A study of the nature of fire

risks in tall buildings

David Charters and Carl Sherwood BRE Global

(2)

Overview

1. Introduction

2. Challenges of tall buildings 3. Analysis of fire statistics

4. Quantitative risk assessment 5. Summary

(3)

Fire engineering…

Engineering is…

“… the art of modelling materials we do not wholly understand, into shapes we can not precisely analyse, so as to withstand forces we can not properly assess, in such a way that the public at large has no reason to suspect the extent of our ignorance.”

(4)

Regulations/British Standards

Fire Engineering since 1985: – 5 Functional requirements, eg:

Prescriptive guidance (very flexible): – British Standard 9999

Code of practice for Fire Safety Engineering: – British Standard 7974

Means of warning and escape

B1.The building shall be designed and constructed so that

there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.

(5)

‘Normal’/traditional buildings

– Low rise

– Small number of people – Stairs:

– Main means of access – Main means of egress

– Only means of emergency egress – Relatively small in number and area – Low evacuation times:

(6)

High rise buildings

– Large numbers of people

– High probability of fire in floor below – Fire may spread from floor to floor – Evacuation route unfamiliar?

– Access/egress via lifts

– Emergency evacuation by stairs – Extended evacuation time:

– Phased evacuation

(7)

Fire service intervention

– Vehicular access often difficult – Extended travel distances

– Potential interaction between fire-fighters and evacuating occupants in high-rise buildings

– Simultaneous egress – Phased egress

– Fire-fighting may affect means of escape – Logistical challenges

– fire-fighting lift – Communications

(8)

Triangle Shirtwaist fire

– 1911 – New York – 146 people died – NFPA code – Escape code – All occupancies

(9)

One Meridian Plaza, Philadelphia

– 23 February 1991 – 38 storey

– Fire started on 22nd floor – Fire spread upwards

– Tennant sprinkler on 30th floor – Façade spread spandrel failures

(10)

Windsor building, Madrid

– 12 February 2005 – 32 storeys

– Fire started on 21st floor

– Fire spread upwards and downwards – Second façade attachment failure

– Technical floor slab on 17th floor stopped downward fire spread

(11)

New challenges

– Super high rise buildings – 500m+ high

– 10,000+ people – Improved healthcare

– Ageing population

– Increased availability of food – Increase in obesity

– Sedentary lifestyle – Reduced fitness

(12)

Importance of structural fire resistance

Relative fire risk for different building heights and levels of fire resistance (unsprinklered)

0 500 1000 1500 2000 2500 3000 3500 0 20 40 60 80 100

Number of floors above ground

L eve l o f ri sk re la ti ve to a two st o re y build in g wi th no fi re re si st ance

zero fire resistance 30 minutes fire resistance 60 minutes fire resistance 90 minutes fire resistance 120 minutes fire resistance

(13)

Building Regulations

Prescriptive guidance for tall buildings: – >18m additional requirements

– >30m:

– Sprinklers and

(14)

Importance of automatic sprinklers

Relative fire risk for different building heights for solutions that comply with AD B

-1 0 1 2 3 4 5 6 7 0 100 200 300 400

Building height above ground (m)

L eve l o f fi re r isk re la ti ve t o a tw o st o rey b ui ldin g w it h ze ro f ire res is ta n ce Without sprinklers With sprinklers

(15)

London Fire Brigade data

The dates 01/04/1996 to 03/11/2008 inclusive: – 14,575 incidents are reported

– 266 fatalities and 4,439 injuries

– Building heights four to about 40 storeys tall : – 9,349 fires in 4 and 5 storey buildings – 2,275 fires in 6 and 7 storey buildings – 1,582 fires in 8 to 11 storey buildings – 981 fires in12 to 19 storey buildings

(16)

Analysis of Real Fire Library

London fire data between 1996 and 2008: – Between 300 and 500 fire injuries per year – Between 10 and 40 deaths per year

– 30 fatalities in buildings with 10+ storeys (up to 21 storeys) – 55% of fatalities were in purpose built blocks of flats

– Accidental most likely cause of 70% percent of fires

(17)

Number of fatalities against the number of

rooms/spaces involved in the fire

(18)

Probability of spread to additional rooms/spaces per

fire by building height

(19)
(20)
(21)

High rise building risk model

Quantitative Fire Risk Assessment (QRA) model developed including: – Physical dimensions of the building

– Type(s) of occupancy and the number of occupants – Nature of fires in different types of occupancy

– Types of fire protection in the building – including effectiveness and reliability The model uses this information to predict:

– number of potential deaths and injuries from fire – property type and the building use

(22)

Predictions from high rise building risk model

Building

Date Purpose group No of storeys Overall individual risk per occupant year Individual risk per occupant year due to building Height Average percentage of risk due to the height of the building (%) Recent Residential and office 150+ 2.0 x 10 -7 1.1 x 10-7 55 Recent Office ~100 1.5 x 10-7 1.2 x 10-7 80 1970’s Office 100+ 5.1 x 10-7 4.6 x 10-7 90

(23)

Probability of fire spread to a number of rooms for residential buildings broken down for different building height categories

(24)

Conclusions

Fire safety challenge in high rise buildings includes:

– Safe and timely evacuation of large numbers of people who may be several hundred metres above ground level.

– Ensuring that smoke and fire cannot spread to threaten occupants beyond the compartment of fire origin.

– Fire-fighting access and provisions need to enable safely and quickly access to any height in the building and facilitate timely and effective emergency intervention.

(25)

Conclusions

Analysis of fire statistics for high-rise buildings in London indicates that:

– There is very little difference on the probability of fire spread as a function of height

– There is very little difference in the probability of injury from fire as a function of height

– There is very little difference in the probability of death from a fire as a function of height.

(26)

Conclusions

Quantitative assessment of fire risk in high rise buildings shows that:

– Increases in the effectiveness and reliability of fire resistance floors in high rise buildings are a key way of reducing the extent of this increase in risk due to the height of the building.

– Similarly the effectiveness and reliability of automatic suppression systems, such as sprinklers, are crucial in minimising the proportion of fire risk due to the height of the building.

(27)

Fire Safety Issues – experience from real fires and

relevant research – concealed fire spread

– Cavity barriers – Fire stopping

– Combustible linings

(28)

Main Face 2800 1500 9675 2000 Combustion Chamber 2000 550 250 Wing Main Face 2800 1500 2500 2000 Combustion Chamber 2000 550 250 Wing 2500

(29)

Will the fire precautions work?

Are they reliable? – Testing

(30)

New challenges

Include: – Fire – Earthquake – Wind – Flood – Loss of power – Aircraft crash – Terrorism – Other?

References

Related documents

It was decided that with the presence of such significant red flag signs that she should undergo advanced imaging, in this case an MRI, that revealed an underlying malignancy, which

Also, both diabetic groups there were a positive immunoreactivity of the photoreceptor inner segment, and this was also seen among control ani- mals treated with a

The paper assessed the challenges facing the successful operations of Public Procurement Act 2007 and the result showed that the size and complexity of public procurement,

19% serve a county. Fourteen per cent of the centers provide service for adjoining states in addition to the states in which they are located; usually these adjoining states have

patient is worse in June and gives a positive skin test to grass pollen, grass pollen is given as part.. of

Field experiments were conducted at Ebonyi State University Research Farm during 2009 and 2010 farming seasons to evaluate the effect of intercropping maize with

Experiments were designed with different ecological conditions like prey density, volume of water, container shape, presence of vegetation, predator density and time of

exceedance, and the allowable volume of eroded bedload (AV) standard, Log(AV) = - 0.64(Q c ) – 1.52, represented both magnitude and duration of exceedance while remaining stable.