Dual Maximum
VAV Box Controls
Steven T. Taylor, PE FASHRAE
Taylor Engineering LLC
staylor@taylor‐engineering.com
ASHRAE Golden Gate Chapter
November 13, 2014
Agenda
VAV Box basics
•
Sizing VAV Boxes
•
How low can you go?
VAV Box control logic
•
Conventional VAV box control logic
•
“Dual Maximum” control logic
•
Non-complying dual maximum control logic
•
Determining setpoints
How well does “Dual Maximum” logic work?
VAV Box Sizing
Oversized box
•
Less pressure drop
•
Less noise
•
Higher box min → more reheat, higher fan energy
•
Cost more
Undersized box
•
Higher pressure drop
•
More noise
VAV Box Sizing: LCC Analysis
Compared ∆TP from 0.3” to 0.8”
Low rise office building
Sensitivity Analysis
•
Climate
•
Loads
•
operating schedules
•
Utility rates
•
Load calc’ (aggressive, conservative)
•
8 bit versus 10 bit A/D converter
•
SAT (50°F-60°F), SAT reset, SP reset
RESULT: Size VAV Boxes for ~0.5” ∆TP
VP
SP
TP
VAV Box Sizing: Sample Calc.
Nominal size Inlet dia. (in.) Outlet width (in.) Outlet height (in.) ∆SP (in. w.g.)* ∆VP (in. w.g.) ∆TP (in. w.g.) Max CFM Radiated NC* 4 4 12 8 0.08 0.42 0.50 230 21 5 5 12 8 0.15 0.35 0.50 333 20 6 6 12 8 0.24 0.25 0.49 425 21 7 7 12 10 0.25 0.25 0.50 580 20 8 8 12 10 0.33 0.17 0.50 675 22 9 9 14 13 0.27 0.23 0.50 930 17 10 10 14 13 0.32 0.18 0.50 1100 19 12 12 16 15 0.32 0.17 0.49 1560 19 14 14 20 18 0.31 0.19 0.50 2130 18 16 16 24 18 0.32 0.18 0.50 2730 22*From selection software using ARI 885-95 and assuming inlet SP = 1.5 and outlet SP = 0.25
What is the lowest minimum?
•
Function of
–
DDC Controller: What’s the lowest
controllable velocity pressure (VP) signal?
• DDC velocity pressure transducer accuracy
• A/D converter resolution (bits)
–
VAV Box:
• Amplification factor, F
• Inlet size, D
4
2
min
min
D
FPM
CFM
F
VP
FPM
min
4005
min
Why Not Just Look in the VAV Box
Catalog?
Equates to ~0.03” minimum VP and about 30% of design CFM for typical box selections
Why Not Just Look in the VAV Box
Catalog?
Still too high
Controllable VP Minimum
Some manufacturers list the range in catalog
Some you have to ask
Most available from ASHRAE RP 1353 and PG&E
research projects (see references)
•
Almost all controllers ± 10% at 0.003”
Typical DDC Performance
Highly accurate down to about 50 CFM (0.003”)
-40 -30 -20 -10 0 10 20 30 0 100 200 300 400 500 600 700 800 Reference Flow [cfm] Fl o w E rr o r [c fm ]
Nailor VAV Box Titus VAV Box “A”
Flow Probe Amplification
229 358 515 702 916 1160 1432 2062 3665 7000 2806 4 inch 5 inch 6 inch 7 inch 8 inch 9 inch 10 inch 12 inch 14 inch 16 inch 22 inch 10 100 1000 10000 0.01 0.1 1Flow Probe Velocity Pressure Signal (Inches W.G.) C F M C F M @ O n e I n c h S i g n a l I n l e t S i z e 2
4005
K
A
F
F = amplification factorK = actual flow in CFM at flow probe output of 1.0” w.c.
A = is the nominal inlet area in ft2
K
Typical Flow Probe Performance
V e lo c ity [ fp m ]Flow Grid Pressure [iwc]
1 .5 .1 .05 .01 .005 .001 50 100 200 500 1000 2000
6
.
2
~
slope
F
Specify ≥2.0
Sample Controllable Minimum
F
VP
FPM
min
4005
min3
.
2
004
.
0
4005
170
Box Inlet Diameter Maximum CFM at 0.5 in.w.g. pressure drop Minimum CFM at 0.004 in.w.g. sensor reading Minimum Ratio at Highest Maximum, % Minimum Ratio at lowest Maximum, % 6 425 33 7.8% ‐ 8 715 58 8.1% 13.6% 10 1,100 91 8.3% 12.7% 12 1,560 130 8.3% 11.8% 14 2,130 177 8.3% 11.3% 16 2,730 232 8.5% 10.9%
4
2 min minD
FPM
CFM
Q: Why do some buildings use 3 -5
times as much energy as others?
0 500 1,000 1,500 2,000 2,500
Mar-02 Apr-02 May-02 Jun-02 Jul-02
B o il e r In p u t ( B tu /s f) Site #1 Site #2
A: Reheat
Conventional VAV Box Minimum
Setpoint
No less than larger of:
•
Minimum ventilation rate
Per Title 24
•
Controller minimum
Not an issue for conventional logic – see discussion above
•
Limit “dumping”
Not an issue – see RP-1515 results below
•
Limit stratification
No more than 20°F above space temperature (~≤95°F) per Standard 90.1
No more than larger of:
•
30% of cooling maximum
Per Title 24/Standard 90.1. Now only allowed for non-DDC controls
Title 24 VAV Control Requirement
Dual Maximum Control
Dual Maximum Logic in Action
Start heating,
Sort of Dual Maximum Control
(Found in some configurable controllers)
Sort of Dual Maximum Control
(Found in some configurable controllers)
VAV Box Dual Maximum Control Setpoints
per Title 24 and Standard 90.1
Minimum:
1.
No less than larger of:
Minimum ventilation rate for the zone Controller minimum
2.
No more than 20% of cooling
maximum
Heating Maximum:
1.
No less than larger of:
Minimum
Limit stratification - ≤20°F SAT above space temperature (≤~90°F to 95°F)
2.
No more than 50% of cooling maximum
Always use Option 1 above
•
Do not use code maximum just because it’s legal!
•
Avoid using %-of-cooling-maximum setpoints – boxes are
usually oversized!
COOL MIN HEAT VR‐101 12 1035 135 260 VR‐102 10 810 90 230 VR‐103 6 210 50 50 MARK INLET SIZE DESIGN CFM
What about Standard 62.1 Multiple
Spaces compliance?
How Well Does “Dual Max”
Logic Actually Work?
RP 1515, "Thermal and Air Quality Acceptability in Buildings that Reduce Energy by
Reducing Minimum Airflow from Overhead Diffusers"
Objectives
Measure energy savings & validate simulations
Identify comfort issues that may occur at low flowFunding
California Energy Commission - PIER
ASHRAE
UC Berkeley - Center for the Built EnvironmentResearch Team
UC Berkeley
Taylor Engineering
Price IndustriesMethod
Field Study in 7 buildings
Background survey
“Right now” survey matched to zone trends
Energy monitoring
Laboratory StudyYahoo! Sunnyvale Campus
1073 Zones
3700 Occupants
800 Ferry Building
22 Zones
Perforated Diffuser
with blades in face
Measured flow fractions: Yahoo campus
0 20 40 60 80 100 0. 00 0. 05 0. 1 0 0. 15Warm Season All Occupied Hours
Flow Fraction [%] D ens it y Low Minimum 30% Minimum 0 20 40 60 80 100 0. 00 0. 05 0. 1 0 0. 15
Cool Season All Occupied Hours
Flow Fraction [%] D ens it y Low Minimum 30% Minimum
Occupant Comfort Survey
Questions
•
When the logic changed from conventional (High minimum) to Dual Maximum (Low minimum): Did occupants become less comfortable?
Was their sense of air movement stronger due to “dumping”?
Approach
•
3 surveys: Yahoo warm and cool seasons 800 Ferry building warm season
•
3 – 4 weeks of surveying each season•
Switched between high and low minimum operation in the middle of each survey period•
Surveys administered 3 times/day% Dissatisfied people HIGH Conventional LOW Dual Maximum 800 Ferry Building 27.3% 12.5% Yahoo! cool season 8.7% 9.4% Yahoo! warm season 20.1% 10.3% 249 1408 681 463 1793 766 0.0% 5.0% 10.0% 15.0% 20.0% 25.0% 30.0%
800 Ferry Building Yahoo! Cool season Yahoo! Warm season
% dissa tis fied of people
"How satisfied are you with the temperature in your workspace?“
HIGH min flow rate LOW min flow rateThermal sensation distribution
Loads are very low!
0.2 0.5 1 CFM/FT
2at 20˚F
∆T
What happens when load is less than
airflow minimum?
Actual Required CFM
Conventional Logic
Air temperature
(800 Ferry building)
09/ 22 09/ 23 09/ 26 09/ 27 09/ 28 09/ 29 09/ 30 10/ 03 10/ 04 10/ 05 10/ 06 10/ 07 10/ 10 10/ 11 10/ 12 10/ 13 10/ 14 10/ 17 10/ 18 10/ 19 10/ 20 60 65 70 75 80 85 Dates z one t em p er at ur e [ F ] 1.4 2 1.8 1.5 1.6 1.5 1.4 1.8 1.6 1.5 2 0.89 1.6 1.5 1.1 1.9 1.1 1.4 1.3 1.2 2.1 72 72 71 71 72 71 71 71 70 71 71 72 73 74 74 73 74 74 75 75 73 14 27 23 35 45 36 35 41 47 34 65 23 30 51 45 64 25 37 67 27 48 sd Mean NHIGH minimum flow rate
LOW minimum flow rate
How about Drafts?
Price Lab Tests
Perforated diffusers with blades in the neck, Cooling Mode.
Results:
• Negligible impact on ADPI – all near 1
• Negligible impact on ACE – all near 1
Dual Maximum VAV Box Logic
Summary
Title 24 requires Dual Maximum logic for VAV zones with DDC
Setpoints
•
Set minimum and heating-maximum setpoints as low as possible
Minimum allowed by controls is seldom a factor if box properly sized Do not use maximum allowed by T-24 just because it is legal
Cost impact
•
Requires discharge temperature sensor
This is nice for diagnostics anyway
•
Usually requires programmable zone controller
Configurable controller programming should soon catch up