309 6" CONCRETE BOLLARD W/ BLACK HOUSING 601 COLUMN, SEE STRUCTURAL DRAWINGS

801 PASS-THRU WINDOW, BASIS OF DESIGN: READY ACCESS 275-LP (48"X44") BLACK 803 ALUMINUM STOREFRONT SYSTEM

1002 MANUFACTURED METAL LADDER WITH LOCKED SECURITY PANEL. PAINT BLACK WITH HIGHT-PERFORMANCE PAINT.

2101 FIRE DEPARTMENT CONNECTION

2102 INSTALL FIRE RISER IN THIS LOCATION PER NFPA REQUIREMENTS. EXTEND MAIN LINE ABOVE BOTTOM CHORD OF ROOF TRUSS FOR FUTURE CONNECTION

2103 INSTALL KNOX BOX PER FIRE MARSHALL'S REQUIREMENTS. CONTACT FIRE DEPT TO PURCHASE KNOX BOX.

2202 INSTALL BRASS OVERFLOW DRAIN AT 18" A.F.F. CONNECT TO OVERFLOW ROOF DRAIN ABOVE 2602 ELECTRICAL POWER AND DISCONNECT PER ELECTRICAL PLANS

3301 GAS METERS, SEE MECHANICAL DRAWINGS

#

DESCRIPTION

DOOR

FRAME

DETAILS

HW

REMARKS

TY

PE

WIDT

H

HEIG

HT

MATERIAL

FINISH

TYPE MATERIAL

FINISH

THRESHO

LD

JAMB/HE

AD

01 HM FLUSH 03 3'-0" 7'-0" H.M. PTD H.M. PTD 7/B-A401 8/B-A401 3.0 PAINT DOOR/FRAME TO MATCH ADJACENT MATERIAL 02 HM FLUSH 03 3'-0" 7'-0" H.M. PTD H.M. PTD 7/B-A401 8/B-A401 3.0 PAINT DOOR/FRAME TO MATCH ADJACENT MATERIAL 03 SINGLE STOREFRONT 01 3'-0" 7'-0" GLASS/ALUM. ANOD. BLK ALUMINUM ANOD. BLK 10/B-A401 3/B-A401 2.0

04 SINGLE STOREFRONT 01 3'-0" 7'-0" GLASS/ALUM. ANOD. BLK ALUMINUM ANOD. BLK 10/B-A401 3/B-A401 2.0 05 SINGLE STOREFRONT 01 3'-0" 7'-0" GLASS/ALUM. ANOD. BLK ALUMINUM ANOD. BLK 10/B-A401 3/B-A401 2.0 Grand total: 5

*DOOR HARDWARE GROUPS LOCATED IN SPEC ON B-G001

(2)

t-B-4

B-4

B-3

B-3

B-2

B-2

B-1

B-1

B-A

B-A

B-B

B-B

B-C

B-C

1 /4 " / 1 2 " 1 /4 " / 1 2 " 1 /4 " / 1 2 " 1 /4 " / 1 2 " 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 2 B-A300 1 B-A300 1'-4 3/8" 17'-2" 1'-5 5/8" 2' -5 1 /8 " 8' -4 1 /2 " 2' -5 7 /8 " 3'-0" 3' -0 " TYP 703 TYP 2201 TYP 705 TYP 704 1'-6" 1/4" / 12" 1/4" / 12" TYP 704 1002 T.O.P. 120'-2" T.O.P. 120'-2" 1' -6 " SE R V IC E SI D E SE R V IC E SI D E T.O.P. 118'-2" T.O.P. 120'-2" T.O.P. 118'-2" T.O.P. 118'-2" 1'-6" 9 B-A400 TYP T.O.P. 120'-2" T.O.P. 114'-2" T.O.P. 120'-2" T.O.P. 118'-2" T.O.P. 120'-2" TYP 501 TYP 501 2303 2303 B-A401 4 B-A400 11 TYP B-A400 11 TYP TYP 501 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 1'-4 3/8" 17'-2" 1'-5 5/8" 2' -5 1 /8 " 8' -4 1 /2 " 2' -5 7 /8 " 3'-0" 3' -0 " 2'-0" 2'-0" 2'-0" 2'-0" 2' -0 " 1'-6" 704 EQ EQ SE R V IC E SI D E 2303 1 /4 " / 1 2 " 801.427.2233 | JARRETTARCHITECTURE.COM L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

p a n is h F o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2 0 2 1 8 :3 0 :4 1 A M

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

P

A

D

B

R

O

O

F

P

LA

N

PROJECT #: 2101.02

KEYNOTES

#

DESCRIPTION

501 PRE FINISHED METAL PARAPET CAP W/ DRIP EDGE.

703 ROOFING MEMBRANE OVER PROTECTION BOARD, OVER ROOF SHEATHING. TOP CHORD OF ROOF TRUSS SLOPED TO ROOF DRAINS MIN. 1/4" PER FOOT. ROOFING MEMBRANE TO WRAP UP AND OVER PARAPET FRAMING.

704 ROOF CRICKET SLOPED TO ROOF DRAINS MIN. 1/4" PER FOOT. 705 HEAVY DUTY WALKWAY PAD

1002 MANUFACTURED METAL LADDER WITH LOCKED SECURITY PANEL. PAINT BLACK WITH HIGHT-PERFORMANCE PAINT.

2201 ROOF DRAINS, SEE PLUMBING DRAWINGS

2303 PROVIDE ROOF TOP UNITS IN LOCATIONS, QUANITY AND SIZE AS SHOWN ON MECHANICAL PLANS. COORDINATE OPENINGS TO BE BETWEEN TRUSS CAVITIES.

3/16" = 1'-0"

B-A200

1

PAD B - ROOF PLAN

(3)

TO BE TEMPERED-SAFETY GLAZING.

2. STOREFRONT GLASS PANES TO BE 5' MAXIMUM IN WIDTH AND MAXIMUM 7' IN HEIGHT. STOREFRONT GRID SIZES TO BE DESIGNED AS SUCH.

3. PROVIDE SEALANT AT ALL JOINTS WHERE DIFFERENT MATERIALS MEET. SEAL BY MANUF. WARRANTY AND REQ'S.

4. ALL EXTERIOR WALL LIGHTING TO BE MOUNTED AT 7'-0" TO BOTTOM OF FIXTURE U.N.O.

5. PROVIDE J-BOXES FOR ALL TENANT SIGNAGE LOCATIONS. J-BOXES ARE INTERIOR OF BUILDING. AVOID J-BOX LOCATIONS ABOVE ROOF LINE. IF J-BOX IS INSTALLED IN KICKER, AN ACCESS PANEL IS TO BE PROVIDED.

6. ALL STEEL CANOPIES TO BE FACTORY PRIMED AND PAINTED ON SITE.

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-4

B-3

B-2

B-1

2 B-A300 TYP 501 TYP 1003 803 803 803 TYP 2303 TYP 503 THIN-BRICK VENEER

THIN-BRICK VENEER LIGHT

STUCCO 01 WOOD SIDING T.O.P. 120'-2" T.O.P. 118'-2" T.O.P. 120'-2" T.O.P. 114'-2" 3 B-A400 4 B-A400 4 B-A400 10 '-0 " 2' -1 1" 5' -7 " 1' -6 " 1 B-A401 BOARDFORM CONCRETE 2 B-A400 TYP 601 5'-0" 3'-2" 5'-0" 3'-11" 3'-2" 3'-11" 4'-0" 4'-0" 3'-2" 4'-0" 4'-0" 10 '-0 " 2' -1 1" 5' -7 " 1' -6 " 5'-0" 3'-2" 5'-0" 3'-11" 3'-2" 3'-11" 4'-0" 4'-0" 3'-2" 4'-0" 4'-0"

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-A

B-B

B-C

1 B-A300 STUCCO 01 WOOD SIDING

STUCCO 01 STUCCO 02 STUCCO 01 STUCCO 02

2602 2 B-A400 TYP 2 B-A400 TYP TYP 501 TYP 803 TYP 501 T.O.P. 120'-2" T.O.P. 114'-2" 1 B-A401 1 B-A401 3 B-A400 3 B-A400 3301 TYP 2202 4'-0" 4'-0" 10 '-0 " 1' -6 " 5' -7 " 2' -1 1" 4'-0" 4'-0" 10 '-0 " 1' -6 " 5' -7 " 2' -1 1"

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-A

B-B

B-C

1 B-A300 4 B-A400 3 B-A400 T.O.P. 120'-2" T.O.P. 120'-2" T.O.P. 118'-2" 2 B-A400 TYP STUCCO 02

THIN-BRICK VENEER LIGHT THIN-BRICK VENEER BOARDFORM CONCRETE

THIN-BRICK VENEER LIGHT

TYP 501 TYP 801 3' -6 " TYP 309 1002 503 8 1 /2 " / 1 2 " 110'-0" 10 '-0 " 102'-0"

THIN-BRICK VENEER LIGHT

1 B-A401 1 B-A401 1 B-A401 7' -6 " 4 B-A400 4 B-A400

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-4

B-3

B-2

B-1

2 B-A300 TYP 501 1002 503 TYP 2202 1 B-A401 3 B-A400 1003 TYP 501 T.O.P. 120'-2" T.O.P. 118'-2" T.O.P. 120'-2" 2 B-A400 TYP STUCCO 01 STUCCO 02

THIN-BRICK VENEER LIGHT

THIN-BRICK VENEER 309 802 802 707 L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

P

A

D

B

E

LE

V

A

TI

O

N

S

KEYNOTES

#

DESCRIPTION

309 6" CONCRETE BOLLARD W/ BLACK HOUSING 501 PRE FINISHED METAL PARAPET CAP W/ DRIP EDGE.

503 LIGHT GAUGE FRAMED AWNING W/ STANDING SEAM METAL ROOF 601 COLUMN, SEE STRUCTURAL DRAWINGS

707 THROUGH WALL SCUPPER WITH DOWNSPOUT DRAINED INTO LANDSCAPING BELOW 801 PASS-THRU WINDOW, BASIS OF DESIGN: READY ACCESS 275-LP (48"X44") BLACK 802 DOOR AS SCHEDULED

803 ALUMINUM STOREFRONT SYSTEM

1002 MANUFACTURED METAL LADDER WITH LOCKED SECURITY PANEL. PAINT BLACK WITH HIGHT-PERFORMANCE PAINT.

1003 RETAIL SPACE SIGN PER CITY REQUIREMENTS, PROVIDED BY TENANT

2202 INSTALL BRASS OVERFLOW DRAIN AT 18" A.F.F. CONNECT TO OVERFLOW ROOF DRAIN ABOVE 2303 PROVIDE ROOF TOP UNITS IN LOCATIONS, QUANITY AND SIZE AS SHOWN ON MECHANICAL

PLANS. COORDINATE OPENINGS TO BE BETWEEN TRUSS CAVITIES. 2602 ELECTRICAL POWER AND DISCONNECT PER ELECTRICAL PLANS 3301 GAS METERS, SEE MECHANICAL DRAWINGS

NAME MANUF. MODEL/COLOR SIZE

BOARDFORM CONCRETE N/A BOARDFORMED CONCRETE PLANTER

6" PROFILE

GLAZING TBD CLEAR 1" INSULATED

GLAZING - TEMPERED TBD CLEAR SAFETY GLASS / TEMPERED 1" INSULATED

PAINT 01 SHERWIN WILLIAMS HIGH PERFORMANCE / MATCH ADJACENT FINISH

N/A

STUCCO 01 MASTERWALL WEST MANUF.

SW 7064 - PASSIVE VERSATEX 0.5

STUCCO 02 MASTERWALL WEST MANUF.

SW 7066 - GRAY MATTERS VERSATEX 0.5

THIN-BRICK VENEER INTERSTATE BRICK MODULAR THIN BRICK - MIDNIGHT BLACK

2 1/4" X 7 5/8"

THIN-BRICK VENEER LIGHT

INTERSTATE BRICK MODULAR THIN BRICK -ARCTIC WHITE

2 1/4" X 7 5/8"

WOOD SIDING MONTANA TIMBER PRODUCTS RANCHWOOD YELLOWSTONE CIRCLESAWN SHIPLAP 1/8" REVEAL

3/16" = 1'-0"

B-A101

4

NORTH ELEVATION - PAD B

3/16" = 1'-0"

B-A101

3

SOUTH ELEVATION - PAD B

(4)

--LEVEL 1

100'-0"

RF BRNG

114'-0"

B-4

B-3

B-2

B-1

2 B-A300 B-A301 1 B-A301 2 306 601 604 2303 307 TYP 501 706 R01 1002 2201 706

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-A

B-B

B-C

1 B-A300 B-A301 3 B-A301 4 306 307 601 604 2303 2201 R01 TYP 501 801.427.2233 | JARRETTARCHITECTURE.COM L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

p a n is h F o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2 0 2 1 8 :3 0 :4 7 A M

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

B

U

IL

D

IN

G

S

E

C

TI

O

N

S

PROJECT #: 2101.02

KEYNOTES

#

DESCRIPTION

306 CONCRETE FOOTING, SEE STRUCTURAL 307 CONCRETE SLAB OVER COMPACTED FILL 501 PRE FINISHED METAL PARAPET CAP W/ DRIP EDGE. 601 COLUMN, SEE STRUCTURAL DRAWINGS

604 PREMANUFACTURED ROOF TRUSS. TOP CHORD SLOPED TO ROOF DRAIN.

706 WRAP ROOFING MEMBRANE UP PARAPET WALLS OVER COMPATIBLE ROOFING SUBSTRATE. 1002 MANUFACTURED METAL LADDER WITH LOCKED SECURITY PANEL. PAINT BLACK WITH

HIGHT-PERFORMANCE PAINT.

2201 ROOF DRAINS, SEE PLUMBING DRAWINGS

2303 PROVIDE ROOF TOP UNITS IN LOCATIONS, QUANITY AND SIZE AS SHOWN ON MECHANICAL PLANS. COORDINATE OPENINGS TO BE BETWEEN TRUSS CAVITIES.

3/16" = 1'-0"

B-A101

1

PAD B - NORTH TO SOUTH BLDG SECTION

(5)

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-4

B-A400 1 305 306 701 701 803 604 703 501 B-A400 10 B-A400 3 706 B-A401 10 TYP T.O.P. 114'-2" T.O.P. 120'-2"

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-1

B-A400 5 B-A401 11 306 305 801 503 604 501 B-A400 10 B-A400 3 110'-0" B-A401 12 TYP 307 T.O.P. 120'-2"

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-A

B-A400 5 2202 305 306 701 604 501 703 706 B-A400 3 B-A400 10 T.O.P. 120'-2"

LEVEL 1

100'-0"

RF BRNG

114'-0"

B-C

B-A400 1 305 307 803 701701 706 703 TYP 501 T.O.P. 120'-2" B-A400 10 B-A400 3 L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2 0 2

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

W

A

LL

S

E

C

TI

O

N

S

KEYNOTES

#

DESCRIPTION

305 CONCRETE FOUNDATION WALL, SEE STRUCTURAL 306 CONCRETE FOOTING, SEE STRUCTURAL

307 CONCRETE SLAB OVER COMPACTED FILL 501 PRE FINISHED METAL PARAPET CAP W/ DRIP EDGE.

503 LIGHT GAUGE FRAMED AWNING W/ STANDING SEAM METAL ROOF 604 PREMANUFACTURED ROOF TRUSS. TOP CHORD SLOPED TO ROOF DRAIN. 701 RIGID INSULATION

703 ROOFING MEMBRANE OVER PROTECTION BOARD, OVER ROOF SHEATHING. TOP CHORD OF ROOF TRUSS SLOPED TO ROOF DRAINS MIN. 1/4" PER FOOT. ROOFING MEMBRANE TO WRAP UP AND OVER PARAPET FRAMING.

706 WRAP ROOFING MEMBRANE UP PARAPET WALLS OVER COMPATIBLE ROOFING SUBSTRATE. 801 PASS-THRU WINDOW, BASIS OF DESIGN: READY ACCESS 275-LP (48"X44") BLACK

803 ALUMINUM STOREFRONT SYSTEM

2202 INSTALL BRASS OVERFLOW DRAIN AT 18" A.F.F. CONNECT TO OVERFLOW ROOF DRAIN ABOVE

1

WALL SECTION

3

PAD B - WEST TO EAST BLDG SECTION - Callout 1

4

(6)

3/ 16 " 1/2" 3/16" 1/ 2" SLOPED

VERTICAL EIFS REVEAL HORIZONTAL EIFS REVEAL

ROOF MEMBRANE UP AND OVER TOP OF WALL NEOPRENE GASKETED SCREWS @ 18" O.C.

HEMMED EDGE CONTINUOUS CLEAT

STUCCO SYSTEM

WEATHER RESISTANT BARRIER PREFINISHED METAL CAP

MANUFACTURED APPROVED ROOFING SUBSTRATE

7"

STUCCO SYSTEM

1/2"

WALL SHEATHING, SEE STRUCTURAL

SLOPE

ROOF MEMBRANE UP AND OVER TOP OF WALL NEOPRENE GASKETED

SCREWS @ 18" O.C. HEMMED EDGE

CONTINUOUS CLEAT

THIN BRICK VENEER

WEATHER RESISTANT BARRIER PREFINISHED METAL CAP

MANUFACTURED APPROVED ROOFING SUBSTRATE

WALL SHEATHING, SEE STRUCTRUAL THIN BRICK VENEER - SOLDIER COURSE

SLOPE

ALUM. FRAME AS SCHEDULED

CONC. WALL, SEE STRUCTURAL

SIDEWALK, SEE CIVIL BACKER ROD & SEALANT SHIM SPACE

EXPANSION JOINT WITH SEALANT, TYP.

2" RIGID BUILDING PERIMETER INSULATION, EXTEND INSULATION 48" HORIZ. BENEATH SLAB

GRAVEL BASE PER GEOTECH

SLAB WITH TURNDOWN, SEE STRUCTURAL GLAZING AS SCHEDULED

SMOOTH TROWEL FINISH TOP OF WALL AT ALL STOREFRONT LOCATIONS

2"2"

GRD

CONCRETE FOOTING, SEE STRUCTURAL 2" RIGID INSULATION

STEM WALL, SEE STRUCTURAL 2"x48" RIGID INSULATION

GRAVEL FILL PER GEOTECH WEATHER-RESISTANT BARRIER

1/2" RIGID INSULATION

LIQUID APPLIED DAMPPROOFING BELOW GRADE AT ALL EXTERIOR FOUNDATION WALLS

6"

2"

2"

1/2"

CONCRETE SLAB, SEE STRUCTURAL EXTERIOR FINISH

SHEATHING PER STRUCTURAL R19 INSUALTION 1" 5 1/2" 1 1/2" 6" 2" 2" 1" 5 1/2" 1 1/2" ALUMINUM STOREFRONT AS SCHEDULED

CONT. SEALANT BOTH SIDES BEHIND WINDOW FRAME IN SHIM SPACE

GLAZING AS SCHEDULED

THIN BRICK VENEER CORNER PIECE WEATHER RESISTANT BARRIER

WALL SHEATHING, SEE STRUCTRUAL THIN BRICK VENEER AS SCHEDULED EXTERIOR FINISH - SEE

ELEVATIONS

WEATHER RESISTANT BARRIER

PARAPET 2X FRAMING ROOFING MEMBRANE

ROOF SHEATHING, SEE STRUCT. PROTECTION BOARD COMPATIBLE WITH ROOFING MEMBRANE COPING WEDGE 2X NAILER INSULATION PER COMMCHECK PROTECTION BOARD FASTEN 12" O.C. METAL CAP FLASHING BONDING ADHESIVE

ROOF SHEATHING TOP CHORD OF TRUSS

NOTES:

1. BONDING ADHESIVE IS NOT REQ'D WHEN FLASH'G HGT IS 12" OR LESS AND MEMBANE IS FASTENED "AS SHOWN" @ TOP OF CURB.

2. WHEN TERMINATION BAR IS USED BENEATH THE COUNTERFLASHING, BONDING ADHESIVE CAN BE ELIMINATED WHEN THE FLASHING HEIGHT IS 18" OR LESS

3. FLASH'G MEMBRANE FASTENED APPROXIMATELY 12" O.C. IF FASTENER PENETRATES MTL. COUNTERFLASHING, USE NEOPRENE WASHER OR APPLY WATER CUT-OFF MASTIC UNDER COUNTERFLASHING OR CAULK FASTENER HEAD.

4. APPROXIMATELY 1/8" BEAD OF CUT-EDGE SEALANT IS REQ'D ON CUT EDGES OF TPO REINFORCED MEMBRANE.

5. REFER TO MANUFACTURER SPECIFICATION FOR ACCEPTABLE

6.

FASTENERS AND PLATES.

FOR CORNER FLASHING SEE DETAIL

FASTENING PLATE, 12" O.C. MAX.

USE ONE CONT. SHEET OF TPO REINFORCED MEMBRANE TO WRAP AROUND CURB OR FORM FROM COATED METAL OUTSIDE CORNER SEE DETAIL

TPO REINFORCED MEMBRANE

MINIMUM 1-1/2" HOT AIR WELD

CUT-EDGE SEALANT (SEE NOTE 4)

TPO REINFORCED MEMBRANE

CONTINUOUS BEAD OF LAP SEALANT R.M. PRE-FORMED JOINT COVER

PRE-FORMED CORNER FLASHING ROOFING MEMBRANE

3" M IN.

R.M. FLASHING (SECOND FLASHING) 6" FLASHING (FIRST

FLASHING)

3" M

IN. 3" MIN.

R.M. MEMBRANE OR CURB FLASHING

ROOF DRAIN PIPES UNDERDECK CLAMP ROOF SYSTEM TAPERED ROOF INSULATION 2" HIGH OVERFLOW DAM OVERFLOW DRAIN DRAIN SUMP RECEIVER MAIN ROOF DRAIN SHAPED RIGID INSULATION & ROOF MEMBRANE SUMP PAN

1'-0" 2'-0" 1'-0"

4'-0" SUMP

ROOF STRUCTURE WRAP ROOF MEMBRANE

AROUND WALL

EXTERIOR WALL FINISH WEATHER RESISTANT BARRIER APPROVED ROOFING

SUBSTRATE

WALL SHEATHING, SEE STRUCTRUAL FLEXIBLE CONT. SEALANT BETWEEN FINISH AND ANGLE

PROVIDE END ANGLE TO CAP EXTERIOR FINISH

LAP ROOFING MEMBRANE OVER WEATHER BARRIER 6" MIN.

801.427.2233 | JARRETTARCHITECTURE.COM L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

p a n is h F o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2 0 2 1 8 :3 0 :4 9 A M

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

D

E

TA

IL

S

PROJECT #: 2101.02

2

TYP STUCCO DETAIL

3

PARAPET CAP AT STUCCO

4

PARAPET CAP AT BRICK

1

TURN DOWN AT STOREFRONT

1 1/2" = 1'-0"

B-A100

5

FOUNDATION DETAIL

3" = 1'-0"

6

STOREFRONT HEADER AT BRICK

3" = 1'-0"

B-A301

10

PARAPET WALL TO TRUSS DETAIL

3" = 1'-0"

12

RTU CURB FLASHING (TYP.)

1 1/2" = 1'-0"

13

R.M. OUTSIDE CORNER FLASHING DETAIL

3/4" = 1'-0"

B-A120

9

DRAIN & OVERFLOW SECTION

3" = 1'-0"

B-A120

11

PARAPET WALL TERMINATION

#

REV IS IO N D ES C R IP TI O N D A TE -1

A:ZC-iir=cruR=

-''4

1<'

1$.. 'I NI

4--4~VA

_jV-I-~

-I

I -~T~NV7V7> ~zzzzzz~\' \\' - //////////-///Z,/ZZ-/ZZZ-/ZZZ ZZZ ... / ... ; .. L'

\\\\'

\\\\\\ \

E

I

L

Avr

... ...

i

-4

4,'

-' - -A'

-Al

LVL

-A-It-tn.-"V -/- ti

A

TC'

4

4" -4 4 44 I

~ijj2iTj

A. - --

-_______1-i-

/ /1A / I

r---

4 4 -- A-. A I , " 2 -, -- Ol A I I I -4' 4 A -~ ML--- 4--- <A>-.' - - A--- -S -- '-s-- I - -

-A

-'lu

III

III

(7)

1" GLASS

STOREFRONT DOOR THRESHOLD TO COVER GAP BETWEEN SLAB & EXTERIOR CONCRETE

DOOR AS SCHEDULED

1" GLASS

1/

2"

SLOPE AWAY MIN 1/4" PER FOOT @ EXTERIOR

DOOR JAMB BEYOND SCHEDULED DOOR ALUMINUM TRESHOLD SET IN MASTIC SCHEDULED FLOORING COVER CONCRETE SLAB 1/2" EXPANSION MATERIAL; WHERE OCCURS SWEEP 1/ 2" 11 GA ALUMINUM SHEET DOOR AND FLANGES

WALL MOUNT FLANGES OR DIRECT LADDER MOUNT

CONTINUOUS HINGE STAINLESS STEEL

SAFETY HASP

CONCRETE PAD AS REQ. PROVIDE SLOTTED HOLES FOR ADJUSTMENT OF 1/4" ANCHOR BOLTS 3" x 1 3/4" x 1/8" THICK TUBING ALUM. STRINGER 1 1/4" RUNG CORRUGATED ALUM., TYP. EQ U A L SP A C ES @ 1 2" O .C . V A R IE S O V ER A LL L A D D ER H EI G H T 42 " 1 1/4" CRAB RAIL CORRUGATED ALUMINUM, TYP. 4' -0 " O .C . T YP . 8' -0 " 32"

SECURELY ATTACH TO BUILDING PER IBC AND OSHA REQ'S

24" EQ U A L SP A C ES @ 1 2" O .C . V A R IE S O V ER A LL L A D D ER H EI G H T 4' -0 " O .C . T YP . 8' -0 " 1" STOREFRONT GLAZING

THERMALLY BROKEN STOREFRONT MULLION

DOOR AS SCHEDULED 2" PER MANUF. 2" PER MANUF. G LA SS 1" G LA SS 1" DOOR SEAL G LA SS 1" G LA SS 1" 2 " 1" STOREFRONT GLAZING

THERMALLY BROKEN STOREFRONT MULLION

PER MANUF. PER MANUF.

WALL AS SCHEDULED - SEE WALL TYPES

HOLLOW METAL FRAME AS SCHEDULED. FILLED WITH SPRAY-FOAM INSULATION DOOR AS SCHEDULED WEATHER-RESISTANT BARRIER EXTERIOR SHEATHING EXTERIOR FINISH CONT. SEALANT FLASHING CONT. SEALANT SHIM SPACE

WOOD SHEATHING, SEE STRUCTURAL

ZIP STRIP OR EQUAL ALUMINUM STOREFRONT

AS SCHEDULED GLAZING AS SCHEDULED WEATHER RESISTANT BARRIER 1/4" V NOTCH CORNER BEAD EXTERIOR WALL AS SCHEDULED STUCCO SYSTEM

WEATHER RESISTANT BARRIER

STUCCO SYSTEM

WALL SHEATHING, SEE STRUCTURAL

1/2"

INSUALATION, SEE COM CHECK

7"

THIN BRICK VENEER

WEATHER RESISTANT BARRIER

THIN BRICK VENEER

WALL SHEATHING, SEE STRUCTURAL INSUALATION, SEE COM CHECK

7" 7" 7" 4" M IN . TP O L A P

1/4" PER FOOT MIN. SLOPE

2X FRAMING AS REQUIRED ROOFING MEMBRANE OVER WEATHER BARRIER, OVER PLYWOOD SLOPED TO ROOF DRAIN

PERFORATED METAL DEBRIS & BUG SCREEN SECURELY FASTENED TO CONTINUOUS ANLGE SUPORTS

PREFINISHED PARAPET CAP W/ DRIP EDGE PREFINISHED FLASHING W/ DRIP EDGE

WOOD SIDING SOFFIT, MITERED AT ALL CORNERS CONTINUOUS WEATHER BARRIER

WOOD SIDING, SEE ELEVATIONS & WALL TYPES

4" M IN . TP O L A P CONTINUOUS 1/4" 'V' NOTCH ROUTED IN WOOD SIDING 8 3/ 8" SILL WEATHER-RESISTANT BARRIER WINDOW AS SCHED.

FLEXIBLE WINDOW FLASHING FLEXIBLE WINDOW FLASHING

VAPOR BARRIER POLYURETHANE FOAM

OVERLAP UPPER WRB OVER LOWER AND TAPE JOINTS WITH COMPATIBLE TAPE

CONT. SEALANT AND BACKER ROD

FULL DEPTH INSULATION THIN BRICK VENEER, SEE ELEVATIONS

SHEATHING PER STRUCT FLASHING HEAD/JAMB WEATHER-RESISTANT BARRIER WINDOW AS SCHED. VAPOR BARRIER POLYURETHANE FOAM OVERLAP UPPER WRB OVER LOWER AND TAPE JOINTS WITH COMPATIBLE TAPE

FLASHING

CONT. SEALANT AND BACKER ROD FULL DEPTH INSULATION

SCHEDULED WALL SHEATHING PER STRUCT

PREFINISHED FLASHING

BLACK STANDING SEAM METAL ROOFING

ALUMINUM METAL TUBE FRAME W/ SUPPORTS WALL AS SCHEDULED L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

F o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

D

E

TA

IL

S

2

THRESHOLD

3

H.M. THRESHOLD

4

EXTERIOR ROOF LADDER

3" = 1'-0"

5

STOREFRONT DOOR HEADER

3" = 1'-0"

6

STOREFRONT DOOR CENTER JAMB

3" = 1'-0"

7

HORIZONAL MID MULLION

3" = 1'-0"

8

TYPICAL EXTERIOR HOLLOW MEATAL HEAD

3" = 1'-0"

9

EXTERIOR STOREFRONT HEAD - STUCCO

1

BASE WALL DETAIL

1 1/2" = 1'-0"

B-A301

10

WOOD SIDING BUILD OUT

(8)

TR

10'-0"

17

'-6

"

6" THICK CONC. SLAB WITH 10-10 W.W.F. 12'-0" MIN 3 B-AS101 3 B-AS101 BOLLARDS 6" 1' -9 " 4' -8 " 3' -2 " 4' -8 " 1' -9 " 6" EQ EQ

6" THICK CONC. SLAB WITH 10-10 W.W.F. 2% MIN SLOPE 2% MIN SLOPE B-AS101 4

/

11 B-AS101

16 '-0 " 10'-0" 17 '-6 " 12'-0" MIN 6" 6" 16 '-0 " 2' -8 " M IN . 1' -0 " 5' -4 " 3" 10-10 WWF 9"

PRECAST CONCRETE CAP

COMPACTED GRANULAR BASE #5 BARS CONT. HORZ., # 5 BARS @24" VERT. #5 BARS @ 32" O.C. VERT. AND #5 BARS @ 48" O.C. HORZ.

NOTE: CONCRETE TO HAVE COMPRESSIVE STRENGTH fc=4500psi 2000 PSI MIN CMU BLOCK

6" CONCRETE PAD WITH APRON STUCCO FINISH ON CMU WALL 6" 1' -0 " 2'-8" (3) #5 CONTINUOUS TRANSVERSE, #4 AT 48" O.C. MAX B-AS101 6 2' -8 " M IN . 1' -0 " 5' -4 " 3" 9" 6" 1' -0 " 2'-8" 9" EQ EQ EQ EQ 3"

DRIP EDGE (BOTH SIDES) PRECAST CONC. CAP REBAR CMU WALL STUCCO FINISH ON EXTERIOR TO MATCH EIFS 01 9" EQ EQ EQ EQ 3" 2" 2 " 1 " 1" 5" 1/2" CENTER DECKING ON T.S. FRAME CONT. WELD 45° ANGLED STEEL DECKING TO T.O.S.

1" STRIP OF PLATE STEEL; WELD TO FRAME

NOTE: ALL STEEL SHALL BE POWDER COATED

3/8" HANDLE; 12" LONG; 4" OFF FROM GATE; WELD TO FRAME 2x4x1/4 HSS FRAME

WELD TABS TO FRAME

RAISED ROD CATCH TAB WELDED TO FRAME

HEAVY DUTY STEEL DROP ROD

1' -0 " 3" 5 1/ 2" 5" 2" 1/2"

CAST INTO CONC. 1 1/2" DIA. COLLAR 1' -0 " 3" 5 1/ 2" 5" 2" 1/2"

CAST INTO CONC. 1 1/2" DIA. COLLAR 4" 2" 1/4" CENTER DECKING ON T.S. FRAME CONT. WELD 45° ANGLED STEED DECKING TO HSS (BOTH SIDES)

1" STEEL FLAT BAR, CONT. WELD TO T.S.

4" 2"

1/4"

CENTER DECKING ON HSS FRAME

CONT. WELD 45° ANGLED STEEL DECKING TO HSS

(BOTH SIDES)

CL

1" STEEL FLAT BAR, CONT. WELD TO T.S. 4" 2" 1/4" 4" 2" 1/4" 2" CONCRETE FILLED 6x6x.25 TS

MTL DECK; WELD TO FRAME

HSS 2x4x.25 FRAME; MITER AND WELD CORNERS HEADY DUTY GATE HINGE; 3000 LBS

CAPACITY

CL

1" STRIP OF PLATE; WELD TO FRAME

3/ 4" 2"

70

0

E

A

S

T

S

T

R

E

E

T

3,599 SF

PAD C

1 3,602 SF

PAD B

1 12'-0" 2'-9 5/8" 62'-6 1/2" 9'-9 7/8" 24 '-0 " 2' -3 5 /8 " 61 '-1 0 1/ 2" 11 3 /8 " 11 '-0 " 2' -0 " 11 '-0 " 11 3 /8 " 59 '-6 1 /2 " 1' -2 1 /4 " 11 '-0 " 8' -1 1 3/ 8" 12'-0" 1'-5 5/8" 62'-6 1/2" 11'-1 7/8" TYP 309 TYP 3301 TYP 2602 2104 3302 3302 3201 3201 3201 3201 TYP 2203 TYP 3202 3203 3203 2604 2203 B-AS101 9 B-AS101 4 1002 1002 26'-0" 36'-0" 26'-0" 18'-0" 9' -0 " T YP . 18'-0" TYP. 24'-6" 4'-0" 24'-6" 36 '-0 " 26 '-0 " 8' -6 " 81 '-0 " 8' -6 " 311 311 311 5'-2 3/8" 8 9 9 8 6 TYP 2605 C-AS101 4 TYP. TYP 2607 3201 3201

HEAVY-DUTY STEEL HINGES; 3000 LBS CAPACITY MIN; TYP

6x6x1/4 CONCRETE-FILLED TUBE WITH WELDED PLATE CAP

NOTE: ALL EXPOSED STEEL SHALL BE POWDER COATED BLACK

LOCKABLE LATCH

HEAVY DUTY DROP RODS 6x6x1/4 STEEL TUBE; SET INTO

CONCRETE 4" 1' -6 " 1'-6"

SET TUBE IN CONCRETE; MIN 4" AROUND PIPE SLOPE AWAY FROM TUBE

2' -6 " 6" 1' -0 " PRECAST CONC. CAP ON CMU WALL PLATE CAP MTL DECK; PAINTED SEE PLAN SEE PLAN 2 B-AS101 10 B-AS101 B-AS101 7 5 B-AS101 8 B-AS101 4" 1' -6 " 1'-6" 2' -6 " SEE PLAN SEE PLAN 1'-6" 4' -0 " 3' -0 " 6"

DOMED CONC. CAP PAINTED

6" Ø PAINTED STEEL PIPE FILLED SOLID WITH CONC.

SLOPE TOP TO PAVING OR GRADE 7' -0 " 1'-6" 3' -0 " 6" 801.427.2233 | JARRETTARCHITECTURE.COM L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

/S p a n is h F o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2 0 2 1 8 :3 0 :5 4 A M SCALE: As indicated

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

A

R

C

H

IT

E

C

TU

R

A

L

SI

TE

PROJECT #: 2101.02

3/8" = 1'-0"

B-AS101

9

TRASH ENCLOSURE PLAN

3

DUMPSTER ENCLOSURE WALL

1 1/2" = 1'-0"

B-AS101

6

DUMPSTER ENCLOSURE CAP

3" = 1'-0"

B-AS101

7

GATE DROP LATCH

3" = 1'-0"

B-AS101

8

DUMPSTER GATE HANDLE

3" = 1'-0"

B-AS101

5

DUMPSTER GATE DROP ROD

2

DUMPSTER GATE SECTION

3" = 1'-0"

B-AS101

10

DUMPSTER GATE HINGE DETAIL1

1

SITE PLAN

3/8" = 1'-0"

11

DUMPSTER GATE ELEVATION

4

BOLLARD DETAIL

KEYNOTES

#

DESCRIPTION

309 6" CONCRETE BOLLARD W/ BLACK HOUSING

311 BOARD FORMED CONCRETE PLANTER WITH 1/2" PVC WEEPS AT BASE OF WALL ON TOP OF FOOTING SPACED 24" ON CENTER. SEE LANDSCAPE DRAWINGS FOR DETAILS.

1002 MANUFACTURED METAL LADDER WITH LOCKED SECURITY PANEL. PAINT BLACK WITH HIGHT-PERFORMANCE PAINT.

2104 FIRE HYDRANT PER CIVIL

2203 SITE DRAINAGE, SEE CIVIL DRAWINGS.

2602 ELECTRICAL POWER AND DISCONNECT PER ELECTRICAL PLANS

2604 ELECTRICAL TRANSFORMER PER CIVIL AND ELECTRICAL PLANS AND DETAILS 2605 POLE LIGHT, SEE ELECTRICAL DRAWINGS

2607

3201 DETECTABLE WARNING SURFACE, PER APWA PLAN NO. 238 AND ADA COMPLIANT RAMP 3202 ACCESSIBLE PARKING SIGNAGE

3203 6" CONCRETE CURB

3301 GAS METERS, SEE MECHANICAL DRAWINGS 3302 8 YD DUMPSTER AND 8 YD RECYLCE DUMPSTER

(9)

B-4

B-4

B-3

B-3

B-2

B-2

B-1

B-1

B-A

B-A

B-B

B-B

B-C

B-C

60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 1" T YP . 60'-0" 20'-0" 20'-0" 20'-0" 2'-4" 1" 8'-5" 11'-7" 2'-4" 1" 1'-0 1/2" 17'-1 3/4" 1'-9 3/4" 4 3/4" 19'-7 1/4" 1" 63 '-0 " 30 '-0 " 33 '-0 " 1" 6' -1 1" 10 '-6 1 /8 " 12 '-6 7 /8 " 1' -1 1 3/ 8" 20 '-5 " 2' -2 1 /2 " 8' -5 1 /4 " 1" 2' -0 " 1" 11" C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A C8A H O LD S LA B BA C K FO R P LU M BI N G 5' -0 " 701 TYP 601 601 2 3/4" 2 3/ 4" TYP 303 C8 C8 C8A C8 C8 C8A 1'-5 1/2" 1' -5 1 /2 " 13'-2" 3'-11 3/4" 3'-4 3/8" 13'-2" 3'-5 5/8" 307 307 TYP 302 TYP 302 T.O.F. 100'-0" T.O.F. 100'-0" T.O.F. 100'-0" T.O.F. 100'-0" TYP 306 TYP 306 TYP 306 5 B-A400 5 B-A400 1 B-A400 1 B-A400 1 B-A400 1 B-A400 5 B-A400 1 B-A400 1 B-A400 T.O.F. 99'-8" T.O.F. 99'-8" T.O.F. 99'-8" T.O.F. 100'-0" T.O.F. 99'-5" T.O.F. 99'-8" TYP 702 60'-0" 20'-0" 20'-0" 20'-0" 63 '-0 " 30 '-0 " 33 '-0 " 7' -0 " 23 '-1 " 4' -8 3 /8 " 13 '-5 1 /2 " 14 '-1 0 1/ 8" 2' -1 " 1" T YP . 60'-0" 20'-0" 20'-0" 20'-0" 2'-4" 1" 8'-5" 11'-7" 2'-4" 1" 1'-0 1/2" 17'-1 3/4" 1'-9 3/4" 4 3/4" 19'-7 1/4" 1" 63 '-0 " 30 '-0 " 33 '-0 " 1" 6' -1 1" 10 '-6 1 /8 " 12 '-6 7 /8 " 1' -1 1 3/ 8" 20 '-5 " 2' -2 1 /2 " 8' -5 1 /4 " 1" 2' -0 " 1" 11" 2 3/4" 2 3/ 4" 1'-5 1/2" 1' -5 1 /2 " 13'-2" 3'-11 3/4" 3'-4 3/8" 13'-2" 3'-5 5/8" 10'-7" 9'-5" 1" 10'-7" 9'-5" 1" 9" 3'-4" 5'-4" 9" 3'-4" 4'-4"

1. TOP OF SLAB AND FOUNDATION WALLS SHALL BE AT A REFERENCE ELEVATION 100'-0". 2. DIMENSIONS ARE TO FACE OF CONCRETE U.N.O.

3. PROVIDE ARCHITECTURAL CONCRETE FINISH WHERE FOUNDATION IS EXPOSED TO VIEW. 4. FOUNDATION WALLS ARE 8" CONCRETE WALLS U.N.O.

5. SEE STRUCTURAL FOR CONTROL JOINT SPACING.

6. ALL CONTROL JOINTS SHALL BE SAW CUT TO A DEPTH OF 1/4 OF THE THICKNESS OF THE SLAB, BUT NOT LESS THAN 1".

7. PROVIDE ISOLATION JOINTS BETWEEN SLABS AND COLUMNS, WALLS AND FOOTINGS. 8. APPLY DAMPPROOFING TO ALL EXTERIOR BELOW GRADE SURFACES OF EXTERIOR

UNDERGROUND WALLS IN CONTACT WITH EARTHWORK.

9. EXTEND VERTICAL DAMPPROOFING DOWN WALLS FROM FINISH GRADE LINE TO TOP OF FOOTING. EXTEND OVER TOP OF FOOTING AND TURN DOWN MIN. OF 6" OVER OUTSIDE FACE OF FOOTING. DO NOT EXTEND ONTO SURFACES THAT WILL BE EXPOSED TO VIEW WHEN PROJECT IS COMPLETED.

10. FINISH FLOOR AND SLABS

A. COMPLY WITH ACI 302.1R RECOMMENDATOINS FOR SCREEDING, RESTRAIGHTENING, AND FINISHING OPERATIONS FOR CONCRETE SURFACES. DO NOT WET CONCRETE SURFACES.

B. TROWEL FINISH: AFTER APPLYING FLOAT FINISH, APPLY FIRST TROWELING AND CONSOLIDATE CONCRETE BY HAND OR POWER-DRIVEN TROWEL. CONTINUE

TROWELING PASSES AND RESTRAIGHTEN UNTIL SURFACE IS FREE OF TROWEL MARKS AND UNIFORM IN TEXTURE AND APPEARANCE. GRIND SMOOTH ANY SURFACE DEFECTS THAT WOULD TELEGRAPH THROUGH APPLIED COATINGS OR FLOOR COVERINGS.

a. APPLY A TROWEL FINISH TO SURFACES EXPOSED TO VIEW OR TO BE COVERED WITH RESILIENT FLOORING, CARPET, CERAMIC OR QUARRY TILE SET OVER A CLEAVAGE MEMBRANE, PAINT, OR ANOTHER THIN-FILM-FINISH COATING SYSTEM.

b. FINISH SURFACES TO THE FOLLOWING TOLERANCES, ACCORDING TO ASTM E 1155 (ASTM E 1155M), FOR A RANDOMLY TRAFFICKED FLOOR SURFACE: • SPECIFIED OVERALL VALUES OF FLATNESS, F(F) 30; AND OF LEVELNESS,

F(L) 20; WITH MINIMUM LOCAL VALUES OF FLATNESS, F(F) 24; AND OF LEVELNESS, F(L) 15; FOR SUSPENDED SLABS.

C. FINISH AND MEASURE SURFACE SO GAP AT ANY POINT BETWEEN CONCRETE SURFACE AND AN UNLEVELED, FREESTANDING, 10-FT LONG STRAIGHTEDGE RESTING ON TWO HIGH SPOTS AND PLACED ANYWHERE ON THE SURFACE DOES NOT EXCEED 3/16 INCH.

L I C E N S E D A RCHI TE CT ST AT E OF UTA H

NYBO

11318093-0301

EMILY

70

11

E

A

ST

8

00

N

O

R

TH

SP

A

N

IS

H

F

O

R

K

U

T,

8

46

60

o rk R e ta il/ S p a n is h F o rk R e ta il P a d s B a n d C .r v t 2 /1 6 /2 0

SP

A

N

IS

H

F

O

R

K

R

E

TA

IL

C

O

N

TR

O

L

P

LA

N

3/16" = 1'-0"

B-A200

1

PAD B - LEVEL 1 CONTROL PLAN

KEYNOTES

#

DESCRIPTION

302 CONCRETE CONTROL JOINT

303 SMOOTH TROWEL FINISH TOP OF CONCRETE POUR-BACK SLAB AT 100'-0" AFF. SEE STRUCTURAL DETAILS

306 CONCRETE FOOTING, SEE STRUCTURAL 307 CONCRETE SLAB OVER COMPACTED FILL 601 COLUMN, SEE STRUCTURAL DRAWINGS 701 RIGID INSULATION

702 RIGID INSULATION BELOW SLAB, SEE COMMCHEC

References

Related documents

The current research describes the adaptation of an informant-rating instrument (the Extreme Demand Avoid- ance Questionnaire; O’Nions et al. 2014b ; EDA-Q) for use as a

This model posits four types of health beliefs that affect an individual’s health behavior, in this case, the decision to seek mental health services: perceived

The rhetoric of the supremacy of the ‘golden coin’ of free markets and democracy championed by Johnson in his vision for Global Britain and future engagement with Africa

• CAIR Research pilot using community based participatory principles to document stories of resilience among urban American Indian elders at the Tucson Indian Center. •

The kitchen, the dining room, the hall and even the downstairs bedroom all have French doors that open onto a large patio terrace and then the rest of the garden is laid to lawn..

This Service Level Agreement (SLA or Agreement) document describes the general scope and nature of the services the Company will provide in relation to the System Software (RMS

Game referred to in the second column in the affected Magisterial Districts referred to in the third column, excluding the Magisterial Districts referred to in the fourth.. column

A synthetic jet flow which has a wide range of flow field features including high velocity gradients and regions of high vorticity was used as a rigorous test bed to determine