Non-extensible circuit breakers

200A

0

Ringmaster range

Specification

Ringmaster range

Specification

CN2-T1 CN2-T6 Environment Indoor / outdoor b b IP54 b b Ratings

Normal rated current 200A b b

12kV 16kA 3 seconds 75kV BIL b b

13.8kV 21kA 3 seconds 95kV BIL O O

Cable earth switch 16kA 3 seconds b b

Cable earth switch 21kA 3 seconds O O

Transformer earth switch 3.15kA 3 seconds b b

Mechanism

Independent manual b b

Protection & control - circuit breaker

CT’s dual ratio - 100/50/5A class X b

CT’s ratio - 200/1A class X b

Overcurrent & earth fault CT operated trip coils b

Time fuse Link O

IDMT overcurrent & earth fault relay - VIP 300 b

20V-250V shunt trip coil b b

Circuit breaker auxiliary switch 1NO 2NC b b

Indication

Mechanical ON/OFF b b

Mechanical EARTH/MAIN b b

Neon indication (6.6 - 13.8kV) O O

Auxiliary switch contacts 1NO 2NC b b

Gas pressure indicator b b

Test facility

Integral cable test facility b b

Standard features

Operating handle b b

Transformer earth switch 3.15kA 3 seconds b b

Cable (see available cable kit accessories)

Bottom entry up 300mm2 1 x 3c b b

Bottom entry up 630mm2 3 x 1c b b

(2)

20

Non-extensible circuit breakers

200A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

CN2-T1 CN2-T6 Kit no. Cable kits

Tee-off cable box v v RMR-F47

Gland plate 1 x 3C O O RMR-A48

Gland plate 3 x 1C O O RMR-A49

Angled gland plates (RMR) O O RMR-A50 Blank

Blank aluminium gland plate O O RMR-A52

Brass wiping gland 1 x 3C O O RMR-A10

Brass wiping gland 3 x 1C O O RMR-A11

Tubular gland 1 x 3C O O RMR-A12

Tubular gland 3 x 1C O O RMR-A13

CES5 gland plate 1 x 3C O O RMR-A132

Installation items

Set of padlocks - 6 no O O RMR-A18/6

Anti-vandal fixings, including tool O O RMR-A19

Foundation bolts (not required for transformer mounting) O O RMR-A22

Multicore pilot glands O O RMR-A16

Time limit fuses (set of 2 - specify rating as table page 113) O RMR-A17 Operational items

Operating handle b b RMR-A23

Neon indication (6.6-13.8kV) v v RMR-F108

Neon lamp test unit (including lamp) O O RMR-A24

Neon lamp O O RMR-A81

VAP 6 test unit for VIP 300 O RMR-A202

Mechanical interlocks

Key free, earth on v v RMR-F85

Key free, unit off v v RMR-F86

Transformer earth switch, key free, earth on v v RMR-F110

N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms

Order codes

12kV, 16kA, 75kV BIL, 0.35bG CN2-T1/16 CN2-T6/16

13.8kV, 21kA, 95kV BIL, 0.8bG CN2-T1/21 CN2-T6/21

General arrangement drawing - transformer mounted RMINST-04 Page 70 RMINST-04 Page 70 General arrangement drawing - freestanding RMINST-09 Page 111 RMINST-09 Page 111 Schematic diagram RMSCH-26 Page 100 RMSCH-11 Page 90 Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

(3)

21

Non-extensible circuit breaker

200A

0

CN2-T1

Ringmaster range

Panel types

Ringmaster range

Panel types

Transformer protection up to 3.5MVA

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142

Protection CT’s - 200/1A class X

b Setting range:

v Overcurrent: 20-200A

v Earth fault: 2A-160A

Shunt trip coil, 20V DC-250V AC

Transformer ratings See table - page 113 Documents

Transformer mounted installation drawing ref: RMINST-04

Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: RMSCH-26

Environment Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Tee-off earth switch, 3.15kA 3s Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator CB auxiliary contacts 1NO 2 NC Test facility

Integral cable test facilities Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Tee-off cable box Glands and plates Interlocks

See page 20 for details Order information

Code Rating

CN2-T1/16 16kA, 12kV, 75kV BIL CN2-T1/21 21kA, 13.8kV, 95kV BIL

(4)

22

Non-extensible circuit breaker

200A

0

CN2-T6

Ringmaster range

Panel types

Ringmaster range

Panel types

Transformer protection up to 1.5MVA

Protection & control - CB

Overcurrent and earth fault protection using CT operated trip coils with provision for time fuse links.

Protection CT’s - 100/50/5A class X

Shunt trip coil, 20V DC-250V AC

Transformer ratings See table - page 113 Documents

Transformer mounted installation drawing ref: RMINST-04

Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: RMSCH-11

Environment Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Transformer earth switch, 3.15kA 3s Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator CB auxiliary contacts 1NO 2 NC Test facility

Integral cable test facilities Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Tee-off cable box Glands and plates Interlocks

See page 20 for details Order information

Code Rating

CN2-T6/16 16kA, 12kV, 75kV BIL CN2-T6/21 21kA, 13.8kV, 95kV BIL

(5)

23

Non-extensible switch 630A

0

Ringmaster range

Specification

Ringmaster range

Specification

SN6-S1 SN6-S2 Environment Indoor / outdoor b b IP54 b b Ratings

Normal rated current 630A b b

13.8kV 21kA 3 seconds 95kV BIL b b

Cable earth switch 21kA 3 seconds b b

Transformer earth switch 3.15kA 3 seconds b b

Mechanism

Independent manual b b

Provision for actuator 24V DC b

Actuator 24V DC O

Indication

Mechanical ON/OFF b b

Mechanical EARTH/MAIN b b

Neon indication (6.6 - 13.8kV) O O

Auxiliary switch contacts 1NO 2NC b

Phase and earth fault detection CT’s for Easergy 200E O

Provision for EFPI O O

Test facility

Integral cable test facility b b

Standard features

Operating handle b b

Transformer earth switch 3.15kA 3 seconds b b

Cable (see available cable kit accessories)

Bottom entry up 300mm2 1 x 3c b b

Bottom entry up 630mm2 3 x 1c b b

(6)

24

Non-extensible switch 630A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

SN6-S1 SN6-S2 Kit no. Cable kits

Tee-off cable box v v RMR-F47

Gland plate 1 x 3C O O RMR-A48

Gland plate 3 x 1C O O RMR-A49

Angled gland plates (RMR) O O RMR-A50

Blank aluminium gland plate O O RMR-A52

Brass wiping gland 1 x 3C O O RMR-A10

Brass wiping gland 3 x 1C O O RMR-A11

Tubular gland 1 x 3C O O RMR-A12

Tubular gland 3 x 1C O O RMR-A13

CES5 gland plate 1 x 3C O O RMR-A132

Installation items

Set of padlocks - 6 no O O RMR-A18/6

Anti-vandal fixings, including tool O O RMR-A19

Foundation bolts (not required for transformer mounting) O O RMR-A22

Multicore pilot glands O O RMR-A16

Operational items

Operating handle b b RMR-A23

Neon indication (6.6-13.8kV) v v RMR-F108

Neon lamp test unit (including lamp) O O RMR-A24

Neon lamp O O RMR-A81

Actuator 24V DC v RMR-F67

Mechanical interlocks

Key free, earth on v RMR-F85

Key free, unit off v RMR-F86

Transformer earth switch, key free, earth on v v RMR-F110

N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms

Order codes

13.8kV, 21kA, 95kV BIL, 0.8bG SN6-S1/21 SN6-S2/21

General arrangement drawing - transformer mounted RMINST-04 Page 69 RMINST-04 Page 69 General arrangement drawing - freestanding RMINST-09 Page 111 RMINST-09 Page 111

Schematic diagram N/A RMSCH-28 Page 101

(7)

25

Non-extensible switch 630A

0

SN6-S1

Ringmaster range

Panel types

Ringmaster range

Panel types

Switch disconnector

Protection & control - CB Non-automatic

Documents

Installation drawing ref: RMINST-04

Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: N/A

Environment Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features

Transformer earth switch, 3.15kA 3s Cable earth switch, 21kA 3s Anti-reflex operating handle

Indication

Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Test facility

Integral cable test facilities Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Tee-off cable box Neon indication Glands and plates Interlocks

See page 24 for details Order information

Code Rating

SN6-S1/21 21kA, 13.8kV, 95kV BIL

(8)

26

Non-extensible switch 630A

0

SN6-S2

Ringmaster range

Panel types

Ringmaster range

Panel types

Switch disconnector

Protection & control - CB Non-automatic

Documents

Installation drawing ref: RMINST-04

Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: RMSCH-28

Environment Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual

Provision for actuator, 24V DC

Standard features

Transformer earth switch, 3.15kA 3s Cable earth switch, 21kA 3s Anti-reflex operating handle

Indication

Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Auxiliary contacts 1NO 2NC Earth selected auxiliary contact 1NO Test facility

Integral cable test facilities Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Tee-off cable box

Actuator, 24V DC

Neon indication Glands and plates See page 24 for details Order information

Code Rating

SN6-S2/21 21kA, 13.8kV, 95kV BIL

(9)

27

Non-extensible metering unit

200A

0

Ringmaster range

Specification

Ringmaster range

Specification

MU2-M1 MU2-M2 MU2-M3

Environment

Indoor / outdoor b b b

IP54 b b b

Ratings

Normal rated current 200A b b b

12kV 16kA 1 second 75kV BIL b b b

Metering*

CT’s -50/25/5A 0.5s 7.5VA b

CT’s -100/50/5A 0.5s 10VA b

CT’s -200/100/5A 0.5s 10VA b

VT’s -11kV/110V 0.5 50VA b b b

*CT’s - 2 phases (R & B), VT’s phase to phase. 6.6kV VT’s are available - contact Merlin Gerin

Cable (see available cable kit accessories)

Bottom entry up 300mm2 1 x 3c O O O

Bottom entry up 630mm2 3 x 1c O O O

(10)

28

Non-extensible metering unit

200A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

MU2-M1 MU2-M2 MU2-M3 Kit no.

Cable kits

Tee-off cable box v v v RMR-F47

Gland plate 1 x 3C O O O RMR-A48

Gland plate 3 x 1C O O O RMR-A49

Angled gland plates (RMU) O O O RMR-A51 Blank

Blank aluminium gland plate O O O RMR-A52

Brass wiping gland 1 x 3C O O O RMR-A10

Brass wiping gland 3 x 1C O O O RMR-A11

Tubular gland 1 x 3C O O O RMR-A12

Tubular gland 3 x 1C O O O RMR-A13

CES5 gland plate 1 x 3C O O O RMR-A132

Installation items

Set of padlocks - XX no O O O RMR-A18/6

Foundation bolts (not required for transformer mounting) O O O RMR-A22

Multicore pilot glands O O O RMR-A16

RMU - MU2 installation kit O O O RMR-A350

Freestanding installation kit O O O RMR-A90

Order codes

12kV, 16kA, 75kV BIL, 0.35bG MU2-M1/16 MU2-M2/16 MU2-M3/16

General arrangement drawing - transformer mounted RMINST-07/08

Page 72 - 73 RMINST-07/08 Page 72 - 73 RMINST-07/08 Page 72 - 73 Schematic diagram RMSCH-14 Page 90 RMSCH-14 Page 90 RMSCH-14 Page 90 Key: v Factory fitted accessory O Loose accessory, assembled on site

(11)

29

Non-extensible metering unit

200A

0

MU2-M1

Ringmaster range

Panel types

Ringmaster range

Panel types

Non-extensible metering unit

Protection & control - CB N/A

Metering transformers b Metering CT’s R & B phases

v 50/25/5A v 7.5VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents

Installation drawing ref: RMINST-07/08 Schematic drawing ref: RMSCH-14 Environment

Indoor/outdoor IP54

Ratings

Short time withstand 16kA 1s Normal current rating 200A Normal rated voltage 12kV Normal rated BIL 75kV Standard features

Direct coupling between RMU and transformer (optional freestanding cable connection) Cable connection Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Cable box Glands and plates Installation kits See page 28 for details Order information

Code Rating

MU2-M1/16 16kA, 12kV, 75kV BIL

(12)

30

Non-extensible metering unit

200A

0

MU2-M2

Ringmaster range

Panel types

Ringmaster range

Panel types

Non-extensible metering unit

Protection & control - CB N/A

Metering transformers b Metering CT’s R & B phases

v 100/50/5A v 10VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents

Installation drawing ref: RMINST-07/08 Schematic drawing ref: RMSCH-14 Environment

Indoor/outdoor IP54

Ratings

Short time withstand 16kA 1s Normal current rating 200A Normal rated voltage 12kV Normal rated BIL 75kV Standard features

Direct coupling between RMU and transformer (optional freestanding cable connection) Cable connection Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Cable box Glands and plates Installation kits See page 28 for details Order information

Code Rating

MU2-M2/16 16kA, 12kV, 75kV BIL

(13)

31

Non-extensible metering unit

200A

0

MU2-M3

Ringmaster range

Panel types

Ringmaster range

Panel types

Non-extensible metering unit

Protection & control - CB N/A

Metering transformers b Metering CT’s R & B phases

v 200/100/5A v 10VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents

Installation drawing ref: RMINST-07/08 Schematic drawing ref: RMSCH-14 Environment

Indoor/outdoor IP54

Ratings

Short time withstand 16kA 1s Normal current rating 200A Normal rated voltage 12kV Normal rated BIL 75kV Standard features

Direct coupling between RMU and transformer (optional freestanding cable connection) Cable connection

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Cable box Glands and plates Installation kits See page 28 for details Order information

Code Rating

MU2-M3/16 16kA, 12kV, 75kV BIL

(14)

32

Extensible circuit breakers 200A

0

Ringmaster range

Specification

Ringmaster range

Specification

CE2-T2 CE2-T3 CE2-T7 CE2-T11 CE2-T12 CE2-T13 CE2-T14 CE2-T15 CE2-T16 CE2-T19 CE2-T20 CE2-T21 Environment

Indoor / outdoor b b b b b b b b b b b b

IP54 b b b b b b b b b b b b

Ratings

Busbars 630A b b b b b b b b b b b b

Circuit breaker normal rated current 200A b b b b b b b b b b b b

12kV 16kA 3 seconds 75kV BIL b b b b b b b b b b b b

13.8kV 21kA 3 seconds 95kV BIL O O O O O O O O O O O O

Cable earth switch 16kA 3 seconds b b b b b b b b b b b b

Cable earth switch 21kA 3 seconds O O O O O O O O O O O O

Mechanism

Independent manual b b b b b b b b b b b b

Provision for actuator 24V DC b b b b

Actuator 24V DC O O O O

Operating handle b b b b b b b b b b b b

Protection system

CT’s dual ratio - 500/200/1A class x b b

Overcurrent relay - VIP 30 b

CT’s dual ratio - 100/50/5A class X b

CT ratio - 200/1A class X b b b b b b b b b

Overcurrent & earth fault CT operated trip coils b

Overcurrent & earth fault relay VIP 35 b

Time fuse link O

IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b

20V-250V shunt trip coil b b b b b b b b b b b b

Auxiliary switch 1NO 2NC b b b b b b b b b b b b

Metering

CT’s -200/100/5A 0.5s 10VA b b b b b b b

VT’s -13.8kV/110V 0.5 10VA 13.8/110V/110v 0.5 50VA 3P 20VA b b

VT’s -11kV/110V 0.5 50VA b b b

VT’s -6.6kV/110V 0.5 50VA b b

VT’s phase - phase, CT’s R & B b b b b

VT’s phase - earth, CT’s RYB b b b

Indication

Mechanical ON/OFF b b b b b b b b b b b b

Mechanical EARTH/MAIN b b b b b b b b b b b b

Cable neon indication (6.6 - 13.8KV) O O O O O O O O O O O O

Auxiliary switch contacts 1NO 2NC b b b b b b b b b b b b

Earth selected auxiliary contacts 1NO b b b b

Test facility

Integral cable test facility b b b b b b b b b b b b

Cable

Bottom entry up to 300mm2 1 x 3c b b b b b b b b b b b b

Bottom entry up to 630mm2 3 x 1c b b b b b b b b b b b b

Top entry cables O O O O O O O O O O O O

(15)

33

Extensible circuit breakers 200A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

CE2-

T2 CE2- T3 CE2- T7 CE2-T11 CE2-T12 CE2-T13 T14CE2- CE2-T15 CE2-T16 CE2-T19 CE2-T20 CE2-T21 Kit no. Cable kits

Gland plate 1 x 3C O O O O O O O O O O O O RMR-A48

Gland plate 3 x 1C O O O O O O O O O O O O RMR-A49

Angled gland plates (RMR) O O O O O O O O O O O O RMR-A50

Blank aluminium gland plate O O O O O O O O O O O O RMR-A52

Brass wiping gland 1 x 3C O O O O O O O O O O O O RMR-A10

Brass wiping gland 3 x 1C O O O O O O O O O O O O RMR-A11

Tubular gland 1 x 3C O O O O O O O O O O O O RMR-A12

Tubular gland 3 x 1C O O O O O O O O O O O O RMR-A13

CES5 gland plate 1 x 3C O O O O O O O O O O O O RMR-A132

Top entry cables standard

panels v v v v v RMR-F93

Top entry cables MU6 only v v v v v v v RMR-F94

Installation items

3 phase busbars 630A O O O O O RMR-A14

3 phase busbars 630A O O O O O O O RMR-A78

Busbar end kit O O O O O O O O O O O O RMR-A15

Set of padlocks - 6 no O O O O O O O O O O O O RMR-A18/6

Foundation bolts (not required for transformer mounting)

b b b b b b b b b b b b RMR-A22

Multicore pilot glands O O O O O O O O O O O O RMR-A16

Time limit fuses (set of 2 - specify

rating as table page 113) O RMR-A17

Operational items

Operating handle b b b b b b b b b b b b RMR-A23

Cable neon indication

(6.6 - 13.8kV) v v v v v v v v v v v v RMR-F108

Neon lamp test unit

(including lamp) v v v v v v v v v v v v RMR-A24

Neon lamp O O O O O O O O O O O RMR-A81

VAP 6 test unit for VIP 300 O O O O O O O O O O O RMR-A202

Actuator 24V DC v v v RMR-F67

Polarity conversion kit** v v v RMR-F391

Mechanical interlocks

Key free, EARTH ON v v v v v v RMR-F85

Key free, MAIN OFF v v v v v v RMR-F86

N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

(16)

34

Extensible circuit breakers 200A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

CE2-

T2 CE2- T3 CE2- T7 CE2-T11 CE2-T12 CE2-T13 T14CE2- CE2-T15 CE2-T16 CE2-T19 CE2-T20 CE2-T21 Kit no. Earth fault passage

indication (choose provision kit and an EFPI required if not using Easergy 200E) EFPI provision kit, inside

cable box O O O O O O O O O O O O RMR-F30

Bowden STD EFPI type NB O O O O O O O O O O O O RMR-A277

Bowden LV reset EFPI type NB1O O O O O O O O O O O O RMR-A278 Bowden LV reset & alarm

type NB2 O O O O O O O O O O O O RMR-A279

Bowden “RR” EFPI and CT O O O O O O O O O O O O RMR-A56

Fundamentals ER “FIND”

EFPI and CT O O O O O O O O O O O O RMR-A57

Ancillary items

Tool box O O O O O O O O O O O O RMR-A80

Order code

12kV, 16kA, 75kV BIL, 0.35bG CE2-

T2/16 CE2- T3/16 CE2- T7/16 CE2- T11/16 CE2- T12/16 T13/16CE2- CE2- T14/16 CE2- T15/16 CE2- T16/16 N/A CE2- T20/16 N/A 13.8kV, 21kA, 95kV BIL, 0.8bG CE2-

T2/21 CE2- T3/21 CE2- T7/21 CE2- T11/21 CE2- T12/21 CE2- T13/21 CE2- T14/21 CE2- T15/21 CE2- T16/21 CE2- T19/21 N/A CE2- T21/21 General arrangement drawing RMINST-03

Page 68 RMINST-02 Page 67 RMINST-03 Page 68 RMINST-02 Page 67 RMINST-03 Page 68 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-03 Page 68 RMINST-03 Page 68 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67

Schematic drawing RMSCH-07

Page 86 RMSCH-09 Page 88 RMSCH-06 Page 85 RMSCH-09 Page 88 RMSCH-19 Page 94 RMSCH-20 Page 95 RMSCH-20 Page 95 RMSCH-07 Page 86 RMSCH-07 Page 86 RMSCH-35 Page 103 RMSCH-35 Page 103 RMSCH-36 Page 104

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

(17)

35

Extensible circuit breaker 200A

0

CE2-T2

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 3.5MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 200/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 20-200A

v Earth fault: 2-160A Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-07 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Gas pressure indicator Test facility

Integral cable test facilities Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information

Code Rating

CE2-T2/16 16kA, 12kV, 75kV BIL CE2-T2/21 21kA, 13.8kV, 95kV BIL

(18)

36

Extensible circuit breaker 200A

0

CE2-T7

Ringmaster range

Panel types

Ringmaster range

Panel types

Transformer protection up to 1.5MVA at 11kV

Protection & control - CB

Overcurrent and earth fault protection using CT operated trip coils with provision for time fuse links.

Protection CT’s - 100/50/5A class X

Shunt trip coil, 20V DC-250V AC

Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-06 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Gas pressure indicator Test facility

Integral cable test facility Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information

Code Rating

CE2-T7/16 16kA, 12kV, 75kV BIL CE2-T7/21 21kA, 13.8kV, 95kV BIL

(19)

37

Extensible circuit breaker 200A

0

CE2-T*

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 3.5MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 200/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 20-200A

v Earth fault: 2-160A Metering transformers b Metering CT’s R & B phases

v 200/100/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual

Anti-reflex operating handle

Standard features

Cable earth switch, 16/21kA 3s

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Gas pressure indicator Test facility

Integral cable test facility Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order code

16kA, 12kV, 75kV BIL

21kA, 13.8kV, 95kV BIL CE2-T3/16 CE2-T3/21 CE2-T11/16 CE2-T11/21 N/A CE2-T19/21 CE2-T20/16 N/A Metering VT information: Phase to phase b b Phase to earth b b 6.6kV/110V b 11kV/110V* b b 13.8kV/110V b

General arrangement drawing RMINST-02

Page 67 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-09

Page 88 RMSCH-09 Page 88 RMSCH-35 Page 103 RMSCH-35 Page 103 *Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500

DE60252

(Select VT rating and switchgear rating from table below).

DE60252

(20)

38

Extensible circuit breaker 200A

0

CE2-T12

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 3.5MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 200/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 20-200A

v Earth fault: 2-160A Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-19 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual

Provision for actuator, 24V DC

Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2 NC

Earth selected auxiliary contact1NO Gas pressure indicator

Test facility

Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information

Code Rating

CE2-T12/16 16kA, 12kV, 75kV BIL CE2-T12/21 21kA, 13.8kV, 95kV BIL

DE60253 MM

(21)

39

Extensible circuit breaker 200A

0

CE2-T*

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 3.5MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 200/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 20-200A

v Earth fault: 2-160A Metering transformers b Metering CT’s v 200/100/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual

Provision for actuator, 24V DC

Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Earth selected auxiliary contact1NO Gas pressure indicator

Test facility

Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order code

16kA, 12kV, 75kV BIL

21kA, 13.8kV, 95kV BIL CE2-T14/16 CE2-T14/21 N/A CE2-T21/21 Metering VT information: Phase to phase b Phase to earth b 6.6kV/110V b 11kV/110V* 13.8kV/110V b

General arrangement drawing RMINST-02

Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-20

Page 95 RMSCH-36 Page 104

*Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500

DE60254

(Select VT rating and switchgear rating from table below).

DE60254

(22)

40

Extensible circuit breaker 200A

0

CE2-T13

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 3.5MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 200/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 20-200A

v Earth fault: 2-160A Metering transformers b Metering CT’s v 200/100/5A v 10VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents

Installation drawing ref: RMINST-02 Schematic drawing ref: RMSCH-20 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual

Actuator, 24V DC

Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Earth selected auxiliary contact1NO Gas pressure indicator

Test facility

Integral cable test facility Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information

Code Rating

CE2-T13/16 16kA, 12kV, 75kV BIL CE2-T13/21 21kA, 13.8kV, 95kV BIL

(23)

41

Extensible circuit breaker 200A

0

CE2-T15

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 2.5MVA at 11kV

Protection & control - CB

Self powered overcurrent relay, VIP 30.

Protection CT’s - 500/200/1A class X

b Setting range: 500/1A

v Overcurrent: 20-200A

b Setting range: 200/1A

v Overcurrent: 8-80A Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-12 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Gas pressure indicator Test facility

Integral cable test facilities Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information

Code Rating

CE2-T15/16 16kA, 12kV, 75kV BIL CE2-T15/21 21kA, 13.8kV, 95kV BIL

(24)

42

Extensible circuit breaker 200A

0

CE2-T16

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 2.5MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 35.

Protection CT’s - 500/200/1A class X CH30 core balance CT

b Setting range: 500/1A

v Overcurrent: 20-200A

v Earth fault: 25-300A

b Setting range: 200/1A

v Overcurrent: 8-80A

v Earth fault: 10-120A Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-13 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Gas pressure indicator Test facility

Integral cable test facilities Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information

Code Rating

CE2-T16/16 16kA, 12kV, 75kV BIL CE2-T16/21 21kA, 13.8kV, 95kV BIL

(25)

43

Extensible circuit breakers 630A

0

Ringmaster range

Specification

Ringmaster range

Specification

CE6-

T4 CE6- T5 CE6- T6 CE6- T8 T9CE6- CE6-T10 CE6-T22 CE6-T23 CE6-T24 Environment

Indoor / outdoor b b b b b b b b b

IP54 b b b b b b b b b

Ratings

Busbars 630A b b b b b b b b b

Circuit breaker normal rated current 630A b b b b b b b b b

12kV 16kA 3 seconds 75kV BIL b b b b b b b b b

13.8kV 21kA 3 seconds 95kV BIL O O O O O O O O O

Cable earth switch 16kA 3 seconds b b b b b b b b b

Cable earth switch 21kA 3 seconds O O O O O O O O O

Mechanism

Independent manual b b b b b b b b b

Provision for actuator 24V DC b b b b

Actuator 24V DC O O O O

Operating handle b b b b b b b b b

Protection system

CT ratio - 800/1A class X b b b b b b b b b

IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b

20V-250V shunt trip coil b b b b b b b b b

Auxiliary switch 1NO 2NC b b b b b b b b b

Metering

CT’s - 400/200/5A 0.5s 10VA b b b b b b b

VT’s - 13.8kV/110V/110V/ 0.5 50VA 3P 20VA b b

VT’s - 11V/110V 0.5 50VA b b b

VT’s - 6.6kV/110V 0.5 50VA b b

VT’s - phase - phase, CT’s R & B b b b b

VT’s phase - earth, CT’s RYB b b b

Indication

Mechanical ON/OFF b b b b b b b b b

Mechanical EARTH/MAIN b b b b b b b b b

Cable neon indication (6.6 - 13.8KV) O O O O O O O O O

Auxiliary switch contacts 1NO 2NC b b b b b b b b b

Indication CT 600/5A 5VA CLS 1 Yph b b b b b b b b b

Ammeter 0-600A b b b b b b b b b

Earth selected auxiliary contacts 1NO b b b

Gas pressure indicator b b b b b b b b b

Test facility

Integral cable test facility b b b b b b b b b

Cable

Bottom entry up to 300mm2 1 x 3c b b b b b b b b b

Bottom entry up to 630mm2 3 x 1c b b b b b b b b b

Top entry cables O O O O O O O O O

(26)

44

Extensible circuit breakers 630A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

CE6-T4 CE6-T5 CE6-T6 CE6-T8 CE6-T9 CE6-T10 CE6-T22 CE6-T23 CE6-T24 Kit no. Cable kits

Gland plate 1 x 3C O O O O O O O O O RMR-A48

Gland plate 3 x 1C O O O O O O O O O RMR-A49

Angled gland plates (RMR) O O O O O O O O O RMR-A50

Blank aluminium gland plate O O O O O O O O O RMR-A52

Brass wiping gland 1 x 3C O O O O O O O O O RMR-A10

Brass wiping gland 3 x 1C O O O O O O O O O RMR-A11

Tubular gland 1 x 3C O O O O O O O O O RMR-A12

Tubular gland 3 x 1C O O O O O O O O O RMR-A13

CES5 gland plate 1 x 3C O O O O O O O O O RMR-A132

Top entry cables standard panels v v RMR-F93

Top entry cables MU6 only v v v v v v v RMR-F94

Installation items

3 phase busbars 630A O O RMR-A14

3 phase busbars 630A O O O O O O O RMR-A78

Busbar end kit O O O O O O O O O RMR-A15

Set of padlocks - 6 no O O O O O O O O O RMR-A18/6

Foundation bolts (not required for transformer mounting)

b b b b b b b b b RMR-A22

Multicore pilot glands O O O O O O O O O RMR-A16

Operational items

Operating handle b b b b b b b b b RMR-A23

Cable neon indication (6.6 - 13.8kV) v v v v v v v v v RMR-A108

Neon lamp test unit (including lamp) O O O O O O O O O RMR-A24

Neon lamp O O O O O O O O O RMR-A81

VAP 6 test unit for VIP 300 O O O O O O O O RMR-A202

Actuator 24V DC v v v v RMR-F67

Polarity conversion kit** v v v v RMR-F391

Mechanical interlocks

Key free, EARTH ON v v v v v RMR-F85

Key free, MAIN OFF v v v v v RMR-F86

N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms

Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T200E)

EFPI provision kit, inside cable box O O O O O O O O O RMR-F30

Bowden STD EFPI type NB O O O O O O O O O RMR-A277

Bowden LV reset EFPI type NB1 O O O O O O O O O RMR-A278

Bowden LV reset & alarm type NB2 O O O O O O O O O RMR-A279

Bowden “RR” EFPI and CT O O O O O O O O O RMR-A56

Fundamentals ER “FIND” EFPI and CT O O O O O O O O O RMR-A57 Ancillary items

Tool box O O O O O O O O O RMR-A80

Order code

12kV, 16kA, 75kV BIL, 0.35bG CE6-

T4/16 CE6- T5/16 CE6- T6/16 CE6- T8/16 CE6- T9/16 CE6-T10/16 N/A N/A CE6-T24/16 13.8kV, 21kA, 95kV BIL, 0.8bG CE6-

T4/21 CE6- T5/21 CE6- T6/21 CE6- T8/21 CE6- T9/21 CE6-T10/21 CE6-T22/21 CE6-T12321 N/A General arrangement drawing RMINST-03

Page 68 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-03 Page 68 Page 67RMINST-02 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67

Schematic drawing RMSCH-08

Page 87 RMSCH-10 Page 89 RMSCH-10 Page 89 RMSCH-23 Page 98 Page 99RMSCH-24 RMSCH-24 Page 99 RMSCH-37 Page 105 RMSCH-38 Page 106 RMSCH-37 Page 105

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

(27)

45

Extensible circuit breaker 630A

0

CE6-T4

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 12MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 800/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 80-800A

v Earth fault: 8-640A Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-08 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2 NC

Ammeter 0-600A

Indication CT Y ph - 600/5A class 1.0, 5VA

Gas pressure indicator Test facility

Integral cable test facility Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order information

Code Rating

CE6-T4/16 16kA, 12kV, 75kV BIL CE6-T4/21 21kA, 13.8kV, 95kV BIL

(28)

46

Extensible circuit breaker 630A

0

CE6-T*

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 12MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 800/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 80-800A

v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2 NC

Ammeter 0-600A

Indication CT Y ph - 600/5A class 1.0, 5VA

Gas pressure indicator Test facility

Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order code

16kA, 12kV, 75kV BIL

21kA, 13.8kV, 95kV BIL CE6-T5/16 CE6-T5/21 CE6-T6/16 CE6-T6/21 N/A CE6-T22/21 CE6-T24/16 N/A Metering VT information: Phase to phase b b Phase to earth b b 6.6kV/110V b 11kV/110V* b b 13.8kV/110V b

General arrangement drawing RMINST-02

Page 67 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-10

Page 89 RMSCH-10 Page 89 RMSCH-37 Page 105 RMSCH-37 Page 105 *Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500

DE60197

(Select VT rating and switchgear rating from table below).

DE60197

(29)

47

Extensible circuit breaker 630A

0

CE6-T8

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 12MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 800/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 80-800A

v Earth fault: 8-640A Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-23 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual

Provision for actuator, 24V DC

Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2 NC

Earth selected auxiliary contact1NO Ammeter 0-600A

Indication CT Y ph - 600/5A class 1.0, 5VA

Gas pressure indicator Test facility

Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order information

Code Rating

CE6-T8/16 16kA, 12kV, 75kV BIL CE6-T8/21 21kA, 13.8kV, 95kV BIL

(30)

48

Extensible circuit breaker 630A

0

CE6-T*

Ringmaster range

Panel types

Ringmaster range

Panel types

Feeder protection up to 12MVA at 11kV

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 800/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 80-800A

v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

Cable earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2 NC

Earth selected auxiliary contacts Ammeter 0-600A

Indication CT Y ph- 600/5A class 1.0, 5VA

Gas pressure indicator Test facility

Integral cable test facility Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order code

16kA, 12kV, 75kV BIL

21kA, 13.8kV, 95kV BIL CE6-T9/16 CE6-T9/21 CE6-T10/16 CE6-T10/21 N/A CE6-T23/21 Metering VT information: Phase to phase b b Phase to earth b 6.6kV/110V b 11kV/110V* b 13.8kV/110V b

General arrangement drawing RMINST-02

Page 67 RMINST-02 Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-24

Page 99 RMSCH-24 Page 99 RMSCH-38 Page 106 *Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500

DE60199

(Select VT rating and switchgear rating from table below).

DE60199

(31)

49

Extensible switches 630A

0

Ringmaster range

Specification

Ringmaster range

Specification

SE6-S1 SE6-S2 SE6-E1

Environment

Indoor / outdoor b b b

IP54 b b b

Ratings

Busbars 630A b b b

Switch normal rated current 630A b b b

13.8kV 21kA 3 seconds 95kV BIL b b b

Cable earth switch 21kA 3 seconds b b

Mechanism

Independent manual b b b

Provision for actuator 24V DC b

Actuator 24V DC O

Operating handle b b b

Indication

Mechanical ON/OFF b b

Mechanical EARTH/MAIN b b b

Cable neon indication (6.6-13.8kV) v v

Busbar neon indication (6.6-13.8kV) v v

Auxiliary switch contacts1NO 1 NC v

Phase and earth fault detection CT’s for Easergy T200E O

EFPI provision only CT inside box O O b

Gas pressure indicator b b b

Test facility

Integral cable test facility b b

Integral test facility

RH/LH busbar earthing b

Cable (see available cable kit accessories)

Bottom entry up to 300mm2 1 x 3c b b

Bottom entry up to 630mm2 3 x 1c b b

Top entry cables O O

(32)

50

Extensible switches 630A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

SE6-S1 SE6-S2 SE6-E1 Kit no.

Cable kits

Gland plate 1 x 3C O O RMR-A48

Gland plate 3 x 1C O O RMR-A49

Angled gland plates (RMR) O O RMR-A50

Blank aluminium gland plate O O RMR-A52

Brass wiping gland 1 x 3C O O RMR-A10

Brass wiping gland 3 x 1C O O RMR-A11

Tubular gland 1 x 3C O O RMR-A12

Tubular gland 3 x 1C O O RMR-A13

CES5 gland plate 1 x 3C O O RMR-A132

Top entry cables v v RMR-F93

Installation items

3 phase busbars 630A O O v RMR-A14

Set of padlocks - 6 no O O O RMR-A18/6

Busbar end kit (1 end kit required per switchboard) O O O RMR-A15 Foundation bolts (not required for transformer mounting) b b b RMR-A22

Multicore pilot glands O RMR-A16

Operational items

Operating handle b b b RMR-A23

Cable neon indication (6.6-13.8kV) v v RMR-F108

Cable and busbar neon indication (6.6-13.8kV) v v RMR-F92

Neon lamp test unit (including lamp) O O RMR-A24

Neon lamp O O RMR-A81

Actuator 24V DC v RMR-F67

Polarity conversion kit* v RMR-F391

Mechanical interlocks

Key free, earth ON v v RMR-F85

Key free, main OFF v RMR-F86

N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms

Indication

EFPI provision kit, inside cable box O O RMR-F30

Bowden STD EFPI NB O O RMR-A277

Bowden LV reset EFPI type NB1 O O RMR-A278

Bowden LV reset & alarm type NB2 O O RMR-A279

Bowden “RR” EFPI and CT O O RMR-A56

Fundamentals ER “FIND” EFPI and CT O O RMR-A57

Ancillary items

Tool box O O O RMR-A80

Order code

13.8kV, 21kA, 95kV BIL, 0.8bG SE6-S1/21 SE6-S2/21 SE6-E1/21

General arrangement drawing RMINST-03

Page 68 RMINST-03 Page 68 RMINST-03 Page 68

Schematic drawing N/A RMSCH-29

Page 102 N/A Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

(33)

51

Extensible switch 630A

0

SE6-S1

Ringmaster range

Panel types

Ringmaster range

Panel types

Switch disconnector

Protection & control - CB Non-automatic

Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-N/A Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features

Cable earth switch, 21kA 3s Anti-reflex operating handles

Indication

Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Test facility

Integral cable test facility Cable

Bottom entry up to 300mm2 1 x 3c

Bottom entry up to 630mm2 3 x 1c

Accessories Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 50 for details Order information

Code Rating

SE6-S1/21 21kA, 13.8kV, 95kV BIL

(34)

52

Extensible switch 630A

0

SE6-S2

Ringmaster range

Panel types

Ringmaster range

Panel types

Switch disconnector

Protection & control - CB Non-automatic

Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-29 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual

Provision for actuator, 24V DC

Standard features

Cable earth switch, 21kA 3s Anti-reflex operating handle

Indication

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2NC

Earth selected auxiliary contact 1NO Gas pressure indicator

Test facility

Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 50 for details Order information

Code Rating

SE6-S2/21 21kA, 13.8kV, 95kV BIL

(35)

53

Extensible busbar earthing switch

630A

0

SE6-E1

Ringmaster range

Panel types

Ringmaster range

Panel types

Busbar earthing switch

Documents

Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-N/A Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features

Cable earth switch, 21kA 3s Anti-reflex operating handle

Indication

Mechanical earth/main indicator Gas pressure indicator Test facility N/A Cable N/A Accessories Interlocks Busbar kit

See page 50 for details Order information

Code Rating

SE6-E1/21 21kA, 13.8kV, 95kV BIL

(36)

54

Extensible bus-section 630A

0

Ringmaster range

Specification

Ringmaster range

Specification

SE6-B1 CE6-B3 CE6-B5

Environment

Indoor / outdoor b b b

IP54 b b b

Ratings

Busbars 630A b b b

Circuit breaker normal rated current 630A b b

Switch normal rated current 630A b

12kV 16kA 3 seconds 75kV BIL b b

13.8kV 21kA 3 seconds 95kV BIL b O O

RH busbar earth switch 16kA 3 seconds b b

RH busbar earth switch 21kA 3 seconds b O O

Mechanism

Independent manual b b b

Provision for actuator 24V DC b

Actuator 24V DC O

Operating handle b b b

Protection system

CT ratio - 800/1A class X b b

IDMT overcurrent & earth fault relay - VIP 300 b b

20V - 250V shunt trip coil b b

Auxiliary switch1NO 2 NC b b

Metering

CT’s - 400/200/5A 0.5s 10VA b b

VT’s - 11kA/110V 0.5 50VA b b

VT’s phase - phase, CT’s R & B b b

Indication

Mechanical ON/OFF b b b

Mechanical EARTH/MAIN b b b

Earth selected auxiliary contact1NO b

RH busbar neon indication O O O

Auxiliary switch contacts1NO 2NC b b

Indication CT 600/5A 5VA CLS 1 Y phase b b

Ammeter 0-600A b b

Gas pressure indicator b b b

Integral test facility

RH busbar earthing b b b

LH busbar earthing ( using SE6-E1) O O O

(37)

55

Extensible bus section 630A

0

Ringmaster range

Accessories

Ringmaster range

Accessories

SE6-B1 CE6-B3 CE6-B5 Kit no.

Installation items

3 phase busbars 630A RMR-A14

3 phase busbars 630A (Joggle metering) v v v RMR-A79

3 phase busbars 630A double width (metering) v v v RMR-A78

Set of padlocks - XX no O O O RMR-A18/6

Busbar end kit (1 end kit required per switchboard) O O O RMR-A15 Foundation bolts (not required for transformer mounting) b b b RMR-A22

Multicore pilot glands O O RMR-A16

Operational items

Operating handle b b b RMR-A23

LH and RH busbar neon indication v v v RMR-F92

Neon lamp test unit (including lamp) O O RMR-A24

Neon lamp O O O RMR-A81

VAP6 test unit for VIP 300 O O RMR-A202

Actuator 24V DC v RMR-F67

Polarity conversion kit* v RMR-F391

Mechanical interlocks

Key free, earth ON v v RMR-F85

Key free, main OFF v v RMR-F86

N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms

Ancillary items

Tool box O O O RMR-A80

Order code

12kV, 16kA, 75BIL, 0.35bG N/A CE6-B3/16 CE6-B5/16

13.8kV, 21kA, 95kV BIL, 0.8bG SE6-B1/21 CE6-B3/21 CE6-B5/21

General arrangement drawing RMINST-01

Page 66 RMINST-01 Page 66 RMINST-01 Page 66

Schematic drawing N/A RMSCH-21

Page 91 RMSCH-22 Page 97 Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

(38)

56

Extensible bus-section 630A

0

SE6-B1

Ringmaster range

Panel types

Ringmaster range

Panel types

Bus-section disconnector

Protection & control Non-automatic Documents

Installation drawing ref: RMINST-01 Schematic drawing ref: N/A Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features

RH busbar earth switch, 21kA 3s Anti-reflex operating handle

Indication

Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Test facility

Integral RH busbar test facility Cable N/A Accessories Neon indication Interlocks Busbars

See page 55 for details Order information

Code Rating

SE6-B1/21 21kA, 13.8kV, 95kV BIL

(39)

57

Extensible bus-section 630A

0

CE6-B3

Ringmaster range

Panel types

Ringmaster range

Panel types

Bus-section circuit breaker

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 800/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 80-800A

v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT ph-ph v 11kV/110V 50VA v class 0.5 Documents

Installation drawing ref: RMINST-01 Schematic drawing ref: RMSCH-21 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features

RH busbar earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2 NC

Ammeter 0-600A

Indication CT Y ph- 600/5A class 1.0 5VA

Gas pressure indicator Test facility

Integral RH busbar test facility Cable N/A Accessories Neon indication Interlocks Busbars

See page 55 for details Order information

Code Rating

CE6-B3/16 16kA, 12kV, 75kV BIL CE6-B3/21 21kA, 13.8kV, 95kV BIL

(40)

58

Extensible bus-section 630A

0

CE6-B5

Ringmaster range

Panel types

Ringmaster range

Panel types

Bus-section circuit breaker

Protection & control - CB

Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with

IEC 60255 and BS142. Protection CT’s - 800/1A class X

Shunt trip coil, 20V DC-250V AC

b Setting range:

v Overcurrent: 80-800A

v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT ph-ph v 11kV/110V 50VA v class 0.5 Documents

Installation drawing ref: RMINST-01 Schematic drawing ref: RMSCH-22 Environment

Indoor/outdoor IP54

Ratings Busbars 630A

Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual

Provision for actuator, 24V DC

Standard features

RH busbar earth switch, 16/21kA 3s Anti-reflex operating handle

Indication

Mechanical tripped on fault flag indicator

Mechanical ON/OFF indicator Mechanical earth/main indicator

Auxiliary contacts,1NO 2 NC

Earth selected auxiliary contacts1NO Ammeter 0-600A

Indication CT Y ph- 600/5A class 1.0 5VA

Gas pressure indicator Test facility

Integral RH busbar test facility Cable N/A Accessories Actuator, 24V DC Neon indication Interlocks Busbars

See page 55 for details Order information

Code Rating

CE6-B5/16 16kA, 12kV, 75kV BIL CE6-B5/21 21kA, 13.8kV, 95kV BIL

References