1.a) Explain the various factors that affect optimum operation to be considered in allocating generators of different power stations, neglect line losses.

b) Explain how the incremental production cost of a thermal power station can be

determined. [8+8]

2. a) Assume any relevant data and notation, derive the transmission loss formula. b) Discuss about the optimum generator allocation without line losses. [8+8] 3. a) Explain about spinning reserve in hydro power plants.

b) Explain about Co-ordination in hydro thermal system. [8+8] 4. a) Derive the transfer function of speed governing system?

b) Explain turbine model with block diagram? [8+8] 5.a) What is flat frequency control? Explain its requirements.

b) A 500 MW generator has speed regulation of 4%. If the frequency drops by 0.12Hz with unchanged reference, determine the increase in turbine power. Also find by how much the reference power setting be changed if the turbine power remain unchanged.

[8+8] 6.a) Explain how the tie-line power deviation can be unincorporated in two-area system block diagram.

b) What are the features of the dynamic response of a two area system for step load

disturbances? [8+8]

7.a) Explain economic dispatch control problem in detail.

b) Explain how the frequency error in the load frequency control problem is reduced

to zero. [8+8]

8.a) Explain about the losses that occur due to VAR flow in power system. b) Explain how the generators act as VAR sources in a power network.

[8+8]

(2)

SET-2

R05

Code.No: 37026

JAWAHARLAL NEHRU TECHNOLOGICAL UNIVERSITY HYDERABAD IV .B.TECH – I SEM REGULAR EXAMINATIONS JANUARY- 2010

POWER SYSTEM OPERATION AND CONTROL (ELECTRICAL & ELECTRONICS ENGINEERING)

Time: 3hours Max.Marks:80

Answer any FIVE questions All questions carry equal marks

- - -

1.a) Explain input – output characteristics of thermal power stations.

b) Define in detail cost curve of thermal stations. [8+8] 2.a) Explain with neat diagram the physical interpretation of Co-ordination equation. b) Explain various uses of general loss formula and state the assumptions made for the Calculations of Bm coefficients. [7+9] 3. In a two plant operation system, the hydro plant is operating for 8 hrs. During each day and the steam plant is operated all over the day. The characteristics of the steam and Hydro plants are.

Rs/hr 2 0.04 30 20 T GT GT C = P + P + 3 2 0.0012 GH 7.5 GHm W P P Sec µ = +

When both plants are running, the power flow from steam plant to load is 190MW and the total quantity of water is used for the hydro plant operation during 8hrs is . Determine the generation of hydro plant and cost of water used. Neglect

the transmission losses. [16]

6 3

220 10 m×

4.a) Explain the necessity of maintaining a constant frequency in power system operation. b) Two generators rated 100MW and 400MW are operating in parallel. The drop characteristics of their governors are 2% and 4% respectively from no-load to full load, Assuming that the generators are operating at 50Hz at no-load, how would a load of 500MW be shared between them? What will be the system frequency at this load?

Assume free governor operator. [6+10]

5.a) Explain in detail the importance of load frequency problem.

b) A 100MVA synchronous generator operates on full load at a frequency of 50Hz. The load is suddenly reduced to 50 MW. Due to time log in governor system, the steam value begins to close after 0.4 seconds. Determine the change in frequency that occurs in this time. Given the initial constant H = 5 KW – Sec/KVA of generator rating. [8+8] 6. Two power stations A and B operate in parallel. They are inter connected by a short Transmission line. The station capacities are 100MW and 200MW respectively. The Generators ‘A’ and ‘B’ have speed regulations of 3% and 2% respectively. Calculate the output of each station and load on the interconnection, if

(3)
(4)

SET-3

R05

Code.No: 37026

JAWAHARLAL NEHRU TECHNOLOGICAL UNIVERSITY HYDERABAD IV .B.TECH – I SEM REGULAR EXAMINATIONS JANUARY- 2010

POWER SYSTEM OPERATION AND CONTROL (ELECTRICAL & ELECTRONICS ENGINEERING)

Time: 3hours Max.Marks:80

Answer any FIVE questions All questions carry equal marks

- - -

1.a) Explain production cost and incremental fuel cost

b) Explain hydro-thermal scheduling problem. [8+8] 2.a) Discuss the general problem of economic operation of large inter connected area. b) What are the factors that can be taken into consideration for scheduling of

generators in a plant? [8+8]

3. Using dynamic programming method, how do you find the most economical combination of the units to meet a particular load demand? [16] 4. Draw the block diagram of a power system showing the governor, turbine and synchronous generator, indicating their transfer functions. For a step disturbance of ∆ , obtain the response of “increment in frequency” making suitable assumptions. PD

a) Without proportional plus integral controller and

b) With proportional plus integral control [8+8] 5. a) Explain about control area and control area error.

b) Two generators of rating 100MW and 200MW are operating with drop

characteristic of 6% from no-load to full load. Determine the load shared by each generator, if a load of 270MW is connected across the parallel combination of these

generators. [8+8]

6.a) What are the advantages of inter connected operation of power system? Explain. b) Two areas of a power system network are inter connected by a tie-line, whose capacity is 500MW, operating at a power angle of . If each area has a capacity of 5000MW and the equal speed regulation of 3Hz/puMW, determine the frequency of oscillation of the power for step change in load. Assume that both areas have the same

inertia constants of H = 4 Sec [8+8]

0

35

7. Explain the optional design of load frequency control problem. What are limitations of optional control theory in designing the load frequency control problem? [16] 8. a) Describe in detail off load and on load top changing transformers.

b) Discuss in detail about the generation and absorption of reactive power in power

system components. [8+8]

(5)

1. a) Explain in detail about incremental heat rate curve and cost curve

b) Write the expression for hourly loss of economy resulting from error incremental

cost representation. [8+8]

2. The incremental fuel cost for two plants are

1 1 1 0.075 G 18 G dC P dP = + Rs./MWh 2 2 2 0.08 G 16 G dC P dP = + Rs./MWh

The loss coefficients are given as

11

B = 0.0015/MW, B = -0.0004/MW and 12

22

B = 0.0032/MW for λ = 25 Rs./MWh.

Find the real power generator, total load demand and the transmission power. [16] 3. Derive the co-ordination equation for the optimal scheduling of hydro thermal inter

connected power plants. [16]

4. Explain the state-space model of synchronous machine. [16] 5. A generator in single area load frequency control has the following parameters:

Total generator capacity = 2500MW Normal operating load = 1500MW

Inertia constant = 5KW – Seconds per KVA; load damping constant,

B = 1%; frequency, f = 50Hz; and speed regulation, R = 2.5Hz/PU MW. If there is a 1.5% increase in the load, find the frequency drop

a) Without governor control

b) With governor control [8+8]

6. a) What are the features of the dynamic response of a two area system for step load disturbances?

b) What are the considerations in selecting the frequency bias parameters?

(6)

7. Show that the critical gain magnitude of integral controller of a load frequency control system in terms of system parameters is given by

Ki, Critical = 2 0 1 8 f B H R+ ⎤ ⎢ ⎥ ⎣ ⎦ [16]

8. a) A single – phase motor connected to a 230V, 50Hz supply takes 30A at a Pf of 0.7 lag. A capacitor is shunted across the motor terminal to improve the Pf to 0.9 lag. Determine the capacitance of the capacitor to be shunted across the motor terminals.

b) Explain the specifications of load compensation. [8+8]

References

Related documents

If you want to do extra work then try to draw in the full eyes, nose, ears and hair, but from a basic understanding point if you can just grasp where to place those features, that

Sera from the majority of mouse strains immunized with the PA1, PA2-4, and PA4 antigens had considerably less LeTx- neutralizing capacity than sera from mice immunized with PA1-4

(2013): UNESCO-sva blaga svijeta: prvi put u Hrvatskoj svi lokaliteti kulturne i prirodne baštine svijeta na jednome mjestu, Meridijani, Samobor, str.. Konvencija po prvi put

While the rise of religious fundamentalist movements, especially in the last three decades, pose a significant threat to women’s rights, we are also witnessing a generalized

In making this argument, with the aid of a content analysis of 26 educational policies from the 15 member states of the Caribbean Community (CARICOM), this article first locates

residential pro?ects located in and out o& the )etro. -n 2011 Megaworld unveiled a total o& eight new pro?ects E )ostly lu*ury condos in the business districts o& the

Based on the trend analysis, it was found that there is no clear pattern emerges from the graph plotted using the average figure for each of the ratios (current ratio, EPS, net

Vol 12, Issue 6, 2019 Online 2455 3891 Print 0974 2441 INTERPENETRATING POLYMER NETWORK IN DRUG DELIVERY FORMULATIONS REVISITED SUBHASISH PRAMANIK*, PRITHVIRAJ CHAKRABORTY Department