• No results found

600 Volt Class Transformers

N/A
N/A
Protected

Academic year: 2021

Share "600 Volt Class Transformers"

Copied!
66
0
0

Loading.... (view fulltext now)

Full text

(1)

600 V

olt Class

600 Volt Class Transformers

600 V

(2)

600 V

olt Class

Table of Contents - 600 Volt Class Transformers

Full Load Current Tables . . . .12

General Information, Standards, Testing . . . . .13

Selection and Application Considerations . . . .14

Transformer Descriptions

Type FB, Non-Ventilated, Compound Filled . .16

Type FH, Ventilated . . . .17

Optional Temperature Rise Transformers . . . .18

Electrostatically Shielded Transformers . . . . .18

Energy Efficient Transformers . . . .19

Buck-Boost Transformers . . . .20

Technical Data/Selection Tables

Buck Boost . . . .21

Single-Phase General Purpose . . . .25

Single-Phase Optional Temperature Rise . . . .27

Three-Phase General Purpose,

Aluminum and Copper . . . .28

Three-Phase Optional Temperature Rise

Aluminum and Copper . . . .32

NEMA Premium

®

. . . .38

Motor Drive Isolation Transformer . . . .40

Machine Tool Transformers . . . .42

K-Factor Rated Transformers . . . .43

Accessories . . . .59

Specification Guide . . . .60

Buck-Boost Connection Diagrams . . . .61

Wiring Diagrams . . . .66

Page

Page

Full Load Current Ratings

KVA

Rating 120 V Full Load Current (Amperes)240 V 480 V 600 V

.050 0 .42 0 .21 0 .1 0 .08 .075 0 .63 0 .31 0 .16 0 .13 .100 0 .83 0 .42 0 .21 0 .17 .150 1 .25 0 .63 0 .31 0 .25 .250 2 .08 1 .04 0 .52 0 .42 .500 4 .17 2 .08 1 .04 0 .83 .750 6 .25 3 .13 1 .56 1 .25 1 8 .33 4 .17 2 .08 1 .67 1 .5 12 .5 6 .25 3 .13 2 .5 2 16 .7 8 .33 4 .17 3 .33 3 25 12 .5 6 .25 5 5 41 .7 20 .8 10 .4 8 .33 7 .5 62 .5 31 .3 15 .6 12 .5 10 83 .3 41 .7 20 .8 16 .7 15 125 62 .5 31 .2 25 25 208 104 52 41 .7 37 .5 312 156 78 .1 62 .5 50 417 208 104 83 .3 75 625 312 156 125 100 833 417 208 167 167 1392 696 348 278 KVA Rating

Full Load Current (Amperes)

208 V 240 V 480 V 600 V 3 8 .33 7 .22 3 .61 2 .89 6 16 .6 14 .4 7 .22 5 .77 9 25 21 .6 10 .8 8 .66 15 41 .6 36 .1 18 14 .4 25 69 .4 60 .1 30 .1 24 .1 30 83 .3 72 .2 36 .1 28 .9 37 .5 104 90 .2 45 .1 36 .1 45 125 108 54 .1 43 .3 50 139 120 60 .1 48 .1 60 166 144 72 .2 57 .7 75 208 180 90 .2 72 .2 100 278 241 120 96 .2 112 .5 312 271 135 108 150 416 361 180 144 225 625 541 271 217 300 833 722 361 289 400 1110 962 481 385 500 1388 1203 601 481 750 2082 1804 902 722 1000 2776 2406 1203 962

(3)

600 V

olt Class

General Information

What is a Transformer?

A transformer is an electrical ap-paratus designed to convert alter-nating voltage from one voltage level to another . Transformers are completely static devices without continuously moving mechanical parts, which, by electromagnetic induction, transform electrical en-ergy from one or more circuits to one or more other circuits at the same frequency .

In most cases, transformers change the voltage from an incoming source to its outgoing load . Trans-formers can be used to increase (step up) or decrease (step down) voltages . Sometimes transform-ers do not change voltages; that is, they are not used for step up or step down purposes . These transformers are only used for isolation .

Electric power is always distributed over a wide area by means of alter-nating current . Direct current is not used for several reasons, the most important being that it cannot be changed from one voltage level to another without expensive conver-sion equipment . Alternating current however can be simply changed to any convenient voltage by the use of transformers .

Description

Federal Pacific dry-type transform-ers rated 600 volts and below are available in a wide variety of types and ratings to provide reliable and versatile electrical distribution for lighting and power loads in indus-trial and commercial applications . Ratings in the 600V class are avail-able from .050 through 333 KVA in single-phase configurations and from 3 through 1500 KVA in three-phase . All standard primary and secondary voltage ratings are pro-vided to match load requirements to the distribution system .

for installation . The units may be located in almost any indoor loca-tion convenient to the load being served . Most transformers are also available for outdoor installations . Maintenance requires only periodic inspection of cable connections and removal of any dust accumulation .

Industry Standards

Federal Pacific dry-type trans-formers are UL® Listed and are

designed, tested, and manufactured in accordance with applicable in-dustry standards: • UL-5085, UL 1561, UL 1562 • CUL • IEEE C57 .12 .01 • IEEE C57 .12 .91 • NEMA ST-20 • EPACT 2005

• Meets DOE Efficiency Levels as required by 10 CFR 431 and NEMA TP1(1)

Tested Performance

Ratio Test is performed on rated

voltage connection and tap connec-tions to assure proper turns ratio on all connections .

Polarity Test and phase relation

tests are made to ensure proper po-larity and marking because of their importance in paralleling or bank-ing two or more transformers .

No-load (excitation) Loss Test

de-termines the losses of a transformer which is excited at rated voltage and frequency, but which is not supplying a load . Transformer ex-citation loss consists mainly of the iron loss in the transformer core .

Load Loss Test determines the

amount of losses in the transformer when carrying full rated load . These losses consist primarily of I2R losses in the primary and

sec-ondary winding and ensure that specifications of the transformer design are met .

Excitation Current Test

deter-mines the current necessary to maintain transformer excitation .

Resistance Test is performed on

the transformer windings and is used to determine I2R loss .

Impedance Test is made to insure

that transformer design standards are attained .

Dielectric Test (applied and

in-duced potential) checks the insula-tion and workmanship to demon-strate that the transformer has been designed and manufactured to meet the insulation tests required by the standards .

Applied Potential Tests are made

by impressing between windings and between each winding and ground, a low frequency voltage .

Induced Potential Tests call for

over-exciting the transformer by applying between the terminals on one winding a voltage of twice the normal voltage developed in the winding for a period of 7200 cycles .

Primary Taps

All Federal Pacific three-phase transformers and most single-phase models are provided with taps in the primary winding to compensate for input voltage variations . The taps will provide a range of volt-age adjustment above and/or below the nominal voltage rating of the transformer . The available quantity, location, and percentage of the tap connections are shown in the trans-former listings . All transtrans-formers are furnished with a nameplate show-ing the terminal and tap arrange-ments .

(4)

600 V

olt Class

be equal to or greater than the transformer sound level . Avoid locating units in corners . Make connections with flexible conduits and couplings to prevent transmitting vibration to other equipment . Larger units should be installed on flexible mountings to isolate the transformer from the building structure . Federal Pacific transformers are designed, built, and comply with NEMA maximum sound level requirements as measured in accordance with NEMA ST 20-2014 .

Temperature

Insulation system limiting temperatures for FH Style dry-type transformers are classified by industry standards based on a 40°C ambi-ent, 25°C ambient for FB Styles .

Selection and Application Considerations

For a Wye-Wye connection Federal Pacific recommends that a four-legged or five-legged core be employed .

For auto-transformers:

Federal Pacific recommends using a Wye-Wye connection to minimize cost. Precau-tions to avoidunbalanced phase loading con-ditions should be undertaken.

Sound Levels

A humming sound is an inherent charac-teristic of transformers due to the vibration caused by alternating flux in the magnetic core . Sound levels will vary according to transformer size . Attention to installation methods can help reduce any objectionable noise . When possible, locate the transformer in an area where the ambient sound will

Selection Steps

• Determine the system supply voltage available (primary voltage) .

• Determine the required load voltage rating (secondary voltage) .

• Determine the KVA rating of the load . (If the load rating is given only in amperes, the proper KVA size of the transformer can be selected from the charts on page 12 .) The KVA capacity of the transformer must equal or be greater than the load rat-ing .

• Select a transformer model from the listings on the following pages .

Connections

Many single-phase transformers are provided with a series multiple winding construction and a dual voltage primary or secondary iden-tification (i.e. 240 x 480 to 120/240). These transformers will have two windings on the primary or secondary that can be connected either in series for the higher voltage or in parallel for the lower voltage . Transformers with voltage ratings containing an "x" can only be connected for one or the other of the two voltages . On those units with voltage rat-ings separated by a "slant", the windrat-ings can be connected to provide either or both volt-ages (three wire operation) .

Three-phase transformers are provided with a delta primary for three wire input and either a wye secondary for four wire output or a delta secondary for three wire output . Trans-formers with 240 volt delta secondaries may have a 120 volt single-phase lighting tap as a standard feature . Maximum single-phase 120 volt load should not exceed 10% of the three-phase KVA rating . The load should also be balanced at 5% maximum between ter-minals X1 to X4 and 5% between terter-minals X2 to X4 . The three-phase KVA must also be reduced by 30% of the nameplate rating . For example, a 45 KVA transformer can have a 4 .5 KVA maximum single-phase, 120 volt load . Of that 4 .5 KVA, 2 .25 KVA must be loaded between X1 - X4 and 2 .25 KVA must be loaded between X2 - X4 . The three-phase KVA rating must be reduced to 31 .5 KVA .

Preferred 3-Phase

Connections

(Applies to 600 volt and medium volt ratings)

For two winding transformers:

The preferred winding connections are: Del-ta-Wye, Delta-Delta and Wye-Delta . For all

150°C Rise 115°C Rise 80°C Rise

Average Temperature Rise 115°C Average Temperature Rise 80°C Hot Spot 30°C 30% Thermal Overload 15% Thermal Overload Max. Max. Hot Spot 30°C Average Temperature Rise 150°C Hot Spot 30°C Max. 220°C 220°C 220°C

Average Sound Level, Decibels

Self Cooled Ventilated Self Cooled Sealed

A B C D Equivalent Winding kVA Range K Factor = 1 K Factor = 4

K Factor = 9 K Factor = 13K Factor = 20 Forced Air WhenFans Running

3.00 and below 40 40 67 45 3.01 to 9.00 40 40 67 45 9.01 to 15.00 45 45 67 50 15.01 to 30.00 45 45 67 50 30.01 to 50.00 45 48 67 50 50.01 to 75.00 50 53 67 55 75.01 to 112.50 50 53 67 55 112.51 to 150.00 50 53 67 55 150.01 to 225.00 55 58 67 57 225.01 to 300.00 55 58 67 57 300.01 to 500.00 60 63 67 59 500.01 to 700.00 62 65 67 61 700.01 to 1000.00 64 67 67 63

Greater than 1000 Consult Factory

Note 1: Consult factory for non-linear requirements exceeding a K-factor rating of 20. Note 2: When the fans are not running columns A & B apply

(5)

600 V

olt Class

The angular displacement for three-phase transformers with delta-wye connections is 30 degrees with the low voltage lagging the high volt-age .

Parallel Operation

Transformers with the same KVA ratings can be connected in parallel if required conditions are met . Sin-gle-phase transformers must have the same voltage rating, tap settings and frequency rating . Plus, the im-pedance values of the transformers must be within 7 .5% of each other . When paralleling three-phase trans-formers, the same conditions would apply and, in addition, the angular displacement of the transformers must be the same .

Transformer Banking

Three single-phase transformers can be properly connected to sup-ply a three-phase load . The single-phase units can be used in a three-phase bank with delta connected primary and wye or delta connected secondary . The equivalent three-phase capacity would be three times the nameplate rating of each single-phase transformer . For ex-ample, three 15 KVA single-phase transformers will, when properly banked, accommodate a 45 KVA three-phase load .

Balanced Loading

Single-phase loads connected to the secondary of a transformer must be distributed so as not to overload any one winding of the transformer . Single-phase transformers gener-ally have two winding secondaries that can be connected for 120/240 volt three wire operation . When so arranged, care must be taken when connecting 120 volt loads to assure that the total connected load on each secondary winding does not exceed one-half the nameplate KVA rating .

Selection and Application Considerations

each phase must be considered as a single-phase transformer . The sin-gle-phase loading on each phase of a three-phase transformer must not exceed one-third of the nameplate KVA rating . For example, a 45 KVA three-phase transformer with a 208Y/120 Volt secondary should not have any 120 volt single-phase loads distributed such that more than 15 KVA of single-phase load is applied to any one phase .

Transformer Protection

(Reference N.E.C. Article 450)

Transformers - 600 Volts or Less Primary Protection Only

If secondary protection is not vided, a transformer must be pro-tected by an individual overcurrent device on the primary side . The primary overcurrent device must be rated: No more than 125% of the rated primary current or the next higher standard device rating (for primary currents of 9 amperes or more); no more than 167% of the rated primary current (for 2 am-peres to 9 amam-peres); and no more than 300 % of the rated primary current (for ratings less than 2 am-peres) . An individual transformer primary protective device is not necessary where the primary circuit overcurrent protective device pro-vides the required protection .

Primary & Secondary Protection

If the transformer secondary is pro-tected by an overcurrent protective device rated no more than 125% of the transformer rated secondary current (or the next higher standard rating device), an individual prima-ry protective device is not required provided the primary feeder circuit overcurrent device is rated no more than 250% of the transformer rated primary current .

Altitude

Standard self-cooled dry-type transformers are designed for oper-ation with normal temperature rise at altitudes up to 3300 ft . above sea level . The transformer rated KVA should be reduced by 0 .3% for each 330 ft . the transformer is installed above 3300 ft .

Polarity

Transformer polarity is an indica-tion of the direcindica-tion of current flow through the high voltage terminals with respect to the direction of cur-rent flow through the low voltage terminals at any given instant in the alternating cycle .

Primary and secondary terminals are said to have the same (or addi-tive) polarity when, at a given in-stant, the current enters the primary terminal in question and leaves the secondary terminal in question in the same direction as though the two terminals formed a continuous circuit .

Single-phase transformers rated 600 volts and below normally have additive polarity .

The polarity of a three-phase transformer is fixed by the internal connections between phases . It is usually designated by means of a vector diagram showing the angu-lar displacement of the windings and a sketch showing the markings of the terminals .

Angular Displacement

The angular displacement of a three-phase transformer is the time angle expressed in degrees between the line-to-neutral voltage of a specified high voltage terminal and the line-to-neutral voltage of a specified low voltage terminal. The angular displacement between the high voltage and low voltage terminal voltages of three-phase

(6)

600 V

olt Class

Type FB Transformers

Non-Ventilated • Indoor / Outdoor

Single-Phase: .050 to 15 KVA

Three-Phase: 3 to 15 KVA

Construction

The Type FB dry-type transformer is a totally enclosed, compound filled transformer. The core and coil assembly connections. Compartment

tem-peratures can attain temtem-peratures reaching 90°C; therefore 90°C cable should be used.

• These units are supplied with flex-ible cable leads marked with easy identification, and are supplied with wall-mounting brackets to reduce installation time.

Application

Federal Pacific UL & CUL Listed Type FB dry-type transformers can be used in industrial, commercial, institutional, and residential

installa-tions for economical, efficient distri-bution of power.

Typical loads served include tan-ning beds, motors, lighting, heating, ranges, air conditioners, exhaust fans, control circuits, appliances, and portable tools. Other applica-tions are found in pumping staapplica-tions, mining and shipboard distribution systems.

Type FB units are ideal for dusty industrial areas and are suitable for

Indoor / Outdoor applications.

is embedded in a polyester resin compound, which provides a solid insulation. The embedding com-pound has an extremely high heat transfer rate, which permits a de-sign of minimum size and weight. The compound-filled assembly is completely encased in a sturdy steel housing and cannot be dam-aged by dust, moisture, or adverse atmospheric conditions.

• Intentionally designed for a low enclosure temperature rise, no UL-506 special markings are needed to indicate clearance be-tween the enclosure and adjacent surfaces.

• Type FB transformers are made in a temperature class based on a 25°C ambient, 115°C rise, 180°C insulation system.

• Sound level problems are negli-gible with Type FB transformers because the core and coils are rig-idly encased in the polyester resin which is mechanically strong and acts as sound deadening material. Average sound levels are

consis-Selection and Application Considerations

Step-down transformers may be

reverse fed for step-up operation to increase voltage. This means that the incoming power is connected to the low voltage (X’s) and the load is connected to the high voltage (H’s). If the low voltage is wye, the X0 terminal must NOT be con-nected in any way. Likewise, if the

For Reverse Feed (Back feed), or Step-Up Operation Only

low voltage is a delta with a 120 volt lighting tap (high-leg), the X4 terminal must NOT be connected in any way.

CAUTION: Much higher than

normal inrush currents may occur with reverse feed operation and may cause nuisance fuse blowing

or breaker tripping. For this reason, fuses and breakers with time-delay characteristics must be used. If a breaker is used for incoming over-current protection, it must be a thermal-magnetic type breaker, not a magnetic-only type breaker.

(7)

600 V

olt Class

Type FH Transformers

Construction

The Type FH line of ventilated dry-type transformers incorporates wire and/or strip wound coils in a barrel wound configuration. Horizontal and vertical spacers are strategi-cally positioned in the windings to brace the winding layers and allow maximum ventilation . The electri-cal grade core steel is arranged in a construction designed to accommo-date the coils .

Vibration Dampening

System

The core and coil assembly is an-chored to the enclosure through a vibration dampening system to reduce noise levels . Units through 600 KVA are provided with neo-prene isolating pads while larger units are furnished with three layer rubber and cork pads. A flexible grounding conductor is installed between the core and coil assembly and the transformer enclosure .

Rugged Enclosure

Enclosures are rigidly braced and covers are fastened with slotted hex head screws for ease of removal . A rugged steel base supported by mounting feet opened outward pro-vides safe handling with a fork lift and easy attachment to mounting pad .

Wiring Compartments

Front accessible wiring compart-ments are approved for 90°C cable . Terminals are sized to carry the full current capacity of the transformers .

UL Listed 220 °C Insulation

System

To attain UL listing, it was neces-sary to complete an accelerated ag-ing test as specified by Underwrit-ers Laboratories, Inc .

This insulation system was sub-jected to a series of exposures to heat, vibration, moisture, and di-electric tests . As a proven system this insulation system has received from Underwriters Laboratories, Inc . a recognized 220°C continu-ous rating . This total temperature of 220°C is derived from the aver-age conductor temperature rise of 150°C, hotspot temperature gradi-ent of 30°C, and an ambigradi-ent tem-perature of 30°C .

The major components that allow for this 220°C rating are Nomex®

paper, resin-glass laminates, sili-con rubber, and polyester varnish .

This combination of materials and the care taken in construction and workmanship, not only give Feder-al Pacific Type FH Transformers a long operating life, but helps insure their quiet operation .

Versatile Performance

The design features of the Federal Pacific Type FH family of UL List-ed transformers assures versatile, economical, and reliable distribu-tion of power . All transformers are fully tested to insure trouble-free installation and operation . The unique combination of ratings makes the FH family suitable for a wide variety of applications . † Dupont T.M.

Ventilated

Single-Phase: 15 to 333 KVA

Three-Phase: 7.5 to 1500 KVA

(8)

600 V

olt Class

Electrostatically Shielded Transformers

Electrostatically shielded transformers are designed to protect primary systems from unwanted high-frequency signals generated by loads connected to the transformers secondary .

While all transformers with sepa-rate primary and secondary wind-ings isolate the load circuits, tran-sients and electrical noise can be transmitted through the interwind-ing capacitance of the transformer . These disturbances may have a detrimental effect on sensitive electronic equipment and can cause improper operation . Electrostatic shielding brings these unwanted signals to ground thus preventing the electrical disturbances from be-ing transmitted to the load circuits . Federal Pacific UL Listed electro-statically shielded transformers

provide all the quality features of the transformer plus an electrostatic shield consisting of a single turn, full height, copper or aluminum strip placed between the primary and secondary windings with a lead run to the transformer ground .

Applications

Electronic products ranging from solid state control relays to com-plex medical equipment are suscep-tible to malfunction due to transient disturbances in the power supply .

Typical applications would include: • Hospital Operating Rooms • X-Ray Equipment

• Computer Installations • Data Processing • Instrumentation

• Programmable Controllers

Optional Temperature Rise Transformers

Energy Saving Optional

Temperature Rises

Transformers are specifically designed for optimum performance on systems with a continuous high loading factor. The units

feature either 80°C or 115°C temperature rise utilizing a 220°C insulation system which provides extended life and inherent overload capability (15% for 115°C and 30% for 80°C.) The transformers provide lower losses and minimize

operating costs. The amount of savings will depend on loading factors and local energy costs. (See page 27 for single-phase model listings and 32-37 for three-phase model listings.)

Secondary Winding

Electrostatic Shield (grounded) Primary Winding

(9)

600 V

olt Class

Energy Efficient Transformers

Federal Pacific's Energy Efficient

Transformers are designed to meet the guidelines offered by the National Electrical Manufacturers Association (NEMA) Standard TP-1-2002 and EPACT 2005 . The NEMA guidelines require low voltage (600 V or less) isolation-type distribution transformers 15 kVA and above to have

efficiency ratings as set forth in the NEMA Standard "Guide for Determining Energy Efficiency for Distribution Transformers" .

This guideline considers the Total Ownership Cost (TOC) method

where loading is defined as being 35% of nameplate at a temperature of 75° C .

The Key Product Criteria as defined in Table 1 (below) for Industrial Transformers (Single and Three-Phase) relates the required efficiency level by kVA.

Federal Pacific "Energy Efficient Transformers" are in compliance with 10 CFR 431 . Test procedures are performed in accordance with Apendix A to Subpart K of 10 CFR Part 431 .

15 kVA through 1000 kVA

All Federal Pacific dry-type transformers are built and tested to applicable Industry Standards of ANSI, NEMA and IEEE .

Standards and

Certifications

*Efficiencies shown at 35% load and 75°C as defined by NEMA®

Standard TP-1-2002

TABLE 1*

NEMA Class 1 Efficiency Levels for Dry-Type Distribution Transformers

Single Phase Three Phase

kVA Efficiency Level (%) kVA Efficiency Level (%)

15 97.7 15 97.0 25 98.0 30 97.5 37 98.2 45 97.7 50 98.3 75 98.0 75 98.5 112.5 98.2 100 98.6 150 98.3 157 98.7 225 98.5 250 98.8 300 98.6 333 98.9 500 98.7 750 98.8 1000 98.9

(10)

600 V

olt Class

Application

The Type FB Insulating and Buck-Boost Transformer has four sepa-rate windings, two windings in the primary and two windings in the secondary . The unit is designed for use as an isolating transformer or as an auto-transformer . As an autotrans-former the unit can be connected to Buck (decrease) or Boost (increase) a supply voltage . When connected in either the Buck or Boost mode, the unit is no longer an isolating transformer but is an autotransformer . Autotransformers are more eco-nomical and physically smaller than equivalent two-winding transformers designed to carry the same load . They will perform the same function as two-winding transformers with the exception of isolating two circuits . Since autotransformers may transmit line disturbances directly, they may be prohibited in some areas by lo-cal building codes . Before applying them, care should be taken to assure that they are acceptable according to local code .

Note: Three autotransformers are not used in closed delta connections as they introduce into the circuit a phase shift .

As isolating transformers, these units can accommodate a high voltage of 120x240 volts (SB12N and SB16N series) or 240x480 volts (SB24N se-ries .) For the units with two 12 volt secondaries, the low voltage output can be 12 volts, 24 volts, or 3-wire 24/12 volts . For the units with two 16 volt secondaries, the output voltages can be 16 volts, 32 volts, or 3-wire 32/16 volts . For the units with two 24 volt secondaries, the output voltages can be 24 volts, 48 volts, or 3 wire 48/24 volts .

Operation

Electrical and electronic equipment is designed to operate on a standard supply voltage . When the supply volt-age is constantly too high or too low, (usually greater than ± 5%), the equip-ment may fail to operate at maximum efficiency. A Buck-Boost transformer

up to ± 20% . A Buck-Boost trans-former will NOT, however, stabilize a fluctuating voltage.

Buck-Boost transformers are suitable for use in a three-phase autotrans-former bank in either direction to supply 3-wire loads . They are also suitable for use in a three-phase au-totransformer bank which provides a neutral return for unbalanced current . They are not suitable for use in a three-phase autotransformer bank to supply a 4-wire load when the source is only a 3-wire circuit, having no neutral .

Selection

To select the proper transformer for Buck-Boost applications, determine:

1. Input Line Voltage- the voltage

that you want to buck (decrease) or boost (increase) . This can be found by measuring the supply line voltage with a voltmeter .

2. Output Load Voltage- the voltage

at which your equipment is designed to operate . This is listed on the name-plate of the load equipment .

3. Load KVA or Load Amps- you

do not need to know both - one or the other is sufficient for selection purposes . This information usually can be found on the nameplate of the equipment that you want to operate .

4. Number of Phases- single- or

three-phase line and load should match because a transformer is not capable of converting single-phase to three-phase . It is, however, a common application to make a single-phase transformer connection from a three-phase supply by use of one leg of the three-phase supply circuit . Care must always be taken not to overload the leg of the three-phase supply . This is particularly true in a Buck-Boost application because the supply must provide the load KVA, not just the nameplate rating of the Buck-Boost transformer .

5. Frequency- the supply line

fre-quency must be the same as the frequency of the equipment to be

Six Step Selection

1. Choose the selection table with the

correct number of phases . Tables I, III and V for single-phase applica-tions and Tables II, IV and VI for three-phase applications . Tables I and II are for 120x240-12/24 volt units, tables III and IV are for 120x240-16/32 volt units and tables V and VI are for 240x480-24/48 volt units .

2. Line/Load voltage combinations

are listed across the top of the selec-tion table . Use the boosting or bucking columns where appropriate .

3. Follow the selected column down

until you find either the load KVA or load amps of your application . If you do not find the exact value, go on to the next highest rating .

4. Follow across the table to the far

left-hand side to find the catalog number of the transformer you need .

5. Follow the column of your line/

load voltage to the bottom to find the connection diagram for this applica-tion . NOTE: Connecapplica-tion diagrams show low voltage and high voltage connection terminals . Either can be input or output depending on buck or boost application .

6. In the case of three-phase loads,

two (open Delta) or three (Wye) single-phase transformers are re-quired as indicated in the "quantity required" line at the bottom of Table II, IV or VI . Select depending on whether a Wye connected bank of three transformers with a neutral is required or whether an open Delta connected bank of two transformers for a Delta connected load will be suitable .

For line/load voltages not listed on table, use the pair listed on the table that is slightly above your application for reference. Then apply the first formula at the bottom of the page to determine "New" output voltage . The new KVA rating can be found using the second formula .

For more extensive Buck-Boost combinations and connections go to

(11)

600 V

olt Class

Buck-Boost Technical Data

N/R - Not Required

† Connection diagram when used as an isolation transformer

Type FB: 115° C Rise • 180° C Insulation System • Non-Ventilated • Indoor/Outdoor

Type KVA NumberCatalog Taps Approximate EnclosureDimension - Inches Approx.Total Lbs.

Weather

Shield Diagram Wiring

Wall Mount Bracket H W D 120 x 240 - 12/24 Volts, 60 Hz, No Taps FB

0 .050 SB12N .050F No Taps 8 .25 3 .25 4 .25 8 N/R 10A N/A 0 .100 SB12N .100F No Taps 8 .25 3 .25 4 .25 10 N/R 10A N/A 0 .150 SB12N .150F No Taps 9 .25 4 5 14 N/R 10A N/A 0 .250 SB12N .250F No Taps 9 .25 4 5 15 N/R 10A N/A 0 .500 SB12N .500F No Taps 11 .25 5 .25 6 .5 21 N/R 10A N/A 0 .750 SB12N .750F No Taps 11 .25 5 .25 6 .5 25 N/R 10A N/A 1 SB12N1F No Taps 11 .25 5 .25 6 .5 28 N/R 10A N/A 1 .5 SB12N1 .5F No Taps 13 .25 6 .25 7 .75 45 N/R 10A N/A 2 SB12N2F No Taps 13 .25 6 .25 7 .75 50 N/R 10A N/A 3 SB12N3F No Taps 13 .25 6 .25 7 .75 60 N/R 10A N/A 5 SB12N5F No Taps 15 10 .187 10 .625 110 N/R 10A N/A

120 x 240 - 16/32 Volts, 60 Hz, No Taps

FB

0 .050 SB16N .050F No Taps 8 .25 3 .25 4 .25 8 N/R 10A N/A 0 .100 SB16N .100F No Taps 8 .25 3 .25 4 .25 10 N/R 10A N/A 0 .150 SB16N .150F No Taps 9 .25 4 5 14 N/R 10A N/A 0 .250 SB16N .250F No Taps 9 .25 4 5 15 N/R 10A N/A 0 .500 SB16N .500F No Taps 11 .25 5 .25 6 .5 21 N/R 10A N/A 0 .750 SB16N .750F No Taps 11 .25 5 .25 6 .5 25 N/R 10A N/A 1 SB16N1F No Taps 11 .25 5 .25 6 .5 28 N/R 10A N/A 1 .5 SB16N1 .5F No Taps 13 .25 6 .25 7 .75 45 N/R 10A N/A 2 SB16N2F No Taps 13 .25 6 .25 7 .75 50 N/R 10A N/A 3 SB16N3F No Taps 13 .25 6 .25 7 .75 60 N/R 10A N/A 5 SB16N5F No Taps 15 10 .187 10 .625 110 N/R 10A N/A

240 x 480 - 24/48 Volts, 60 Hz, No Taps

FB

0 .050 SB24N .050F No Taps 8 .25 3 .25 4 .25 8 N/R 10A N/A 0 .100 SB24N .100F No Taps 8 .25 3 .25 4 .25 10 N/R 10A N/A 0 .150 SB24N .150F No Taps 9 .25 4 5 14 N/R 10A N/A 0 .250 SB24N .250F No Taps 9 .25 4 5 15 N/R 10A N/A 0 .500 SB24N .500F No Taps 11 .25 5 .25 6 .5 21 N/R 10A N/A 0 .750 SB24N .750F No Taps 11 .25 5 .25 6 .5 25 N/R 10A N/A 1 SB24N1F No Taps 11 .25 5 .25 6 .5 28 N/R 10A N/A 1 .5 SB24N1 .5F No Taps 13 .25 6 .25 7 .75 45 N/R 10A N/A 2 SB24N2F No Taps 13 .25 6 .25 7 .75 50 N/R 10A N/A 3 SB24N3F No Taps 13 .25 6 .25 7 .75 60 N/R 10A N/A 5 SB24N5F No Taps 15 10 .187 10 .625 110 N/R 10A N/A

Buck-Boost Selector Program

For a more comprehensive selection use the following link:

(12)

600 V

olt Class

Buck-Boost Selection Tables

120 x 240 Volts Primary - 12/24 Volts Secondary • Buck - Boost Dry-Type Transformers

AMPS = Load Amps

KVA = Load Circuit KVA

Three-Phase

Single-Phase

TABLE I BOOSTING BUCKING

Catalog Number Line-Voltage 96 100 105 109 189 208 218 220 125 132 229 245 250 252 Load 115 120 116 120 208 229 240 242 114 120 208 223 227 240 Voltage SB12N.050F KVAAMPS 2.080.24 2.080.25 0.484.17 4.170.50 0.432.08 2.080.48 2.080.50 0.502.08 0.524.58 0.554.58 0.482.29 0.512.29 0.522.29 1.054.38 SB12N.100F KVAAMPS 4.170.48 4.170.50 0.968.33 8.331.00 0.874.17 4.170.95 4.171.00 1.014.17 1.049.17 1.109.17 0.954.58 1.024.58 1.044.58 2.108.75 SB12N.150F KVAAMPS 6.250.72 6.250.75 12.501.44 12.501.50 1.306.25 6.251.43 6.251.50 1.516.25 13.751.56 13.751.65 1.436.87 1.536.87 1.566.87 13.133.15 SB12N.250F KVAAMPS 10.421.20 10.421.25 20.832.41 20.832.50 10.422.17 10.422.38 10.422.50 10.422.52 22.922.60 22.922.75 11.462.39 11.462.55 11.462.60 21.885.25 SB12N.500F KVAAMPS 20.832.40 20.832.50 41.674.81 41.675.00 20.834.33 20.834.77 20.835.00 20.835.04 45.835.21 45.835.50 22.924.77 22.925.10 22.925.21 10.5043.75 SB12N.750F KVAAMPS 31.253.60 31.253.75 62.507.22 62.507.49 31.256.5 31.257.15 31.257.49 31.257.56 68.757.81 68.758.25 34.377.16 34.377.66 34.377.81 15.7565.63 SB12N1F KVAAMPS 41.674.80 41.675.00 83.339.63 83.339.99 41.678.66 41.679.53 41.679.99 41.6710.08 91.6710.42 91.6711.00 45.839.54 45.8310.21 45.8310.42 21.0087.50 SB12N1.5F KVAAMPS 62.507.20 62.507.5 125.0014.44 125.0014.99 12.9962.50 62.5014.30 62.5014.99 15.1362.50 137.5015.62 137.5016.50 14.3168.75 15.3168.75 15.6268.75 131.2531.50 SB12N2F KVAAMPS 83.339.60 10.0083.33 166.6719.25 166.6719.98 17.3283.33 19.0783.33 83.3319.98 83.3320.17 183.3320.83 183.3322.00 91.6719.08 91.6720.42 91.6720.83 175.0042.00 SB12N3F KVAAMPS 125.0014.40 125.0015.00 250.0028.88 250.0029.98 125.0025.99 125.0028.60 125.0029.98 125.0030.25 275.0031.25 275.0033.00 137.5028.62 137.5030.62 137.5031.25 262.5063.00 SB12N5F KVAAMPS 208.3324.00 208.3325.00 416.6748.13 416.6749.96 208.3343.31 208.3347.67 208.3349.96 208.3350.42 458.3352.08 458.3355.00 229.1747.71 229.1751.04 229.1752.08 105.00437.50 *DIAGRAM B B A A D D D D A A D D D C

TABLE II BOOSTING BUCKING

Catalog Number

Line

Voltage 189Y/109 195Y/113 200Y/115 208Y/120 416Y/240 416Y/240 189 208 220 218 229 250 255 264 Load

Voltage 208Y/120 234Y/135 240Y/139 229Y/132 458Y/264 437Y/252 208 229 242 208 208 227 232 240

SB12N.050F KVAAMPS 1.504.17 0.842.08 0.872.08 1.654.17 1.652.08 3.154.17 2.080.75 2.080.83 2.080.87 4.381.57 2.290.83 2.290.90 2.290.92 0.952.29 SB12N.100F KVAAMPS 3.008.33 1.694.17 1.734.17 3.308.33 3.304.17 6.308.33 4.171.50 4.171.65 4.171.75 8.753.15 4.581.65 4.581.80 4.581.84 1.914.58 SB12N.150F KVAAMPS 12.504.5 2.536.25 2.606.25 12.504.95 4.956.25 12.509.46 6.252.25 6.252.48 6.252.62 13.134.72 6.872.48 6.872.71 6.882.76 2.866.88 SB12N.250F KVAAMPS 20.837.50 10.424.22 10.424.33 20.838.26 10.428.26 15.7620.83 10.423.75 10.424.13 10.424.37 21.887.87 11.464.13 11.464.51 11.464.60 11.464.76 SB12N.500F KVAAMPS 15.0041.67 20.838.44 20.838.66 16.5141.67 16.5120.83 31.5241.67 20.837.50 20.838.26 20.838.73 43.7515.73 22.928.26 22.929.02 22.929.20 22.929.53 SB12N.750F KVA1AMPS 22.5162.50 12.6731.25 12.9931.25 24.7762.50 24.7731.25 47.2862.50 31.2511.25 31.2512.38 31.2513.10 65.6323.60 34.3712.39 34.3713.53 34.3713.80 14.2934.38 SB12N1F KVAAMPS 30.0183.33 16.8941.67 17.3241.67 33.0283.33 33.0241.67 63.0583.33 41.6715.00 41.6716.51 41.6717.46 87.5031.47 45.8316.53 45.8318.04 45.8318.40 19.0545.83 SB12N1.5F KVAAMPS 125.0045.01 25.6662.50 25.9862.50 125.0049.54 49.5462.50 125.0094.57 62.5022.51 62.5024.77 62.5026.20 131.2547.20 68.7524.79 68.7527.06 68.7527.60 28.5868.75 SB12N2F KVAAMPS 166.6760.02 33.7783.33 34.6483.33 166.6766.05 66.0583.33 126.09166.67 83.3330.01 83.3333.02 83.3334.93 175.0062.93 91.6733.05 91.6736.08 91.6736.81 38.1191.67 SB12N3F KVAAMPS 250.0090.02 125.0050.66 125.0051.96 250.0099.07 125.0099.07 189.14250.00 125.0045.01 125.0049.54 125.0052.39 262.5094.40 137.5049.58 137.5054.13 137.5055.21 137.5057.16 SB12N5F KVAAMPS 150.04416.67 208.3384.44 208.3386.60 165.12416.67 165.12208.33 315.23416.67 208.3375.02 208.3382.56 208.3387.32 437.50157.33 229.1782.63 229.1790.21 229.1792.02 229.1795.26 No. of Transformers 3 3 3 3 3 3 2 2 2 2 2 2 2 2

(13)

600 V

olt Class

Buck-Boost Selection Tables

120 x 240 Volts Primary - 16/32 Volts Secondary • Buck - Boost Dry-Type Transformers AMPS = Load Amps

KVA = LoadCircuit KVA

TABLE IV BOOSTING BUCKING

Catalog Number

Line 183Y/106 208Y/120 195 208 225 240 245 250 256 265 272

Voltage Load 208Y/120 236Y/136 208 236 240 208 230 234 240 234 240 Voltage SB16N.050F KVAAMPS 1.123.13 1.283.13 1.133.12 0.641.56 3.121.30 1.560.56 3.331.33 3.331.35 3.331.39 1.770.72 0.741.77 SB16N.100F KVAAMPS 2.256.25 2.556.25 2.256.25 1.283.13 6.252.60 3.131.13 6.672.65 6.672.71 6.672.77 3.541.43 1.473.54 SB16N.150F KVAAMPS 3.379.38 3.839.38 3.389.37 1.914.69 9.373.90 4.691.69 10.003.98 10.004.06 10.004.16 5.312.15 2.215.31 SB16N.250F KVAAMPS 15.635.61 15.626.38 15.625.63 3.197.81 15.626.50 7.812.81 16.676.63 16.676.77 16.676.93 8.853.59 3.688.85 SB16N.500F KVAAMPS 31.2511.23 12.7631.25 11.2631.25 15.636.38 31.2512.99 15.635.63 33.3313.26 33.3313.53 33.3313.86 17.717.17 17.717.36 SB16N.750F KVA1AMPS 16.8446.88 19.1446.88 16.8946.87 23.449.58 46.8719.49 23.448.44 50.0019.89 50.0020.30 50.0020.78 26.5610.76 11.0426.56 SB16N1F KVAAMPS 22.4562.50 25.5262.50 22.5262.50 12.7631.25 62.5025.98 31.2511.26 66.6726.52 66.6727.06 66.6727.71 35.4214.34 14.7235.42 SB16N1.5F KVAAMPS 33.6893.75 38.2893.75 33.7793.75 19.1446.88 93.7538.97 46.8816.89 100.0039.78 100.0040.59 100.0041.57 53.1321.52 22.0853.13 SB16N2F KVAAMPS 125.0044.90 125.0051.04 125.0045.03 25.5262.50 125.0051.96 62.5022.52 133.3353.04 133.3354.13 133.3355.43 70.8328.69 29.4470.83 SB16N3F KVAAMPS 187.5067.36 187.5076.56 187.5067.55 38.2893.75 187.5077.94 93.7533.77 200.0079.57 200.0081.19 200.0083.14 106.2543.03 106.2544.17 SB16N5F KVAAMPS 112.26312.50 127.59312.50 112.58312.50 156.2563.80 312.50129.90 156.2556.29 333.33132.61 333.33135.32 333.33138.56 177.0871.72 177.0873.61

Three-Phase

Single-Phase

TABLE III BOOSTING BUCKING

Catalog Number Line 95 100 105 208 215 215 220 225 135 240 240 245 250 255 Voltage Load 120 113 119 236 244 229 235 240 120 212 225 230 234 239 Voltage SB16N.050F KVAAMPS 1.560.19 3.130.35 0.373.13 1.560.37 0.381.56 3.120.72 3.130.73 0.753.12 0.423.54 0.381.77 0.753.33 0.773.33 0.783.33 0.803.33 SB16N.100F KVAAMPS 3.130.38 6.250.71 0.746.25 3.130.74 0.763.13 6.251.43 6.251.47 1.506.25 0.847.08 0.753.54 1.506.67 1.536.67 1.566.67 1.596.67 SB16N.150F KVAAMPS 4.690.56 9.381.06 1.129.38 4.691.11 1.144.69 9.372.15 9.372.20 2.259.37 10.631.27 1.135.31 10.002.25 10.002.30 10.002.34 10.002.39 SB16N.250F KVAAMPS 7.810.94 15.631.77 15.631.86 7.811.84 1.907.81 15.623.58 15.623.67 15.623.75 17.712.11 1.888.85 16.673.75 16.673.83 16.673.91 16.673.98 SB16N.500F KVAAMPS 15.631.88 31.253.54 31.253.72 15.633.68 15.633.81 31.257.17 31.257.33 31.257.50 35.424.22 17.713.75 33.337.50 33.337.66 33.337.81 33.337.97 SB16N.750F KVAAMPS 23.442.82 46.885.31 46.885.58 23.445.53 23.445.71 46.8710.75 46.8711.00 46.8711.25 53.136.33 26.565.63 11.2550.00 11.4850.00 11.7250.00 11.9550.00 SB16N1F KVAAMPS 31.253.76 62.507.08 62.507.44 31.257.37 31.257.61 14.3362.50 62.5014.67 62.5015.00 70.838.44 35.427.50 66.6715.00 66.6715.31 66.6715.62 15.9466.67 SB16N1.5F KVAAMPS 46.885.64 93.7510.63 11.1693.75 46.8811.05 11.4246.88 93.7521.50 93.7522.00 22.5093.75 106.2512.66 11.2553.13 100.0022.50 100.0022.97 100.0023.44 100.0023.91 SB16N2F KVAAMPS 62.507.52 125.0014.71 125.0014.88 14.7362.50 15.2362.50 125.0028.67 125.0029.33 125.0030.00 141.6716.88 70.8315.00 133.3330.00 133.3330.62 133.3331.25 133.3331.87 SB16N3F KVAAMPS 93.7511.28 187.5021.25 187.5022.31 22.1093.75 22.8493.75 187.5043.00 187.5044.00 187.5045.00 212.5025.31 106.2522.50 200.0045.00 200.0045.94 200.0046.87 200.0047.81 SB16N5F KVAAMPS 156.2518.80 312.5035.42 312.5037.19 156.2536.83 156.2538.07 312.5071.67 312.5073.33 312.5075.00 354.1742.19 177.0837.50 333.3375.00 333.3376.56 333.3378.12 333.3379.69 *DIAGRAM B A A D D C C C A D C C C C

(14)

600 V

olt Class

240 x 480 Volts Primary - 24/48 Volts Secondary • Buck - Boost Dry-Type Transformers

Buck-Boost Selection Tables

Three-Phase

Single-Phase

AMPS = Load Amps KVA = Load Circuit KVA

TABLE V BOOSTING BUCKING

Catalog Number Line-Voltage 230 380 416 425 430 435 440 450 460 132 277 480 480 504 Load 276 418 458 468 473 457 462 495 483 126 231 436 457 480 Voltage SB24N.050F KVAAMPS 1.040.29 1.040.44 0.481.04 1.040.49 0.491.04 2.080.95 2.080.96 0.521.04 1.012.08 0.282.19 0.291.25 0.501.15 1.002.19 1.052.19 SB24N.100F KVAAMPS 2.080.58 2.080.87 0.952.08 2.080.97 0.992.08 4.171.90 4.171.93 1.032.08 2.014.17 0.554.38 0.582.50 1.002.29 2.004.38 2.104.38 SB24N.150F KVAAMPS 3.130.86 3.131.31 1.433.13 3.131.46 1.483.13 6.252.85 6.252.89 1.553.13 3.026.25 0.836.56 0.873.75 1.503.44 3.006.56 3.156.56 SB24N.250F KVAAMPS 5.211.44 5.212.18 2.385.21 5.212.43 2.465.21 10.424.76 10.424.81 2.585.21 10.425.03 10.941.38 1.446.25 2.505.73 10.945.00 10.945.25 SB24N.500F KVAAMPS 10.422.88 10.424.35 10.424.77 10.424.87 10.424.93 20.839.52 20.839.63 10.425.16 10.0620.83 21.882.75 12.502.89 11.465.00 10.0021.88 10.5021.88 SB24N.750F KVAAMPS 15.634.31 15.636.53 15.627.15 15.637.30 15.637.39 31.2514.27 31.2514.44 15.637.73 15.0931.25 32.814.13 18.754.33 17.197.50 15.0032.81 15.7532.81 SB24N1F KVAAMPS 20.835.75 20.838.71 20.839.53 20.839.74 20.839.85 19.0341.67 41.6719.25 20.8310.31 41.6720.13 43.755.50 25.005.77 22.9210.00 43.7520.00 21.0043.75 SB24N1.5F KVAAMPS 31.258.63 31.2513.06 14.3031.25 31.2514.61 14.7831.25 62.5028.55 62.5028.88 15.4731.25 30.1962.50 65.638.25 37.508.66 15.0034.37 30.0065.63 31.5065.63 SB24N2F KVAAMPS 41.6711.50 17.4241.67 19.0741.67 19.4841.67 19.7141.67 38.0683.33 83.3338.50 41.6720.63 83.3340.25 87.5011.00 50.0011.54 45.8320.00 87.5040.00 42.0087.50 SB24N3F KVAAMPS 17.2562.50 26.1362.50 28.6062.50 29.2262.50 29.5662.50 125.0057.09 125.0057.75 62.5030.94 125.0060.38 131.2516.50 75.0017.31 68.7530.00 131.2560.00 131.2563.00 SB24N5F KVAAMPS 104.1728.75 104.1743.54 104.1747.67 104.1748.70 104.1749.27 208.3395.16 208.3396.25 104.1751.56 208.33100.63 218.7527.50 125.0028.85 114.5850.00 218.75100.00 105.00218.75 *DIAGRAM B D D D D C C D C C B D C C

TABLE VI BOOSTING BUCKING

Catalog Number Line 399Y/230 380 430 440 460 460 480 480 440 440 460 460 480 480 500 500 Voltage Load 480Y/277 418 473 462 506 483 528 504 400 419 438 418 457 436 455 476 Voltage SB24N.050F KVAAMPS 0.861.04 1.040.75 0.851.04 2.081.67 0.911.04 1.742.08 0.951.04 1.822.08 1.150.79 2.191.59 2.191.66 1.150.83 2.191.73 1.150.87 1.150.90 1.802.19 SB24N.100F KVAAMPS 1.732.08 2.081.51 1.712.08 4.173.33 1.832.08 3.494.17 1.912.08 3.644.17 2.291.59 4.383.18 4.383.32 2.291.66 4.383.46 2.291.73 2.291.80 3.614.38 SB24N.150F KVAAMPS 2.593.13 3.132.26 2.563.13 6.255.00 2.743.13 5.236.25 2.863.13 5.466.25 3.442.38 6.564.76 6.564.98 3.442.49 6.565.20 3.442.60 3.442.71 5.416.56 SB24N.250F KVAAMPS 4.325.21 5.213.77 4.275.21 10.428.34 4.565.21 10.428.71 4.765.21 10.429.09 5.733.97 10.947.94 10.948.30 5.734.15 10.948.66 5.734.33 5.734.51 10.949.02 SB24N.500F KVAAMPS 10.428.64 10.427.54 10.428.53 20.8316.67 10.429.13 17.4320.83 10.429.53 18.1920.83 11.467.94 21.8815.88 21.8816.60 11.468.30 21.8817.32 11.468.66 11.469.02 18.0421.88 SB24N.750F KVA1AMPS 12.9615.62 15.6311.31 12.8015.63 31.2525.01 13.6915.63 26.1431.25 14.2915.63 27.2831.25 17.1911.91 32.8123.82 32.8124.90 17.1912.45 32.8125.98 17.1912.99 17.1913.53 27.0632.81 SB24N1F KVAAMPS 17.2820.83 20.8315.08 17.0720.83 41.6733.34 18.2620.83 34.8641.67 19.0520.83 36.3741.67 22.9215.88 43.7531.75 43.7533.20 22.9216.60 43.7534.64 22.9217.32 22.9218.04 36.0843.75 SB24N1.5F KVAAMPS 25.9231.25 31.2522.62 25.6031.25 62.5050.01 27.3931.25 52.2962.50 28.5831.25 54.5662.50 34.3823.82 65.6347.63 65.6349.80 34.3824.90 65.6351.96 34.3725.98 34.3727.06 54.1365.63 SB24N2F KVAAMPS 34.5541.67 41.6730.17 34.1441.67 83.3366.68 36.5241.67 69.7283.33 38.1141.67 72.7583.33 45.8331.75 87.5063.51 87.5066.40 45.8333.20 87.5069.28 45.8334.64 45.8336.08 72.1787.50 SB24N3F KVAAMPS 51.8362.50 45.2562.50 51.2062.50 100.03 54.78 104.57 57.16125.00 62.50 125.00 62.50 125.00109.12 68.7547.63 131.25 131.2595.26 99.59 68.75 131.2549.80 103.92 68.7551.96 68.7554.13 108.25131.25 SB24N5F AMPSKVA 104.1786.39 104.1775.42 104.1785.34 166.71 91.29 174.29 95.26208.33 104.17 208.33 104.17 208.33181.87 114.58 218.75 218.75 114.58 218.75 114.58 114.58 218.7579.39 158.77 165.99 82.99 173.21 86.60 90.21 180.42 No. of Transformers 3 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

(15)

600 V

olt Class

Single-Phase General Purpose Technical Data

1All transformer catalog numbers shown are in a NEMA 2 enclosure, which covers all the requirements of NEMA 1 by offering a

degree of protection against the ingress of falling dirt and dripping liquid . The addition of a weather shield kit converts the indoor

Type FB: 115°C Rise • 180°C Insulation System • Non-Ventilated • Indoor/Outdoor

Type FH: 150°C Rise • 220°C Insulation System • Indoor Ventilated • Floor Mounted

Type KVA NumberCatalog Taps Approximate EnclosureDimensions - Inches Approx.Wt. in

Lbs.

Weather

Shield1 DiagramWiring

Wall Mount Bracket H W D 120 x 240 - 120/240 Volts, 60 Hz, No Taps FB

1 SE120N1F No Taps 11 .25 5 .25 6 .5 28 N/R 5 N/A 1 .5 SE120N1 .5F No Taps 13 .25 6 .25 7 .75 45 N/R 5 N/A 2 SE120N2F No Taps 13 .25 6 .25 7 .75 50 N/R 5 N/A 3 SE120N3F No Taps 13 .25 6 .25 7 .75 60 N/R 5 N/A 5 SE120N5F No Taps 15 10 .187 10 .625 110 N/R 5 N/A 7 .5 SE120N7 .5F No Taps 15 10 .187 10 .625 150 N/R 5 N/A 10 SE120N10F No Taps 17 13 .187 13 .125 175 N/R 5 N/A 15 SE120N15F No Taps 17 13 .187 13 .125 270 N/R 5 N/A

208 - 120/240 Volts, 60 Hz FB 1 SE201D1F -2 x 5% 11 .25 5 .25 6 .5 28 N/R 6 N/A 1 .5 SE201D1 .5F -2 x 5% 13 .25 6 .25 7 .75 45 N/R 6 N/A 2 SE201D2F -2 x 5% 13 .25 6 .25 7 .75 50 N/R 6 N/A 3 SE201D3F -2 x 5% 13 .25 6 .25 7 .75 60 N/R 6 N/A 5 SE201D5F -2 x 5% 15 10 .187 10 .625 110 N/R 6 N/A 7 .5 SE201D7 .5F -2 x 5% 15 10 .187 10 .625 150 N/R 6 N/A 10 SE201D10F -2 x 5% 17 13 .187 13 .125 175 N/R 6 N/A 15 SE201D15F -2 x 5% 17 13 .187 13 .125 270 N/R 6 N/A 240 X 480 - 120/240 Volts, 60 Hz FB

0 .050 SE2N .050F No Taps 8 .25 3 .25 4 .25 8 N/R 1 N/A 0 .075 SE2N .075 .F No Taps 8 .25 3 .25 4 .25 9 N/R 1 N/A 0 .100 SE2N .100F No Taps 8 .25 3 .25 4 .25 10 N/R 1 N/A 0 .150 SE2N .150F No Taps 9 .25 4 5 14 N/R 1 N/A 0 .250 SE2N .250F No Taps 9 .25 4 5 15 N/R 1 N/A 0 .500 SE2N .500F No Taps 11 .25 5 .25 6 .5 21 N/R 1 N/A 0 .750 SE2N .750F No Taps 11 .25 5 .25 6 .5 25 N/R 1 N/A 1 SE2N1F No Taps 11 .25 5 .25 6 .5 28 N/R 1 N/A 1 .5 SE2N1 .5F No Taps 13 .25 6 .25 7 .75 45 N/R 1 N/A 2 SE2N2F No Taps 13 .25 6 .25 7 .75 50 N/R 1 N/A 3 SE2N3FS No Taps 13 .25 6 .25 7 .75 60 N/R 10 N/A 3 SE2T3F +2, -4 x 2 .5% 13 .25 6 .25 7 .75 60 N/R 8 N/A 5 SE2N5FS No Taps 15 10 .187 10 .625 110 N/R 10 N/A 5 SE2T5F +2, -4 x 2 .5% 15 10 .187 10 .625 110 N/R 8 N/A 7 .5 SE2N7 .5F No Taps 15 10 .187 10 .625 150 N/R 1 N/A 7 .5 SE2T7 .5F +2, -4 x 2 .5% 15 10 .187 10 .625 150 N/R 8 N/A 10 SE2N10F No Taps 17 13 .187 13 .125 175 N/R 1 N/A 10 SE2T10F +2, -4 x 2 .5% 17 13 .187 13 .125 175 N/R 8 N/A 15 SE2N15F No Taps 17 13 .187 13 .125 270 N/R 1 N/A 15 SE2T15F +2, -4 x 2 .5% 17 13 .187 13 .125 270 N/R 8 N/A FH 15 S2T15E2 +2, -4 x 2 .5% 33 16 .625 18 .375 170 WS-3 9 WMB-3 25 S2T25E2 +2, -4 x 2 .5% 33 16 .625 18 .375 195 WS-3 9 WMB-3 37 .5 S2T37E2 +2, -4 x 2 .5% 37 22 .375 19 .875 270 WS-4 9 WMB-3 50 S2T50E2 +2, -4 x 2 .5% 37 22 .375 19 .875 300 WS-4 9 WMB-3 75 S2T75E2 +2, -4 x 2 .5% 45 .5 24 .75 20 450 WS-5 9 WMB-4 100 S2T100E2 +2, -4 x 2 .5% 52 25 .375 23 610 WS-7 9 WMB-4 167 S2T167E2 +2, -4 x 2 .5% 60 33 .375 26 1070 WS-9 9 NONE

(16)

600 V

olt Class

Single-Phase General Purpose Technical Data

1All transformer catalog numbers shown are in a NEMA 2 enclosure, which covers all the requirements of NEMA 1 by

offering a degree of protection against the ingress of falling dirt and dripping liquid . The addition of a weather shield kit converts the indoor NEMA 2 transformer to an outdoor NEMA 3R .

2 Can be furnished with CSA EEV label in compliance with CSA C802 .2-06 .

N/R - Not Required

Type FB: 115°C Rise • 180°C Insulation System • Non-Ventilated • Indoor/Outdoor

Type FH: 150°C Rise • 220°C Insulation System • Indoor Ventilated • Floor Mounted

Type KVA NumberCatalog Taps Approximate EnclosureDimensions - Inches Approx.Wt. in

Lbs.

Weather

Shield1 DiagramWiring

Wall Mount Bracket H W D 277 - 120/240 Volts, 60 Hz FB 1 SE271D1F -2 x 5% 11 .25 5 .25 6 .5 28 N/R 7 N/A 1 .5 SE271D1 .5F -2 x 5% 13 .25 6 .25 7 .75 45 N/R 7 N/A 2 SE271D2F -2 x 5% 13 .25 6 .25 7 .75 50 N/R 7 N/A 3 SE271D3F -2 x 5% 13 .25 6 .25 7 .75 60 N/R 7 N/A 5 SE271D5F -2 x 5% 15 10 .187 10 .625 110 N/R 7 N/A 7 .5 SE271D7 .5F -2 x 5% 15 10 .187 10 .625 150 N/R 7 N/A 10 SE271D10F -2 x 5% 17 13 .187 13 .125 175 N/R 7 N/A 15 SE271D15F -2 x 5% 17 13 .187 13 .125 270 N/R 7 N/A 480- 120 x 240 Volts, 60 Hz FB 1 SE481D1F -2 x 5% 11 .25 5 .25 6 .5 28 N/R 2 N/A 1 .5 SE481D1 .5F -2 x 5% 13 .25 6 .25 7 .75 45 N/R 2 N/A 2 SE481D2F -2 x 5% 13 .25 6 .25 7 .75 50 N/R 2 N/A 3 SE481D3F -2 x 5% 13 .25 6 .25 7 .75 60 N/R 2 N/A 5 SE481D5F -2 x 5% 15 10 .187 10 .625 110 N/R 2 N/A 7 .5 SE481D7 .5F -2 x 5% 15 10 .187 10 .625 150 N/R 2 N/A 10 SE481D10F -2 x 5% 17 13 .187 13 .125 175 N/R 2 N/A 15 SE481D15F -2 x 5% 17 13 .187 13 .125 270 N/R 2 N/A

600 - 120/240 Volts, 60 Hz, Electrostatically Shielded

FB 1 SE61D1FS -2 x 5% 11 .25 5 .25 6 .5 28 N/R 3 N/A 1 .5 SE61D1 .5FS -2 x 5% 13 .25 6 .25 7 .75 45 N/R 3 N/A 2 SE61D2FS -2 x 5% 13 .25 6 .25 7 .75 50 N/R 3 N/A 3 SE61D3FS -2 x 5% 13 .25 6 .25 7 .75 60 N/R 3 N/A 5 SE61D5FS -2 x 5% 15 10 .187 10 .625 110 N/R 3 N/A FB 7 .510 SE61D7 .5FSSE61D10FS -2 x 5%-2 x 5% 1517 13 .18710 .187 10 .62513 .125 150175 N/RN/R 33 N/AN/A 15 SE61G15FS -4 x 2 .5% 17 13 .187 13 .125 270 N/R 4 N/A FH 15 S61T15SE2 +2, -4 x 2 .5% 33 16 .625 18 .375 170 WS-3 11 WMB-3 25 S61T25SE2 +2, -4 x 2 .5% 33 16 .625 18 .375 195 WS-3 11 WMB-3 37 .5 S61T37SE2 +2, -4 x 2 .5% 37 22 .375 19 .875 300 WS-4 11 WMB-3 50 S61T50SE2 +2, -4 x 2 .5% 37 22 .375 19 .875 300 WS-4 11 WMB-3 75 S61T75SE2 +2, -4 x 2 .5% 45 .5 24 .75 20 450 WS-5 11 WMB-4 100 S61T100SE2 +2, -4 x 2 .5% 52 25 .375 23 610 WS-7 11 WMB-4 167 S61T167SE2 +2, -4 x 2 .5% 60 33 .375 26 1070 WS-9 11 NONE

600 - 120/240 Volts, 60 Hz, Electrostatically Shielded Copper

FH

15 S61T15CSE2 +2, -4 x 2 .5% 33 16 .625 18 .375 210 WS-3 11 WMB-3

25 S61T25CSE2 +2, -4 x 2 .5% 33 16 .625 18 .375 260 WS-3 11 WMB-3

37 .5 S61T37CSE2 +2, -4 x 2 .5% 37 22 .375 19 .875 400 WS-4 11 WMB-3

(17)

600 V

olt Class

Single-Phase Optional Temperature Rise Technical Data

1All transformer catalog numbers shown are in a NEMA 2 enclosure, which covers all the requirements of NEMA 1 by

offering a degree of protection against the ingress of falling dirt and dripping liquid . The addition of a weather shield kit converts the indoor NEMA 2 transformer to an outdoor NEMA 3R .

Type FH: 115°C and 80°C Rise • 180°C Insulation System

Indoor Ventilated • Floor Mounted

Type KVA NumberCatalog Taps Approximate EnclosureDimensions - Inches Approx.Wt. in

Lbs.

Weather

Shield1 DiagramWiring

Wall Mount Bracket H W D 115° C Rise, 240 x 480 - 120/240 Volts, 60 Hz FH 15 S2T15FE +2, -4 x 2 .5% 33 16 .625 18 .375 170 WS-3 9 WMB-3 25 S2T25FE +2, -4 x 2 .5% 37 22 .375 19 .875 270 WS-4 9 WMB-3 37 .5 S2T37FE +2, -4 x 2 .5% 37 22 .375 19 .875 270 WS-4 9 WMB-3 50 S2T50FE +2, -4 x 2 .5% 45 .5 24 .75 20 450 WS-5 9 WMB-4 75 S2T75FE +2, -4 x 2 .5% 52 25 .375 23 610 WS-7 9 WMB-4 100 S2T100FE +2, -4 x 2 .5% 52 25 .375 23 820 WS-7 9 WMB-4 167 S2T167FE +2, -4 x 2 .5% 60 33 .375 26 1090 WS-9 9 NONE 80° C Rise, 240 x 480 - 120/240 Volts, 60 Hz FH 15 S2T15BE +2, -4 x 2 .5% 33 16 .625 18 .375 195 WS-3 9 WMB-3 25 S2T25BE +2, -4 x 2 .5% 37 22 .375 19 .875 270 WS-4 9 WMB-3 37 .5 S2T37BE +2, -4 x 2 .5% 37 22 .375 19 .875 300 WS-4 9 WMB-3 50 S2T50BE +2, -4 x 2 .5% 45 .5 24 .75 20 450 WS-5 9 WMB-4 75 S2T75BE +2, -4 x 2 .5% 52 25 .375 23 610 WS-7 9 WMB-4 100 S2T100BE +2, -4 x 2 .5% 60 33 .375 26 1070 WS-9 9 NONE

(18)

600 V

olt Class

Three-Phase General Purpose Technical Data

1All transformer catalog numbers shown are in a NEMA 2 enclosure, which covers all the requirements of NEMA 1 by

offering a degree of protection against the ingress of falling dirt and dripping liquid . The addition of a weather shield kit converts the indoor NEMA 2 transformer to an outdoor NEMA 3R .

2 Can be furnished with CSA EEV label in compliance with CSA C802 .2-06 .

N/R - Not Required

Type FB: 115°C Rise • 180°C Insulation System • Non-Ventilated • Indoor/Outdoor

Type FH: 150°C Rise • 220°C Insulation System • Indoor Ventilated • Floor Mounted

Type KVA NumberCatalog Taps Approximate EnclosureDimensions - Inches Approx.Wt. in

Lbs.

Weather

Shield1 DiagramWiring

Wall Mount Bracket

H W D

208 - 208Y/120 Volts, 60 Hz, Electrostatically Shielded

FH 15 T202H15SE +2, -2 x 2 .5% 29 17 .125 19 .375 185 WS-2 19 WMB-3 30 T202H30SE +2, -2 x 2 .5% 34 22 .375 19 .875 370 WS-4 19 WMB-3 45 T202H45SE +2, -2 x 2 .5% 34 22 .375 19 .875 400 WS-4 19 WMB-3 75 T202H75SE +2, -2 x 2 .5% 37 26 19 .875 585 WS-18A 19 WMB-4 112 .5 T202H112SE +2, -2 x 2 .5% 43 28 .5 23 .5 760 WS-18 19 WMB-4 150 T202H150SE +2, -2 x 2 .5% 46 32 28 915 WS-10B 19A NONE 225 T202J225SE +2, -2 x 3% 51 42 .125 26 1385 WS-12 19B NONE 300 T202L300SE +2, -2 x 3 .5% 63 46 .5 30 .875 1630 WS-14 19C NONE 500 T202E500SE +1, -1 x 5% 72 .75 53 .375 36 .875 2620 WS-16 19E NONE

208 - 480Y/277 Volts, 60 Hz FH 15 T204H15E +2, -2 x 2 .5% 29 17 .125 19 .375 185 WS-2 23 WMB-3 30 T204H30E +2, -2 x 2 .5% 34 22 .375 19 .875 370 WS-4 23 WMB-3 45 T204H45E +2, -2 x 2 .5% 34 22 .375 19 .875 400 WS-4 23 WMB-3 75 T204H75E +2, -2 x 2 .5% 37 26 19 .875 585 WS-18A 23 WMB-4 112 .5 T204H112E +2, -2 x 2 .5% 43 28 .5 23 .5 760 WS-18 23 WMB-4 150 T204H150E +2, -2 x 2 .5% 46 32 28 915 WS-10B 23A NONE 225 T204J225E +2, -2 x 3% 51 36 30 1190 WS-12A 23B NONE

240 - 208Y/120 Volts, 60 Hz, Electrostatically Shielded

FB 3 TE242D3FS -2 x 5% 12 .062 12 .125 8 .375 95 N/R 12 N/A 6 TE242D6FS -2 x 5% 14 .562 20 .125 10 .625 225 N/R 12 N/A 9 TE242D9FS -2 x 5% 14 .562 20 .125 10 .625 270 N/R 12 N/A 15 TE242D15FS -2 x 5% 16 .062 21 .125 15 .125 435 N/R 12 N/A FH 15 T242T15SE2 +2, -4 x 2 .5% 29 17 .125 19 .375 185 WS-2 26 WMB-3 30 T242T30SE2 +2, -4 x 2 .5% 34 22 .375 19 .875 370 WS-4 26 WMB-3 45 T242T45SE +2, -4 x 2 .5% 34 22 .375 19 .875 400 WS-4 26 WMB-3 75 T242T75SE2 +2, -4 x 2 .5% 37 26 19 .875 575 WS-18A 26 WMB-4 112 .5 T242T112SE +2, -4 x 2 .5% 43 28 .5 23 .5 760 WS-18 26 WMB-4 150 T242T150SE +2, -4 x 2 .5% 46 32 28 915 WS-10B 26A NONE 225 T242J225SE +2, -2 x 3% 51 36 30 .5 1190 WS-12A 26B NONE 300 T242L300SE +2, -2 x 3 .5% 63 46 .5 30 .875 1630 WS-14 26C NONE 500 T242B500SE +1, -1 x 4% 72 .75 53 .375 36 .875 2620 WS-16 26D NONE

References

Related documents

A process was developed to identify potential defects in previous layers of Selective Laser Melting (SLM) Powder Bed Fusion (PBF) 3D printed metal parts using a mid-IR thermal camera

Silicon Valley San Francisco San Francisco Peninsula Austin Seattle Raleigh-Durham Salt Lake City Denver Boston Baltimore New York Washington DC San Diego Pittsburgh

The companies Berlin Partner GmbH and ZukunftsAgentur Branden- burg GmbH (Brandenburg Economic Development Board) support with a large range of services, from recruiting

Resume recovery feature of Stellar Phoenix Photo Recovery allows you to recover photos, audio and video files using saved scan information file or image file.. You can use the

College Mathematics (3 Credits) Biology (6 Credits) Arts and Humanities 3 Arts and Humanities 3 TOTAL 35 20 8.00 **Total up RED # ** Excess credits 0.00 8.00 Analyzing and

Steele of Stanford University Online High said that shift is already underway: In a recent survey of ASCA members, she and her colleagues found that more than one-fourth of

Keywords: Biodiesel, bio fuel, renewable energy, chicken fat, waste cooking oils, process

Based on the review and analysis of CTS documents and processes, interviews with staff and clients, and the onsite visit completed by Tina Oliphant, Grameen Foundation certifies