19
Non-extensible circuit breakers
200A
0Ringmaster range
Specification
Ringmaster range
Specification
CN2-T1 CN2-T6 Environment Indoor / outdoor b b IP54 b b RatingsNormal rated current 200A b b
12kV 16kA 3 seconds 75kV BIL b b
13.8kV 21kA 3 seconds 95kV BIL O O
Cable earth switch 16kA 3 seconds b b
Cable earth switch 21kA 3 seconds O O
Transformer earth switch 3.15kA 3 seconds b b
Mechanism
Independent manual b b
Protection & control - circuit breaker
CT’s dual ratio - 100/50/5A class X b
CT’s ratio - 200/1A class X b
Overcurrent & earth fault CT operated trip coils b
Time fuse Link O
IDMT overcurrent & earth fault relay - VIP 300 b
20V-250V shunt trip coil b b
Circuit breaker auxiliary switch 1NO 2NC b b
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b
Neon indication (6.6 - 13.8kV) O O
Auxiliary switch contacts 1NO 2NC b b
Gas pressure indicator b b
Test facility
Integral cable test facility b b
Standard features
Operating handle b b
Transformer earth switch 3.15kA 3 seconds b b
Cable (see available cable kit accessories)
Bottom entry up 300mm2 1 x 3c b b
Bottom entry up 630mm2 3 x 1c b b
20
Non-extensible circuit breakers
200A
0Ringmaster range
Accessories
Ringmaster range
Accessories
CN2-T1 CN2-T6 Kit no. Cable kitsTee-off cable box v v RMR-F47
Gland plate 1 x 3C O O RMR-A48
Gland plate 3 x 1C O O RMR-A49
Angled gland plates (RMR) O O RMR-A50 Blank
Blank aluminium gland plate O O RMR-A52
Brass wiping gland 1 x 3C O O RMR-A10
Brass wiping gland 3 x 1C O O RMR-A11
Tubular gland 1 x 3C O O RMR-A12
Tubular gland 3 x 1C O O RMR-A13
CES5 gland plate 1 x 3C O O RMR-A132
Installation items
Set of padlocks - 6 no O O RMR-A18/6
Anti-vandal fixings, including tool O O RMR-A19
Foundation bolts (not required for transformer mounting) O O RMR-A22
Multicore pilot glands O O RMR-A16
Time limit fuses (set of 2 - specify rating as table page 113) O RMR-A17 Operational items
Operating handle b b RMR-A23
Neon indication (6.6-13.8kV) v v RMR-F108
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O RMR-A81
VAP 6 test unit for VIP 300 O RMR-A202
Mechanical interlocks
Key free, earth on v v RMR-F85
Key free, unit off v v RMR-F86
Transformer earth switch, key free, earth on v v RMR-F110
N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms
Order codes
12kV, 16kA, 75kV BIL, 0.35bG CN2-T1/16 CN2-T6/16
13.8kV, 21kA, 95kV BIL, 0.8bG CN2-T1/21 CN2-T6/21
General arrangement drawing - transformer mounted RMINST-04 Page 70 RMINST-04 Page 70 General arrangement drawing - freestanding RMINST-09 Page 111 RMINST-09 Page 111 Schematic diagram RMSCH-26 Page 100 RMSCH-11 Page 90 Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
21
Non-extensible circuit breaker
200A
0CN2-T1
Ringmaster range
Panel types
Ringmaster range
Panel types
Transformer protection up to 3.5MVA
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CT’s - 200/1A class X
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2A-160A
Shunt trip coil, 20V DC-250V AC
Transformer ratings See table - page 113 Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: RMSCH-26
Environment Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Tee-off earth switch, 3.15kA 3s Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator CB auxiliary contacts 1NO 2 NC Test facility
Integral cable test facilities Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Tee-off cable box Glands and plates Interlocks
See page 20 for details Order information
Code Rating
CN2-T1/16 16kA, 12kV, 75kV BIL CN2-T1/21 21kA, 13.8kV, 95kV BIL
22
Non-extensible circuit breaker
200A
0CN2-T6
Ringmaster range
Panel types
Ringmaster range
Panel types
Transformer protection up to 1.5MVA
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for time fuse links.
Protection CT’s - 100/50/5A class X
Shunt trip coil, 20V DC-250V AC
Transformer ratings See table - page 113 Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: RMSCH-11
Environment Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Transformer earth switch, 3.15kA 3s Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator CB auxiliary contacts 1NO 2 NC Test facility
Integral cable test facilities Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Tee-off cable box Glands and plates Interlocks
See page 20 for details Order information
Code Rating
CN2-T6/16 16kA, 12kV, 75kV BIL CN2-T6/21 21kA, 13.8kV, 95kV BIL
23
Non-extensible switch 630A
0Ringmaster range
Specification
Ringmaster range
Specification
SN6-S1 SN6-S2 Environment Indoor / outdoor b b IP54 b b RatingsNormal rated current 630A b b
13.8kV 21kA 3 seconds 95kV BIL b b
Cable earth switch 21kA 3 seconds b b
Transformer earth switch 3.15kA 3 seconds b b
Mechanism
Independent manual b b
Provision for actuator 24V DC b
Actuator 24V DC O
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b
Neon indication (6.6 - 13.8kV) O O
Auxiliary switch contacts 1NO 2NC b
Phase and earth fault detection CT’s for Easergy 200E O
Provision for EFPI O O
Test facility
Integral cable test facility b b
Standard features
Operating handle b b
Transformer earth switch 3.15kA 3 seconds b b
Cable (see available cable kit accessories)
Bottom entry up 300mm2 1 x 3c b b
Bottom entry up 630mm2 3 x 1c b b
24
Non-extensible switch 630A
0Ringmaster range
Accessories
Ringmaster range
Accessories
SN6-S1 SN6-S2 Kit no. Cable kitsTee-off cable box v v RMR-F47
Gland plate 1 x 3C O O RMR-A48
Gland plate 3 x 1C O O RMR-A49
Angled gland plates (RMR) O O RMR-A50
Blank aluminium gland plate O O RMR-A52
Brass wiping gland 1 x 3C O O RMR-A10
Brass wiping gland 3 x 1C O O RMR-A11
Tubular gland 1 x 3C O O RMR-A12
Tubular gland 3 x 1C O O RMR-A13
CES5 gland plate 1 x 3C O O RMR-A132
Installation items
Set of padlocks - 6 no O O RMR-A18/6
Anti-vandal fixings, including tool O O RMR-A19
Foundation bolts (not required for transformer mounting) O O RMR-A22
Multicore pilot glands O O RMR-A16
Operational items
Operating handle b b RMR-A23
Neon indication (6.6-13.8kV) v v RMR-F108
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O RMR-A81
Actuator 24V DC v RMR-F67
Mechanical interlocks
Key free, earth on v RMR-F85
Key free, unit off v RMR-F86
Transformer earth switch, key free, earth on v v RMR-F110
N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms
Order codes
13.8kV, 21kA, 95kV BIL, 0.8bG SN6-S1/21 SN6-S2/21
General arrangement drawing - transformer mounted RMINST-04 Page 69 RMINST-04 Page 69 General arrangement drawing - freestanding RMINST-09 Page 111 RMINST-09 Page 111
Schematic diagram N/A RMSCH-28 Page 101
25
Non-extensible switch 630A
0SN6-S1
Ringmaster range
Panel types
Ringmaster range
Panel types
Switch disconnector
Protection & control - CB Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: N/A
Environment Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features
Transformer earth switch, 3.15kA 3s Cable earth switch, 21kA 3s Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Test facility
Integral cable test facilities Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Tee-off cable box Neon indication Glands and plates Interlocks
See page 24 for details Order information
Code Rating
SN6-S1/21 21kA, 13.8kV, 95kV BIL
26
Non-extensible switch 630A
0SN6-S2
Ringmaster range
Panel types
Ringmaster range
Panel types
Switch disconnector
Protection & control - CB Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09 Schematic drawing ref: RMSCH-28
Environment Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual
Provision for actuator, 24V DC
Standard features
Transformer earth switch, 3.15kA 3s Cable earth switch, 21kA 3s Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Auxiliary contacts 1NO 2NC Earth selected auxiliary contact 1NO Test facility
Integral cable test facilities Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Tee-off cable box
Actuator, 24V DC
Neon indication Glands and plates See page 24 for details Order information
Code Rating
SN6-S2/21 21kA, 13.8kV, 95kV BIL
27
Non-extensible metering unit
200A
0Ringmaster range
Specification
Ringmaster range
Specification
MU2-M1 MU2-M2 MU2-M3
Environment
Indoor / outdoor b b b
IP54 b b b
Ratings
Normal rated current 200A b b b
12kV 16kA 1 second 75kV BIL b b b
Metering*
CT’s -50/25/5A 0.5s 7.5VA b
CT’s -100/50/5A 0.5s 10VA b
CT’s -200/100/5A 0.5s 10VA b
VT’s -11kV/110V 0.5 50VA b b b
*CT’s - 2 phases (R & B), VT’s phase to phase. 6.6kV VT’s are available - contact Merlin Gerin
Cable (see available cable kit accessories)
Bottom entry up 300mm2 1 x 3c O O O
Bottom entry up 630mm2 3 x 1c O O O
28
Non-extensible metering unit
200A
0Ringmaster range
Accessories
Ringmaster range
Accessories
MU2-M1 MU2-M2 MU2-M3 Kit no.
Cable kits
Tee-off cable box v v v RMR-F47
Gland plate 1 x 3C O O O RMR-A48
Gland plate 3 x 1C O O O RMR-A49
Angled gland plates (RMU) O O O RMR-A51 Blank
Blank aluminium gland plate O O O RMR-A52
Brass wiping gland 1 x 3C O O O RMR-A10
Brass wiping gland 3 x 1C O O O RMR-A11
Tubular gland 1 x 3C O O O RMR-A12
Tubular gland 3 x 1C O O O RMR-A13
CES5 gland plate 1 x 3C O O O RMR-A132
Installation items
Set of padlocks - XX no O O O RMR-A18/6
Foundation bolts (not required for transformer mounting) O O O RMR-A22
Multicore pilot glands O O O RMR-A16
RMU - MU2 installation kit O O O RMR-A350
Freestanding installation kit O O O RMR-A90
Order codes
12kV, 16kA, 75kV BIL, 0.35bG MU2-M1/16 MU2-M2/16 MU2-M3/16
General arrangement drawing - transformer mounted RMINST-07/08
Page 72 - 73 RMINST-07/08 Page 72 - 73 RMINST-07/08 Page 72 - 73 Schematic diagram RMSCH-14 Page 90 RMSCH-14 Page 90 RMSCH-14 Page 90 Key: v Factory fitted accessory O Loose accessory, assembled on site
29
Non-extensible metering unit
200A
0MU2-M1
Ringmaster range
Panel types
Ringmaster range
Panel types
Non-extensible metering unit
Protection & control - CB N/A
Metering transformers b Metering CT’s R & B phases
v 50/25/5A v 7.5VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents
Installation drawing ref: RMINST-07/08 Schematic drawing ref: RMSCH-14 Environment
Indoor/outdoor IP54
Ratings
Short time withstand 16kA 1s Normal current rating 200A Normal rated voltage 12kV Normal rated BIL 75kV Standard features
Direct coupling between RMU and transformer (optional freestanding cable connection) Cable connection Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Cable box Glands and plates Installation kits See page 28 for details Order information
Code Rating
MU2-M1/16 16kA, 12kV, 75kV BIL
30
Non-extensible metering unit
200A
0MU2-M2
Ringmaster range
Panel types
Ringmaster range
Panel types
Non-extensible metering unit
Protection & control - CB N/A
Metering transformers b Metering CT’s R & B phases
v 100/50/5A v 10VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents
Installation drawing ref: RMINST-07/08 Schematic drawing ref: RMSCH-14 Environment
Indoor/outdoor IP54
Ratings
Short time withstand 16kA 1s Normal current rating 200A Normal rated voltage 12kV Normal rated BIL 75kV Standard features
Direct coupling between RMU and transformer (optional freestanding cable connection) Cable connection Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Cable box Glands and plates Installation kits See page 28 for details Order information
Code Rating
MU2-M2/16 16kA, 12kV, 75kV BIL
31
Non-extensible metering unit
200A
0MU2-M3
Ringmaster range
Panel types
Ringmaster range
Panel types
Non-extensible metering unit
Protection & control - CB N/A
Metering transformers b Metering CT’s R & B phases
v 200/100/5A v 10VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents
Installation drawing ref: RMINST-07/08 Schematic drawing ref: RMSCH-14 Environment
Indoor/outdoor IP54
Ratings
Short time withstand 16kA 1s Normal current rating 200A Normal rated voltage 12kV Normal rated BIL 75kV Standard features
Direct coupling between RMU and transformer (optional freestanding cable connection) Cable connection
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Cable box Glands and plates Installation kits See page 28 for details Order information
Code Rating
MU2-M3/16 16kA, 12kV, 75kV BIL
32
Extensible circuit breakers 200A
0Ringmaster range
Specification
Ringmaster range
Specification
CE2-T2 CE2-T3 CE2-T7 CE2-T11 CE2-T12 CE2-T13 CE2-T14 CE2-T15 CE2-T16 CE2-T19 CE2-T20 CE2-T21 Environment
Indoor / outdoor b b b b b b b b b b b b
IP54 b b b b b b b b b b b b
Ratings
Busbars 630A b b b b b b b b b b b b
Circuit breaker normal rated current 200A b b b b b b b b b b b b
12kV 16kA 3 seconds 75kV BIL b b b b b b b b b b b b
13.8kV 21kA 3 seconds 95kV BIL O O O O O O O O O O O O
Cable earth switch 16kA 3 seconds b b b b b b b b b b b b
Cable earth switch 21kA 3 seconds O O O O O O O O O O O O
Mechanism
Independent manual b b b b b b b b b b b b
Provision for actuator 24V DC b b b b
Actuator 24V DC O O O O
Operating handle b b b b b b b b b b b b
Protection system
CT’s dual ratio - 500/200/1A class x b b
Overcurrent relay - VIP 30 b
CT’s dual ratio - 100/50/5A class X b
CT ratio - 200/1A class X b b b b b b b b b
Overcurrent & earth fault CT operated trip coils b
Overcurrent & earth fault relay VIP 35 b
Time fuse link O
IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b
20V-250V shunt trip coil b b b b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b b b b
Metering
CT’s -200/100/5A 0.5s 10VA b b b b b b b
VT’s -13.8kV/110V 0.5 10VA 13.8/110V/110v 0.5 50VA 3P 20VA b b
VT’s -11kV/110V 0.5 50VA b b b
VT’s -6.6kV/110V 0.5 50VA b b
VT’s phase - phase, CT’s R & B b b b b
VT’s phase - earth, CT’s RYB b b b
Indication
Mechanical ON/OFF b b b b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b b b b
Cable neon indication (6.6 - 13.8KV) O O O O O O O O O O O O
Auxiliary switch contacts 1NO 2NC b b b b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b b
Test facility
Integral cable test facility b b b b b b b b b b b b
Cable
Bottom entry up to 300mm2 1 x 3c b b b b b b b b b b b b
Bottom entry up to 630mm2 3 x 1c b b b b b b b b b b b b
Top entry cables O O O O O O O O O O O O
33
Extensible circuit breakers 200A
0Ringmaster range
Accessories
Ringmaster range
Accessories
CE2-T2 CE2- T3 CE2- T7 CE2-T11 CE2-T12 CE2-T13 T14CE2- CE2-T15 CE2-T16 CE2-T19 CE2-T20 CE2-T21 Kit no. Cable kits
Gland plate 1 x 3C O O O O O O O O O O O O RMR-A48
Gland plate 3 x 1C O O O O O O O O O O O O RMR-A49
Angled gland plates (RMR) O O O O O O O O O O O O RMR-A50
Blank aluminium gland plate O O O O O O O O O O O O RMR-A52
Brass wiping gland 1 x 3C O O O O O O O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O O O O O RMR-A11
Tubular gland 1 x 3C O O O O O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O O O O O RMR-A13
CES5 gland plate 1 x 3C O O O O O O O O O O O O RMR-A132
Top entry cables standard
panels v v v v v RMR-F93
Top entry cables MU6 only v v v v v v v RMR-F94
Installation items
3 phase busbars 630A O O O O O RMR-A14
3 phase busbars 630A O O O O O O O RMR-A78
Busbar end kit O O O O O O O O O O O O RMR-A15
Set of padlocks - 6 no O O O O O O O O O O O O RMR-A18/6
Foundation bolts (not required for transformer mounting)
b b b b b b b b b b b b RMR-A22
Multicore pilot glands O O O O O O O O O O O O RMR-A16
Time limit fuses (set of 2 - specify
rating as table page 113) O RMR-A17
Operational items
Operating handle b b b b b b b b b b b b RMR-A23
Cable neon indication
(6.6 - 13.8kV) v v v v v v v v v v v v RMR-F108
Neon lamp test unit
(including lamp) v v v v v v v v v v v v RMR-A24
Neon lamp O O O O O O O O O O O RMR-A81
VAP 6 test unit for VIP 300 O O O O O O O O O O O RMR-A202
Actuator 24V DC v v v RMR-F67
Polarity conversion kit** v v v RMR-F391
Mechanical interlocks
Key free, EARTH ON v v v v v v RMR-F85
Key free, MAIN OFF v v v v v v RMR-F86
N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
34
Extensible circuit breakers 200A
0Ringmaster range
Accessories
Ringmaster range
Accessories
CE2-T2 CE2- T3 CE2- T7 CE2-T11 CE2-T12 CE2-T13 T14CE2- CE2-T15 CE2-T16 CE2-T19 CE2-T20 CE2-T21 Kit no. Earth fault passage
indication (choose provision kit and an EFPI required if not using Easergy 200E) EFPI provision kit, inside
cable box O O O O O O O O O O O O RMR-F30
Bowden STD EFPI type NB O O O O O O O O O O O O RMR-A277
Bowden LV reset EFPI type NB1O O O O O O O O O O O O RMR-A278 Bowden LV reset & alarm
type NB2 O O O O O O O O O O O O RMR-A279
Bowden “RR” EFPI and CT O O O O O O O O O O O O RMR-A56
Fundamentals ER “FIND”
EFPI and CT O O O O O O O O O O O O RMR-A57
Ancillary items
Tool box O O O O O O O O O O O O RMR-A80
Order code
12kV, 16kA, 75kV BIL, 0.35bG CE2-
T2/16 CE2- T3/16 CE2- T7/16 CE2- T11/16 CE2- T12/16 T13/16CE2- CE2- T14/16 CE2- T15/16 CE2- T16/16 N/A CE2- T20/16 N/A 13.8kV, 21kA, 95kV BIL, 0.8bG CE2-
T2/21 CE2- T3/21 CE2- T7/21 CE2- T11/21 CE2- T12/21 CE2- T13/21 CE2- T14/21 CE2- T15/21 CE2- T16/21 CE2- T19/21 N/A CE2- T21/21 General arrangement drawing RMINST-03
Page 68 RMINST-02 Page 67 RMINST-03 Page 68 RMINST-02 Page 67 RMINST-03 Page 68 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-03 Page 68 RMINST-03 Page 68 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67
Schematic drawing RMSCH-07
Page 86 RMSCH-09 Page 88 RMSCH-06 Page 85 RMSCH-09 Page 88 RMSCH-19 Page 94 RMSCH-20 Page 95 RMSCH-20 Page 95 RMSCH-07 Page 86 RMSCH-07 Page 86 RMSCH-35 Page 103 RMSCH-35 Page 103 RMSCH-36 Page 104
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
35
Extensible circuit breaker 200A
0CE2-T2
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-07 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator Test facility
Integral cable test facilities Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information
Code Rating
CE2-T2/16 16kA, 12kV, 75kV BIL CE2-T2/21 21kA, 13.8kV, 95kV BIL
36
Extensible circuit breaker 200A
0CE2-T7
Ringmaster range
Panel types
Ringmaster range
Panel types
Transformer protection up to 1.5MVA at 11kV
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for time fuse links.
Protection CT’s - 100/50/5A class X
Shunt trip coil, 20V DC-250V AC
Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-06 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator Test facility
Integral cable test facility Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information
Code Rating
CE2-T7/16 16kA, 12kV, 75kV BIL CE2-T7/21 21kA, 13.8kV, 95kV BIL
37
Extensible circuit breaker 200A
0CE2-T*
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A Metering transformers b Metering CT’s R & B phases
v 200/100/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual
Anti-reflex operating handle
Standard features
Cable earth switch, 16/21kA 3s
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator Test facility
Integral cable test facility Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order code
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL CE2-T3/16 CE2-T3/21 CE2-T11/16 CE2-T11/21 N/A CE2-T19/21 CE2-T20/16 N/A Metering VT information: Phase to phase b b Phase to earth b b 6.6kV/110V b 11kV/110V* b b 13.8kV/110V b
General arrangement drawing RMINST-02
Page 67 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-09
Page 88 RMSCH-09 Page 88 RMSCH-35 Page 103 RMSCH-35 Page 103 *Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500
DE60252
(Select VT rating and switchgear rating from table below).
DE60252
38
Extensible circuit breaker 200A
0CE2-T12
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-19 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO Gas pressure indicator
Test facility
Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information
Code Rating
CE2-T12/16 16kA, 12kV, 75kV BIL CE2-T12/21 21kA, 13.8kV, 95kV BIL
DE60253 MM
39
Extensible circuit breaker 200A
0CE2-T*
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A Metering transformers b Metering CT’s v 200/100/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO Gas pressure indicator
Test facility
Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order code
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL CE2-T14/16 CE2-T14/21 N/A CE2-T21/21 Metering VT information: Phase to phase b Phase to earth b 6.6kV/110V b 11kV/110V* 13.8kV/110V b
General arrangement drawing RMINST-02
Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-20
Page 95 RMSCH-36 Page 104
*Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500
DE60254
(Select VT rating and switchgear rating from table below).
DE60254
40
Extensible circuit breaker 200A
0CE2-T13
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A Metering transformers b Metering CT’s v 200/100/5A v 10VA class 0.5s b Metering VT ph - ph v 11kV/110V 50VA v class 0.5 Documents
Installation drawing ref: RMINST-02 Schematic drawing ref: RMSCH-20 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual
Actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO Gas pressure indicator
Test facility
Integral cable test facility Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information
Code Rating
CE2-T13/16 16kA, 12kV, 75kV BIL CE2-T13/21 21kA, 13.8kV, 95kV BIL
41
Extensible circuit breaker 200A
0CE2-T15
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 2.5MVA at 11kV
Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CT’s - 500/200/1A class X
b Setting range: 500/1A
v Overcurrent: 20-200A
b Setting range: 200/1A
v Overcurrent: 8-80A Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-12 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator Test facility
Integral cable test facilities Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information
Code Rating
CE2-T15/16 16kA, 12kV, 75kV BIL CE2-T15/21 21kA, 13.8kV, 95kV BIL
42
Extensible circuit breaker 200A
0CE2-T16
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 2.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 35.
Protection CT’s - 500/200/1A class X CH30 core balance CT
b Setting range: 500/1A
v Overcurrent: 20-200A
v Earth fault: 25-300A
b Setting range: 200/1A
v Overcurrent: 8-80A
v Earth fault: 10-120A Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-13 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 200A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator Test facility
Integral cable test facilities Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Operating handle Busbar kit Top entry cables See page 33 for details Order information
Code Rating
CE2-T16/16 16kA, 12kV, 75kV BIL CE2-T16/21 21kA, 13.8kV, 95kV BIL
43
Extensible circuit breakers 630A
0Ringmaster range
Specification
Ringmaster range
Specification
CE6-T4 CE6- T5 CE6- T6 CE6- T8 T9CE6- CE6-T10 CE6-T22 CE6-T23 CE6-T24 Environment
Indoor / outdoor b b b b b b b b b
IP54 b b b b b b b b b
Ratings
Busbars 630A b b b b b b b b b
Circuit breaker normal rated current 630A b b b b b b b b b
12kV 16kA 3 seconds 75kV BIL b b b b b b b b b
13.8kV 21kA 3 seconds 95kV BIL O O O O O O O O O
Cable earth switch 16kA 3 seconds b b b b b b b b b
Cable earth switch 21kA 3 seconds O O O O O O O O O
Mechanism
Independent manual b b b b b b b b b
Provision for actuator 24V DC b b b b
Actuator 24V DC O O O O
Operating handle b b b b b b b b b
Protection system
CT ratio - 800/1A class X b b b b b b b b b
IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b
20V-250V shunt trip coil b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b
Metering
CT’s - 400/200/5A 0.5s 10VA b b b b b b b
VT’s - 13.8kV/110V/110V/ 0.5 50VA 3P 20VA b b
VT’s - 11V/110V 0.5 50VA b b b
VT’s - 6.6kV/110V 0.5 50VA b b
VT’s - phase - phase, CT’s R & B b b b b
VT’s phase - earth, CT’s RYB b b b
Indication
Mechanical ON/OFF b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b
Cable neon indication (6.6 - 13.8KV) O O O O O O O O O
Auxiliary switch contacts 1NO 2NC b b b b b b b b b
Indication CT 600/5A 5VA CLS 1 Yph b b b b b b b b b
Ammeter 0-600A b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b
Gas pressure indicator b b b b b b b b b
Test facility
Integral cable test facility b b b b b b b b b
Cable
Bottom entry up to 300mm2 1 x 3c b b b b b b b b b
Bottom entry up to 630mm2 3 x 1c b b b b b b b b b
Top entry cables O O O O O O O O O
44
Extensible circuit breakers 630A
0Ringmaster range
Accessories
Ringmaster range
Accessories
CE6-T4 CE6-T5 CE6-T6 CE6-T8 CE6-T9 CE6-T10 CE6-T22 CE6-T23 CE6-T24 Kit no. Cable kits
Gland plate 1 x 3C O O O O O O O O O RMR-A48
Gland plate 3 x 1C O O O O O O O O O RMR-A49
Angled gland plates (RMR) O O O O O O O O O RMR-A50
Blank aluminium gland plate O O O O O O O O O RMR-A52
Brass wiping gland 1 x 3C O O O O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O O RMR-A11
Tubular gland 1 x 3C O O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O O RMR-A13
CES5 gland plate 1 x 3C O O O O O O O O O RMR-A132
Top entry cables standard panels v v RMR-F93
Top entry cables MU6 only v v v v v v v RMR-F94
Installation items
3 phase busbars 630A O O RMR-A14
3 phase busbars 630A O O O O O O O RMR-A78
Busbar end kit O O O O O O O O O RMR-A15
Set of padlocks - 6 no O O O O O O O O O RMR-A18/6
Foundation bolts (not required for transformer mounting)
b b b b b b b b b RMR-A22
Multicore pilot glands O O O O O O O O O RMR-A16
Operational items
Operating handle b b b b b b b b b RMR-A23
Cable neon indication (6.6 - 13.8kV) v v v v v v v v v RMR-A108
Neon lamp test unit (including lamp) O O O O O O O O O RMR-A24
Neon lamp O O O O O O O O O RMR-A81
VAP 6 test unit for VIP 300 O O O O O O O O RMR-A202
Actuator 24V DC v v v v RMR-F67
Polarity conversion kit** v v v v RMR-F391
Mechanical interlocks
Key free, EARTH ON v v v v v RMR-F85
Key free, MAIN OFF v v v v v RMR-F86
N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms
Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T200E)
EFPI provision kit, inside cable box O O O O O O O O O RMR-F30
Bowden STD EFPI type NB O O O O O O O O O RMR-A277
Bowden LV reset EFPI type NB1 O O O O O O O O O RMR-A278
Bowden LV reset & alarm type NB2 O O O O O O O O O RMR-A279
Bowden “RR” EFPI and CT O O O O O O O O O RMR-A56
Fundamentals ER “FIND” EFPI and CT O O O O O O O O O RMR-A57 Ancillary items
Tool box O O O O O O O O O RMR-A80
Order code
12kV, 16kA, 75kV BIL, 0.35bG CE6-
T4/16 CE6- T5/16 CE6- T6/16 CE6- T8/16 CE6- T9/16 CE6-T10/16 N/A N/A CE6-T24/16 13.8kV, 21kA, 95kV BIL, 0.8bG CE6-
T4/21 CE6- T5/21 CE6- T6/21 CE6- T8/21 CE6- T9/21 CE6-T10/21 CE6-T22/21 CE6-T12321 N/A General arrangement drawing RMINST-03
Page 68 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-03 Page 68 Page 67RMINST-02 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67
Schematic drawing RMSCH-08
Page 87 RMSCH-10 Page 89 RMSCH-10 Page 89 RMSCH-23 Page 98 Page 99RMSCH-24 RMSCH-24 Page 99 RMSCH-37 Page 105 RMSCH-38 Page 106 RMSCH-37 Page 105
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
45
Extensible circuit breaker 630A
0CE6-T4
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 12MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-08 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600A
Indication CT Y ph - 600/5A class 1.0, 5VA
Gas pressure indicator Test facility
Integral cable test facility Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order information
Code Rating
CE6-T4/16 16kA, 12kV, 75kV BIL CE6-T4/21 21kA, 13.8kV, 95kV BIL
46
Extensible circuit breaker 630A
0CE6-T*
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 12MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600A
Indication CT Y ph - 600/5A class 1.0, 5VA
Gas pressure indicator Test facility
Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order code
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL CE6-T5/16 CE6-T5/21 CE6-T6/16 CE6-T6/21 N/A CE6-T22/21 CE6-T24/16 N/A Metering VT information: Phase to phase b b Phase to earth b b 6.6kV/110V b 11kV/110V* b b 13.8kV/110V b
General arrangement drawing RMINST-02
Page 67 RMINST-02 Page 67 RMINST-02 Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-10
Page 89 RMSCH-10 Page 89 RMSCH-37 Page 105 RMSCH-37 Page 105 *Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500
DE60197
(Select VT rating and switchgear rating from table below).
DE60197
47
Extensible circuit breaker 630A
0CE6-T8
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 12MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-23 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO Ammeter 0-600A
Indication CT Y ph - 600/5A class 1.0, 5VA
Gas pressure indicator Test facility
Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order information
Code Rating
CE6-T8/16 16kA, 12kV, 75kV BIL CE6-T8/21 21kA, 13.8kV, 95kV BIL
48
Extensible circuit breaker 630A
0CE6-T*
Ringmaster range
Panel types
Ringmaster range
Panel types
Feeder protection up to 12MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT v see below Environment Indoor/outdoor IP54 Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 12/13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
Cable earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contacts Ammeter 0-600A
Indication CT Y ph- 600/5A class 1.0, 5VA
Gas pressure indicator Test facility
Integral cable test facility Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 44 for details Order code
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL CE6-T9/16 CE6-T9/21 CE6-T10/16 CE6-T10/21 N/A CE6-T23/21 Metering VT information: Phase to phase b b Phase to earth b 6.6kV/110V b 11kV/110V* b 13.8kV/110V b
General arrangement drawing RMINST-02
Page 67 RMINST-02 Page 67 RMINST-02 Page 67 Schematic diagram RMSCH-24
Page 99 RMSCH-24 Page 99 RMSCH-38 Page 106 *Please consult Merlin Gerin when ordering units with 95kV BIL voltage Tel: +44(0)113 290 3500
DE60199
(Select VT rating and switchgear rating from table below).
DE60199
49
Extensible switches 630A
0Ringmaster range
Specification
Ringmaster range
Specification
SE6-S1 SE6-S2 SE6-E1
Environment
Indoor / outdoor b b b
IP54 b b b
Ratings
Busbars 630A b b b
Switch normal rated current 630A b b b
13.8kV 21kA 3 seconds 95kV BIL b b b
Cable earth switch 21kA 3 seconds b b
Mechanism
Independent manual b b b
Provision for actuator 24V DC b
Actuator 24V DC O
Operating handle b b b
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b b
Cable neon indication (6.6-13.8kV) v v
Busbar neon indication (6.6-13.8kV) v v
Auxiliary switch contacts1NO 1 NC v
Phase and earth fault detection CT’s for Easergy T200E O
EFPI provision only CT inside box O O b
Gas pressure indicator b b b
Test facility
Integral cable test facility b b
Integral test facility
RH/LH busbar earthing b
Cable (see available cable kit accessories)
Bottom entry up to 300mm2 1 x 3c b b
Bottom entry up to 630mm2 3 x 1c b b
Top entry cables O O
50
Extensible switches 630A
0Ringmaster range
Accessories
Ringmaster range
Accessories
SE6-S1 SE6-S2 SE6-E1 Kit no.
Cable kits
Gland plate 1 x 3C O O RMR-A48
Gland plate 3 x 1C O O RMR-A49
Angled gland plates (RMR) O O RMR-A50
Blank aluminium gland plate O O RMR-A52
Brass wiping gland 1 x 3C O O RMR-A10
Brass wiping gland 3 x 1C O O RMR-A11
Tubular gland 1 x 3C O O RMR-A12
Tubular gland 3 x 1C O O RMR-A13
CES5 gland plate 1 x 3C O O RMR-A132
Top entry cables v v RMR-F93
Installation items
3 phase busbars 630A O O v RMR-A14
Set of padlocks - 6 no O O O RMR-A18/6
Busbar end kit (1 end kit required per switchboard) O O O RMR-A15 Foundation bolts (not required for transformer mounting) b b b RMR-A22
Multicore pilot glands O RMR-A16
Operational items
Operating handle b b b RMR-A23
Cable neon indication (6.6-13.8kV) v v RMR-F108
Cable and busbar neon indication (6.6-13.8kV) v v RMR-F92
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O RMR-A81
Actuator 24V DC v RMR-F67
Polarity conversion kit* v RMR-F391
Mechanical interlocks
Key free, earth ON v v RMR-F85
Key free, main OFF v RMR-F86
N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms
Indication
EFPI provision kit, inside cable box O O RMR-F30
Bowden STD EFPI NB O O RMR-A277
Bowden LV reset EFPI type NB1 O O RMR-A278
Bowden LV reset & alarm type NB2 O O RMR-A279
Bowden “RR” EFPI and CT O O RMR-A56
Fundamentals ER “FIND” EFPI and CT O O RMR-A57
Ancillary items
Tool box O O O RMR-A80
Order code
13.8kV, 21kA, 95kV BIL, 0.8bG SE6-S1/21 SE6-S2/21 SE6-E1/21
General arrangement drawing RMINST-03
Page 68 RMINST-03 Page 68 RMINST-03 Page 68
Schematic drawing N/A RMSCH-29
Page 102 N/A Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
51
Extensible switch 630A
0SE6-S1
Ringmaster range
Panel types
Ringmaster range
Panel types
Switch disconnector
Protection & control - CB Non-automatic
Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-N/A Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features
Cable earth switch, 21kA 3s Anti-reflex operating handles
Indication
Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Test facility
Integral cable test facility Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 50 for details Order information
Code Rating
SE6-S1/21 21kA, 13.8kV, 95kV BIL
52
Extensible switch 630A
0SE6-S2
Ringmaster range
Panel types
Ringmaster range
Panel types
Switch disconnector
Protection & control - CB Non-automatic
Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-29 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 21kA 3s Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact 1NO Gas pressure indicator
Test facility
Integral cable test facility Cable Bottom entry up to 300mm2 1 x 3c Bottom entry up to 630mm2 3 x 1c Accessories Actuator, 24V DC Neon indication Glands and plates Interlocks Busbar kit Top entry cables See page 50 for details Order information
Code Rating
SE6-S2/21 21kA, 13.8kV, 95kV BIL
53
Extensible busbar earthing switch
630A
0SE6-E1
Ringmaster range
Panel types
Ringmaster range
Panel types
Busbar earthing switch
Documents
Installation drawing ref: RMINST-03 Schematic drawing ref: RMSCH-N/A Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features
Cable earth switch, 21kA 3s Anti-reflex operating handle
Indication
Mechanical earth/main indicator Gas pressure indicator Test facility N/A Cable N/A Accessories Interlocks Busbar kit
See page 50 for details Order information
Code Rating
SE6-E1/21 21kA, 13.8kV, 95kV BIL
54
Extensible bus-section 630A
0Ringmaster range
Specification
Ringmaster range
Specification
SE6-B1 CE6-B3 CE6-B5
Environment
Indoor / outdoor b b b
IP54 b b b
Ratings
Busbars 630A b b b
Circuit breaker normal rated current 630A b b
Switch normal rated current 630A b
12kV 16kA 3 seconds 75kV BIL b b
13.8kV 21kA 3 seconds 95kV BIL b O O
RH busbar earth switch 16kA 3 seconds b b
RH busbar earth switch 21kA 3 seconds b O O
Mechanism
Independent manual b b b
Provision for actuator 24V DC b
Actuator 24V DC O
Operating handle b b b
Protection system
CT ratio - 800/1A class X b b
IDMT overcurrent & earth fault relay - VIP 300 b b
20V - 250V shunt trip coil b b
Auxiliary switch1NO 2 NC b b
Metering
CT’s - 400/200/5A 0.5s 10VA b b
VT’s - 11kA/110V 0.5 50VA b b
VT’s phase - phase, CT’s R & B b b
Indication
Mechanical ON/OFF b b b
Mechanical EARTH/MAIN b b b
Earth selected auxiliary contact1NO b
RH busbar neon indication O O O
Auxiliary switch contacts1NO 2NC b b
Indication CT 600/5A 5VA CLS 1 Y phase b b
Ammeter 0-600A b b
Gas pressure indicator b b b
Integral test facility
RH busbar earthing b b b
LH busbar earthing ( using SE6-E1) O O O
55
Extensible bus section 630A
0Ringmaster range
Accessories
Ringmaster range
Accessories
SE6-B1 CE6-B3 CE6-B5 Kit no.
Installation items
3 phase busbars 630A RMR-A14
3 phase busbars 630A (Joggle metering) v v v RMR-A79
3 phase busbars 630A double width (metering) v v v RMR-A78
Set of padlocks - XX no O O O RMR-A18/6
Busbar end kit (1 end kit required per switchboard) O O O RMR-A15 Foundation bolts (not required for transformer mounting) b b b RMR-A22
Multicore pilot glands O O RMR-A16
Operational items
Operating handle b b b RMR-A23
LH and RH busbar neon indication v v v RMR-F92
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O O RMR-A81
VAP6 test unit for VIP 300 O O RMR-A202
Actuator 24V DC v RMR-F67
Polarity conversion kit* v RMR-F391
Mechanical interlocks
Key free, earth ON v v RMR-F85
Key free, main OFF v v RMR-F86
N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms
Ancillary items
Tool box O O O RMR-A80
Order code
12kV, 16kA, 75BIL, 0.35bG N/A CE6-B3/16 CE6-B5/16
13.8kV, 21kA, 95kV BIL, 0.8bG SE6-B1/21 CE6-B3/21 CE6-B5/21
General arrangement drawing RMINST-01
Page 66 RMINST-01 Page 66 RMINST-01 Page 66
Schematic drawing N/A RMSCH-21
Page 91 RMSCH-22 Page 97 Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
56
Extensible bus-section 630A
0SE6-B1
Ringmaster range
Panel types
Ringmaster range
Panel types
Bus-section disconnector
Protection & control Non-automatic Documents
Installation drawing ref: RMINST-01 Schematic drawing ref: N/A Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 95kV Operating mechanism Independent manual Standard features
RH busbar earth switch, 21kA 3s Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator Mechanical earth/main indicator Gas pressure indicator Test facility
Integral RH busbar test facility Cable N/A Accessories Neon indication Interlocks Busbars
See page 55 for details Order information
Code Rating
SE6-B1/21 21kA, 13.8kV, 95kV BIL
57
Extensible bus-section 630A
0CE6-B3
Ringmaster range
Panel types
Ringmaster range
Panel types
Bus-section circuit breaker
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT ph-ph v 11kV/110V 50VA v class 0.5 Documents
Installation drawing ref: RMINST-01 Schematic drawing ref: RMSCH-21 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual Standard features
RH busbar earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600A
Indication CT Y ph- 600/5A class 1.0 5VA
Gas pressure indicator Test facility
Integral RH busbar test facility Cable N/A Accessories Neon indication Interlocks Busbars
See page 55 for details Order information
Code Rating
CE6-B3/16 16kA, 12kV, 75kV BIL CE6-B3/21 21kA, 13.8kV, 95kV BIL
58
Extensible bus-section 630A
0CE6-B5
Ringmaster range
Panel types
Ringmaster range
Panel types
Bus-section circuit breaker
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142. Protection CT’s - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A Metering transformers b Metering CT’s v 400/200/5A v 10VA class 0.5s b Metering VT ph-ph v 11kV/110V 50VA v class 0.5 Documents
Installation drawing ref: RMINST-01 Schematic drawing ref: RMSCH-22 Environment
Indoor/outdoor IP54
Ratings Busbars 630A
Short time withstand 16/21kA 3s Normal current rating 630A Normal rated voltage 13.8kV Normal rated BIL 75/95kV Operating mechanism Independent manual
Provision for actuator, 24V DC
Standard features
RH busbar earth switch, 16/21kA 3s Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contacts1NO Ammeter 0-600A
Indication CT Y ph- 600/5A class 1.0 5VA
Gas pressure indicator Test facility
Integral RH busbar test facility Cable N/A Accessories Actuator, 24V DC Neon indication Interlocks Busbars
See page 55 for details Order information
Code Rating
CE6-B5/16 16kA, 12kV, 75kV BIL CE6-B5/21 21kA, 13.8kV, 95kV BIL