Datapoints Configuration
PCL
PCL
PCL
PCL
PACiS
PACiS
PACiS
PACiS Technical
Technical
Technical
Technical Training
Training
Training
Training Level
Level
Level
Level 2
2
2
2
CS&P
CS&P
CS&P
• Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
• Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
TYPED DIGITAL INFORMATION
It is an information which is representing a special input regarding the MiCOM C264 inner automations.
Examples :
- Switchgear Position DPS, Locking device status SPS, Bay Local/Remote DPS
• Typed / Generic xPS
GENERIC INFORMATION
It is a standard information which can be configured at any level. Examples :
Mapping SPS
It is an input which is produced by mapping to another DP. Each state of
this DP is mapped and corresponds to a state of the mapping SPS.
• Typed / Generic xPS
Day cyclic SPS
Day cyclic SPS
Day cyclic SPS
Day cyclic SPS
It is a transient SPS which is triggered every day at fixed time. (accuracy of
+/- 1 minute)(8 max per C264).
• Add / Configure a SPS (1)
1) SPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation
level in Electric
hierarchy. Some SPS are
System Info
.
Short Name :
SCE Key + appears in C264 local SOE
Detection Mode :
permanent : DI remains ON as far as signal is ON
Time tagging :
done at starting/end of signal filtering
2) SPS attributes
Long Name :
appears in viewers + printers
Persistence filtering :
SPS should remain valid “Set” or “Reset” during the configured timer
Forcing Management :
if FSS enabled, auto/manual force
LHMI display :
• Add / Configure a SPS (2)
3) SPS can be acquired by DIU/CCU
board,
IED. Some SPS are computed by
C264 application (C264 automation, …)
=> Relations under a SPS
Has for IED address :
SPS acquired by IED
Wired on : DI Channel
SPS acquired by DIU/CCU board
V4.7
V4.7
V4.7
V4.7
1) DPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation
level in Electric
hierarchy. Some DPS are
System Info
.
Short Name :
SCE Key + appears in C264 local SOE
Time tagging :
done at starting/end of motion
2) DPS attributes
Long Name :
appears in viewers + printers
Motion & Persistence filtering :
Motion : eliminate transients 00 and/or 11 motion states
Persistence : DPS should remain valid “Open” or “Closed” during the configured timer
Forcing Management :
if FSS enabled, auto/manual force
LHMI display :
yes = DPS in state list (MSC)
• Add / Configure a DPS (2)
3) DPS can be acquired by DIU/CCU
board,
IED. Some DPS are computed by
C264 application (C264 automation, …)
=> Relations under a DPS
Has for IED address :
DPS acquired by IED
Wired on :
DPS acquired by 2 channels (“open” and “closed”) on DIU/CCU board
DPS computed from 2 SPS :
DPS acquired using 2 SPS, 1 for “open” and 1 for “closed”
1) MPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation
level in Electric
hierarchy. Some MPS are
System Info
.
A MPS can have a maximum 16 valid states.
Short Name :
SCE Key + appears in C264 local SOE
2) MPS attributes
Long Name :
appears in viewers + printers
Motion & Persistence filtering :
Motion : inhibition (cf. next slide)
Persistence : MPS should remain in one valid state during the configured timer
Forcing Management :
if FSS enabled, auto/manual force
LHMI display :
yes = MPS in state list (MSC)
Example :
Change State with Filtering “all DI =0 “
During
change all DI =0
End
of change state
Before
change state
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
During
change all DI =1
Example :
Change State with Filtering “all DI =1 “
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
0
0
0
0
0
0
0
1
1
0
0
0
0
0
0
0
• Add / Configure a MPS (2)
• Add / Configure a MPS (3)
3) MPS can be acquired by DIU/CCU
board,
IED. Some MPS are computed by
C264 application (C264 automation, …)
=> Relations under a MPS
Has for IED address :
MPS acquired by IED
Wired on :
MPS acquired by a maximum of 16 channels on DIU/CCU boards
• Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
• Add / Configure a MV (1)
1) MV can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation
level in Electric
hierarchy. Some MV are
System Info
.
Short Name :
SCE Key + appears in C264 local SOE
2) MV attributes in General Tab
Long Name :
appears in viewers + printers
Analogue Type :
Analogue (AI,CT/VT,IED) or Digital Measurement
Forcing Management :
if FSS enabled, automatic force to a given value
LHMI display :
yes = MV in measurements list (MSC)
MV transmission :
• Add / Configure a MV (2)
Minimum / Maximum Value :
scaled values for SCADA and OI display + Full Scale definition
3) MV attributes in Value Features Tab
Thresholds definition :
scaled values for LLL, LL, L, H, HH, HHH thresholds + hysteresis
• Add / Configure a MV (3)
Scaling Low :
Linear / Quadratic
4) MV attributes in Scaling Tab
Minimum / Maximum acquisition values :
- if transducer 0/10 mA : min=0, max=10* - if transducer 4/20 mA :
min=0, max=16*
- if voltage of CT/VT with nominal ph-N = 57.7 V min=0, max=57.7*
- if IED (T103 : min=0, max=1; Modbus : cf. IED documentation)
…
* schedule a max value = 120% of expected max max=12, max=20, max=70 ... (transducers can measure more and display overflow and
undershoot measurements).
Scaling coefficients :
scaled value = A1 x acq. Value + B1
Up to 20 segments
Additional segments :
• Add / Configure a MV (4)
5) MV can be acquired by AIU/TMU/DIU/CCU
board,
IED. Some MV are
computed by C264 application (C264 automation, …)
=> Relations under a MV
Has for IED address :
MV acquired by IED
Wired on DI Channels :
Digital Measurements acquired by a maximum of 64 channels on DIU/CCU boards
Wired on AI Channel :
Computed by CT/VT board :
• Add / Configure a MV (5)
6) AI Board channel configuration
Transducer range :
Scanning acquisition period :
• Add / Configure a TPI (1)
1) TPI can
ONLY
be added under a Tap Changer
object belonging to a
Transformer
module.
=> Add / Configure a Tap Changer
object :
Built-in function :
Tap Changer
Min TAP, Max TAP
Execution timeout :
• Add / Configure a TPI (2)
2) TPI attributes :
2.1) General Tab
TPI type :
- Analogue Tap Position acquired by AIU or IED,
- Coded Digital Measurement (1/N, decimal, gray, BCD) acquired by DIU
Note : Tabs are not the same
- Value Features is common to Analogue and Digital TPI - Scaling & Tap Position for Analogue
• Add / Configure a TPI (3)
2) TPI attributes :
2.2) Value Features Tab
Minimum / Maximum Value :
Should comply with Tap Changer object configuration
Thresholds definition :
scaled values for LLL, LL, L, H, HH, HHH thresholds
• Add / Configure a TPI (4)
2) TPI attributes :
2.3) Scaling Tab (for Analogue
TPI only)
Minimum / Maximum Acquisition Value :
Same as for a MV
2.4) Tap Position Tab
For
Analogue
TPI :
filtering => transient “intertap” filtering
current valid range => gives validity DC input range for each tap
For
Digital
TPI :
filtering => signal validation
• Add / Configure a TPI (5)
3) TPI can be acquired by AIU/DIU/CCU
board,
IED.
=> Relations under a TPI
Has for IED address :
TPI acquired by IED
Wired on DI Channels :
Digital TPI acquired by a maximum of 64 channels on DIU/CCU boards
Wired on AI Channel :
• Add / Configure a Counter (1)
1) Counter can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation
level in Electric
hierarchy.
Short Name :
SCE Key + appears in C264 local SOE
2) Counter attributes in General Tab
Long Name :
appears in viewers + printers
Counter Type :
Standard (standard DI counting) Energy import / Energy export
Counter Acquisition :
validation => min pulse length to be counted invalidity => for double, non complementarity
LHMI display :
yes = Counter in
measurements list (MSC)
Counter Management :
• Add / Configure a Counter (2)
2) Counter attributes in General Tab
Counter cumulative period :
- configure a period at the end of which the counter value is transmitted (SBUS, LHMI)
- possible values : 10mn, 15mn, 30mn, 1h, 2h, 3h, … 24h
-at the end of this period, counter value can be reset (C264 re-start counting from 0)
Counter Total for
IED counters
:
Yes => IED is sending real counter value
No => IED is sending non-scaled value
• Add / Configure a Counter (3)
3) Counter can be acquired by DIU/CCU
board,
IED. Some Counters are
computed by C264 application (C264 automation, …)
=> Relations under a Counter
Has for IED address :
Counter acquired by IED
Wired on :
Single counter => 1 DI Channel Double counter => 2 DI Channels
integrate :
Counter computed by MV integration (example : P) Counter type is not “Standard” but “Energy import” or “Energy export”
Integration of P or Q :
In case the scale and unit is to big (
In case the scale and unit is to big (
In case the scale and unit is to big (
In case the scale and unit is to big (MVarh
MVarh
MVarh
MVarh for ex.), if
for ex.), if
for ex.), if
for ex.), if
energy is changing of less than 1MVarh in 10 minutes,
energy is changing of less than 1MVarh in 10 minutes,
energy is changing of less than 1MVarh in 10 minutes,
energy is changing of less than 1MVarh in 10 minutes,
the value is not sent (counter is integer so 0.2 value is
the value is not sent (counter is integer so 0.2 value is
the value is not sent (counter is integer so 0.2 value is
the value is not sent (counter is integer so 0.2 value is
equal to 0).
equal to 0).
equal to 0).
equal to 0).
• Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
TYPED CONTROL
It is an information which is representing a special functionality regarding the MiCOM C264 inner automations.
Examples :
- Switch Ctrl DPC, Locking device status SPC, Bay Local/Remote DPC, Sync CB Close
• Typed / Generic xPC
GENERIC CONTROL
It is a standard control which can be configured at any level. Examples :
• Add / Configure a SPC (1)
1) SPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation
level in Electric
hierarchy. Some SPC are
System Info
.
Short Name :
SCE Key + appears in C264 local SOE
Activation Mode :
- transient => configure pulse duration - permanent
- permanent until feedback
2) SPC attributes General Tab
Long Name :
appears in viewers + printers
LHMI display :
yes = SPC in control list (MSC)
Inter Control timeout :
no possibility to execute 2 consecutive orders during this timer
• Add / Configure a SPC (2)
3) SPC execution may be dependant on Local/Remote status of
Substation/Bay, on SBMC and/or on control uniqueness
=> SPC attributes Dependencies tab
Substation Local/Remote :
SS Local => control from OI allowed, from SCADA forbidden
Control Uniqueness
Bay Local/Remote :
Bay Local => control from LHMI allowed, from OI & SCADA not allowed
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in Remote
• Add / Configure a SPC (3)
4) SPC can be executed on DOU/CCU
board,
IED. Some SPC are computed
by C264 application (C264 automation, …)
=> Relations under a SPC
Has for IED address :
Wired on : DO Channel
SPC executed on DOU/CCU board
Interlock SPS :
holds a logic allowing/blocking the control
Associated DO channel status SPS :
for hardwired SPC only
Auto/Manu dependency :
blocks the operator control if an automation is in progress => connect to SPS/DPS giving
automation status
Feedback definition :
for C264 acknowledgement cf. slide “§3.4”
• Add / Configure a DPC (1)
1) DPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF
automation
level in Electric
hierarchy. Some DPC are
System Info
.
Short Name :
SCE Key + appears in C264 local SOE
Activation Mode :
- transient => configure pulse duration (2 channels “open” / “close”)
- permanent
- permanent until feedback
2) DPC attributes
Long Name :
appears in viewers + printers
LHMI display :
yes = DPC in control list (MSC)
Inter Control timeout :
no possibility to execute 2 consecutive orders during this timer
• Add / Configure a DPC (2)
3) DPC execution is dependant on one hand from Local/Remote status of
Substation/Bay and on the other hand from control uniqueness
=> DPC attributes Dependencies tab
Substation Local/Remote :
SS Local => control from OI allowed, from SCADA forbidden
Control Uniqueness
Bay Local/Remote :
Bay Local => control from LHMI allowed, from OI & SCADA not allowed
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in Remote
• Add / Configure a DPC (2)
4) DPC can be executed on DOU/CCU
board,
IED. Some DPC are computed
by C264 application (C264 automation, …)
=> Relations under a DPC
Has for IED address :
DPC executed by IED
Wired on : DO Channel
DPC executed on DOU/CCU board
2 Interlock SPS (open/close):
holds a logic allowing/blocking the controls
2 Associated DO channel status SPS :
for hardwired DPC only
Auto/Manu dependency :
blocks the operator control if an automation is in progress => connect to SPS/DPS giving
automation status
Feedback definition :
for C264 acknowledgement cf. slide “§3.4”
• Configure a xPC feedback
1) SPC/DPC can have for feedback a SPS/DPS
=> C264 checks if control success (ex: CB control, feedback CB position)
=> Example given for DPC with DPS feedback
Relation “has for feedback”
with 2 attributes :
- execution timeout : maximum time allowed to get feedback - status check : C264 will check status before performing control
DPC
• Add / Configure a SetPoint (1)
1) SetPoints can be added at Substation, Voltage Level, Bay, Module,
ISaGRAF automation
level in Electric
hierarchy.
Short Name :
SCE Key + appears in C264 local SOE
SetPoint type :
2) SetPoint attributes
Long Name :
appears in viewers + printers
LHMI display :
yes = SetPoint in control list (MSC)
Minimum / Maximum value :
raw values for SetPoint validity
For
Digital
SetPoint :
increment value pulse duration
• Add / Configure a SetPoint (2)
3) SetPoint execution is dependant on one hand from Local/Remote status of
Substation/Bay and on the other hand from control uniqueness
=> SetPoint attributes Dependencies tab
Substation Local/Remote :
SS Local => control from OI allowed, from SCADA forbidden
Control Uniqueness
Bay Local/Remote :
Bay Local => control from LHMI allowed, from OI & SCADA not allowed
SBMC :
advised not to use SBMC (put No)
if needed, local transfer when SS is in Remote
Note : This is internal automation existing and configurable for all Setpoints.
• Add / Configure a SetPoint (3)
4) SetPoints can be executed on DOU/CCU
board,
IED. Some SetPoints are
computed by C264 application (C264 automation, …)
=> Relations under a SetPoints
Has for IED address :
SP executed by IED
DO Channels :
C264 will close DO channels using configured code (BCD, binary, …)
Auto/Manu dependency :
blocks the operator control if an automation is in progress => connect to SPS/DPS giving
automation status