Flexi EDGE BTS Troubleshooting
w w .docu-track.co m w w .docu-track.co mObjective
After completing this learning element, the participant will be
able to:
•
Perform preventive maintenance tasks
•
Perform corrective maintenance
•
Identify the problem as part of troubleshooting process
•
Recognize and recover the most common alarms in the BTS
•
Group alarms and faults into a few main categories
•
Use Flexi EDGE BTS Manager for troubleshooting
•
Recognize current features and failures of the SW Configuration and
compatibility
•
Replace faulty modules process
•
Perform the troubleshooting process to solve the cases
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
•
Introduction
•
Preventive Maintenance
•
Corrective Maintenance
•
Troubleshooting process
•
Problem symptoms for Troubleshooting
•
Troubleshooting Problem Situation
•
Example Cases
•
Appendix
w w .docu-track.co m w w .docu-track.co mIntroduction
Some Definitions
Maintenance
In Flexi EDGE BTS
Maintenance
In Flexi EDGE BTS
Preventive Maintenance
Provide regular maintenance to the Flexi EDGE
BTS in order to reduce the possibility of failures
or decreasing of performance
Corrective Maintenance
The activity in order to rectify
or solve
faults
happened in the network, which have main
purpose is to solve the problem and get the
system/unit in the network back into normal
Detecting,
tracing
and analysis
the mistakes of fault in the system networks, in
order
to find the fault locating
or
root cause
of the faults and also to
recommend
solution
to solve the fault.
Troubleshooting
Troubleshooting
So, based on above explanation
the corrective maintenance tasks are
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Performing Routine Maintenance Tasks
•
The purpose of preventive maintenance
is to provide regular maintenance to the
exchange in order to reduce the
possibility of failures.
•
Before performing any tasks, determine
whether there will be any interruption in
service.
•
If so, then certain steps need to be
taken before the task is executed.
•
It should be seen as a need to perform
these on a regular basis, which can be
different for each type of maintenance
•
On the right hand, there is the example
of how to perform routine maintenance
tasks
Check that the grounding cables
are properly connected
Check the fans and air circulation
Check the connector seals
(rubber boots)
Check the cable connectors
Check the screws
1
1
2
2
3
3
4
4
5
5
w w .docu-track.co m w w .docu-track.co mPreventive Maintenance
Performing Routine Maintenance Tasks
Due to flexibility of installation of Flexi EDGE BTS, these following physical
check should be done:
•
Cleanness of the unit, especially for outdoor installation. Here is example
of unit in flexi edge BTS which is dirty
in some circumstances, we need to provide more protective action to
avoid Flexi EDGE BTS from unfriendly environment, such as rats as
Mouse attack
Mouse protection
Broken seal because
of rats
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Performing Routine Maintenance Tasks
•
For cabling and connector installation, please follow the standard
installation document from NED as recommended by NSN.
•
These following pictures are example of mistakes that might happen in the
field that can affect the performance of the system.
No cover on the LMP port
TX Cable broken
w w .docu-track.co m w w .docu-track.co m
Preventive Maintenance
Performing Routine Maintenance Tasks
Very sharp curve of TX Cable
Unnecessary bending of cable
(blue line is ideal way)
Transmission cable is
left open
Broken cable
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
•
Corrective Maintenance is the activity in order to
rectify
or
solve
faults
happened in the network, which have main purpose is to solve the
problem and get the system/unit in the network back into normal.
•
Usually, the corrective maintenance tasks are executed after the
troubleshooting
has been done.
•
Replacing the module is the example of how the corrective maintenance is
doing.
•
Replacing the module could be one of the solution if there’s an alarm
related to specific unit and after we do troubleshooting, we find out that
specific unit is faulty.
•
Here is the example of corrective maintenance related to the HW:
–
Disconnecting the cables
–
Replacing the module Fans
–
Disabling and enabling power with Flexi EDGE BTS
–
Replacing modules, such as: EXxA, ERxA, ESMA, FIxA, EWxA/B, ECxA
w w .docu-track.co m w w .docu-track.co m
Corrective Maintenance
Disconnecting Cables
The steps how to disconnect cables:
1.
Remove any cable ties.
2.
Detach the cable connector seal from
the module mechanics.
3.
Hold the cable with one hand and pull
the seal backwards with your other
hand so that the connector is exposed.
4.
If you are disconnecting an optical
cable or a power cable, push the locking
clips all the way down and pull
simultaneously.
5.
Pull the connector out carefully.
6.
If you are disconnecting an optical
transceiver, first turn the locking ring
into a horizontal position and then pull
the optical transceiver out.
Grip the connector seal by the stiffened end
of the seal (the end connected to the
connector) as shown in the following figure
The optical cable has a locking clip on the top of
the connector, and the power cable has locking
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Replacing Module Fans
•
The purpose is if a module fan fails or becomes degraded, replace it with a new
one.
•
In stack, wall, pole and Flexi Cabinet for Indoor (FCIA) installation, fans can be
replaced from the back of the module if there is enough space behind the BTS.
•
When removing fans from the back of FCIA, we need to remove the back panel.
•
When removing fans from the back, make sure we have a screwdriver that fits the
clearance.
•
If there is not enough space for replacing the fans from the back, you can also
replace the fans from the front. In this case you need to disable power to the
module and pull it out from the casing or cabinet. In Flexi Cabinet for Outdoor
(FCOA), fans are replaced from the front.
•
Note that when replacing fans, an
alarm indicating a broken fan may be
seen. But after we have replaced the
fan, the alarm is cancelled.
w w .docu-track.co m w w .docu-track.co m
Corrective Maintenance
Replacing Module Fans – for Dual TRX Module (EXxA) and Remote Tune
Combiner Module (ECxA)
Note :
Before start, shut down the module before replacing fans.
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Replacing Module Fans – for System Module (ESMA), System Extension
Module (ESEA) and Power DC/DC Module 24V (FPDA)
Note :
Before start, shut down the
module before replacing fans.
Do not touch the rotating
fans.
w w .docu-track.co m w w .docu-track.co mCorrective Maintenance
Replacing Module Fans – Optical Converter Module (EOCA)
Note :
Before start, shut down the module before replacing fans.
Do not touch the rotating fans.
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Disabling and enabling power with the Flexi EDGE BTS Manager
•
We need to disable power from the Power Control dialog when adding modules to
or removing modules from an operational BTS.
•
The power control from the BTS Manager allows each power output to be
controlled independently so that a single module can be added or removed.
•
First disable the power to that output, add or remove the module, and then restore
power.
Steps:
1. After local BTS Manager connection has been setup, open the Power Control dialog (from
BTS Control | Power Control).
2. If BTS is the Outputs Controller, click Change.
3. Click Turn Off to disable power from the modules needed.
4. Perform the maintenance needed, for example,
add and remove modules.
5. To enable power in the modules,
click Turn On for each unit.
6. Click Change to change Outputs Controller to BTS.
7. Click Close.
w w .docu-track.co m w w .docu-track.co mCorrective Maintenance
Replacing Modules – Introduction
Purpose:
•
If a module fails and we have carried out troubleshooting,
replace the module with a new one.
•
The module needs to be removed also when we are replacing
a fan from the back of the module.
•
Before start, make sure the configuration-specific
instructions available for checking how to re-connect the
cables.
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Replacing Modules – Dual TRX (EXxA)
Note, If the Dual TRX Module carries the
BCCH TRX or provides power for the Dual
Duplexer Module, the whole sector may be
disabled. In these cases it is recommended to
block the sector.
General Procedure for replacing EXxA:
•
Disable power with Flexi EDGE Manager.
•
Disconnect cables and loosen the screw
•
Pull out the module and also EWxx (if there
is) submodule
•
Install the new EXxA module and also install
Ewxx (if there is) in a new EXxA module
•
Connect the cables and fix the screw
•
Enable the power and check functionality
using Flexi EDGE BTS manager.
Please the slide notes for detail.
Note that the Dual TRX Module is HW reset when the
bus cables are removed and reconnected.
w w .docu-track.co m w w .docu-track.co m
Note, if the Dual Duplexer Module is
connected to the Dual TRX Module which
carries the BCCH TRX, the whole sector may
be disabled. In this case it is recommended to
block the sector.
General Procedure for replacing ERxA:
•
Disable power to EXxA connected to ERxA
with Flexi EDGE Manager.
•
Disconnect cables and loosen the screw
•
Pull out the module
•
Install the new one
•
Connect the cables and fix the screw
•
Enable the power and check the
functionality using Flexi EDGE BTS
manager.
Corrective Maintenance
Replacing Modules – Dual Duplexer (ERxA)
Click to buy NOW!w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Replacing Modules – System Module (ESMA)
Note, save the site configuration file (SCF) to
the PC's hard disk by selecting 'Fetch SCF
from BTS' from the Commission menu before
replace ESMA module
General Procedure for replacing EXxA:
•
Switch off power from the BTS
•
Disconnect power main breaker, other
cables and loosen the screw
•
Pull out the module, and also transmission
submodule
•
Install the new EXxA module and also install
transmission submodule in a new ESMA
module
•
Connect the cables and fix the screw
•
Switch on the power and do commissioning
using Flexi EDGE BTS manager.
Please the slide notes for detail.
Note that the Dual TRX Module(s) and Remote Tune
Combiner Module(s) are HW reset when the bus cables
w w .docu-track.co m w w .docu-track.co m
Corrective Maintenance
Replacing Modules – Transmission Submodule
General Procedure for replacing
Transmission submodule:
•
Switch off power from the BTS
•
Disconnect cables on transmission
submodule and loosen the screw
•
Pull out transmission submodule
•
Install the transmission submodule
•
Connect the cables and fix the screw
•
Switch on the power of BTS and check the
functionality using Flexi EDGE BTS
manager.
Please the slide notes for detail.
Caution
New transmission sub-modules may be
damaged and will not operate correctly if the
sub-modules are replaced when the BTS
power is switched on. Switch off the Nokia
Flexi EDGE BTS before replacing the
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Replacing Modules – Wideband Combiner (Ewxx)
General Procedure for replacing EWxx
submodule:
•
Disconnect cables on EWxx submodule and
loosen the screw
•
Pull out EWxx submodule
•
Install the EWxx submodule
•
Connect the cables and fix the screw
•
Switch on the power of BTS and check the
functionality using Flexi EDGE BTS
manager.
Please the slide notes for detail.
Note: block the TRXs connected to the EWxx with
Nokia Flexi EDGE BTS Manager or, if the module
is in a sector where Baseband or Antenna Hopping
is used, block the whole sector.
w w .docu-track.co m w w .docu-track.co m
Corrective Maintenance
Replacing Modules – Remote Tine Combiner (ECxA)
General Procedure for replacing Remote
Tune Combiner (ECxA):
•
Disable power to Remote Tine Combiner
Module and its connected EXxA module(s)
with Flexi EDGE BTS Manager.
•
Disconnect cables and loosen the screw
•
Pull out the module
•
Install the new one
•
Connect the cables and fix the screw
•
Enable the power and check the
functionality using Flexi EDGE BTS
manager.
Note: If the Remote Tune Combiner Module is
connected to the Dual TRX Module which carries
the BCCH TRX, the whole sector may be disabled.
In this case it is recommended to block the sector.
Note that the Remote Tune Combiner Module is HW
reset when the bus cables are removed and
reconnected.
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Troubleshooting learning model
P
e
r
s
o
n
a
l
c
o
m
f
o
r
t
l
e
v
e
l
T I M E
UNCONSCIOUSLY UNABLE
CONSCIOUSLY UNABLE
CONSCIOUSLY ABLE
UNCONSCIOUSLY ABLE
AWARENESS PRACTICE APPLICATIONEXPECTATION AFTER
COURSE
w w .docu-track.co m w w .docu-track.co mTroubleshooting Principle
Troubleshooting Style
Gamble
r
Teste
r
Thinker
Wanderer
-
random
search
Risk Taker
-
experimental
search
Odds maker
-guess the
fault
Sensor
-look, listen, touch
and smell
Tracer
-follow diagram
Splitter
- “divide and
conquer”
Reader
-use documents
Recaller
-good memory
Designer
-theoretical knowledge
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Troubleshooting Questions
When analyzing the problem, you might want to ask yourself
the following questions:
•
When was the problem first reported?
•
How did the problem become known?
•
From which geographical area was it first reported?
•
Are there similar complaints coming from other cells?
•
Is the problem spreading in the network or is it happening only in one/few
BTSs?
•
Which types of calls are affected?
•
Does it happen all the time or occasionally?
•
…
w w .docu-track.co m w w .docu-track.co mTroubleshooting Principle
Brainstorming
What comes up in your mind when you read the questions?
Collect everything together at the board.
What kind of
documents
could help me in
troubleshooting?
Which people
could help me in
troubleshooting?
What kind of
alarms could
help me in
troubleshooting?
Which hard- and
software could
help me in
troubleshooting?
Click to buy NOW!w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Find the symptoms of the problem
Assumptions
Analyze and verify the problem
Carry out corrective action
Make sure the problem has been
solved
1
1
2
2
3
3
4
4
5
5
w w .docu-track.co m w w .docu-track.co mTroubleshooting Process
Find the symptoms of the problem
•
Symptoms are indication that represent problem might
happen in the system.
•
Symptoms also can help user to approach and identify the
cause of the problem.
•
For Flexi EDGE BTS, user can find the symptoms of the
problem such as:
–
Alarms appear in the BSC and/or BTS (using BTS Manager)
–
Message appear when executing a task with BTS Manager, e.g: MIV
message box
–
Reporting result, e.g: commissioning report, test result.
–
Experience of the mobile user
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Find the symptoms of the problem
Error message
LED Indication
Alarm in BTS
Manager
Alarm comes to
BSC
w w .docu-track.co m w w .docu-track.co mTroubleshooting Process
Make assumption
•
Based on symptoms, user can make assumption of what
happened actually in the equipment, what the probably cause
of the problem, and also how to solve it.
•
Making assumption is very important, due to:
•
Can be used for directing what should be done in order to approach
the problem
•
Reduce the time of troubleshooting, if the problem has been
experienced before.
•
Assumption can be more than one.
•
There could be that the assumption is not right (false), but
after the verification/analysis process, user can prove it.
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Make assumption – example
•
For example, during local connection with Flexi EDGE BTS
Manager, comes up this following message:
•
So, what is your assumption due to:
–
Problem might occur later on?
–
Cause of the problem?
–
How to solve it?
w w .docu-track.co m w w .docu-track.co m
Troubleshooting Process
Analyze and verify the problem
•
After make assumption, then user can start to analyze and verify what he/she
assume. In this process actually need the troubleshooting skill.
•
These tools could help user to identify the problem when do troubleshooting:
•
Software tools:
–
Flexi EDGE BTS Manager, includes testing process, monitoring & supervision
–
Flexi Hub Manager
–
Latest Flexi EDGE BTS SW Package
•
Hardware tools:
–
Personal Computer
–
Basic tools: multimeter, wrench
–
Handset + SIM card for call testing
–
Spare equipment : units, cables, connector
–
Advance measurement tool: site master, spectrum analyzer
•
References:
–
Product Documentation
–
SW Package documentation
–
Technical Notes
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Analyze and verify the problem using BTS Manager
•
If a fault occurs during BTS operation, connect Nokia Flexi
EDGE BTS Manager laptop PC to the System Module
(ESMA).
•
These elements could help you identify the problem when do
troubleshooting:
–
Flexi EDGE BTS Manager windows,
–
Supervision,
–
BTS Events,
–
and Alarms
w w .docu-track.co m w w .docu-track.co mTroubleshooting Process
Analyze and verify the problem using BTS Manager
Alarms
BTS Events
Supervision
Flexi
Edge
BTS
Manager
Window
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Analyze and verify the problem – define the caused
Find the caused problem:
Depending on the problem, one or more following causes may be as type of
problem:
Commissioning
Electrical power
Nokia Flexi EDGE BTS Manager connection
Dual TRX Module (EXxA) operation
TRX test and TRX loop test failures
Illegal modules
Local software download from Flexi EDGE BTS Manager
(E)GPRS packet switched data transfer
Q1 management
PseudoWire operation
w w .docu-track.co m w w .docu-track.co mTroubleshooting Process
Analyze and verify the problem – replacing unit
If replacing unit needed, after having replaced the faulty module/unit,
send it to hardware service.
These following items should be provided when returning the
faulty unit:
Exact failure details, such as the alarm number, environmental information
Configuration information (such as dusty, hot SITE, large configuration)
Exact alarm description for all modules. Except for the EXxx DTRX modules,
are capable of recording internally to nonvolatile memory the fault condition,
including the environmental information and TRX-level configuration
information in case a blocking alarm has occurred.
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Analyze and verify the problem – failure report
If a fault still exists after troubleshooting, contact your
local Nokia Siemens Networks representative.
Report all damages, failures, or faults to Nokia Siemens
Networks using the
Failure Report Form (FRF)
that your local
Nokia Siemens Networks representative has provided.
Note : example of returning faulty unit form is as attached:
Failure report template w w .docu-track.co m w w .docu-track.co m
Problem symptoms for Troubleshooting
BTS
a
larm in BSC (1/2)
•
Nokia Flexi EDGE Base Station alarms issued at the BSC or NetAct have
a four-digit alarm number and an alarm name, and an optional fault reason
(see the figure below).
•
To interrogate BTS alarm in BSC, use MML command:
ZEOL
•
For other fields in the figure below, refer to BSC/TCSM Product
Documentation.
Severity/ urgency level *** requires immediate actions
** requires actions during working hours
* no actions required
MML command under BSC to interrogate the current BTS alarm under BSC number 99 Alarm number BSC name BCF number TRX number
BTS number Event type
COMM communication failure QUAL quality of service PROCES processing failure EQUIPM equipment failure ENVIR environmental failure
Date
Time Date
Consecutive alarm number
A short description of the alarm. Supplementary information
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
BTS
a
larm in BSC (2/2)
•
Please note that one alarm can have more than one fault reason, although the alarm number
remains the same.
•
Different faults may have the same effect on the operation of a base station object, which is
why they have the same alarm number and name.
w w .docu-track.co m w w .docu-track.co m
Problem symptoms for Troubleshooting
BTS
a
larm in Flexi EDGE BTS Manager
Alarm generation real Time stamp
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Alarm Classification (1/3)
•
In fault situations, Nokia Flexi EDGE Base Station runs an
automatic
reclassification procedure
for major (**) and critical
(***) alarms before it sends an alarm to the BSC.
•
When an object becomes faulty, only one critical (***) alarm
from a BCF/BTS object or only one major (**) alarm from a
faulty TRX can be active at a time.
•
In reclassification, the alarm handling detects which logical
base station object is affected by a module level fault.
•
After reclassification, only
one object level alarm with only
one fault reason
is sent to the BSC.
•
However, the
same alarm can be caused by several
different fault reasons
.
w w .docu-track.co m w w .docu-track.co m
Problem symptoms for Troubleshooting
Alarm Classification (2/3)
BCF
BTS 1
TRX 1
TRX 2
TRX 3
TRX 4
BTS 1
Fault situation 1:
Alarm Output
7606 TRX FAULTY (TRX 1)
BCF
BTS 1
TRX 1
TRX 2
Fault situation 2:
Alarm Output, in this order
7606 TRX FAULTY (TRX 1)
7603 BTS FAULTY (BTS 1)
1.
TRX 1 becomes faulty and ceases to operate. 7606
TRX FAULTY alarm is issued.
1.
TRX 1 becomes faulty and ceases to operate. 7606 TRX
FAULTY alarm is issued.
2.
TRX 2 becomes faulty and ceases to operate.
3.
Now both TRXs are not operating, which causes BTS 1
cease to operate. A BTS alarm, 7603 BTS FAULTY, is
issued.
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Alarm Classification (3/3)
BCF
BTS 1
TRX 1
TRX 2
TRX 3
TRX 4
BTS 1
Fault situation 3:
Alarm Output
7606 TRX FAULTY (TRX 1)
7604 BTS OPERATION DEGRADED (BTS 1)
BCF
BTS 1
TRX 1
TRX 2
TRX 3
BTS 1
Fault situation 4:
Alarm Output, in this order
7607 TRX OPERATION DEGRADED (TRX 1) start
7607 TRX FAULTY (TRX 2)
7607 TRX OPERATION DEGRADED (TRX 1) cancel
7607 BTS OPERATION DEGRADED (BTS 1)
Functioning object
Degraded object
1.
TRX 1 becomes faulty and ceases to operate. 7606
TRX FAULTY alarm is issued.
2.
TRX 2 becomes partially faulty but calls are getting
through.
3.
Now the sector is partially faulty, and a BTS alarm,
7604 BTS OPERATION DEGRADED, is issued
.
1.
TRX 1 becomes partially faulty but calls are getting
through. 7607 TRX DEGRADED alarm is issued.
2.
TRX 2 becomes faulty and ceases to operate. 7606
TRX FAULTY alarm is issued for TRX 2. 7607 TRX
DEGRADED alarm is cancelled for TRX 1.
3.
Now the sector is partially faulty and a BTS alarm,
7604 BTS OPERATION DEGRADED, is issued.
w w .docu-track.co m w w .docu-track.co m
Problem symptoms for Troubleshooting
Alarms Tables (1/2)
•
The alarm tables show the faults and instructions on how to correct the fault (see
an example of an alarm table below):
•
Description of fields in the alarm table is shown below:
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Alarm Tables (2/2)
Instruction of
troubleshooting
activity in order to
rectify the
problem caused
by specific fault
reason
Fault reason
How user can
cancelling the
alarm
Same alarm
number can have
different fault
reason,
instruction and
how to cancel it
w w .docu-track.co m w w .docu-track.co mProblem symptoms for Troubleshooting
Alarm based on object
Object
Alarm Title & Severity
Faulty
(Critical)
Operation
Degraded
(Major)
Notification
(Minor)
BCF
7600
7601
7602
BTS
7603
7604
7605
TRX
7606
7607
7608
Site Powering
7612
7613
7614
Other alarms:
•
7208
LOCAL BLOCK
•
7401 – 7424 EXTERNAL ALARM
•
7615 RTS IN TEST USE
•
7616 OSCILLATOR ADJUSTMENT TEMPORARILY INTERRUPTED
•
7621 INTOLERABLE CONDITIONS ON SITE
Alarms based on Radio Network Objects & Site Powering
Click to buy NOW!w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Identifying faulty modules
•
In the Alarms window of Nokia Flexi EDGE BTS Manager, you can see
the object that the alarm refers to in the Object column.
•
When troubleshooting the alarm at the site, follow the troubleshooting
instructions in Nokia Flexi EDGE BTS Trouble Management.
•
It is not always the alarming module that is faulty, it may also be the
connected cable or the interworking module that causes the alarm.
•
At the site, you can easily locate the alarming module by checking the
colour of the LED.
•
Depending on the unit, a fault can be indicated by a red LED, a blinking
red LED or, in some cases, a blinking yellow LED.
•
If the module does not have a LED (for example the Wideband Combiner
sub-module EWxx) or the module is not responding and no LED colour is
displayed, read carefully the alarm description to locate the module
causing the alarm.
•
For identifying a faulty transmission sub-module connected to the Q1 bus
and its alarms, follow the troubleshooting instructions in the sub-module
product documentation.
w w .docu-track.co m w w .docu-track.co mProblem symptoms for Troubleshooting
LED in Units -
System Module (ESMA)
States BTS OM not runnin g Platfor m Startup Auto DetectComms Wait for LAPD BCF_SW Loading BCF Configuring BCF Supervisory Background SW Loading BCF Reset OMUSI G on OMUSI G off OMUSI G on OMUSI G off OMUSI G on OMUSI G off OMUSI G on OMUSI G off BCF Highlight SR BY CC CC CC CC CC CC CC CC CC CC CC SR Alarm BCF Critical SR BY SR SR SR SR SR SR SR SR SR SR SR SR Alarm BCF Major SR BY BR BR BR BR BR BR BR BR BR BR BR SR Alarm TRS Critical SR BY SY SY SY SY SY SY SY
Same Priority as BCF Alarms SR Alarm
TRS Major SR BY SY SY SY SY SY SY SY SR
Local_Mo
de SR BY BY BY N/A N/A N/A BY BY SG N/A N/A BG SR
BCF OBJ Lock SR BY SY SY SY SY SY SY SY SY N/A SY SY SR BCF OBJ Colour Explanation SR = Stable Red
BTS_OM SW is not running
BCF/TRS critical alarm (except during platform startup), or
BCF reset
BR = Blinking Red
BCF/TRX major alarm (except during platform startup or BCF reset)
SY = Stable Yellow
BCF is locked (except during platform startup or BCF reset)
Normal mode: BCF SW is loading (OMU signal off); BCF is configuring (OMU signal off)
Blocked BCF: BCF is in supervisory mode or background SW loading
BY = Blinking Yellow
Platform startup
Normal mode: auto detection in progress; BCF is commissioning or waiting for LDAP; BCF is configuring (OMU signal on)
Local module: auto detection in progress; BCF is commissioning or configuring
SG = Stable Green
Normal mode: BCF is in supervisory mode; BCF background SW is loading (OMU signal off) Local mode: BCF is in supervisory mode
BG = Blinking Green
Normal mode: BCF SW is loading or background SW is loading (OMU signal on)
Local mode: BCF background SW is loading
CC = BCF Highlight
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Problem situation that needs troubleshooting effort can be
divided into following:
•
Commissioning
•
Electrical power
•
Flexi EDGE BTS Manager connection
•
Dual TRX Module (EXxA) operation
•
TRX test and TRX loop test failures
•
Illegal modules
•
Local software download from Flexi EDGE BTS
Manager
•
(E)GPRS packet switched data Transfer
•
Q1 management
•
PseudoWire operation
Troubleshooting
problem
situation
Each of them has Potential Cause and Corrective Action tables that
explained in Trouble Management of Nokia Flexi EDGE BTS document in
w w .docu-track.co m w w .docu-track.co m
Flexi EDGE BTS Trouble Management
Example cases
Click to buy NOW!w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Case 1:
MIV Message
Case 2:
Commissioning partial failed due to test reporting failed
Case 3:
Alarm 7606 when power reset given to split DTRX module
Case 4
:
Rx Diversity is not tested when apply to TRX testing
Case 5:
TRX test failed in BSC
Case 6:
EDAP is missing from the Abis Allocation view after modifying the TCH
allocation
Case 7:
External alarm input 24 doesn’t appear using FSEB
w w .docu-track.co m w w .docu-track.co m
List of cases
Case 7:
External alarm input 24 doesn’t appear using FSEB
Case 8:
Alarm 8179 FAR END Alarm is raised in the BSC
Case 9:
TRX Faulty alarm : EXxx TRX module has lost connection to ERxx DDU
module
Case 10:
TRX Testing failed after Recomissioning
Case 11:
TRX test is failed
Case 12:
Alarm 7607 - Frequency band mismatch between commissioning file
Case 13:
RSSI detected Rx signal difference exceeding threshold
Case 14:
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
MIV Message
Detail of the case
•
When user access the Flexi EDGE BTS locally,
comes the Management Interface Mismatch
message.
•
But after click on yes button, user can use as usual
•
Advise needed according to:
–
What is the root cause ?
–
What are the possible impact if user still go on?
–
How to fix this problem
Product / SW
Release
Nokia Flexi EDGE
BTS / EP1.1
CD1.0
Impact
•
-w w .docu-track.co m w w .docu-track.co mCase 2:
Commissioning partial failed due to test reporting failed
Detail of the case
•
At the end of commissioning step, there comes up message as follow:
Commissioning has partially failed due to following:
One or more commissioning test failed.
See commissioning report for details
•
There’s also red dot on TRX test in commissioning progress step
Product / SW
Release
Flexi EDGE BTS EP1.1
CD.1.0
Impact
•
Flexi EDGE BTS cannot be used because of not
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Alarm 7606 when power reset given to split DTRX module
Detail of the case
•
Operator configures the Flexi EDGE BTS with 3 +3
configurations this following specification:
–
three DTRXs are provided,
–
one DTRX is splitted to serve two sectors and both TRX are
BCCH-TRX.
•
When the power on DTRXs where both BCCH-TRX are there
turn off using PDU control, then the BCCH on both sectors are
reconfigured to other TRX objects as expected.
•
However, when the power to the DTRX module is switched
back on, alarm
7606 TRX Faulty 'ERxx DDU module has
detected no Tx power at TxB input'
is activated.
•
Even though the traffic still can be there
Product / SW
Release
Flexi EDGE BTS / EP1
Impact
•
No impact to traffic
w w .docu-track.co m w w .docu-track.co mCase 4:
Rx Diversity is not tested when apply to TRX testing
Detail of the case
•
TRX testing is result is PASS, but no Rx diversity testing
is performed (NOT_TESTED).
•
Commissioning report and cabling have been checked,
and they are ok
.
Product / SW
Release
Flexi EDGE BTS /
EP1.1 CD1.0
Impact
•
No impact to traffic, but the Rx Diversity testing result
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
TRX test failed in BSC
Detail of the case
•
When the TRX Test is run from BSC (remotely), it fails.
•
7735 – TRX TEST FAILED alarms also in the BSC.
•
When user does TRX testing locally using BTS
manager, the result is okay.
Product / SW
Release
Flexi EDGE BTS /
EP1.0
Impact
•
No impact to traffic, but misleading troubleshooting could
happen due to 7735 TRX test failed alarms.
w w .docu-track.co m w w .docu-track.co m
Case 6:
EDAP is missing from the Abis Allocation view after
modifying the TCH allocation
Detail of the case
•
Operator modified TCH allocation in the transmission link that has EDAP
and sent to the BTS from the BTS manager.
•
Once the allocations are retrieved from the BTS with the BTS manager it
has been observed that the EDAP is missing from the Abis Allocation
view.
•
Alarm 7730 -“Configuration of BCF failed”, with supplementary
information detail 15844d: “EGPRS_BTS_TRXS_NOT_IN_DAP_EC
GPRS enabled TRX is not attached to Dynamic Abis Pool, when
GPRS is enabled in the BTS”
Product / SW
Release
Flexi EDGE BTS / EP1
Impact
•
The affected Sector will remain in BL-SYS state until the
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
External alarm input 24 doesn’t appear using FSEB
Detail of the case
•
In order to have 13 up to 24 external alarm inputs, operator must provide
FSEB unit to be connected to ESMA in Flexi EDG BTS.
•
To check the functionality of FSEB unit, user must create external input
alarm in the BSC for external alarm 13 up to 24.
•
During the external alarm testing, operator finds that even though FSEB
has been installed, but they cannot see the alarm for 24 that they have
created.
•
Cable connection has been checked, and didn’t find any problems, and
also there’s no alarms related to the FSEB
Product / SW
Release
BSCi /
S10.5 ED
Impact
•
Operator cannot use the external alarm 13 -24
Problem Type
BSCi /
S10.5 ED
w w .docu-track.co m w w .docu-track.co mCase 8:
Alarm 8179 FAR END Alarm is raised in the BSC
Detail of the case
•
8179 FAR-END ALARM is raised in the BSC
•
All LapD links are failed
•
BCCH is missing
Product / SW
Release
Flexi EDGE BTS /
EP1.1
Impact
•
Since LapD links failed, no calls can be provided
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
TRX Faulty alarm : EXxx TRX module has lost connection to Erxx DDU
module
Detail of the case
•
Two kind of alarms come in the Flexi BTS manager:
–
TRX Faulty alarm : EXxx TRX module has lost connection to Erxx DDU module
for TRX 2 & TRX 3 (ERxA1)
–
BTS Faulty alarm : EXxx TRX module has lost connection to Erxx DDU modules
Sector 1 (ERxA1)
•
What is the cause of these alarms?
Product / SW
Release
Flexi EDGE BTS /
EP1.1
Impact
•
No traffic can be handle by TRX2 & TRX3.
w w .docu-track.co m w w .docu-track.co m
Case 10:
TRX Testing failed after Recomissioning
Detail of the case
•
After recommissioning a Flexi EDGE BTS, operator find that the result of
this APPEND commissioning is successful, but without testing is
performed.
•
In order to complete the reporting, TRX testing is performed. In here
operator found that TRX testing for TRX-1 is failed due to RF RX cable
No connection.
•
No alarms accordingly appear in alarm window.
•
Physical checking on the RF cabling has been done, but no found
problem there.
•
Snapshot of APPEND commissioning and TRX testing result are
attached
Product / SW
Release
Flexi EDG BTS / EP 1.1
Impact
•
TRX test is failed
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
TRX test is failed
Detail of the case
•
When the TRX test is performed for TRX-1, the result of
the test is failed.
•
There are also alarm TRX Faulty: Erxx DDU module has
detected no Tx power at TAxA input for TRX-1 & TRX-3
Product / SW
Release
Flexi EDGE BTS EP1.1
CD.1.0
Impact
•
TRX test is failed
w w .docu-track.co m w w .docu-track.co mCase 12:
Alarm 7607 - Frequency band mismatch between
commissioning file
Detail of the case
•
Alarm 7607 TRX Operation Degraded
- Frequency
band mismatch between commissioning file and
detected hardware raise.
•
This alarm rises when operator use this following
configuration:
–
3+3+8 configuration with ESEA
–
High gain MHA types in use for all DTRX
–
DTRX-1 up to 6 are EXDA (1800 MHz)
–
DTRX-7 up to 14 are EXGA (900 MHz)
Product / SW
Release
Flexi EDGE BTS /
EP1.1
Impact
•
-Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
RSSI detected Rx signal difference exceeding threshold
Detail of the case
•
Alarm 7604 BTS Operation degraded and 7607 TRX Operation
Degraded – RSSI detected Rx signal difference exceeding threshold are
appeared in the BSC.
Product / SW
Release
Flexi EDGE BTS/
EP 1.1
Impact
•
TRX Operation Degraded
w w .docu-track.co m w w .docu-track.co mCase 14:
RSSI measurement results are lost when the alarm is
cancelled
Detail of the case
•
After maintaining the Antenna problem the caused
Alarm
7607 TRX Operation Degraded, “RSSI detected Rx
signal difference exceeding threshold”,
the alarm is
automatically cancelled.
•
The problem is, once it’s cleared, the alarm details are
cleared from the
RSSI Comparison Values and Site
Information report.
•
How can user get the historical reason alarm later on.
Product / SW
Release
Flexi EDGE BTS / EP1
Impact
•
If the RSSI alarm is cancelled before the RSSI results are
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
Flexi EDGE BTS Troubleshooting
Appendix:
•
LED in Units
•
Troubleshooting Problem Situation
•
How to find the reference of Flexi EDGE BTS in NOLS
w w .docu-track.co m w w .docu-track.co m
LED in Units
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
LED in Units - FIPA & FIEA
Colour
Explanation
Dark
Power off
SR = Stable Red
Interface card has power but it is not detected
SG = Stable Green
Interface card is detected by the System Module
w w .docu-track.co m w w .docu-track.co m
Problem symptoms for Troubleshooting
LED in Units - FIFA
Colour
Explanation
SR = Stable Red One or more data lines are not operating correctly, or The fault is in the indoor unit, outdoor units, or far-end units.
SY = Stable Yellow The indoor unit, outdoor units, or far-end units have active alarm(s). (LED will be stabilized for alarm status in about 30s after power on) The data is transmitted in this configuration, but may not be transmitted in other configurations or if another failure occurs. The overall performance capability is reduced., or
SW boot (LED is yellow only during the first second after power on. Afterwards LED blinks all colours during application SW startup).
SG = Stable Green Both terminals over this hop are operating normally and no alarms are active A blinking green LED indicates that there is a connection to the node manager All color blinking Application SW startup
FIFA main status LED indications
Colour
Explanation
FIFA Flexbus status LED indications
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
LED in Units - EXxA
Colour Explanation
SR = Stable Red •The O&M software of the module is not running, or •7606 alarm (TRX faulty) is active on both carriers. BR = Blinking Red •7606 alarm (TRX faulty) is active on one carrier, or
•7607 alarm (TRX operation degraded) is active on one or both carriers. SY = Stable Yellow •Both carriers in the TRX module are blocked/locked from EM/BSC, or
•Both carriers in the TRX module are shutdown from BSC, but TRX module is still providing power and control for an ERxA, or •Both carriers in the TRX module are shutdown from BSC, but TRX module is powered following a reset of ESMA or ESEA module, or
•Both carriers in the TRX module have LAPD on TRXSIG channel disconnected when the carriers state is supervisory, or •One carrier is not in supervisory state but other carrier is in supervisory state with LAPD on TRXSIG channel disconnected. BY = Blinking Yellow •TRX_OM SW state is in TRX_Started State, or
•TRX_OM SW state is Clock sync, or •One or both carriers are configuring: –Wait for LAPD establishment, or
–Wait for system information
•One or both carriers have LAPD on TRXSIG channel disconnected when none of the carriers are in state supervisory. SG = Stable Green •Both carriers are in state supervisory and no 7606 or 7607 alarms are active and LAPD on TRXSIG is connected to both
carriers.
BG = Blinking Green •Only one carrier is in state supervisory and no 7606 or 7607 alarm is active and LAPD on TRXSIG is connected for this carrier, or
•Both carriers are in state supervisory but one carrier has LAPD on TRXSIG channel disconnected.
w w .docu-track.co m w w .docu-track.co m
Problem symptoms for Troubleshooting
LED in Units - ERxA
Colour Explanation
SR = Stable Red Dual Duplexer Module software is not running, or Major alarm (on both antenna paths)
BR = Blinking Red Minor alarm (on one or both antenna paths), or Major alarm (on one antenna path)
BY = Blinking Yellow SW start-up or configuration ongoing
SG = Stable Green Module operational (cell can be locked in BSC)
BG = Blinking Green Module is loading software
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
LED in Units - ECxA
Colour Explanation
SR = Stable Red RTC SW is not running
Alarm is active with class critical (***) and RTC is disabled (all cavities are disabled). RTC module internal HW failure
No Tx power coming to RTC antenna RTC antenna broken, VSWR, or MHA current threshold crossed: •If MHA bypass is disabled:
–There is a major alarm (7607) on other MHA (if the diversity is ON) –The diversity is OFF
BR = Blinking Red Alarm is active with class major (**) and RTC is still enabled (at least one of the cavities is enabled). RTC Antenna degraded, VSWR, or
MHA current threshold crossed: •If MHA bypass is enabled •If MHA bypass is disabled:
–There is no alarm on other MHA
BY = Blinking Yellow RTC SW is in the startup sub-states: Initial boot loader, Wait for external input, software downloading, Initialization and hardware tests or RTC configured
w w .docu-track.co m w w .docu-track.co m
Problem symptoms for Troubleshooting
LED in Units - ESEA
Colour Explanation
SR = Stable Red
System Extension Module is switched on and SW is not yet running
BR = Blinking Red
After startup the POST test has failed or
invalid module connection
SY = Stable Yellow
Not used. Although this is not used the colour/frequency can be set for testing purposes
BY = Blinking Yellow
Not used. Although this is not used the colour/frequency can be set for testing purposes
SG = Stable Green
After startup the POST test was successful. Module is configured and is supervisory
BG = Blinking Green
SW upgrade is running
Click to buy NOW!w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co
LED in Units - EOCA
Colour Explanation
SR = Stable Red Any alarm active except for overcurrent alarm
BR = Blinking Red Overcurrent alarm active in one output (no other alarms active)
SY = Stable Yellow Startup state. LED is changed in this state after receiving first capability request.
SG = Stable Green Supervisory state. This is default state for the LED. Led is changed into green after receiving second status and control request from System Module
CC = Cycling colour EM has requested indication for Optical Converter Module and timer is still running.
w w .docu-track.co m w w .docu-track.co m
Troubleshooting Problem Situation
Click to buy NOW!
w w
w
.docu-track.co
m ww Click to buy NOW!
w
.docu-track.co