Hlecfrical
ter*fifflcaffi$Er
Test amd Review
Booklet
Electrical Certification Test and Review
This test is based on the L999 National Electrical Code@,
a
resource
of over 20000
electrical test questions,
and dozens
of
electrical books and articles. Each Code question is researched
using electronic
versions
of the 1999 NEC@ and the 1999
IYEC@
Handbook including the cross reference
to the 1996
hl-Ec@.
This booklet consists
of 20 tests with 20 questions
Answers and explanations
+ text reference
to the 1999 I\[EC
l .
Test Taking Tips
Calculate
the time per question as soon as you start your test. This is
important so you will not spend too much time on one question. If
thr." are 70 questions
and an allotted time of four (4) hours, then the
time per question
is 4 x SQ
minutes divided by 70 or 3.4 minutes per
qu.rtiott. If there are 70 questions
worth one point each and 3
di"gr"-t worth 10 points each, then find the time allowed per point.
tlrii woutd be (4 x 60) divided by 100 or 2.4 minutes per point. Then
allow 24 minutes
(10 x2.4) for each diagram and2.4 minutes per
question.
Answer the easier
questions
first. Leave the more difEcult ones and
mark them so you can go back to them. Do not spend
too much time
on one question. This is a classic
mistake!
Answer all questions
even if you have to gUess. Remember
you have
a 50 percenfchance
of getting a trre false question correct by simply
guessing.
Read.t.h question
carefully. Do not skim over questions.
Read each
word!
Find out if the test is open book. If it is, index your Code Book and
practice using the indexes. Index the Book before begiffIing your
studies.
o lndex Table 250-L22
for finding equipment
grounding wire
sizes.
o lndex Table 250-66 for finding grounding electrode
and
bonding
jumPer sizes.
o Index Table 8 in Chapter
9 for finding circular mil areas,
dimensions
of bare conductors,
and DC resistance
of
Conductors.
o lndex Section
240-6 for finding the standard
circuit breaker
and
fuse sizes.
o lndex Table 430-148,
Table 430-150,
and Table 430-152
for
sizing motor circuits.
Practice
looking up Code questions.
You should be able to find the
answer
to any single answer
Code question
in less than 3 minutes.
More complex
questions,
especially
calculation
problems, require
more time and more Code sections.
Begin your examination
by unloading
the formulas
onto a blank piece
of paper. This is perfectly
legal and saves
time later when you may
not be able to remember
the particular
formula.
) J . 4. l - J I
6 .
7 .
8. For each and every question try these four steps.
o Locate the given infonnation in the question.
o Locate any unknown infonnation necessary
to solve the
question.
o Locate the ''KFY' word or phrase in the question.
o If you cannot find the answer using the
"KEY", and it is a Code
question search the Code index for ttre
"KEYrr word.
9. After completing the test go back and scan it to make sure you have
answered
every question and have not skipped pages or blanks.
lO.If a question
requires
the use of a Table, be sure and read the notes to
the table. Also remember
each Table has a Section number the same
as the Table number. The section will have additional infonnation
pertaining to the Table.
1 l.It is strongly recommended
that you study no more thaa2 hours per
day and shrdy for about 40 hours prior to taking the journeyman
electrician test, and about 80 hours for the master electrician test.
l2.Be careful about writing formulas in your Code Book. If you are
allowed to use your own Code Book at the exam, it may be checked to
make sr:re that it does not have mirterial written in it, or you may be
given a Code book to use.
l3.If you are allowed to bring a calculator
to the exam buy one and bring
it.
l4.Get plenty of rest before taking the test. It is also a good idea to
practice looking up Code questions
for one hour just before taking the
Test. This increases
test scores
by as much as ten percent for some
people
^ , I
Must Know List for Taking Electrician's Examinations
a a a a
a
Know Ohm's Law and the Power formula. The Basic electrical theory pag€ covers
these fairly well. Buy Ugley's or Ferm's for a more thorough coverage. Know
everything on the Theory page as a minimum.
Know how to hookup nine lead star and delta wound induction motors. Know how to solve turns ratio transformer problems.
Know how to hook up three and four way switches.
Know how to determine motor branch cirpuit and feeder protection and wire sizes.
Know key Sections in the Code. These include:
l. Article 100 is definitions.
2. Article 90 purpose and scope of the Code.
3. Artiole 110 rules for electrical installations such as work clearance and
equipment space rules.
Article 210 for branoh oircuit calculations. Articte 220 for service and feeder calculations. Article 230 for services.
Article 240 is for overcurrent protection.
Article 250 is for grounding.
Articte 300 for general installation rules and methods.
Section 300-5 for burial dePths.
Article 310 for ampacity tables.especially Table 310-16 with notes.
Article 318 for cable traY.
Articles in Chapter three for raceways. Article 348 for EMT.
Article 346 for zugrd Metal Conduit. Article 430 for motors.
Article 440 for refrigeration equipment and motor-comPressors.
Article 450 for generators. Article 490 for high voltage
Article 501 for Class I, Division I and2locations.
Article 600 for signs.
Know that for commercial building a 20 ampere outside sigrr circuit is
required and the load is 1200 volt-amP€res.
know that emergency and standby Power systems requirements in Articles
700, 701, and702. These are extensions of Article 445 on generators.
know that for Hospitals there are additional requirements for emergency
power in Article 517.
25. ifuow that Appendix D has examples for load calculations and motor
circuits. Read and studY them.
26. Know that conduit and conductor dimensions areas, etc., are in Chapter nine,
but for all conductors of the same size the fill tables are in Appendix C.
27. Know that Class 2, Class 3, and Class I circuits and other "low voltage"
requirements are in Article 725.
Basic Electrical Theorv
Series Direct Current Circuit Rules
Rule #1: The same current flows through each part of a series circuit. Rule #22 Total Resistance of a series circuit is equal to the sum of the
individual resistances.
Rule #3: The total voltage across a series circuit is equal to the sum of the individual voltage droPs.
Rule #4: The voltage drop across a resistor in a series circuit is proportional to the size of the resistor.
Rule #5: The total power dissipated in a series circuit is equal to the surn of the individual power dissapations.
SUMMARY OF OHMS I'/IW FORMUI-A9
AMPERES
=
ffi+ANCE
RESTsTANCE
=
ff"*".
Parallel Direct Current Circuit Rules
Rule #1: The same voltage exists across each branch of a parallel circuit and is equal to the source voltage.
Rule #2: The current through a branch of a parallel network is inversety proportional to the amount of resistance of the branch.
Rule #3: The total current of a parallel circuit is equal to the sum of the currents of the indMdual branches of the circuit.
Rule #4: The total resistance of a parallel circuit is equal to the reciprocal of the sum of the reciprocals of the indMdual resistances of the circuit.
Rule #5: The total power dissipated in a parallel circuit is equal to the sum of the individual power dissapations.
SUMMARY OF PAR'4LLEL
CIRCUIT RULES
TOTAL VOLTAGE = E(1) = E(2) = E(3) ...etc.
VOLTS
TOTAL RESISTANCE = AIVfPERES
G l
TO DEEERT'fINE THE TOtrAJ, RESISTAI{CE fN A PARiAILEIT CfRCUIT WI{EN THE I.OTAIJ Ct'RREbIT ATiID TOTAT. VOLTAGE ERE UNKNOI$T USE ETTIIER OF fHE FOLIOIIII}IG FORMULAS:
R r -
l + 1 + l * . . . e t c
RI R2 R3
FOR TWO RESISTORS IN PARALLEL USE
THIS FORMULA CALLED TIIE
''PRODUCT
OVERTM SLIMII
R(1) t'R(2) R r = R(t)+R(2)
POIiIER IN SINGI.E PHASE RESISTI\ZE CIRCUTTS
WHERE PO!{ER FACTOR IS 1OO PERCET'NT
(rmsn EoRMtItAs ARE COM!{ON&I USED lO SOL\'E MOST CTRCUIE PtrilER
PRoBr.EMs! ou lesrs)
trO DETERI4INE TEE POWER CONSUMED BY All TNDTVIDUAJ, RESISTOR rN A SERIES CTRCUIT USE trEIS FORMT]I,A:
t 2 p o g t E R - r X R
_ 8 2
PO!{ER - R
TO DETIIRMTNE trEE TOTAI1 PO?|ER CONSIIMEID BY AII BIDTWDUAJ., CXRCTTIT USE TEIS FORMTII,A:
por{ER - E (TOTAMLTAGE) x I (TOTAI CURRENT)
RIII,TS OF TEUMB:
' TEE IOTAIJ RESXSTAIICE OB RESISTORS XN PARiAJ.LEI. IS ALI$AYS r.nSS TIIA}I TIIE \lALItE OF AI\TY ONE RESISTOR.
. TIIE TOTAIJ RESISTA}ICE OF PARATI'EL RESIStrORS TEAT ARE AII, TEE SAME V?II,I'E IS TEAtr VAJ,I'E DTVTDED BY IT'EE NUMBTR OE' R E S X S T O R S .
' AI.VIB'YS USE TEE PRODUCT O\IER SUM RIII"E trO EIREiAK DOWN gWO PARJAI.I,EIJ RESISEORS NflTO ONE RESISTOR. TIIIS TS MUCE XIASIIIR TEAI{ TRYTNG rO SOL\IE XJARGE A^IrGEBRAfC EXSRTSSIONS. ' 146 !{ATTS IS EQUAL EO ONE EORSEPOI|ER
' EFFTCTENCY rS EQUAL TO OTXPPUT DMDIID BY INPLTII . TN I}IDUCTT.\IE CTRCI'IBS CURRE}III' I,AGS VOIJIA@. O IN CAPACITIVE CXRCUITS CURREDI1I ]JEEDS VOI,TAGE.
o POTVER FACTOR IS A MEliASttRE OF BOW FAR CURRENT IJEiADS OR LAGS VOLTAGE.
I
I
POVTER IN ALrERNAEfNG
CUre
POWER FACTOR IS NOT 1OO PERCEtflI
POWER = E x I x POWTR FACTOR (ron snrer's PEASE)
powER = E x I x 1.132y- PO!{ER FACtrOR (ronrmsr PEA.SE)
THIS POWER IS AISO CEJ.I.ED trRI'E POITER OR REAI POWER AS OPPOSED TO APPEREMT PO!{ER FOT'ICD BY CEIJCuILATING VOLtr-AMI{SRES '
VOLT-AI'{PER.ES = E x I (ron srNer.e euaso)
VoLT-AMPE,RES = E x I x 1.132 (ron rmna rnnse)
IE CJA}T READIIJY BE DETERMTNED BY AI,GEBRA EEAT
P O W E R F A C T O R : APPARENT POWER
MOTOR APPLfCATION FOR!'IqI{4g
IIORSEPOI{ER = t.232 x vol,ts x,rrMPERES x gtr'ptctexcY x
(for three Phaseoowerfacjqt
motors | 746
THREE PHASE A},IPERES = 746 X HORSEPOWER
(for rhree phase motors) 1J32x voLTS x EFFICIENCY x POWER FACTOR
TEREE PEASE SEAR OR Y
I{OTOR UERK:INGS E}ID CONNECTIONS
COXNECTTONS FOR ![I}fE I.IED :TEREE PEA,SB }'C)|IORIg
STAR CONNECTED
-[
Lt". ,
-f
Ltn. 3
-i-
Togethera , & 8 l - 3 & e I
4 & 5 & 6i - 3
t -
4 & , 7 , 5 & 8 , 6 & 9l
2*f
v
5 }1 ,-i \ 6l^
\ 1r & 7
:
i
EERTE PEASE DEI.TA
DELTA CONNECTED
I,IOEOR CONTROI..I.ER W:[:TE TEREE StrARE SEOP StrA:IIONS
(EOI.DrNG COInDACTS NOT SEOIIN)
CRANSFOR!,ER TT'TTNS RATTO
Ep volts
Tp Turns
E s v o l t s '
Ts Turns
Ep - T-p
Es
Ts
Where Ep is primary voltage Es is secondary voltageTp is number of turns in p.imaty Ts is number of tums in secondary
Maximum Horsepower for NEMA-Rated Motor Starters
lls I Zsg l2o8t2so
l46ots7s
V o l t i V o l t l V o l tt oo rrv-lr
--[G--P
t . )i 10
i r
i r . t j r o n s ; 2 s
i - t - l
@ t
r=-l
@t
NEMA RATING FOR ENCLOSURES
NEMA and other organizations have established standards of enclosure construction for control equipment. In general, equipment would be enclosed for one or more of the following reasons:
L Prevent accidental contact with live parts.
2, Protecl the control from harmful environmental conditions'
3. Prevent explosion or fires whictr might result ftom fre electrical arc caused by the control. Common types of enclosures per NEMA classification numbers are:
N E M A I . G E N E R A L P U R P O S E
The general purpose enclosure is intended primarily to prevent accidental contact with the enclosed apparatus. lt'is iuitabte for general purpose applications indoors where it is not exposed to unusual service cirnOitions. A NEMA I encloiure serves as protection against dust and light indirect splashing, but is not dusttight.
NEMA 3. DUSTTIGHT, RAINTIGHT
This enclosure is intended to provide suitable protection against specified weather hazards. A NEMA 3 enclosure is sui+rable for applibtion outdoors, on ship docks, canal and construction work, and for application in subways and tunnels. lt is also sleet-resistant.
This enclosure protects against interference in operation of the contained equipment due to rain, and resists damage from exposure tdsbet. lt is designed with conduil hubs and extemal mounting, as well as drainage provisions.
NEi,IA 4.WATERTIGHT
A watertight enclosure is designed to meet the hose test described in the following note: "Enclosures shall be tested'by subjection to a stream of water. A hose with a one inctr node shall be used and shalldeliver at least 65 gilons per minute. The water shall be directed on the enclosure ftom a distance of not less than 10 feet and ior a pehoO of five minutes. During this period lt may be djrected in any_o-ne or more directions as desired. Therd shall be no leakage of water into the enclosure under these conditions.'
A NEMA 4 enclosure is suitrable for applications outdoors on ship docks and in dairies, breureries, etc. NEMA 4X . WATERTIGHT, CORROSION.RESISTANT
These enclosures are generally constructed along the lines of NEMA 4 enclosures except they are made of a material that's highlf resistai'rt to corrosion. For this reason, they are ideal in applications sucfi as pap€r mills, meat pacrung, tertllizer and cfiemical plants where contaminants rr'rould ordinarily destoy a steel enclosure over a period of Ume.
NEMA 7 . HAZARDOUS LOCATIONS . CLASS I
These endosures are designed to meet the application requirements of the National Electrical Code for Class I ha'ardous locationi. ln this type of equipment, the circuit intemlption occurs in air.
"Class I locations are those in which flammable gases or vaPorc are or may be present in the air in quantities sufftcient to produce explosive or Qnhbble mixtures.'
NEIIIA 9 HAZARDOUS LOCATIONS - CI-ASS II
These enclosures are designed to meet the application requirements of the National Electrical Code for Class ll hazardous locations.
"Class ll locations are those which are hazardous because of the presence of combustible dust."
The letter or letters following the type number indicates the particular group or grgups of hazardous locations (as defined in the National Electri6it Code) for which the enclosure is designed. The designation is
incomplete without a Euffx letter or letters. N E M A 12.INDUSTRIAL U S E
The NEMA 12 enclosure is designed for use in those industries where it is desired to exclude such materials as dust, lint, fibers and f,yings, ol see page or coolant see page. There are no conduit openings or
knockouts in the enclosure, and mounting is by means of flanges or mounting feet. NEMA I3. OILTIGI'TT. DUSTNGHT
NEMA 1 3 enclosures are generally of cast construction, gasketed to permil use in the same environments as NEMA 12 devices. ThJessential difference is that, due to its cast housing, a conduit enty is provided as an integral part of the NEMA 13 endosure, and mounting is by means of blind holes, rather than mounting brackets.
1.
Electrician Practice Test 1
In Class 1, Division 7 locations, conduit seal shall be placed a maximum of
inches Jrom an enclosures lor arc producing devices.
r - { 1 2 (' b) t8 r c 1 2 4 c' d) 30
What length is requiredfor the pullbox in the diagram below? The box is used with 480 volt conductors.
ay 32 inches
D24 inches
c; 48 inches d) anY length
Pull Box fror
uncjer 600 voh circuit
conductors hlo.4 and lcr.rQer
?
t l !
? Whut is the load that can be usedfor the semice calculationlor o dwelling '
unit when the Range has a nameplote rating of 13 KV? r a ; 1 3 k w r b) 8'4 hr/ ? c ; 8 h a " t-
d) none ofthe above
/ What size equipment grounding conductor is requiredfor a circuit
protected with a 50 ampere circuit breaker? l^ a) No' 12 coPPer ' b) No' 1o coPPer t* c) No' 8 coPPer
5. What is the highest voltagefor a Class I power limited circuit?
r a; 1'000 volts (^ b; 3o volts . c1 24 volts r
6.
What is the missing voltage in the sketch below? a; 120 volts U; 120 volt's c1 1200 volts d; 12,000 volts120
votts
1 00 Turns
Vottage
is
1 ,000
Turns
Wtat size Rigid Metal conduit is permittedfor thefollowing 9 conductors? 4 THVN #1, CU, 2 RHll/ (covered) #8 CIl, 3 RHW (covered) #6 Ca
a1 1 1/2 inch U; 1 1/4 inch
e 1 Il2 inch and 1 1/4 inch
d) None of the above
lV'hat is the el/iciency of a motor which draws 4,5 kilowatts from the line
and delivers 5 horsePower? r a) 80 Percent c 5;83 Percent
r
C ('7.
{ (-a8.
9, Power Factor con be defined as: r
a) True Power divided by Apparent Power. '
by Apparent Power divided by True Power '
s1 Appatent Power divided by volts x amperes
t n What is the powerfactorfor a three phase system operating when the
'' t"
wafirneter reads 6,000 watts, the voltneter reads 208 volts, and the ammeter reads 20 amperes? c a) .90 or 90 Percent r u; 1.0+ or 104 Percent (' c) .83 or 83 percent
t f Mtat is the powerfactor of a 8000 watt load connected to a 240 volt AC
L L '
single-phase circuit if the current is 36 amperes?
c a) '8 or 80 Percent c b) .93 or 93 Percent r c; 1.0 or 100 Percent
l !
.
t ). For theJigure below tf No. I or larger conductors are installed in the '-'
raceways dimension X shall be _inches minimwn The box is rcedlor
splices and doe not have the cubic inch dimensiotts marked on iL
a) 18 inches b) 16 inches
e 24 inches
C
73, For the 4-wal Switch, which is the correct hookup? r a ; D t o T , E t o & F t o T , G t o s c b ; D t o S , E t o & F t o T , G t o W c c ; D t o R , E t o T , F t o s , G t o w
4imy s'rvfuh
To 4-Way
Sw
t
i
( :
l
, ,t A dwelline has a floor areaof 2200 sq. ft., exclusive of an unfnished ceilar r-ic
not adaptalle for future use, unlinished attic, and open porches. Appliances
are a lj-kW range and a 5.5-kW, 240-V dryer. Assume rzmge and dryer kW
ratings equivalent to kVA ratings in accordance with Sections 220'18 and
2z}-lg.Computed Load [see Section 220-101
Fill in the following information:
General Lighting Load: sq. ft. at - VA per sq. ft. =
Minimum
Number of Branch Circuits Required:
GeneralLigbtingLoad: VAI l20V:-A
: General Lighting Load: YA I 120 V : - A
-.i ThiJrequires_ 15-A 2-wire or- 20-A,2-wire circuits
Small Appliance Load: 2-wire, 20-A circuits
Laundry Load :One 2-wire, 20'A circuit
one additional bathroom 20 ampere circuit is also required.
Minimum Size Feeder Required :
General Ligbting - VA VA Small Appliance Laundry Total 11100 VA VA at 100% 3000 VA VA - 3000 VA = VA at o/o is Net Load - VA Range - VA Dryer- VA
Net Computed Load - VA
Net Computed Load for 1201240-V, 3-wire, single-phase service or
y A l 2 4 0 V = _ A
Net computed load exceeds 10 kVA.
conductors to be - A.
Would require service VA
VA
VA
feeder
Calculation for Neutral for Feeder and Service:
Ligbting and Small Appliance Net Load
Ranee: VA at 70Yo is 5600 VA
Dryer i - VA at 70% is
Total - VA
Load for Neutral:
VA
What is thetinal computed loadfor the neutral in the above load calculation? r a1 65'9 r b) 63'7 r c1 loo r d ) 1 1 1
15. The correc't hookupfor the 3-woy swilch below is:
r a 1 A t o X , B t o z , c t o Y r b ; A t o Y , B t o x . c t o z r c ) A t o Z , B t o Y , C t o X r d ; A t o Z , B t o X , C t o Y
S U P P L Y
To 4-way
Switch
&iiay s'sribh16.
in the diagran below.Connect the delta wound 480 vott motor leadsfor the high voltage windings (* a7 g_7, 4-6,9-9, 54 r' b) 4_7,5-9, 6-9 c c; 4-9, 6'8,5'777, Find the correct size ventilated cable troyfor the diagram below. {^ a; 6 inches r b) 12 incbes r c) 18 inches ' d)24 inches Gr,sr 4/€ rElultloon4nctot e e b l e a E a c f i c a b l , e l a g incfi es iar dierns er
\
- Und'f, drra rnultiaon€tucto" I cables. E.=ctr +s{'e ;s \ r incn in ,risrraer
\
\
l
\ l
1 8 .
Find the voltage across the 5 ampere load afier the neutral is opened Botltloads are resistive and the powerfactor is 1.0.
(- a; 180 volts c b1 120 volts ' c; 0 volts 2 4 O v . a h J 1 2 9 v € { : l 3 € r v i € .
, O Find the size of inverce time circuit breaker requiredfor thefeeder r '/t
protecting theJoltowing polyphase induction moton. These motors are 'Design
B and-have a S-erviii Factor of 1.15 and are individually protected
with inverse time circuit breakers. c a; 150 amPere r- b) 175 ampere r c; 200 ampere q : J I I I
20.
How many cubic inches is requiredfor thefollowing box? AII conductors are No, 11 and there are no iiternal clamps,r { Qcubic inches (^ b) 16 cubic inches (- c) 18 cubic inches ' d) 20 cubic inches
Electrician Practice Test L
A}[SWBRES
#l b (18) Conduit seals
shall be installed
within 18 in. from the
enclostue.
Only explosion
proof unions' couplings,
reducers,
elbows, cappea
elbbws, and conduit bodies such &s L, T, and X
types not larger than the fiade size of the conduit are permitted
ut.t seal.
Text Reference
section
501-5(a)(1)
#2 a (32 inches) tn sfraight
pulls, the length of the box shall not
be lesi than eight times the trade diaureter
of the largest
raceway'
Text Reference
sectio
n 37 0'28(aX
1 )
#3 b (8.41n
,) 8 kw + 5 percent
of 8 kw is 8'4 kw'
Text Reference
section
table 220-19
Note 1
#4 b CIo. 10 copper)
Table
250-122
lists aNo. 10 copper
for a 50
ampere
circuit breaker.
Text Reference
section
250'L22
#5 b (30 volts) class 1 power
limited
circuits
shall
be supplied
from a source
ihat has Lrated
output
of not more than 30 volts and
1 00
0 volt-amperes.
Text Reference
sectio
n 7 25 -21
(a)
#6 c (1200
volts) l20A/oltage:
100
/1000;
voltage
= (120 x 1000
)/ 100,
voltage
: 1200
volts
#7 c (l % inch & | y4 inch) Problem: What size Rigid Metal conduit is
permitted for the following 9 conductors?
+ nrw}I #12 cIJ,2 RI{W (covered)
#8 cu, 3 RITW (covered)
#6 cu
From Table 5:
Area of #12 TIIV/N is .0.133
x 4 = .0532
Area of # 8 RI{W covered
= .0835
x2: .167
Area of #5 RHW covered
= .1041
x 3 = .3123
Total area: .5325
sq. inches
tn Table 4 for Rigrd Metal Conduit find the first number larger than .5325 that
is 0.610 in column for over 2 wires
40%-This corresponds
to L ll4 inch conduit.
A I I/2 inch conduit would also satisff the requirement.
Answer: C both I l/4 and 1 l/2 nch conduits
can be used.
Text Reference
section Chapter
9 Table l, Table 4, & Table 5
#8 b (83 percent)
efficiency: (5 x 746watts)
/ 4,500 watts
Basic Electrical Theory in aNutsheLl
See Handout
Text Reference
section Basic Electrical Theory
#9 a (True Power divided by Apparent
Power) True Power :
watts, Apparent
poweFvolt-amperes.
PF : watts/ volt amperes
Text Reference
section
Basic Electrical Theory
#10 c (83 or 83 percent)
PF = 6,000
I (208*20*1.732)
Text Reference
section
Basic Electrical Theory
#11 b(.93 or 93 percent)PF:8,000
I (240 volts x 36 amperes)
Text Reference
section
Basic Electrical Theory
#12 c (24 inches)
Use larger of (6 x 3) + 3 +3 : 24 inches
or (6 x
2 ) + 2 + l + 1 : 1 6 i n c h e s .
D i m e n s i o n X s h a l l b e 2 4
i n c h e s .
Text Reference
sectio
n 37 0'28(aX2)
t
#14 b (63.7) This problem
is alnost identical
to Example
D1(a) in Appendix
D of the 1999 Code. This dwelling has a floor arcaof 2200 sq. ft., exclusive of an
rrnfinished cellar not adaptable for future use, unfinished attic, and open porches.
Appliances are a 12-kW range and a 5.5-kW, 240-V dryer. Assune range and dryer kW
ratings equivalent to kVA ratings in accordance with Sections 220-18 aad220'
1 g.Computed Load [see Section 220-l0l
General Lighting Load: 2200 sq. ft. at 3 VA per sq. ft. = 6600 VA Minimum Number of Branch Circuits Required
[see Section 210-11(e)(1)] General Ligbting Load: 5600 VA / l20V: 55 A
This requires for:r l5-A 2-wire or three 20-A" 2-wire circuits
Small Appliance Load: Two 2-wire,20-A circuits [see Section 210-11(cX1)]
Lar:ndry Load:One 2-wbe,20-A circuit [see Section 210-11(c)(2)]
Batlrroom Branch Circuit: One 2-wire,20-A circuit (no additional load calculation is
required for this circuit) [see Section 210-11(cX3)]
Minimum Size Feeder Required [see Section 220-10]
General Lighting 6600 VA Small Appliance 3000 VA Laundry 1500 VA T o t a l 1 1 1 0 0 V A 3000 VA at 100% 3000 VA I I 1 0 0 V A - 3 0 0 0 V A : 8 1 0 0 V A a t 3 5 Y o i s 2 8 3 5 V A Net Load 5835 VA
Range (see Table 220-19) 8000 VA
Dryer (see Table 220-18) 5500 VA
Net Computed Load 19,335 VA
Net Computed Load for 1201240-V, 3-wire, single-phase service or feeder
1 9 , 3 3 5 V A ,240 V = 80.6 A
Net computed load exceeds 10 kVA. Section 230-42@) would require service conductors
to be 100 A.
Calculation for Neutal for Feeder and Service
Lighting and Small Appliance
Net Load 5835 VA Range: 8000 VA at70%o (see Section220-22) 5600 VA Dryer : 5500 YA at70% (see Section220-22) 3850 VA Total 14,550 VA
Computed Load for Neutral
#15 c (A to Z, B to Y, C to X) See Diagam
&vay svribh
To 4-way
Switch
#16 b (4-7,5-8,
6-9) Text Reference
section
Basic Electrical
Theory See
Diagrarn
O v e r 4 / o m u l t l c o n d u c t o r c a b l e s . E a c h c a b l e l s 2 I n c h e s I n d l a m e t e r
!
#17 b ( l2_tqshes
Text Reference
section
318-9(a)(2)
and Table 318-9
# 1 8 a ( 0 v o l t s ) R f o r 1 5 a l o a d
: 1 2 0 1 1 5 : 8 ohms;
R f o r 5 a lo a d
: 1 2 0 1 5
: 24 Neutral open l: 240 /(8 + 241
: 7 .5 a; E across
5 a load :7 .5 ax 24
--180 volts see diagram
N e L J t r a l o r g r o u n d e d c o n d u c t o r
Solution
Problem: Find the voltage across the 5 ampere load after the neutral is opened.
First find the resistance of each load:
l5 ampere load: V o l t s : 1 2 0 R : E / I R: 120 volts / l5 amperes R : 8 o h m s 5 ampere load: R: 120 volts / 5 amperes R : 2 4 o h m s
When neutral is open the two resistors are in series and the Total Resistance is 8 + 24 or 32 ohms'
The voltage is240 volts across the two resistors in series.
To find the curent after the neutral opens:
I= 24Q volts / 32 ohms
[ = 7.5 urmperes
The voltage across the 5 ampere load that has a resistance of 24 ohms is:
E = l x R
#19 b (175 amDere)
see
di
.'^.Problem: Find the size of inverse rime circuit breaker required for the feeder protecting
the following polyphase induction motors. These motors are Design B and have a
Service Factor of I .15 and are individually protected with inverse time circuit breakers.
This is a motor feeder circuit. There is a motor feeder Example D8 in Appendix D of the Code.
Motor Circuit Conductors, Overload Protection, and Short-Circuit and Ground-Fault
Protection
(see Sections 240-6, 430-6,430-22,430-23,430-24, 430-32,430-34,430'52, and 43042,
Tables 430-150 and 430-152)
Feeder Short-Circuit and Gror:nd-Fault Protection
The rating of the feeder protective device is based on the largest branch-circuit protective
device plus the sum of the full-load currents of the other motors [see Sections 240-6 and
a30-62(a)l
For the 5-hp motor FLA is 7.6 'mperes from Table 430-150.
For the 15-hp motor FLA is 21 arnperes from Table 430-150.
For the 40-hp motor FLA is J) ernpercs from Table 430-150.
52 x 1.25= 65 amperes
65 + 2l + 7.6 = 93.6 arnperes
The branch circuit protective device for the 40 hp motor is based on Table 430-152 is 250
percent times 52: 130 amperes. By Section 240-6 the next larger standard size CB is
150 amperes.
Then for the feeder Circuit Breaker: 150 + 2l + 7.6 = 178 amperes.
The nearest standard fuse that does not exceed this value is 175 A [see Sections 240-6
and 430-62(a)1.
#20 b (16 cubic inches)
see di
Problem:
How many cubic inches
is required
for the following box? All
conductors
are No. 14 and there are no intemal clamps'
Conductor Count Switch :2 '
Gror:nding conductors:1
Conductors that originate outside the box and terminate or are spliced in the
. b o x : 5
'
Total:8
;
't
The cubic inch area required by Table 370-16(b) for a No. 14 is 2 cubic inches. -i The cubic inch capacity required is 2 cubic inches x 8 or 16 cubic inches.
:
")
Answer is 16 cubic inches.
i
Reference:
(b) Box Fill Calculations. The volumes in paragraphs (1) through (5), as applicable, shall be added together. No allowance shall be required for small fittings such as locknuts and bushiirgs.
(1) Conductor Fill. Each conductor that originates outside the box and terminates or is spliced within the box shall be counted once, and each conductor that passes through the box without splice or termination shall be counted once. The conductor fill, in cubic inches, shall be computed using Table 370-16(b). A conductor, no part of which leaves the box, shall not be counted.
Exception: A:r equipment grounding conductor or conductors or not over four fixnue wires smaller than No. 1.4, or botb shall be permitted to be omitted from the calculations where they enter a box from a domed fixture or similar canopy and terminate within that box.
(2) Clamp Fill. Where one or more internal cable clamps, whettrer factory or fietd supplied, are present in the bo6 a single volume allowance in accordance with Table 370-16(b) shall be made based on the largest conductor present in the box. No allowance shall be required for a cable connector with its clamping mechanism outside the box.
(3) Support Fittings Fitl. Where one or more fxhrre studs or hickeys are present in the bo>r, a single volume allowance in accordance with Table 370-16(b) shall be made for each type of fitting based on the largest conductor present in the box.
(4) Device or Equipment Fill. For each yoke or strap containing one or more devices or equipment, a double volume allowance in accordance with Table
370-16(b) shall be made for each yoke or strap based on the largest conductor connected to a device(s) or equipment supported by that yoke or strap.
(5) Equipment Grounding Conductor Fill. Where one or more equipment grounding conductors or equipment bonding jr.mpers enters a box, a single volume allowance in accordance with Table 370-16(b) shall be made based on the largest equipment grounding conductor or equipment bonding jumper
present in the box. Where an additional set of equipment grotrnding conductors, as permitted by Section 250-L46(d), is present in the box, an additional volume allowance shall be made based on the largest equipment grounding conductor
Electrician Practice Test 2
I. In the diagram below the total resistance is and the value of R3 is
a) 20,10.7 ohms b) 20,19.7 ohms c) 20,20.7 ohms d ) 1 0 , 3 0 o h m s
(-r
l a 1 0 o h m s I = 6 a m p e r e s R t = itoialreslslanc e)) Wat is the ampacity of 12 No. 12 THHN copper conductors in a I0feet long
-'
EMT raceway where there are 9 current carrying conductors and the ambient
temperature is 42 degree C? (Select nearest answer)
f (-a) b) c) 10 amperes 15 amperes i 8 amperes 120 volts 20 ohms
I '^"Tl
R2 1 0 o h m s2 lVhat is the allowable ampacity of each No. 6 THW copper conductor if there ro
are l0 current carrying conductors in a 21 inch long rigid conduit nipple in a room where the antbient temperature is 55 degrees C? (Select nearest answer)
r a) 65 amPeres r b) $J amPeres (^ c) 50 amPeres r O 44 amperes
/ Find the size EMT nipple required to enclose 3 each 500 kcmil THHN
'rr
conductors bethteen wo
Panek-c a) 1 1/2 inch r b) 2 inch r c) 3irch ' d) 3 1/2 inch
( What size rigid steel conduit is requiredfor 1 each 4/0 XHHV/ and I each
cro
No. 3 bare iquipment grounding conductor if the raceway is 12feet long? c a) I ll2 inch r- b) 2 inch (. c) 2 ll2 inch (- d) 3 inch ' e) 1 inch
.
6. Junction boxes shall be '
C a) accessible '. (- b) readily accessible r .; visible (-
d) inside removable Panels
. i
n The type of lampholder required in a branch circuit in scess of 20 amPeres
/' ,ioi6, ' '.
c a) brass l- b) Porcelain coated (-c) not an interchangeable tYPe
'
d) heavY dutY
g. Ilnless an ucepted load as speciJied by the Code, a 56 ampere load shall be
protected bY a -fuse. t- a) 50 r b) 60 r* c) 70 (- d) 80
O fn a washdown area a metollic rucewoy shall be spacEd not less than "
inchfrom the walls. r a) ll8 c b ) l l 4 (- c) l/2 c d) 314
I n Given: Three (3) 500 kcmil Type THHN copper conductort in a raceway at
L v'
70 degrees C. The maximum allowable current in each conductor b
-amPefes.
r'
tr'
1 a) b) c) d) 249 409 430 705t I Alixture that weighs more than -pounds shall be supported
^ f
independentty of the outlet bon
r a ) 4 0
r
b) 50
c c ) 6 0
7 2. An AC-DC general use snap switch may be used wilh inductive loads at
-percent of its amPere rating at the applied voltage'
c a) 40 c b ) 5 0 e c ) 7 0 (- d) 80
, 2 When utilized as ou&ide bronch circuib andfeeden, overhead conductott t "'
fo, 600 volts or less, for spans up to 50 feet, shall not be less than
copper. (- a) No. 14 c b) No' 12 r c) No' 10 r * O N o . g
t / Conductorc of light and power systems of 600 volts or less may occupy tlte
rq'
ioit enclosire, without regard to whether the individual circuits are AC or
DC, only where all the conductors are -' c
a) insulated for the ma:cimum temperature within the enclosure.
,^ insulated for the maximum voltage of any conductor within the
,
b) enclosure
'
c) insulated for the maximum of 300voits
r'
I < When utilized in overhead services, without any excePtions, conducton t Jo
shalt not be smaller than No. coPper'
r a ) 1 4
c
b) 12
r c ) 1 0
. - o 8
7 A MAde electrodes must have a resistance to ground not to uceed
ru'
ohms when used alone c a) 5 c b ) 1 0 { - c ) 2 5 {- d) 30
t 7 Disregarding all exceptions, the sum of the cross-sectional area of all
r . .
conductors i"-i n:i*ay sh'all not *cied percent of the interior
cross-sectional area of the wireway'
c a) 20 ' b ) 3 0 r c ) 4 0 r d) 60
t R G i v e n : N i n e ( 9 ) N o . ! A V G . T H H N c o p p e r c o n d u c t o r s i n a c o n d u i t a t 3 0 4 v'
degrees C. Wltat is the maximum atloiitte ampacig in each conductor?
C c r* a
a) 33
'3
b) 38's
c) 40'0d) ss
t O The minimum total circuit ampacity reeuyl!lo supply an air conditioning
L "
mobr compressor unit which-corro rs 81500 volt amperes of power at a
l i n e v o l t a g e o f 2 l 0 v o l t s i s a m P e r e s . S e l e c t t h e c l o s e s t a n s w e r . f {-. e C (^ C a) b) c) d) 44.3 40.0 35.4 28.3
) n Given: An ollice building .ttas.a required.general tjshtins load of 50'000
- v'
volt amper"i. Tt , general tighting'toad i supptied by a single phase' 230
vo lt feeder circ uitThe minimum calculate d- iurrent in the feeder circ uit
ungroundeo'i*i conductors rs_ amperes. select the closest anEwer'
a) b) c) 208 217 227
o TOTAI RESISTAIICE : TOTAL VOLTAGE
TOTAI A]VTPERES
o Resistance
of n resistors
in parallel is found using the formula:
l/RT = liRl + 1lF.2
+ 1/R3...+1lRn
o Resistance
of two resistor in parallel is found r:sing the product
over the sum formula:
RT= (R1 x R2)/(R1+R2)
o Resistance
of n resistors
in series
is found using the formula:
RT = Rl + R2 + R3 ...+Rn
Using the above
ntles:
Rt: 120 volts i 6 amperes
Rt = 20 ohms
The resistance
of Rl, R2, and R3 in parallel is Rt minus 10 ohms minus 5 ohms
or 5 ohms.
The resistance
of Rl and R2 in parallel
is (10 x 20) / (10 + 20) or 6,7 ohms.
T h e n 5 o h m s = ( 6 . 7
x R 3 ) l( 6 . 7 + R 3 )
5 ( 6 , 7
+ R 3 ) = 6 . 7
x R 3
3 3 . 5 + 5 R 3 = 6 . 7 x R 3
6.7R3 - 5R3=
33.5
R3 (6.7 - 5) = 33.5
R3 = 33.5
I 1.7
R3 = 19.7
ohms
#2 c (18 amperes)
The derating
factor for 9 c1tlrent
carrying
conductors
in a raceway
is 70 percent,
and the ambient derating
factor for 42 degrees
C. is .87. Ampacity of THHN No. 12 is 30
amperes.
,7 x.87 x 30 : L8.27
Elmperes.
Text Reference
section
310-15(b)
table 310-16
and coffection
factors
at bottom of table and Table 3 1 0- 15(bx2)(a)
#3 d (44 amperes)
THW ampacity is 65 amperes.
The ambient
derating
factor is .67 .67 x 65 : 43.55 uunperes
Text Reference
section
3 10-
I 6 and conection
factors
at bottom of table
#4 b (2 inch) The area for 3 -500 kcmil THHN conductors
is 3 x
.7073
-2.1219 For 60 percent
filI using the.8 round offmethod
requires
a 2 inch EMT. Text Reference
section
348-8; Chapter
9,
table 1 notes
4 and 7, Table 4, and Table 5
#5 b (2 inch)
Area of 4 410: 4 x .3197
:1.2788; arca
of No. 3 is
.053
. 1.2788
+ .053
: 1.3318
sq. in. requiring
a2 inch rigid
conduit with a 40 percent
area
of 1.363
sq. in. Text Reference
section
346-7;
Chapter
9 Table I,4,5, and 8
#6 a (accessible)
Conduit
bodies,
junction, pull, and outlet boxes
shall be installed
so that the wiring contained
in them can be
rendered
accessible
Text Reference
section
37 0'29
#7 d (heavy duty) Where connected
to a branch circuit having a
rating in excess
of 20 amperes,
lampholders
shall be of the
healy-duty type. Text Reference
section210-21(a)
#8 b (60) The next larger size permitted by Code is 60 amperes.
Text Reference
sectio
n 240-3(0; 2a0-6(a)
#g b (Il4) Standard
practice
is to keep electrical
equipment
ll4
inch of the surface
in indoor locations
that may become
wet.
#10 a (249) By Table 310-16(bottom)
the derating
factor for 70
degrees
C in the 90 degree
C. column is .58. .58 x 430 A. :249
amperes.
Text Reference
section
310-16 and derating table at
bottom of page
#11 b (50) A fixture that weighs more than 50 lb (22.7 kg) shall be
supported
independent
of the outlet box unless the outlet box is
listed for the weight to be supported.
Text Reference
section
410-16(a)
#l2b (50) A form of general-use
snap switch suitable for use on
either ac or dc circuits for controlling Inductive loads not
exceeding
50 percent
of the ampere
rating of the switch.vw
Text Reference
section
3 80- 17
4(b)(2)
#I3 c (#10) Open individual conductors
shall not be smaller than
the following: For 600 volts, nominal, or less, No. 10 copper or
No. 8 aluminum for spans
up to 50 ft (15.2 m) in length and No. 8
copper or No. 6 aluminum for a longer sPffi, unless supported.
Text Reference
section
225-(a)(l)
#t4 b (insulated
for the ma:<imum
voltage of any conductor
within
the enclosure)
Text Reference
section
300-3(cXl)
# 15 d (8) The conductors
shall not be smaller than No. 8 copper or
No. 6 aluminum or copper-clad
aluminum.
Text Reference
section
230-23
#16 c (25) A single electrode
consisting
of a rod, PiPe, or plate that
does not have a resistance
to $ound of 25 ohms or less shall be
augrnented
by one additional
electrode
of any of the types
specified
in Sections
250-50
or 250'52.
Text Reference
section
250-56
: . , .
'
# I7 a (20) The sum of cross-sectional
areas
of all contained
conductors
at any cross section
of the wireway shall not exceed
20
:
percent
of the interior cross-sectional
area
of the wireway.
. j
#18 b (38.5)
By Table 310-15(bX2)
the derating
factor
for 9
conductors
in ataceway
is 70Yo. .70 x 55 = 38.5 amperes.
!
Text Reference
section
Table
310-16;
Table
310-15(bX2)(a)
'
#Ig a(44.3)
I: plE:8500 VN 240 volts
- 35.4 amperes.
Frorn
u:r
Table 440-32
125 pet cent of 35 .4: 44.3 amperes'
#20 a(208) I - P / E; 50,000
I 240 volts :208 Etmperes.
.
Text Reference
section
Appendix D
Electrician Practice Test 3
a , , i a h i , r m ' r r a r . N O . 3v u J - 4 l \ u l t u J s l .
I Given: Three (3) 500 kcmit THHN conductors in a raceway at 70 degrees
F-t'o
H/hat is the maximum ollowable current k each conductor if the terminations and equipment is rated at 90 Degtees C?
(-C C (- a) b) c) d)
2. F-texibte cord muy be used in oll of thefollowing locations ucept
--345 3 8 0 430 447 hoists cranes
to replace permanent wiring pendants
Anywhere
Class III, Division 2
Class II, Division I
Unclassified areas at a buik storage plants
r a ) {-
b) r c ) r d )
? Wen a conduit nippte having a maximum lengtft not to exceed 24 inches is
J'
installed, the nippii shall be permined tu beJilled to -percent of its total
cross sectional area
c a ) 3 0
c b )
r c )
c d )
4, Drums of gasoline may be stored in what type of outdoor area?
40 50 60 t I
r
f a) b) c) d)6.
The maximum allowablefiAfor conduit and tubkgfor 3 or more conductors,not lead covered is
5. The interior of paint spray bootlts ore considered
c a )
r b )
(- c) c d )
Class 1, or Class 2, Division I Class 1, Division 2
Class II, Division I Class II, Division 2
c a ) r b ) r c ) c d )
7.
In a conduit seal, the minimum thickness otthe seoling compound, exceptwhere rced in cables, should in no case be le5,s than
8.
30% 40% 50o/o 60% (- a)r b )
(' c) 518' r- d) 3/4uGiven: A 30 hpr 3-phase,160 volt, continuous duty induction motor with a
sembefactor of 1.15 and a temperature rise of 40 degrees C. The maximum
rating otthe required separate overload device is_ amperes.
' - a ) r b ) c c ) ll4u l/2" 46 5 0 5 6
o Given: Measurement across a 3-phase squirrel cage motor atfull load are 7o
460 volts and 65 amperes. What should the honepower rating be rcing the Code? c a ) 3 0 r b) 40 r c) 50 r d) 60
t n Refer to theligure below. Given the circuit shown What is the current in the
L v' neutral conductor? r a ) c b ) . c ) r d ) 25.0amperes 12.5 a.naperes 6.25 amperes 4.2 amperes
u4
U3u2
a t A J t n7 7 .
1 ,OOO \A/atts 5oo \A/a.tts N e u t r a l I | 1 2 O v A ( - l l ' l l l ' ' : : = : : : : : : = = : = = = : : : : = : : : : : : : : - 'Given: A 25footfeeder tap. The ampacity of the tap must be at least -tha,t of thefieder conductor or overcunent protectionfrom which il is tapped ( a t^ a) b) c) d)
t ) The normal current allowed on a coyiper bw in an Awiliary Gutters is '- a'
11000 amperes per squsrc inch. The nuntber of amperes which a 2 1/2 x 1/4
inch square copper bus may carry under thse conditions it- amPercs.
c a ) r b) 750 r c) l,'000 c d) t'250
t ? Given: A 240 volt conductor has a total length of 500feet and supplies d z r '
bad of 10 arqperes. The conductor has a resistance of 1.15 ohms per 1'000
feel The total wltage drop in the conductor circuil conducton is percent Select the closest answen
r
d)
n
| / The maximumftxture weight that may be supported by the screw sltell of a
'Tc
hmpholder is pornds.
7 5 .
t- ' 16
d) r\r
Where a cable is installed through bored holes in woodioists, where
possible, the hoks shall be bored so that the edge of the hole is not less than inch(es) from the nearest edge of the wood member.
r a )
r b )
r c )
J f 7 /- a) c b ) r c ) ) 6 1 0 r a ) c b ) r c ) IL v 4
L U 2
: - . :
76.
The minimum lighting toad requiredfor the general Eghting (only) of achurch huitding having ou&ide dimensions of 100t by 200' is -
volt-amPefes. c a ) r b ) c c ) r d ) 2,000 4,000 20,000 40,000
r
^) r b ) r c ) r d )I p Given: A 240 volt, 20 amPere two wire branch circuil If the ,ruEimum
r 'r'
ailowable voltage drop through the circuit conductors is 2,4 volts, what is
the maximum allowable resistance of the circuit conductorc?
t 7 The minimum size copper equipment grounding conductfor grounding r / '
equipmcnt hmting a 10 ampere automatic overcurrent device in the circuit
ahead of the equiPment isNa
6 8 1 0 1 2 r a ) (- b) r c ) c d ) 12 ohms 1 . 2 o h m s .48 ohms .12 ohms
I O The combined load oif two, 230 voltftxzd heaters on a 30 antlrere branch ^ "
circuit shalt not qceed kilowot&, Select the closest dnsreen
(' a) 2.4
r b )
(- c) (^ d))n Outlet boxes mounted in combustible walls or ceilings must be mounted so
-v'
that thq will be set back not more than a msimum of -kchfrom the
ftnished surface. ) . ) 5 . 9 24.0 U2
r/4
1 / 8 0 (must be flush)r
c.
r
C a) b) c) d)I
Electrician Practice Test 3
. - Q u i z N u m b e r : N o . 3
. _
#1 d (447) the correction
factor at the bottom of Table 310-16
for 70 degrees
F. is 1.04 for 90 degree
rated insulation
such as
I
fHHN. 1.04 x 430 amperes
: 447amperes.
Text Reference
section
Table 310-16
& Temperature
derating
factors
at bottom of table, and section
110-14
#2 c (to replace
pennanent
wiring) Text Reference
section 400-7
,
.,
400-8
#3 d(60) Where conduit or tubing nipples having a maximum
length not to exceed
24 n. (610 mm) are installed
between
boxes,
cabinets,
and similar enclosures,
the nipples shall be pennitted to
"
be filled to 60 percent
of their total cross-sectional
axea.
Text Reference
section Chaptet
9, Table 1 note 4
#4 d (Unclassified
areas
at a bulk storage
plants.) This permission
-
is given for bulk storage
plants and they are defined in Section
5 1 5- I . Text Reference
section
575-2
#5 a (Class
l, or Class
2, Division 1) The following spaces
shall
'
be considered
Class
I or Class
II, Division I locations,
as
applicable: The interiors of spray booths and rooms.
Text Reference
section
51
6-2(a)
#6b (40%) By Table 1 in Chapter
9,40 percent.
Text Reference
4,
section
Chapter
9, Table I
*
#7 c (5/8") In a completed
seal,
1[s minimum thickness
of the
sealing compound
shall not be less than the trade size of the
r
sealinE
fitting ond, in no case,
less than 5/8 in. Text Reference
section
501-5(cX3)
#8 d (60) 125 percent
of 40 is 50 amperes,
but Section 430'34
allows a 140 percent maximum overload.
Text Reference
section
table 430-150;
Sections
430-32(aXl); 430-34
#9 c (50) By Tabl
e 430-150
a 50 horsepower
motor has a fulI load
amperes
of 65. Text Reference
section
430-150
#10 d (4.2 anperes) Cunent through 1000 watt load : L,000/120
-8.3 amperes; Current through 500 watt load : 500/120 = 4.L7
amperes.
8.3 - 4.I -- 4.2 amperes.
Text Reference
section
Basic
Electrical Theory
#11 b (Ll3) Also, the tap conductors
terminate
in a single circuit
breaker or a single set of fuses that will limit the load to the
ampacity of the tap conductors
and shall be protected.
Text
Reference
sectio
n 241 -2l.
(bX2)
#L2b (625)Amperes
: (2.5 x .25) x 1,000: 625 amperes
Text Reference
section
37 4-6(a)
#13 a (3) E:IxR; E:l0 x (500/1,000)xl
.45 : 7 .25 volts;
percent
-(7.251240
) x 100
- 3 percent Text Reference
section
Basic
Electrical Theory
#14 b (6) A fixture that weighs more than 6 lb (2.72 kg) or exceeds
16 in. (406 mm) in any dimension
shall not be supported
by the
screw shell of a lampholder.
Text Reference
section
4L0-
15(a)
#15 b (I %) If this requirement
cannot
be met, standard
*nail
plates* can be used. Text Reference
section
300-4(aX1)
#16 c (2000) 100' x 200' - 20,000
sq. ft.,By Table 220-3(a)
1 VA
per square
foot is required
for churches.
1 x 20,000
:20,000 VA.
#17 c (10) By Table 250-122
a40 ampere
OCPD requtues
a No. 10
copper equipment
grounding
conductor.
Text Reference
section
table 250-122
'
#1 8 d (.12 ohms)
R: El I;R: 2.41
20; R - .12 ohms
. The 240
is (2.41240
)x 100
= I percent.
Text Reference
section
review DC
Theory
,
+19 b (5.5)
.8 x 30 :24 €rmperes.
24x230:5520 watts;
'i
5520/1000:
5.5 lcw. Text Reference
section
a2a-3$)
-.''
#20 d(0 must be flush) In walls and ceilings constucted of wood
or other combustible
material,
boxes shall be flush with the
.
finished surface
or project there from Text Reference
section
:
E
Electrician Practice Test 4
1. Refer to theJigure below. What is wrong with the grounding rod illwtrated?
r
a) It is not 10 feet long.
(-
b) It requires a gror.urd ciamp
r
c) It is not 30 inches deep
f
d) There is nothing wrong, according to the Code
-J
Service
Grounding
Electrode
Conductor
S o i l
t
2 f t . d e e p
I
) Which of thefollowing is not a standardfnse or inverse time chcuit breaker a' size? r a ) . . c ) c d) 55
? fn general, a continuous dttty motor rated at more than I horsepower shall be
"'
protected by a sqarate overload daice rated at no more than - percent
of the motor nancplatefull-load current rating.
3 5 45 50 r a ) r b ) r c ) r d) 125
,t Where direct buried conductors or cab:les emergefrom the ground they shall
ac
be protected by enclosures or raceways. In no case shall the protection be
required to uceed - inches belowJinished grade
r a ) r b ) r c ) r d )
{ Given: Three resistorc (R1, H, and R3) are instuAed in a series circuit The
v'
power used by.R/ ts 100 watts and the power used by M is 75 watts. The total power used by the circuit is 225 wat6. Then the power used by resbtor RJ it
r4tatts,
r
r
a
(-a) b) c) d) 1 0 0 1 1 5 l 2 l 8 24 3 0 24 5 0 175Refer to thefigure below. The total rcsbtance Rt is
closest answen
ohms. Sekct the
6.
c a ) r b ) r c ) r d ) r a ) . . b ) c c ) (- d) 9.4 1 0 . 5grognded by running a ground from the range frame to the outlet
box, wrapping the ground around the cord and then grounding it
to the outlet box. ungrounded
grounded by a 4-wire cord containing the two hot leads, the
neutral, and a green grounding conductor. (the range requires a
4-wire cord)
grounded at the range by bonding the grounded conductor to the
ftrnge frarne.
1 5 40
7 Given: Afree standing electric range b rated n0n40 volts and requires a
r t
neutral connectionfor the 120 vott timer and lights. The range is equipped witlt 3 wire cord with No. 8 copper condaclors ond a 3 prone plugfor two hot
leads and neutraL The rangeframe shall be permitted to be -'
PE
15 ohrns
9.
The Code requires at least two stnall appliance branch circuibfordwellings, These small appliance circuib shall be assigned a load of volt-amperes each when calculatingfeeden and service entrance
requiremen&. r a ) r b ) c c ) f* d) I0. T:"*^*{*efollowing
receptacles may be connected to the small appliance
| | A metal underground water pipe in direct contact with the earth for at least
1 1'
il feet has traditionally be:en a preferred groanding electrode For all new
construction, a metal underground waler pipe is -.
r a ) . - b ) (- c) c a ) r b ) . ^ c ) (- d) 750 1000 I 500 2000
receptacles for electric clocks in the kitchen
garage ceiling receptacles for garage door openers
hallway which are close to the kitchen
still the preferred grounding electrode, by itself, when
available.
still an acceptable grounding elechode, but it must be
supplemented by at least one additional grounding electrode.
no longer accepted as a grounding elechode
accepted as the only grounding electrode when buried at least
three(3) feet below the surface.
t 2 Thermal insulation shall not be installed within inches of a recessed
L -'
figMfirture enclosure unless the recessed ligfutirture is identiJied as
suitablefor dbect contact with insulatiort
c ^) (- b) r c ) r d ) 2 4 5
I
:
t ? The No. 12 or 11 grounded conductor of a bronch circuit shall be identifrcd
t J a
Dv a w,re.
white or gxay color or three continuous white stripes on other
a) than green insulation
t I The Code deJines ttcontinuous loadtt as o load where the maximum current
z "
is upected to continuefor at least -,
c b )
r
c)
r d )
green color or bare copper
yellow color black color
r a )
r b )
l- c) r d )one hour or more two hours or more tfuee hours or more twenty four hours a daY
c a ) r b )
i .
c) ' d )
76.
Outlet boxes mounted in non<ombustible walls or ceilings must bemounted so that they will be set back not morc than a moximum of inch trom th e Jin is hed s urface.
t < For calculating the me,imum nwnber of conduclors allowed in an outlet t '"
box the volume requiredfor each No. 12 conductor it- cubic inches.
I
r
a) b) c) 2 2.25 2 . 5 3 1/8 1 t 4u2
t Z Screr*shell lamphoWers shall be wired so thgt ttle '' ' '
connected to the scret+t-shell
condtrctor is c a )
r b )
r c )
' - d ) grounding grounded ungrounded bare 1 / 8 Ll4 3 t 8 il2 outside dimensions of inside dimensions of heigbt of number of rooms in7 8 .
Enclosuresfor overcurrent devices in damp or wet locations shall bemauinUd so there is at least - inch alr space between the wall or other
support surface. r a )
c b ) c c ) r d )
, A Are least _inches offree conductor shall be left at each outlet and
" '
switch pointfor splices orfor the connection ofJirtures or devices.
r a ) 5 r b) 6 ' c ) 7 r d) 8
20. In determini?8.!o-:d o1th.1,volt'aTlere Pe: squarefoot basis the
the building shall be usedfor eachfloor.
('
r
r
a
a) b) c) d)Electrician Practice Test 4
AIISWERTS
#1 c (it is not 30" deep) Where rock bottom is encountered,
the
electrode
shall be driven at an oblique angle not to exceed
45
degrees
from the vertical or shall be buried in a trench that is at
least 2%ft(762 mm) deep.
Text Reference
section250'52(c)
See Diagram
Grounding Electrode Conductor
a ft. tong by 1/2 inch diameter solid copper rod
#2 d (55) 50 amperes and 60 amperes
are standard
fuse and
circuit breaker sizes but 5 5 is not. Text Reference
Section
240-6(a)
#3 d (125)
Text Reference
Section
430-32(aXl)
#4b (18) Direct-buried
conductors
and cables
emerging
from the
glound shall be protected
by to a point at least
8 ft above
finished
#5 b (50) 225 -75 - 100:50 watts
TextReference
SectionBasic
Electrical
Theory
#6 a (9.4) Basic electrical
theory. Rt - (Rl x R2)/ (Rl + R2); RT
: (25 x 15) I (25 +15) : 9.4 ohrns
Text Reference
Section
Basic
Electrical Theory:
Product
over the sum.
#7 c (grounded
by a 4-wire cord containing
the two hot leads,
the
neutral, and a green grounding conductor.
the range requires a
4-wire cord) A new change
no longer allows ranges
to be grounded
with he grounded
conductor
in new installations.
Text Reference
Section 250-142
#8 b (two (2) single pole circuit breakers,
tied together)
In dwelling
units, a multiwire branch circuit supplying more than one device or
equipment on the same
yoke shall be provided with a means
to
disconnect simultaneously
all ungrounded
conductors
at the
panelboard
where the branch circuit originated.
Text Reference
Section 210-4(b)
#9 c ( 1 500) Text Reference
Secti
on 250-142
# 10 a (receptacles
for electric clocks in the kitchen)
Also the small appliance
branch circuits can supply Receptacles
installed to provide power for supplemental
equipment
and lighting
on gas-fired ranges,
ovens,
or counter-mounted
cooking units. Text
Reference
Section2l0-52(bx2)
Exception
No. 1
R2
1 5 o h m s
# 1 1 b (still an acceptable
gounding electrode,
but it must be
supplemented
by at least one additional
glounding elecfrode.)
Because
plumbers
keep replacing
metal pipe with plastic pipe the
metal underground
water pipe is no longer a reliable underglound
grounding electrode.
Text Reference
Section
250-50(a)
#12 b (3) Thermal
insulation
shall not be installed
above
a recessed
fixture or within 3 in. (76 mm) of the recessed
fixhre*s enclosure,
wiring comparfment,
or ballast unless it is identified for contact
with insulation,
Tnrc IC. Text Reference
Section
410-66(b)
#13 a(white or glay color or three continuous
white stripes
on
other tlan green insulation.)
Ax insulated
grounded
conductor
of
No. 6 or smaller shall be identified by a continuous
white or
natural g;ay outer frrish or by three continuous
white stripes on
other than green insulation
along its entire length. Text Reference
Section
200-6
#14 c (three hours or more) Continuous
Load: A load where the
maximum culrent is expected
to continue
for 3 hours or more'
Text Reference
Section
Article 100
#15 b (2.25)No.
2 requires
2.25 cubic inches
per Table370-16(b)
Text Reference
Section
Table 370-16(b)
# 1 6 b (I I 4") Text Reference
S ectio
n 37 0-20
#17 b (grounded)
For devices
with screw shells,
the terminal
for
ttre gfo*ded conductor
shall be the one connected
to the
# 1 9 b ( 6 ) t l e a s t 6 i n . ( | 5 2 m m ) o f f r e e c o n d u c t o r ' m e a S u r e d f r o m
the point in the box where it emerges
from its raceway or
cable sheath,
shall be left at each outlet junction, ffid switch
point for splices or the connection
of fixtures or devices.
Text Reference
Section
300-14
I
# 2 0 a ( o u t s i d e d i m e n s i o n s o 0 T h e f l o o r a r e a f o r e a c h f l o o r s h a l l b e
computed from the outside dimensions of the building,
dwelling unit, or other area involved. Text Reference
Section
220-3(b)
Electrician Practice Test 5
7 The circuit conductor that is defined os being intentionally grounded is the
1' conductor. r a) grounding ' b) grounded r c) equiPment grounding r d) grounding electrode
2. Class II location are those that are hazardous because of the presence of
a) ignitable vaPors r u; iPitaule fibers c c) combustible dust r d; combr:stible liquids
2 ff tbee resistorc with values 5, 10, and 15 ohms respectively are connected in
Jc
iaraltet, tlrc combined total resbtance b- ohms. Select the closest
answef, c a ) o ' 4 r b) 2'3 c c) 2'7
r
d) 3o'o
/ The wiring in a 200foot long branch circuil measures a total resistance of zo
0.5 ohms. What is the resistance per 1,000feet?
r a) 0'5 ohms r b) 1'o ohms -' C) l'') OnmS ,- 5.0 ohms ' d )