D20MX v1.40 Release Notification
Product Bulletin
Date: September 10, 2014 Classification: GE Information
Release Notification of D20MX v1.40
The D20MX Substation Gateway is a specialized computing platform which executes communications and energy management applications for monitoring and control of electrical substations. The D20MX is capable of consolidating data from multiple slave devices connected through communication channels (DCA: Data Collection Applications) and D20 Input / Output Modules in a single database. The D20MX can execute local logic, aggregate data, process data through one of multiple applications (DTA: Data Translation Applications) and report data upstream to master stations through different server protocols (DPA: Data Processing Applications).
The new D20MX processor card is a pin-for-pin compatible replacement for all generations of the D20 SBC, providing the latest revisions of common D20 applications and performance enhancements to support NERC-compliant Cyber security.
Additional Configurable Applications and Additional Features
The following applications have been introduced for this release:
Application
ID* Base D20 Classic Application Version† Application Name Description
A048 210 Status
Combination DTA Provides one ore more DI points, each of which provides an event-driven logical OR of a set of mapped system DI points. A186-0 213 Western Power
Distribution (WPD) DTA
Calculates power from monitored voltage, current, and phase angle. Also, performs time integrated analog averaging, relative to the top of the hour.
D20MX v1.33 has been replaced by D20MX v1.40.
The minimum version of SGConfig required with D20MX v1.40 is v8.1. However, v8.2 or higher is recommended.
SGConfig v8.2 is available for download free-of-charge from GE’s technical support Website. CDs can be ordered through GE’s Grid Automation Online Store under part number 588-0082 V8.20/00. Version 8.2 supersedes earlier versions of SGConfig software.
Product Bulletin
PRBT-0331 2 GE Information
Application
ID* Base D20 Classic Application Version† Application Name Description
A193-0 302 Top of the Hour Analog
Averaging DTA
Performs time integrated analog averaging, relative to the top of the hour.
A194-0 101 Cooper 2179
DCA Monitors and controls Cooper devices using the Cooper 2179 protocol.
Note: This is a licensed application.
A104-0N 124 Alarm Grouping DTA for the D20MX
Provides DI points each representing a group alarm. The group alarm is generated when the number of DI points in the alarm state exceeds the group threshold value.
A121-0 200 Automatic Frequency Selection DTA
Provides AI points each derived from an Automatic Selection Method (ASM). An ASM selects the highest priority valid frequency measurement from a group of AI points. A161-0 301 Secondary
Master Trip/Close DTA
Translates control requests into conventional trip/close operations in conjunction with secondary control operations to be used as a Secondary Master Trip or Close.
B080-0 214 IEC 60870-5-103
DCA Monitors and controls devices using the IEC 60870-5-103 protocol. B119-1N 103 LAN Redundancy
Manager DTA Provides health and active pseudo DI points for LAN Ports, as well as default gateway monitoring and advanced routing configuration.
* The “N” in the Application Number implies that the application definition has changed from the indicated D20 Classic application definition version.
†The D20MX version of the application is based on this D20 classic application version. However, the D20MX version is not identical to the D20 classic version due to minor changes to improve the robustness and security of the original application.
The following new features have been added for this release: Field upgradeability of FPGAs
and boot loaders After upgrading to D20MX firmware v1.4 and SGConfig v8.2, you will be able to bring the D20MX’s Field-Programmable Gate Arrays (FPGAs) and boot loaders to the latest version, even if you had opted not to upgrade them in previous releases. This allows you to benefit from improvements such as better D.20 link compatibility and traditional SYSFAIL operation. Previously you would have been required to return the D20MX to the factory in order to update the FPGAs. This is no longer necessary as of v1.4.
Refer to the sections on the Hardware Support Package in “994-0140 D20MX Instruction Manual V14x” for further information.
Product Bulletin
PRBT-0331 3 GE Information
Syslog The syslog HOSTNAME field now allows for a text-based host name and identifies from which CCU in a redundant system a log originated.
Refer to “B014-1NCG WESMAINT II+ for the D20MX Configuration Guide V640” available on the D20MX Documentation CD (GE part number 588-0075 V140/00) for further information. Configurable RS-232 Console
Baud Rate The baud rate of the front RS232 console port can now be specified in the order code of a D20MX. In addition, you can configure the console baud rate using the D20M shell command “jbaud”. Once the “jbaud” command is executed, the console baud rate will be permanently set to the specified baud rate (either 9600 or 19200) until the “jbaud” command is executed again. User Log CSV File Export The WESMAINT User Log can now be exported to a CSV file that can be retrieved using an SFTP
client.
Refer to “B014-1NUG WESMAINT II+ for the D20MX Users Guide V640” available on the D20MX Documentation CD (GE part number 588-0075 V140/00) for details.
Improved robustness The D20MX now verifies the version of the firmware applications against the version of the appldefs in the configuration before starting the applications. This prevents the system from going into disabled mode when the wrong configuration is downloaded to the D20MX. DNP DPA SBO compatibility The DNP DPA is now configurable to allow poll requests in between a Select and Operate
request. This allows for compatibility with some master stations that need to acquire data when an operator has selected a control point but not yet operated the control.
This feature is disabled by default and it is not recommended that this setting be used unless the master station requires it.
Refer to “B021-1NCG DNP V300 DPA for D20MX V992 and V915” available on the D20MX Documentation CD (GE part number 588-0075 V140/00) for further information.
What’s next?
To upgrade the firmware and Hardware Support Package to version 1.40:
1. Obtain the D20MX v1.40 Documentation Zip File (part number 588-0075 V140/00) from GE customer service (see contact information below). This file can also be downloaded from the:
•
GE technical support library under the D20MX folder, or the•
GE Digital Energy Web site. 2. Extract the zipped folder.3. Open the documents folder at: SGA0026 V1.40_00 D20MX Documentation CD\ISO Image\D20MX CD\documents. 4. Locate the following Technical Note (TN) document:
•
TN0063_D20MX_V1.4X+_ Upgrade_Procedure_V100_R0.pdf,Product Bulletin
PRBT-0331 4 GE Information
Additional Information
For more detailed information on the D20MX v1.40 release, see the GE Digital Energy web site:
http://www.gedigitalenergy.com/multilin/energy/catalog/d20mx.htm
Product Support
We trust that this information assures you that GE Digital Energy is committed to the continued support of the Substation automation product line. We appreciate your business and look forward to continuing to grow our relationship.
If you need help with any aspect of your GE Digital Energy product, you have a few options:
• Search Technical Support
• Contact Customer Service
Search Technical Support
The GE Digital Energy Web site provides fast access to technical information, such as manuals, release notes and knowledge base topics.
Visit us on the Web at: http://www.gedigitalenergy.com/
Contact Customer Service
The GE Digital Energy Customer Service Center is open 24 hours a day, seven days a week for you to talk directly to a GE representative.
In the U.S. and Canada, call toll-free: 1 800 547 8629 International customers, please call: +1 905 927 7070 Or e-mail to: multilin.tech@ge.com
Copyright Notice
© 2014, General Electric Company. All rights reserved.
The information contained in this online publication is the exclusive property of General Electric Company, except as otherwise indicated. You may view, copy and print documents and graphics incorporated in this online publication (the “Documents”) subject to the following: (1) the Documents may be used solely for personal, informational, non-commercial purposes; (2) the Documents may not be modified or altered in any way; and (3) General Electric Company withholds permission for making the Documents or any portion thereof accessible via the internet. Except as expressly provided herein, you may not use, copy, print, display, reproduce, publish, license, post, transmit or distribute the Documents in whole or in part without the prior written permission of General Electric Company. If applicable, any use, modification, reproduction, release, performance, display, or disclosure of the Software Product and Associated Material by the U.S. Government shall be governed solely by the terms of the License Agreement and shall be prohibited except to the extent expressly permitted by the terms of the License Agreement.
The information contained in this online publication is subject to change without notice. The software described in this online publication is supplied under license and may be used or copied only in accordance with the terms of such license.
Trademark Notice
Product Bulletin
PRBT-0331 5 GE Information
* Trademarks of General Electric Company. Other company or product names mentioned in this document may be trademarks or registered trademarks of their respective companies.
Document Revision History
Version Revision Date Author Change Description