• No results found

4310/4320 Wireless Position Monitor

N/A
N/A
Protected

Academic year: 2021

Share "4310/4320 Wireless Position Monitor"

Copied!
12
0
0

Loading.... (view fulltext now)

Full text

(1)

4310/4320 Wireless Position Monitor

This document is intended to guide you through initial set up of the 4310/4320 wireless position monitor. Steps include:

D Installing power module D Configuration

D Physical Installation D Calibration

D Verifying operation

For detailed information on the 4310 or 4320 wireless position monitor refer to the appropriate instruction manual, available at www.fisher.com or your Emerson Process Management sales office.

4310 Wireless Position Monitor Instruction Manual (D103391X012) 4320 Wireless Position Monitor Instruction Manual (D103392X012)

(2)

Power Module Installation

The power module, along with eight screws (four large/four small), is shipped separately from the 4310 and 4320. The four large screws have a metal contact point on the circuit board and are installed as shown in figure 1. The four small screws go to the right of the large screws.

Figure 1. Power Module

LARGE SCREW SMALL SCREW W9645 W9640 COVER SCREWS HART TERMINALS POWER MODULE Note

There are two versions of the power module - standard life and extended life (refer to figure 2 for identifying labels). Default configuration for the 4310/4320 wireless power module is with a standard life power module; if you ordered the extended life power module you will need to make configuration changes (refer to page 8).

Figure 2. Power Module Labels

STANDARD LIFE POWER MODULE EXTENDED LIFE POWER MODULE

(3)

Configuring the wireless position monitor with the Field

Communicator

You may wish to configure the 4310/4320 before mounting it onto the actuator, then calibrate in the field using the local user interface. This section contains information on using the 475/375 Field Communicator to configure the wireless position monitor.

Note

The Field Communicator or AMS Suite: Intelligent Device Manager (as shown in figure 3) can also be used to make changes to other information, including:

D TAG name for the wireless position monitor D Trip point(s) for open/closed indication D Burst period / update rate

D Power module type D Network ID & Join key

Figure 3. Accessing Manual Setup Using AMS Device Manager

SELECT CONFIGURE > MANUAL SETUP TO CONFIGURE THE WIRELESS POSITION MONITOR USING AMS DEVICE MANAGER

1. Connect the HART leads of the Field Communicator to the power module HART connections (figure 1).

Note

Field Communicator HART leads do not have polarity.

2. Refer to Configuration with the Field Communicator on page 4 for 4310/4320 configuration information. 3. When configuration is complete, remove the HART leads from the wireless position monitor.

(4)

Configuration with the Field Communicator

1. Power up the Field Communicator and wait for the main menu screen to appear.

2. At the main menu, select HART Application > Online > Configure > Manual Setup (refer to figure 4). D Confirm that the Field Communicator is talking to the instrument.

The instrument type and default HART tag is shown at the top left hand corner of the Field Communicator screen. Figure 4. Manual Configuration of Wireless Position Monitor

System Software Ver: 3.2

Field Communicator Main Menu

HART Application

FOUNDATION Fieldbus Application Settings Listen For PC Scratch Pad ValveLink Mobile HART Application 1 Offline 2 Online 3 Utility 4 HART Diagnostics 4310:4310 Online 1 Overview 2 Configure 3 Service Tools SAVE 4310:4310 Configure 1 Guided Setup 2 Manual Setup 3 Alert Setup 4 Calibration SAVE HOME

(5)

HART Tag Configuration

1. Select Device Identification from the Manual Setup menu (figure 5).

2. Select HART tag to change. Enter the new HART tag information and select ENTER.

D If the HART Tag is not specified by the customer, change the HART Tag to the unit serial number. 3. Repeat step 2 to change the HART Long Tag, Descriptor, or Message, as required.

4. Press SEND to save the new HART Tag.

D “*” indicates that the HART Tag has been entered, but not saved. Figure 5. HART Tag Configuration

SAVE HOME 4310:4310 HART Tag 4310 12345678 4310:4310 Manual Setup 1 Device Identification 2 Wireless 3 Burst Mode 4 Broadcast Power 5 Power Information 6 Trigger Points SAVE HOME 4310:12345678 Device Identification 1 *HART Tag 12345678 2 HART Long Tag TEst_4310 3 Descriptor TEST_4310 4 Message

HELP SEND HOME

4310:4310

Device Identification

1 HART Tag 4310 2 HART Long Tag TEst_4310 3 Descriptor TEST_4310 4 Message

HELP DEL ESC ENTER

Network ID & Join Key configuration

1. Select Wireless > Join Device to Network (figure 6).

2. Select OK when the screen “Bursting to the gateway has been disabled. ...” appears.

3. Select OK when the screen “Warning: When changing the network ID or Join Key...” appears,

4. Enter the Network ID and Join Key of the network that the wireless position monitor will be communicating with.

Note

The Network ID and Join Key can be obtained from the administrator of the smart wireless gateway that is being joined.

5. Select Accept new join key and Network ID > ENTER.

(6)

6. Select OK when the screen “In a few minutes, the device...” appears. 7. Configuration of Network ID and Join Key is now complete.

Figure 6. Network ID and Join Key Configuration

4310:12345678 Wireless

1 Wireless Mode Searching 2 Network ID 1234 3 Join Device to Net...

4310:12345678

Bursting to the gateway has been disabled. After the instrument is opera­ tional on the network, re‐enable burst­ ing by running “Change Update Period”. 4310:12345678 Manual Setup 1 Device Identification 2 Wireless 3 Burst Mode 4 Broadcast Power 5 Power Information 6 Trigger Points

SAVE HOME HELP SAVE HOME

ABORT OK

4310:12345678

Warning: When changing the Network ID or Join Key, wireless communications with the device may be lost. Any pending changes that have not been sent to the device may be lost.

ABORT OK

HELP DEL ABORT ENTER HELP DEL ABORT ENTER

4310:12345678

Enter the Wireless HART Network ID that this device should join to: (1229)

1229

4310:12345678

Enter Join Key for the WirelessHART network: (part 1 of 4): (00000000) 00000000 ABORT ENTER 4310:12345678 Join Key (4 of 4): 00000000 Network ID: 1229

1 Accept new join key and Network ID 2 Re‐enter join key and Network ID

ABORT OK

4310:12345678

In a few minutes, the device will join the specified network

(7)

Burst Mode Configuration

1. Select Burst Mode > OK > Yes > Enter the desired Burst Period > ENTER.

2. Select OK and wait for completion of bandwidth allocation. Select OK when complete. Figure 7. Burst Mode Configuration

4310:12345678 Manual Setup 1 Device Identification 2 Wireless 3 Burst Mode 4 Broadcast Power 5 Power Information 6 Trigger Points SAVE HOME 4310:12345678

The instrument is operational on the network. It is possible to set the Update period.

ABORT OK

ABORT ENTER

4310:12345678

This device is configured to take advant­ age of Emerson Smart Wireless Gateway 1 Yes ‐ Continue

2 No ‐ Disable optimizations

4310:12345678

Enter the desired Burst Period (Maximum 1 hour) (4.000 s)

32

HELP DEL ABORT ENTER

4310:12345678

Click Next/OK to request Bandwidth for Burst Mode. Burst mode uses three messages so bandwidth allocation may take a few minutes.

ABORT OK

4310:12345678

Getting bandwidth allocation...

ABORT

4310:12345678

Message 1 of 3 completed.

ABORT

4310:12345678

Burst Update Rate successfully changed.

(8)

Power Module Configuration

Power module configuration is only required when using the extended life power module. The default setting from the factory is for a standard life power module. This configuration is required to provide more accurate power module lifetime estimates.

1. Select Power Information > Power Module Type and select Extended Life as shown in figure 8. Figure 8. Configuring the Power Module Type

4310:12345678 Manual Setup 1 Device Identification 2 Wireless 3 Burst Mode 4 Broadcast Power 5 Power Information 6 Trigger Points SAVE HOME 4310:12345678 Power Information

1 Power Source Power Module 2 Power Module Type Extended Life 3 Power Module Date 2/23/2009 4 Remaining Life 778 Days

(9)

Physical Installation

Mount the 4310/4320 wireless position monitor using the appropriate mounting bracket. Follow the assembly drawing that is shipped with the mounting kit. Once mounted, the antenna should be positioned vertically, as shown in figure 9.

Figure 9. Position the Antenna Vertically

(10)

Calibrating the 4310/4320

Calibrate the 4310/4320 wireless position monitor after the actuator/valve assembly has been calibrated to its required span. Mount the wireless position monitor onto the actuator per the appropriate instruction manual.

Figure 10. User Interface Flow Chart

left SET TO 0% SPAN UNMARKED NEXT SET TO 0% SPAN MARKED NEXT SET TO 100% SPAN UNMARKED NEXT SET TO 100% SPAN MARKED NEXT APPLY? YES NO SUCCESS NEXT CALIBRATE SELECT NEXT

Note: Choose first point of calibration as either 100% or 0% left right right left left Left Right STATUS V1.10 SELECT NEXT

(11)

Verifying Calibration

There are two methods used to verify calibration of the 4310/4320; the Local User Interface or the 1420 Gateway.

Verifying 4310/4320 calibration with the Local User Interface.

To verify the calibration of the 4310/4320, stroke the actuator/valve assembly and hold it at the required position (open or closed).

To perform a quick position check push the left button when the wireless position monitor is in Sleep mode and verify the position (refer to figure 11). Stroke the actuator/valve assembly to the opposite position and push the left button to verify that position.

Figure 11. Push Left Button to Show Quick Position of Valve

Sleep Mode left 100% OF SPAN OPEN 0% OF SPAN CLOSED

Verifying 4310/4320 calibration with the 1420 Gateway

Ensure that the 4310/4320 is Online and communicating with the gateway. A green dot indicates that the instrument is online (figure 12).

Stroke and hold the position to the desired position and wait for the data to appear on the Internet browser.

Note

(12)

Depending on the burst rate, the data may take up to 60 seconds to appear.

D The default value of burst period is set to 60 seconds. In order to have a faster update rate on AMS Device Manager change the burst period (4, 8, 16... 60 seconds).

Note

Faster update rates will have an impact on power module life.

D Burst Rate can be changed with the Field Communicator (Manual Setup) or with AMS Device Manager. Figure 12. Explorer Showing Instrument Status

GREEN DOT INDICATES INSTRUMENT IS ONLINE

Note

Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use, or maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end user.

Emerson Process Management Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.

Fisher is a mark owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. Emerson Process

Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.

References

Related documents

Press the sync button while rack unit and bodypack IR windows are aligned to transfer settings.. ④

Binfathi shall book a gain (negative goodwill) through profit or loss of 3,200 related to the acquisition, recognize expenses of 1,400 and deduct from equity 2,000 relative to the

Although the Transceiver Control Module is shipped with a Battery Pack installed and connected (Figure 2-6), this section details how to install and connect a Battery Pack. 2.4.3.1

home With monitor connected to wireless router and monitor enrolled to you account, setup monitor with the alarms in your home furthest from the monitor. With the monitor in

Refer to your Vehicle Owner’s Manual for detailed information about vehicle belts, LATCH, and preferred Restraint installation positions.... 1

Determination of signal amplitude and position sensitivity of a position monitor requires knowledge of the coupling of the beam to the transducer, whether button or stripline, as

For more information, refer to the “Monitor, climate, audio, phone and voice recognition systems (section 4)” of your Owner’s Manual.. *SiriusXM ® Satellite Radio is only

If you want to manually configure the wireless settings on your router click Manual Wireless Network Setup.. and refer to the